Professional Documents
Culture Documents
Energy Saving by Optimal Energy Recovery (PINCH)
Energy Saving by Optimal Energy Recovery (PINCH)
by
(PINCH Method)
Standort Ostfriesland
(Emden, 02.04.2003)
Table of Contents
Appendix
References
Nomenclature
Worksheets 1-5
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 2 of 26
In many process plants (chemical plants, power stations, air-conditioning) the aim is
to preheat a series of
cold streams
(distillation and reaction products, exhaust air from air conditioning) must be cooled
down to temperature for further processing or storage.
for heating (steam, gas, oil, electricity) and cooling (cooling air or cooling water) are
provided.
The recovery problem should be solved in such a way, that initially the process
streams themselves are used for preheating and precooling of other streams which
require heating or cooling respectively. The external utilities are only used if, because
of the energy balance or the temperature levels, the available hot and cold streams
are insufficient to achieve the required target temperatures.
Modelling a heat exchanger network (HEN) as shown in Fig. 1-1 is the first step to
solving the problem. The heat exchanger network consists of two parts, the inner
system (IS) and the outer system (OS).
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 3 of 26
The cold streams (C) in the inner system are heated up in appropriate heat
exchangers by the hot streams and at the same time the hot streams (H) are cooled
down. Capital costs for the heat exchangers are the consequence.
In the outer system the cold streams are heated by external hot utilities to their target
temperatures and the hot streams require external cold utilities to cool them down to
their target temperatures. Capital costs for the heat exchangers and operating costs
for the external utilities are the consequence. The total costs depend mainly on the
choice of the heat exchange area in the inner system of the heat exchanger network.
An increase of the heat exchange area in the inner system has the following
consequences:
The bigger the heat exchanger area is, the smaller is the temperature difference
between the cold and hot stream. The dependence of the total costs on the minimum
temperature difference (?Tmin) within the inner system is illustrated in Fig. 1-2.
Required is a heat exchanger network with a trade-off between energy and capital
costs, which minimises the
total costs.
optimisation problem.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 4 of 26
The secondary conditions of the energy recovery problem are the specific heat
capacities (first law of thermodynamics) and the temperatures of the cold and hot
streams (second law of thermodynamics).
• Design of the structure, determine the couplings of the cold and hot
streams
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 5 of 26
The solution of the first part of the problem – design the heat exchanger network –
can also be done in two stages:
• Inlet temperatures of the hot and cold streams into the system
• Outlet temperatures of the hot and cold streams out of the system
•
• Heat capacity flow rates ( C p / [W/K]) of the hot and cold streams.
respectively.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 6 of 26
The idea is to replace the hot and cold streams by single hot and cold composite
curves separately to carry out the analysis. Within each temperature interval the
streams are combined to produce a composite hot and cold stream. The composite
• •
curve has a C p in all temperature intervals that is the C p - sum of the individual
streams. In any temperature interval, the enthalpy change of the composite curve is
the sum of the enthalpy changes of the individual streams.
The design steps of the hot and cold composite curves are summed up on the
worksheet 1.
An example of determining the curves for two individual streams are shown in Fig.
2-1 and 2-2.
The hot and cold composite curves have a fixed position on the temperature axis.
The relative position of the two streams can only be changed by moving them
horizontally relative to one another. This is possible because the reference enthalpy
for the hot stream can be changed independently from the reference enthalpy for the
cold stream. This principle is used to set the heat recovery PINCH.
2. Moving the hot and cold composite curves relative to one another (parallel
to the H-axis, no changes on the temperature-axis), until the smallest
vertical distance of the composite curves is reached for a given value of
? Tmin.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 7 of 26
The point, where the composite curves show a minimum temperature difference, is
known as the
The PINCH - point has a special significance for the heat recovery. Fig. 2-3 shows a
T, H - diagram representing the heat recovery PINCH.
From the T, H - diagram with the PINCH some significant conclusions can be drawn.
The complete system is divided at the PINCH into two independent systems.
In the system above the PINCH the energy need of the cold streams is bigger than
the energy supply of the hot streams. That means heat must be received from an
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 8 of 26
external hot utility, and no heat is to be removed. The process above the PINCH acts
as a
heat sink.
In the system below the PINCH the energy supply of the hot streams is bigger than
the energy need of the cold streams. The system is in heat balance with the
minimum cold utility. No heat is received, but heat is rejected to an external cold
utility. The process acts as a
heat source.
The required minimum duties for the hot and cold utilities (these represent the targets
of the hot and cold utilities) can be read directly from Fig. 2-3.
The enthalpy difference beyond the start of the hot composite curve shows the
•
required duty for the hot utility Q H,min.
The enthalpy difference beyond the start of the cold composite curve indicates the
•
duty for the cold utility Q C,min.
Where the curves overlap heat can be transferred vertically from the hot streams into
•
the cold streams. This represents the maximum heat ( Q Rec,max) which can be
exchanged within the inner system.
• • •
Q H,min, Q C,min and Q Rec,max are functions of the given ? Tmin value.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 9 of 26
Three rules are necessary to achieve the energy target set by the composite curves.
These three
PINCH rules
The consequences of violating the PINCH-rules are illustrated in the example 2 (Fig.
