TECHNICAL MANUAL
MT-TLP-100S-R
Rev.0
2018-07-10
Page 2/36
CONTENTS
1. GENERAL DESCRIPTION ..............................................................................................................5
1.1. SYSTEMS DESCRIPTION ........................................................................................................................................ 5
1.2. APPLICATION ........................................................................................................................................................... 6
1.3. GENERAL VIEW ....................................................................................................................................................... 7
1.4. STORAGE.................................................................................................................................................................... 7
6. METHOD OF OPERATION...........................................................................................................25
6.1. LCD DISPLAY DESCRIPTION .............................................................................................................................. 25
6.2. INITIAL LCD DISPLAY .......................................................................................................................................... 26
6.3. SETTING MODE LCD DISPLAY ........................................................................................................................... 27
6.3.1. USER SETTING MODE ........................................................................................................................................ 27
6.3.2. MAKER SETTING MODE ................................................................................................................................... 31
7. OPERATION ....................................................................................................................................33
8. SETTING ...........................................................................................................................................34
CAUTION:
No modifications are permitted without permission from the Notified Body and/or approval of the IECEx’s
authorized person.
WARNING:
Do not install and/or repair while energized.
Do not repair and/or change the electrical and mechanical assembly which may effect on intrinsically safety.
Ex applications: Ex-type TLP-100S was designed and manufactured to ˝product of intrinsic safety i˝ on the
basis of international standards of <IEC 60079-0:2011> electrical apparatus for explosion gas atmospheres part
0 : General requirements and < IEC 60079-11:2011> explosive atmospheres part 11 : equipment protection by
intrinsic safety “i” and Ex-marking used for this product is ˝Ex ia IIC T6-T4 Ga(TLP-100S)˝.
It means, the product is suitable for use in ”Zone0 or Zone1 or Zone 2” areas as specified in the international
standards of IEC 60079-0 and IEC 60079-11 as ˝grade IIC of Explosion gas atmospheres˝.
Ex-type TLP-100S which controls and/or monitors actual liquid level in tank shall be used for Zone0 or Zone1
or Zone 2 area in order to transmit signal generated from TLP-100S to Zener barrier in Safe Area.
All the required Ex-tests for Ex-type TLP-100S was fulfilled with Ex rules based on sample test product,
product drawing and technical data. As the result of testing, these has passed all the required Ex-test items for
Ex ia IIC T6-T4 Ga(TLP-100S) and certified KTL IECEx certificate for Ex-type TLP-100S, Temperature,
Pressure Transmitter which is “IECEx KTL 18.0015X”
- No 1 : Types of ignition protection, ˝Ex ia˝ means Intrinsic Safety of grade ‘a’ for using in Zone 0.
- No 2 : Gas group, ˝IIC˝ means that this apparatus can be used in the area of ethylene and propane.
- No 3 : Temperature class, ˝T6˝ means that the maximum surface temperature of the equipment is 85℃, ˝T5˝
means that the maximum surface temperature of the equipment is 100℃, ˝T4˝ means that the maximum
surface temperature of the equipment is 135℃.
- No 4 : Protection level, “Ga” means that this apparatus can be used in Zone 0, 1 and 2.
MT-TLP-100S-R
Rev.0
2018-07-10
Page 5/36
1. GENERAL DESCRIPTION
1.1. SYSTEMS DESCRIPTION
The radar type level, pressure and temperature transmitters(TLP-100S series) of radar type cargo monitoring
system(TLP-100 system) are intrinsically safe apparatus that are applied in hazardous area, which are used for
measurement of level, pressure and temperature in cargo tanks..
The radar type level sensing part is not included in the equipment and a separate radar level transmitter is
used to measures level. Terminals for only connection between the radar level transmitter and other
intrinsically safe circuits are provided in the equipment. The pressure sensing part measures pressure by using
a pressure sensor. The temperature sensing part measures temperature by using separate RTD sensors(TLP-
100T). TLP-100S, the separate radar level transmitter and TLP-100T can be installed independently. But,
normally, the separate radar level transmitter and TLP-100T are connected optionally to TLP-100S according
to configuration of system and transfer the measured values to TLP-100S. TLP-100S relays the values of
level without any conversion to external equipment and converts the values of pressure and temperature to
digital serial binary code pulses for communication with external equipment. TLP-100S contains three
printed circuit boards such as a display board, a signal processing board and a terminal board for external
connection, and a pressure sensing module, which are housed within a stainless steel enclosures with a glass
window. Internal wiring for connections to the boards in the transmitter are made by using plugs and sockets.