2-7). In example 1 an extra stream is introduced, which only imports energy below
the PINCH. No changes occurred above the PINCH, but below the PINCH the duty of
the cold utility increased by the extra heat amount of stream 3.
With the heat cascade method the energy analysis is set by calculating energy
targets.
Starting with the composite curves they are shifted into two directions.
1. First Shift:
The shifted composite curves now touch at the PINCH (see Fig. 2-9).
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 10 of 26
2. Second shift:
The new cold composite curve is now shifted horizontally under constant
enthalpy conditions parallel to the enthalpy-axis. It can be seen that no hot
utility is now used beyond the start of the hot composite curve.
Furthermore the newly repositioned curves show a maximum overlap in
heat transfer and the biggest negative enthalpy difference at the PINCH
(Fig. 2-9).
The calculation of the heat cascade is done in four steps. The results are
represented in a table as shown in Fig. 2-10.
Step 1:
Corresponding to the procedure illustrated in Fig. 2-9 the temperatures of the hot
streams are shifted down by –? Tmin/2 and the temperatures of the cold streams are
shifted up by value +? Tmin/ 2. The temperature intervals can now be determined and
the differences are entered into the table.
Step 2:
The next step consists of the heat balance setting for each temperature interval, for
•
which the heat capacity flow rates are added ( C p´s of hot streams count as negative
and those of cold streams positive). The results of the heat balance according to the
equation
• • •
∆ Hi = ( ∑ C pC − ∑ C pH )i * ∆Ti
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 11 of 26
can be calculated for each interval. Positive values for heat balances indicate a
deficit and negative values show a surplus.
Step 3:
The heat duty in each interval is solved by removing or adding heat from external
heat sinks or sources (column “Balanced Energy ...”). The heat balance within each
interval allows maximum heat recovery within each interval. However, heat recovery
can also be carried out between intervals. The surplus heat can now be cascaded
down the temperature scale from interval to interval. Looking at the cascade in Fig. 2-
10 it can be seen that some heat flows are negative which is physically impossible.
Heat cannot be transferred up the temperature scale. The point where the biggest
negative heat flow occurs (see column `Cascade 1´) corresponds to the PINCH.
Step 4:
The cascade can be solved by adding the amount of heat with which the energy flow
becomes zero at the PINCH. This does not change the heat balance of the heat
cascade but increases all the heat flows between the intervals (column “Cascade 2”).
At the top of the cascade, the smallest amount of heat can be read off for the hot
utility. The amount of heat to be removed is shown by the value at the bottom of the
cascade. The results agree with the graphical setting of the composite curves as
demonstrated in Fig. 2-4.
The intervals in the column “cascade 3” show the heat surplus and deficit. At the top
a surplus of –115 kW must be added and at the bottom a surplus of –155 kW must
be removed. In many heat cascades like the following the signs of the heat flows
between the intervals are neglected.
The general procedure of the heat cascade can be illustrated in the way that has
been done in Fig. 2-11. The necessary energy flow can be read off between each
temperature interval.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 12 of 26
The required energy duty, calculated with the heat cascade, which is supplied by
external utilities is added at the highest temperature point. This is obviously not
necessary for every heat recovery case. Energy can be added at a certain
temperature level to satisfy an energy deficit in the corresponding temperature
interval. The amount of heat added can be larger than what is required for this
temperature interval. The larger amount of heat can then be used to cover heat
deficits below.
As shown in Fig. 2-12, the amount of heat added to the cascade reduces the heat
supply at the top of the cascade by the equivalent amount of energy. If the energy
supply is as large as the deficit in the corresponding interval, the heat flow
approaches zero. Such a PINCH is described as a utility PINCH. The actual PINCH
introduced in chapter 2.4 is called process PINCH or heat recovery PINCH.
•
2.6. The T, ? H - Diagram (Grand Composite Curve)
Another possible way to represent the energy situation of the heat recovery problem
•
is the T, ? H - diagram.
•
The T, ? H - diagram shows the heat flow through the process against temperature
and indicates the heat streams at the end of each temperature interval (Fig. 2-13).
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 13 of 26
The design of a heat exchanger network requires a set of rules which were
postulated according to the results of the analysis. The application of these rules
leads to a heat exchanger network with maximum heat recovery and minimum use of
hot and cold utilities. A very complex heat exchanger system can be the result. Such
complex systems are characterised by many small duty heat exchangers and many
stream splittings. It is easy to see that a simplification of the designed heat
exchanger system by reducing the number of small heat exchangers and stream
splittings must be carried out under certain considerations.
Note:
Each violation of the PINCH rules leads to increasing operating and capital
costs.
For an effective design of a HEN some additional tools will be explained first:
•
The rules for developing the network design grid and C p - table are shown on
worksheet 2.
Fig. 3-1 and 3-2 show an example of a HEN and the corresponding network design
grid.
From the composite plot (or heat cascade) the PINCH temperature can be
determined.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 14 of 26
With this the requirements are fulfilled to start the actual design of the HEN. The
further procedure and rules, which must be strictly applied, are detailed on the
worksheet 3.
In order to not violate the minimum temperature difference (? Tmin) at the PINCH a
number of criteria must be developed. The following rules are only related to the
• •
number of streams (NH and NC) and to the heat capacity flow rates ( C pH and C pC).
Note that the criteria are postulated for the systems above and below the PINCH
separately. The process should therefore be divided at the PINCH into two
subsystems.
It follows that all hot streams must be cooled to PINCH temperature by heat
recovery. This means that the same number of cold streams as hot streams must
exist at least to prevent a partial violation of the ? Tmin constraint:
NH ≤ NC .
If this is not the case, then the recovery problem can only be resolved by splitting a
cold stream into two parallel branches.
The minimum temperature difference is set at the PINCH, thus it is only permissible
to couple streams with (see Fig. 3-3):
• •
C pH ≤ C pC .
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 15 of 26
It is not permissible to heat below the PINCH, which means that all cold streams
must be heated to PINCH temperature by heat recovery. Thus the same number of
hot streams must be provided as cold streams at least to prevent any ? Tmin
violations.
NH ≥ NC .
If this is not the case, then the problem can only be resolved by splitting a hot stream
into two branches.
The minimum temperature difference is set at the PINCH, thus it is only permissible
to couple streams with (see Fig. 3-4):
• •
C pH ≥ C pC .
Figs. 3-5 and 3-6 show the stream-splitting algorithms for the design of the HEN
above and below the PINCH. If the design strictly follows the guidelines of the
stream-splitting algorithms, the criteria will be fulfilled.
The rules for the design of a HEN at the PINCH are listed in Fig. 3-7.
In the following Figs. another example (example 3) and the results are represented
and discussed.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 16 of 26
The next example (example 4), a frequently discussed case, will be represented in
the next table.
As discussed earlier in chapter 3.2 the design of the HEN is started at the PINCH
and is extended separately above and below the PINCH. Although the guidelines for
the design are accurately applied to the network design grid, several equivalent (in
energy terms) HEN are developed.
The Figs. 3-16 and 3-17 show two possibilities for the network design grid above the
PINCH. Picture 3-18 also presents a design, which satisfies the constraint of the
minimal hot utility. The only difference to the design in Fig. 3-17 is that the positions
of the heat exchangers 1 and 2 have been swapped.
It can be seen (Fig. 3-19) that below the PINCH the stream hot 2 has been split into
two branches to satisfy the stream-number rule. The splitting is done in such a way
that the split streams have the same temperature at the mixing point. Two
possibilities are shown in Figs. 3-19 and 3-20.
One of the possible designs for the completed network design grid is illustrated in
Fig. 3-21. The network flowsheet is described in Fig. 3-22.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 17 of 26
A loop begins and ends at the same point within the network design grid. A loop
leads from one exchanger back to the same exchanger, possibly passing through
several other exchangers. In Fig. 4-1 (example 4) such a loop is determined and
highlighted. Its significant feature is that heat can be shifted around the loop. The
heat duty is subtracted from one exchanger and is added to another one
simultaneously. If more than two exchangers are included in a loop the addition and
subtraction of the heat duty must be done alternately.
The dotted line in Fig. 4-2 designates a second loop. It can be seen that the loop
includes two heaters in a row. To move heat duty within this loop, the heat must be
subtracted from one heater and added to the other one.
A path is a distinct line between a hot utility and a cold utility passing through one or
more heat exchangers. In other words the path links a heater with a cooler within the
network design and can be used to balance the energy duty.
The heat duty is moved along the path possibly being added to the heater,
subtracted from the next exchanger again and finally being added to a cooler.
Fig. 4-3 illustrates a path in the network design grid for example 4.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 18 of 26
The loop concept is now used to simplify the network design grid in example 4. The
heat duty from heat exchanger 4 is completely moved to exchanger 1, which means
that exchanger 4 can be removed from the design. Therefore the specified minimum
temperature difference ? Tmin is violated (Fig. 4-4). In many practical cases the
resulting optimised network design can be now applied without any other
considerations.
The movement of the heat duty along the path can be used for example to reset the
violation of the ? Tmin value. With the export of 4 kW at heat exchanger 1 the specified
? Tmin of 20 K is reached again. However the 4 kW subtracted from exchanger 1 must
be added along the path between the heater and cooler as shown in Fig. 4-5.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 19 of 26
•
5. Utilisation of the T, ? H -Diagram (Grand Composite Curve)
•
The utilisation of the T, ? H -diagram in chapter 2.6 introduced can be best explained
by an example (example 5).
•
The problem, the stream table, the heat cascade, the listing of the results, the C p -
table, the network design grid and the network flow sheet are shown in Figs. 5-1 to 5-
•
7. The construction of the T, ? H -diagram (Fig. 5-8) was completed with the help of
the temperature and enthalpy data taken from the heat cascade. The diagram has a
special significance. At higher temperatures the curve returns to the T-axis. This
indicates that the external hot utility must not necessarily be placed at the highest
temperature level. The vertical dotted line (beginning near 245.0 °C) shows the same
•
? H - values at a temperature of 145.6 °C as just below 245.0 °C. This means that
the whole duty of the hot utility can be imported at the temperature of 145.6 °C.
•
With the altered heat import at a lower temperature the head cascade and T, ? H -
diagram shows a new profile as illustrated in Figs. 5-9 and 5-10. A new PINCH can
now be introduced, the utility PINCH.