The terminal board for external connection is provided for power supply, the separate radar level transmitter
and TLP-100T. TLP-100T contains one printed circuit board and maximum three temperature
sensors(PT1000Ω), housed in stainless steel enclosures. TLP-100S, the separate radar level transmitter and
TLP-100T are made by using cables via a cable gland.
Acquired The input to TLP-100S shall be limited within maximum electrical input parameters (Ui, Ii, Pi) by
connecting to certified intrinsically safe circuits or through safety barriers, and the output limited within
maximum electrical output parameters (Uo, Io, Po) shall be connected to the separate radar level transmitter
not affecting intrinsic safety adversely.
<System Diagram>
MT-TLP-100S-R
Rev.0
2018-07-10
Page 6/36
1.2. APPLICATION
The TLP-100 system is specially developed for tanker applications such as chemical, products and etc. It
also covers temperature measuring and pressure measuring in cargo tanks.
TLP-100 system is consist of the radar level transmitter, pressure transmitter, temperature transmitter(TLP-
100T), TLP-100B(Barrier for TLP-100) and RADAR barrier.
Radar is level transmitter for measuring cargo tank level, measurable product is gasoline, diesel oil, heavy
oil, kerosene and etc.. The pressure transmitter is a transmitter that measures the pressure of the inert gas in
the cargo tank. TLP-100T is a transmitter for measuring the temperature of a product in the cargo tank,
generally maximum measurement point is 3(tank top, tank middle, tank bottom). TLP-100B and radar barrier
is safety module for power supply and communication to the sensor in hazardous area.
TLP-100S is composed of two PCBs, Pressure transmitter is composed of one PCB and one pressure sensor,
TLP-100T is composed of one PCB and temperature sensor(maximum 3 point).
MT-TLP-100S-R
Rev.0
2018-07-10
Page 7/36
1.4. STORAGE
Cargo monitoring system should be stored in factory shipments. The packages must be stored only under the
following conditions:
● Not exposed to corrosive media.
● Dry and dust free.
● Avoiding mechanical shock and vibration.
● Avoiding any shocks or scratches to the transmitter body
● Avoiding any shocks or scratches to the pressure sensor cell surface
MT-TLP-100S-R
Rev.0
2018-07-10
Page 8/36
2. TECHNICAL SPECIFICATIONS
2.1. TLP-100S
2.1.1. DETECTION UNIT
● Detection unit:
Pressure : Ceramic sensor (UC2)
Level : Radar
2.1.2. RANGE
● Detection Range:
Pressure : 800 ~ 2000mbar
2.1.3. ACCURACY
● Sensor Accuracy:
Pressure : 0.3% of full scale
2.2. TLP-100T
2.2.1. DETECTION UNIT
● Detection unit:
Temp : PT-1000RTD
2.2.2. RANGE
● Detection Range:
Temp : -35°C to +120°C(Ex),
-50°C to +150°C(Non. Ex)
2.2.3. ACCURACY
● Sensor Accuracy:
Temp : IEC 751 class B
2.2.4. INSTALLATION
● Installation Position:
Top / Middle / Bottom
3. MECHANICAL INSTALLATION
CAUTION:
It is necessary to protect the diaphragm and surface while any kinds of work are carried out near the
transmitter. Be careful to avoid any shocks to the surface.
3.1. TLP-100S
[4] Fix the TLP-100S I.G Pressure transmitter on the socket with bolts.
3.2. TLP-100T
4. ELECTRICAL CONNECTION
4.1. TLP-100S
4.1.1. CABLE CONNECTION PROCEDURE
[1] Remove the fixing screws from the box.
[2] Check the Connector name on PCB. Connect to each cable line using a 3mm minus screwdriver.
CAUTION:
Power OFF the system before any connecting work.
Check the number of the terminal PCB and the cable. Correspond to the number.
● POWER
TLP100SM(J1) TLP100ST(J2)
1: + (red ) 1 1: + (red)
2: - (black) 2 2: - (black)
3: EARTH (green ) 3 3: EARTH (green )
3P connector
● TEMPEPATURE
TLP100SM(J6) TLP-100ST(J5)
4.2. TLP-100T
4.2.1. CABLE CONNECTION PROCEDURE
[1] Unscrew the housing cover.