With this utility PINCH and the process PINCH the heat exchanger network can be
developed. Figs. 5-11 and 5-12 show two possibilities for the design above the
PINCH. The left segment now needs no external utility, but instead the segment near
the process PINCH must be provided by the 1.67 MW utility. The only difference
between the designs in Figs. 5-11 and 5-12 is the stream splitting above and below
the utility PINCH.
In addition in Fig. 5-11 a loop was determined to simplify the design. The small heat
exchanger with a duty of 0.31 MW can be added to the 1.619 MW exchanger. Thus
new temperatures at the inlets of the heater and exchanger must be set, but
simultaneously the heat duties of these two utilities remain unchanged. The mixing
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 20 of 26
The new ? Tmin of 7.3 K, which was the result of the exchanger removal must now be
considered.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 21 of 26
In this chapter the integration of a heat engine into the heat exchanger network
(HEN) is discussed.
Beginning with a simple heat engine, the energy balance, schematic, working
procedure of a simple Clausius-Rankine steam process and the corresponding T, s-
diagram are illustrated in the Figs. 6-1 to 6-4.
The PINCH rules are useful tools to examine the integration of heat engines.
Corresponding to Fig. 6-5 the heat engine exports heat at the highest HEN
temperature (exhaust heat). The heat engine loses no energy to the environment and
in terms of the HEN no additional hot utility is necessary. Integration in this way is
much more effective than the two separate systems.
The heat export of the heat engine can also take place at various temperatures
above the PINCH. As can be seen in Fig. 6-6 the heat engine exploits the
temperature differences that exists between the temperature intervals and imports
only the deficit which is needed to satisfy the energy balance.
Integrating a heat engine below the PINCH is only advantageous if the surplus of one
•
or several temperature intervals can be used to produce shaftwork ( W ) (Fig. 6-7).
The industrial application of this coupling is generally very difficult because the
conversion of heat at low temperature into shaftwork involves technical problems.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 22 of 26
Integration of the heat engine across the PINCH as shown in Fig. 6-8 is
counterproductive and violates the PINCH rules (no heating below the PINCH and no
•
heat transfer across it). The process still requires Q H,min and the heat engine
performs no better than if operated stand-alone.
This chapter will be discussed how a heat pump can be integrated into the heat
exchanger network (HEN).
Beginning with a simple heat pump, the energy balance, schematic, working
procedure and the corresponding T, s-diagram are illustrated in the Figs. 6-9 to 6-12.
The PINCH rules seem once again to be a useful tool to discuss the coupling of the
heat pump with the HEN.
Looking at the energy balance formally, no disadvantage occurs, but the replacement
of heat by electrical energy is a disadvantage for economic reasons.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 23 of 26
Another way to integrate a heat pump without crossing the PINCH is shown in Fig. 6-
14. This method is uneconomical. Importing shaftwork as heat at a higher
temperature violates a PINCH rule (no heating below PINCH), and turns power into
waste heat.
Heat pump integration across the PINCH is illustrated by Fig. 6-15 and demonstrates
a genuine saving of energy.
•
Below the PINCH surplus heat is exported (cooling Q ) and finally imported back into
• •
the system (heating Q + W ) above the PINCH. Both steps conform to the PINCH
rules.
• •
For the system above the PINCH the hot utility is reduced by the value Q + W and
•
the cold utility below PINCH by Q . The power W (electrical energy) has to be
applied.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 24 of 26
Finally, the integration of a distillation column (DC) into the heat exchanger network
(HEN) will be discussed. A simple distillation column (Fig. 6-16) with reboiler and
condenser is used to explain the integration.
•
As can be seen in Fig. 6-17 the column imports Q reb from the process above the
•
PINCH and exports the heat Q cond to the column at a lower temperature but still
above the PINCH. At the higher temperature interval of the heat cascade the
• •
difference Q reb – Q cond must be added to satisfy the column.
It is not necessary to take the heat for the reboiler from the process, it can also be
imported from an external utility. The question is, at which temperature the heat from
the condenser is to be supplied. If the condenser temperature lies above the PINCH
temperature, the condenser must be integrated above the PINCH - it acts as a heater
(Fig. 6-18). If the condenser temperature lies below PINCH temperature, integration
does not make much sense (no heating below PINCH).
• •
A distillation column below the PINCH imports Q reb from the HEN and exports Q cond
•
to the HEN again. At a lower temperature, where Q cond is reimported, the difference
• •
Q cond – Q reb must be supplied by external utilities. As long as this temperature
difference is relatively small, the integration of the DC with the process is
advantageous. The column then works nearly with practically no additional energy
(Fig. 6-19).
There is no need for the column to export the heat back to the process, instead the
heat can be saved for other recovery purposes (no heating below PINCH). The
question here is, at which temperature the reboiler heat is needed. If it is below
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 25 of 26
PINCH temperature the reboiler must be integrated and would act as cooling (see
Fig. 6-20).
Fig. 6-21 clearly indicates that the integration of DC across the PINCH violates the
PINCH rules in terms of no heating below and no cooling above the PINCH.
The question, how heat engine, heat pump and column can be integrated has only
been discussed from the energy point of view. Of course some other criteria must be
considered such as measurement, control and regulation technology. A breakdown
of a single part of the system causes a failure of the whole system.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Page 26 of 26
7. Conclusion
The design of heat exchanger networks supported by the PINCH - method leads in
all cases to minimal cold and hot utility duties.
The result depends on the choice of the minimum temperature difference (? Tmin),
which must be determined at the beginning for each problem to be solved.
If the resulting exchanger design becomes too complex some additional criteria can
be introduced to simplify the concept. Most of the simplifying procedures result in an
increased utility duty.
Generally the design of the heat exchanger network is a function of operating and
capital costs. Depending on which target – minimum operating or capital costs - is
achieved, the design can only be proceeded as a function of operating costs or
capital costs.
skript_eng_03-04-05.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method References
A. General Reports
Linnhoff, B:
Use Pinch Analysis to Knock Down Capital Costs and Emissions
Chem. Engng. Prog. (1994) 8, S.33-37
Smith, R.:
Chemical Process Design
McGraw Hill, 1995, S.159-213
B. Reports
C. Software
Nomenclature
nomenclature_03-04-02.doc
List of Important
Symbols at the Heat Exchanger
Specific enthalpy h kJ / kg
∆Thot ∆Tsmall
T2 ∆Tm T4
∆Tbig
∆Tcold
T3
H
∆Thot temperature difference of the hot stream
Cold 1
Cold 2
Cold n
II
1-1
Cost Optimum of Heat Exchanger Networks
Total cost
Optimum
Annual cost
Operating cost
Capital cost
∆Tmin
1-2
Problem Table for Example 1
Target enthalpy
Stream
temperature
temperature
number
and
flow rate
flow rate
Supply
Target
type
Heat
T1 T2 H1 H2 Cp
[°C] [°C] [kW] [kW] [kW/K]
2-1
Constructing the Composite Curves
T / °C
100
50
30
2-2
T, H - Plot Including the PINCH
T / °C QH,min
∆Tmin = 10 K
250
200
PINCH Composite curve of
the cold streams
150
Composite curve
of the hot streams ∆T min
100
50
30 Q C,min Q Rec,max
2-3
T / °C
E xa m ple 1
Q H ,m in
∆Tmin = 10 K 11 5 k W
250
200
Composite curve of
Hot 1 the hot streams
150
Cold 1 = Composite curve of
the cold streams
100
Hot 2
50
30 155 kW
QC,min Q Rec,max = 185 kW
2-4
Heat Flows in the HEN
T
Q H,min + Q a,sink + QPINCH
Qa,source
Heat
sink
QPINCH
Heat Qa,sink
source
2-5
PINCH Rules
2-6
Problem Table for Example 2
Target enthalpy
Stream
temperature
number temperature
and
flow rate
flow rate
Supply
Target
type
Heat
T1 T2 H1 H2 Cp
[°C] [°C] [kW] [kW] [kW/K]
2-7
Exam ple 2
T / °C Q H,m in = 11 5 kW
∆Tmin = 10 K
250
200
Composite curve of
the hot streams
150
10 K
100
Composite curve of
the cold streams
50
30
Q C,min = 255 kW
2-8
Graphical Setting of PINCH-Facility
Maximum Q H,min
heat overlap
T
+ ∆Tmin / 2
- ∆Tmin / 2 ∆Tmin
2-9
Heat Cascade (Example 1)
( Please Note: Hot and cold streams must be shifted by ∆Tmin /2. Hot streams: - ∆Tmin /2. Cold streams: + ∆Tmin /2. )
Balanced energy
Surplus
Σ Cp i
Deficit /
Hi
number
Interval
within the interval
Streams Cascade 1 Cascade 2 Cascade 3
[K] [ kW/K ] [ kW ]
Hi
0 115 - 115
T1 = 255 °C
1 60 +1.5 + 90 D - 90 - 90 - 90 + 90
- 90 25 - 25
T2 = 195 °C
2 50 +0.5 + 25 D - 25 - 25 - 25 + 25
- 115 0 0
T3 = 145 °C
3 50 -1.5 - 75 S + 75 + 75 + 75 - 75
- 40 + 75 - 75
T4 = 95 °C
4 40 -0.5 - 20 S + 20 + 20 + 20 - 20
- 20 + 95 - 95
T5 = 55 °C
5 30 -2.0 - 60 S + 60 + 60 + 60 - 60
+ 40 + 155 - 155
T6 = 25 °C
6
T7 = °C
1.5 -1 -2
Q H, min = 115 kW Q C,min = 155 kW TPINCH = 145 °C TPINCH, H = 150 °C TPINCH,C = 140 °C
2 -10
Heat Cascade
Q1 = Q H,min
Interval 1
Q2
Qp-1
Interval p-1
PINCH-
Temperature
Qp = 0
Interval p
Qp+1
Qn
Interval n
Qn+1 = QC,min
2 - 11
The Utility - PINCH
QH,min - Qx QH,min - Qy