INFORMATION:
Standard entry spec. is M28-20b. Optional spec. is seen “8. MODEL NUMBER CODE SYSTEM".
[2] Check the connector name on the PCB. Connect to each cable line, using 3mm minus screwdriver.
CAUTION:
Check the number of the terminal PCB and the cable. Correspond to the number.
[Cable Connection(continue)]
[Cable Connection(finish)]
MT-TLP-100S-R
Rev.0
2018-07-10
Page 23/36
CABLE CONNECTION Center side connection, connect the cable coming from the TLP-100S
5. MECHANICAL REMOVAL
CAUTION:
It is necessary to protect the diaphragm surface while any kinds of work are carried out near the
transmitter. Be careful to avoid any shocks to the surface.
5.1. TLP-100S
[1] Carry out the ELECTRICAL DISCONNECTION.
[2] Unscrew the bolts and washers fixing the TLP-100S on its flange.
[3] Keep the bolts and washers they will be used to fix the TLP-100S.
5.2. TLP-100T
[1] Carry out the ELECTRICAL DISCONNECTION.
[2] Unscrew the nuts and washers fixing the TLP-100T on its flange.
[3] Keep the nuts and washers, they will be used to fix the TLP-100T.
6. METHOD OF OPERATION
6.1. LCD DISPLAY DESCRIPTION
MT-TLP-100S-R
Rev.0
2018-07-10
Page 26/36
TLP-100S
Loading
TLP-100S
Name/Version
TLP-100S
Level data
MT-TLP-100S-R
Rev.0
2018-07-10
Page 27/36
TLP-100S
TLP-100S
TLP-100S
TLP-100S
Next code number
"C04","C05","C06","C07","C08"
TLP-100S
TLP-100S
TLP-100S
TLP-100S
TLP-100S
TLP-100S
TLP-100S
TLP-100S
[Data change -> Use the switch (“A switch”, “C switch”, “B switch”)]
MT-TLP-100S-R
Rev.0
2018-07-10
Page 30/36
TLP-100S
TLP-100S
② D switch (3 second)
TLP-100S
③ “1234” setting
TLP-100S
MT-TLP-100S-R
Rev.0
2018-07-10
Page 32/36
④ D switch
TLP-100S
A switch C switch
TLP-100S TLP-100S
MT-TLP-100S-R
Rev.0
2018-07-10
Page 33/36
7. OPERATION
TLP-100S
[Table. 1]
TLP-100S
Function
Error Message
E01 No Hall IC detection by float(magnet).
E02 Detect many HALL IC.
E03 Detect 2 FLOAT(magnet).
E06 OUTPUT signal is different from CONTROL signal (When SIC signal is "0").
E11 Less than -50℃
E12 Upper than 150℃
E21 Less than -50℃
E22 Upper than 150℃
E31 Less than -50℃
E32 Upper than 150℃
MT-TLP-100S-R
Rev.0
2018-07-10
Page 34/36
8. SETTING
When the button “B” is pressed during 3 sec, them menu of TLP-100 enters to setting mode. The
each code of setting is shown as following Table 2. The password in C08 enables to set C09 and later
codes.
[Table 2] TLP-100S setting code
Setting contents Limit range for setting Data
C00 Level adjustment -99.9 ~ +99.9[mbar] 0.00
C06 Setting for zero pressure value of the pressure sensor 0 ~ 99999 [ 1/10 mbar] 8000
C07 Setting for full pressure value of the pressure sensor 0 ~ 99999 [ 1/10 mbar] 20000
0:bar,1:mbar,2:kPa,3:Kgf/㎠
C56 Unit of pressure data 0
4:atm,5:mmHg,6:Kgf/㎡
Type 0: TLP-100MUX
C79 0
(TLP-100MUX or TLP-80MUX) 1: TLP-80MUX
MT-TLP-100S-R
Rev.0
2018-07-10
Page 36/36
9. ORDERING INFORMATION
● Contact us when the problems happened except above troubles.(Checked by local LCD of the TLP-100S)
- Company : HANLA IMS CO., LTD
- Address : 595-4, HWAJEON-DONG, GANGSEO-GU, BUSAN, KOREA
(115, HWAJEONSANDAN1(il)-RO, GANGSEO-GU, BUSAN, KOREA)
- Tel. : 82-51-601-7000
- Fax. : 82-51-831-1850
- E-mail : hanla@hanlaims.com
- Homepage : http://www.hanlaims.com