QUP = 0 Utility
Qx PINCH
Qy
Process
PINCH
QPP = 0 QPP = 0
QC,min QC,min
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
2 - 12
Grand Composite Curve (Example 1)
T
255°C
115 kW
195°C
25 kW
145°C
75 kW
95°C
95 kW
55°C
155 kW
25°C ∆H
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
2 - 13
Flowsheet
hot 1 hot 2 H
200°C 360°C
C
116 kW
80°C 170°C
C p = 1,8 C p = 2,0
kW/K kW/K
H: Hot utility
C: Cold utility
3-1
HEN Design Grid
Cp in kW/K
Q in kW
H: Hot utility
C: Cold utility
3-2
Pinch Match above the PINCH
T PINCH
CpH
CpC ∆Tmin
CpH < Cp C
3-3
Pinch Match below the PINCH
T
PINCH
Cp H
∆Tmin
Cp C
CpH > Cp C
3-4
Design Procedure above the PINCH
Start
NH < NC
yes no
yes no
feasible design
3-5
Design Procedure below the PINCH
Start
NH > NC
yes no
yes no
feasible design
3-6
Rules for the
Design of a Heat Exchanger Network
3-7
Problem Table for Example 3
temperature
number
and
Supply
Target
type
Heat
T1 T2 Cp
[°C] [°C] [kW/K]
3-8
Heat Cascade (Example 3)
Balanced energy
number
Interval
Σ Cp i Hi
Surplus
Deficit /
Streams within the interval
Cascade 1 Cascade 2 Cascade 3
[K] [ kW/K ] [ kW ] ∆Hi
165 °C 0 20 -20
T1 =
1 20 - 3.0 - 60 S 60 60 60 - 60
60 80 -80
T2 = 145 °C
2 5 - 0.5 - 2.5 S 2.5 2.5 2.5 - 2.5
T3 = 62.5 82.5 -82.5
140 °C
3 55 1.5 82.5 D - 82.5 - 82.5 - 82.5 82.5
T4 = - 20 0 0
85 °C
4 30 - 2.5 - 75 S 75 75 75 - 75
T5 = 55 75 -75
55 °C
5 30 0.5 15 D - 15 - 15 - 15 15
T6 = 40 60 -60
25 °C
6
T7 = °C
2.0 4.0 -3.0 -1.5
Cp H Cp C
Hot 1 3 4 Cold 2
Cp H Cp C
Hot 1 3 2 Cold 1
Hot 2 1.5
3 - 10
HEN Design Grid (Example 3)
Cp in kW/K
Q in kW
H: Hot utility
C: Cold utility
3 - 11
HEN Flowsheet (Example 3)
Hot 2 Hot 1
150°C 170°C
140°C 240 kW
80°C
Cold 2
90°C
90 kW 90 kW 30 kW
135°C
H 125°C 80°C 35°C 20°C
Cold 1
20 kW
90°C 60°C
70°C
C 60 kW
60°C 30°C
H: Hot utility
C: Cold utility
3 - 12
Problem Table for Example 4 1 )
temperature
temperature
number
and
Supply
Target
type
Heat
T1 T2 Cp
[°C] [°C] [kW/K]
Hot 1 150 60 2
Hot 2 90 60 8
3 - 13
Heat Cascade (Example 4)
Balanced energy
number
Interval
Σ Cp i Hi
Surplus
Deficit /
within the interval
Streams Cascade 1 Cascade 2 Cascade 3
[K] [ kW/K ] [ kW ] ∆Hi
0 107.5 -107.5
T1 = 140 °C
1 5 - 2.0 - 10 S 10 10 10 -10
10 117.5 -117.5
T2 = 135 °C
2 25 0.5 12.5 D - 12.5 -12.5 -12.5 12.5
- 2.5 105 -105
T3 = 110 °C
3 30 3.5 105 D - 105 -105 -105 105
- 107.5 0 0
T4 = 80 °C
4 30 - 4.5 - 135 S 135 135 135 -135
27.5 135 -135
T5 = 50 °C
- 82.5 - 82.5 82.5
5 15 5.5 82.5 D - 82.5
- 55 52.5 -52.5
T6 = 35 °C
6 5 2.5 12.5 D - 12.5 - 12.5 -12.5 12.5
- 67.5 40 -40
T7 = 30 °C
2.5 3.0 -2.0 -8.0
Cp H Cp C
Hot 1 2 3 Cold 2
2.5 Cold 1
Cp H Cp C
Hot 2 8 3 Cold 2
3 - 15
HEN Design Grid
above the PINCH (Example 4, Variation 1)
Cp in kW/K
Q in kW
H: Hot utility
3 - 16
HEN Design Grid
above the PINCH (Example 4, Variation 2)
Cp in kW/K
Q in kW
H: Hot utility
3 - 17
HEN Design Grid
above the PINCH (Example 4, Variation 3)
Cp in kW/K
Q in kW
H: Hot utility
3 - 18
HEN Design Grid
below the PINCH (Example 4, Variation 1)
4.5
1
70°C 28°C 20°C Cold 1
2.5
105 20
Cp in kW/K
Q in kW
C: Cold utility
3 - 19
HEN Design Grid
below the PINCH (Example 4, Variation 2)
4.166
1
Cp in kW/K
Q in kW
C: Cold utility
3 - 20
HEN Design Grid (Example 4)
125°C
70°C 28°C 20°C Cold 1
H 2.5
17.5 120 105 20
100°C
70°C 25°C Cold 2
H 3.0
90 135
Cp in kW/K
Q in kW
H: Hot utility
C: Cold utility
3 - 21
HEN Flowsheet (Example 4)
Hot 1 Hot 2
150°C 90°C
120 kW 90°C 20 kW
125°C 118°C 70°C 105 kW 20°C
H 28°C
Cold 1
17.5 kW
90°C 60°C 80°C
90°C
135 kW
100°C 70°C 25°C
H Cold 2
90 kW 60°C
C 40 kW
60°C 60°C
H: Hot utility
C: Cold utility
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
3 - 22
Definition of Loops
125°C
118°C 70°C 28°C 20°C Cold 1
H 2.5
17.5 120 105 20
100°C
70°C 25°C Cold 2
H 3.0
90 135
Cp in kW/K
Q in kW
H: Hot utility
C: Cold utility
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
4-1
Definition of Loops
125°C
118°C 70°C 28°C 20°C Cold 1
H 2.5
17.5 120 105 20
100°C
70°C 25°C Cold 2
H 3.0
90 135
Cp in kW/K
Q in kW
H: Hot utility
C: Cold utility
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
4-2
Definition of Paths
100°C
70°C 25°C Cold 2
H 3.0
90 135
Cp in kW/K
Q in kW
H: Hot utility
C: Cold utility
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
4-3
Simplification of the HEN
125°C
118°C 62°C 20°C Cold 1
H 2.5
17.5 140 105
100°C
70°C 25°C Cold 2
H 3.0
90 135
Cp in kW/K
Q in kW
4-4
Simplification of the HEN
125°C
116.4°C 62°C Cold 1
H 2.5
17.5 + 4 = 21,5 140 - 4 = 136 105
100°C
70°C Cold 2
H 3.0
90 135
Restore the ∆Tmin Constraint (∆Tmin = 20 K), HEN without Heat Exchanger Number 4.
Cp in kW/K
Q in kW
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
4-5
Distillation Column -
Separation of Naphtha and LGO (Example 5)
100°C
OP
40 °C 40 °C
LN
50 t/h 50 t/h
160°C 40 °C
HN
50 t/h
25 °C 185°C
F
170 t/h
F : Feed Product
LN : Light Naphtha 250°C 50 °C
LGO
HN : Heavy Naphtha 70 t/h
LGO : Light Gasoil
OP : Overhead Product
5-1
Problem Table for Example 5
temperature
Stream Stream
number type Supply
Target
Heat
T1 T2 Cp
[°C] [°C] [MW/K]
5-2
Heat Cascade (Example 5)
Balanced energy
number
Σ Cp i
Interval
Hi
Surplus
Deficit /
Streams within the interval Cascade 1 Cascade 2 Cascade 3
[K] [ kW/K ] [ kW ] Hi
3
10 103 0 1.670 -1.670
T1 = 245 °C
0.112
1 55 - 0.047 - 2.585 S 2.585 2.585 2.585 - 2.585
2.585 4.255 -4.255
T2 = 190 °C
2 35 0.065 2.275 D - 2.275 - 2.275 - 2.275 2.275
0.310 1.980 -1.980
T3 = 155 °C
3 60 0.033 1.980 D - 1.980 - 1.980 - 1.980 1.980
- 1.670 0 0
T4 = 95 °C
4 50 - 0.183 - 9.150 S 9.150 9.150 9.150 - 9.150
7.480 9.150 -9.150
T5 = 45 °C
1.360 1.360 - 1.360
5 10 - 0.136 - 1.360 S 1.360
8.840 10.510 -10.510
T6 = 35 °C
- 0.047
- 0.032
- 0.216
3 3
Q H, min = 1.670 10 kW Q C, min = 9.950 10 kW TPINCH = 95°C TPINCH, H = 100°C TPINCH, C = 90°C
5-3
Results from the Heat Cascade
for Example 5
∆Tmin = 10 K (specified)
Q H, min = 1.670 MW
Q C, min = 9.950 MW
T PINCH, H = 100 °C
T PINCH, C = 90 °C
T PINCH = 95 °C
5-4
Cp -Table above the PINCH (Example 5)
Cp H Cp C
Hot 1 0.032
Cp H Cp C
Hot 1 0.047
Hot 2 0.032
5-5
HEN Design Grid (Example 5)
Cp in MW/K
Q in MW
C: Cold utility
H: Hot utility
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
5-6
HEN Flowsheet (Example 5)
7.05 MW
185°C
100°C 25°C
90°C 7.28 MW
Cold 1
1.67 MW 1.92 MW
185°C
H 66.3°C
140.5°C
100°C
C: Cold utility
H: Hot utility
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
5-7
Grand Composite Curve (Example 5)
T
°C
300
245 1.67 MW
200
190 4.225 MW
155 1.98 MW
145.6°C
100
95
9.15 MW
45
35 10.51 MW
30 9.95 MW
2 4 6 8 10 12 ∆H
MW
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
5-8
Grand Composite Curve (Example 5)
T
°C
300
245 1.67 MW
200
190 4.225 MW
100 Process
95 PINCH
9.15 MW
45
35 10.51 MW
30 9.95 MW
2 4 6 8 10 12 ∆H
MW
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
5-9
Grand Composite Curve (Example 5)
T
°C
300
245 1.67 MW
200
190 4.225 MW
100 Process
95 PINCH
9.15 MW
45
35 10.51 MW
30 9.95 MW
2 4 6 8 10 12 ∆H
MW
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
5-9
Heat Cascade (Example 5)
Hot ultility at
Top of Cascade Hot ultility
(Hot end) at Interval 3
1.670 0
245°C
I1 2.585 2.585
4.255 2.585
190°C
I2 - 2.275 - 2.275
1.980 0.310
155°C
0.033x9,4 - 0.31
I3 0
- 1.980 145.6°C
0.033x50,6
+ 1.67
- 1.67
0 0
95°C
I4 9.150 9.150
9.150 9.150
45°C
I5 1.360 1.360
10.510 10.510
35°C
I6 - 0.560 - 0.560
9.950 9.950
30°C
5 - 10
Design with two Segments above
the Process PINCH (Example 5, Variation 1)
Utility Process
PINCH PINCH
226.2°C
Hot 1 250°C 150.6°C
0.047 100°C
Cp in MW/K
Q in MW
H: Hot utility
5 - 11
Design with two Segments above
the Process PINCH (Example 5, Variation 2)
Utility Process
PINCH PINCH
212°C
Hot 1 250°C 150.6°C
100°C
0.047
Cp in MW/K
Q in MW
H: Hot utility
5 - 12
Simplified HEN Design Grid (Example 5)
Utility Process
PINCH PINCH
140.6°C 0.047
2.378
Cp in MW/K
Q in MW
5 - 13
Flowsheet of a simplified HEN with
Utility PINCH (Example 5)
50°C
2.350 MW
C Hot 2 Hot 3
2.378 MW
140.6°C
150.6°C
4.672 MW 7.280 MW
185°C 90°C 25°C
Cold 1
143.2°C
1.920 MW
145.2°C 1.670 MW
H 119.5°C
66.3°C
100°C
Hot 1
40°C 40°C
C: Cold utility
H: Hot utility
University of PROF. DR.
Applied Sciences Energy Recovery KLEEMANN
Emden
5 - 14
Energy Balance of the Heat Engine
Q1
Q2
W = Q1 - Q 2
6-1
Working Principle of a simple Heat Engine
Q1
4 1
Steam Producer
(Evaporator)
Turbine
Pump
W34 W12
Condenser
3 2
Q2
6-2
Working Steps of a
Clausius-Rankine-Steam Process
6-3
T,s - Plot of the
Clausius-Rankine - Steam Process
K
1 Tmax
4´
4
Tmin
3 2
6-4
Integration of a Heat Engine above the PINCH
Q
Q1 Q1 = Q - W
T1
Interval 1 Interval 1
Q2 Q2
T2
Interval 2 Interval 2
Q3 Q3
Q p-1 Q p-1
Tp-1
Interval p Interval p
Q p+1 Q p+1
6-5
Integration of a Heat Engine above the PINCH
Q1 Q1 = 0
T1
Q1
Interval 1 Interval 1
Q2 Q2 = 0
T2
Q2
Interval 2 Interval 2
W
Q3 Q3 = 0
Q p-1 Q p-1 = 0
Tp-1
Q p-1
Interval p-1 Interval p-1
PINCH Q p= 0 Q p= 0
Temperature
Interval p Interval p
Q p+1 Qp+1
6-6
Integration of a Heat Engine below the PINCH
Q1
Interval 1
Q2
Qp-1
Interval p-1
Qp = 0
PINCH
Temperature
Qp+1
Interval p
Qp+1 = 0
W
Qn - Qp+1
Interval n
Qn+1 - Qp+1 Qp+1 - W
6-7
Integration of a Heat Engine across the PINCH
Q1
Interval 1 Q
Q2
Interval p-1
W
Qp = 0
PINCH
Temperature
Q-W
Interval p
Qp+1 + (Q - W)
Interval p+1
Qp+2 + (Q - W)
Qn + (Q - W)
Interval n
Qn+1 + (Q - W)
6-8
Energy Balance of the Heat Pump
Q1
T1
T2
Q2
Q1 = Q 2 + W
6-9
Schematic of a simple Heat Pump
Q1
3 2
Condenser
Expansion Valve
Compressor
W12
Evaporator
4 1
Q2
6 - 10
Working Principle of a Heat Pump Process
6 - 11
T,s - Plot of State Changes during a
Heat Pump Cycle
p2 = p 3
K
x=1
2
p1
3
x=0
1
4
h3 = h4 Q2
s3 s 4 s1 = s2 s
6 - 12
Integration of a Heat Pump above the PINCH
Q 1 -W
T1
Q+W
Interval 1
T2
Q2 +Q
W
Q p-1 +Q
Tp-1
Q
Interval p-1
Tp
Qp = 0
Interval p
Tp+1
Qp+1
Qn
Tn
Interval n
Tn+1
Qn+1
6 - 13
Integration of a Heat Pump below the PINCH
T1 Q1
Interval 1
T2
Q2
Qp-1
Tp-1
Interval p-1
Tp
Qp = 0
Q+W
Interval p
Tp+1
Qp+1 + (Q+W)
W
Qn
Tn
Q
Interval n
Tn+1
Qn+1+W
6 - 14
Integration of a Heat Pump across the PINCH
Q1 - (Q+W)
T1
Interval 1
T2
Q2
Qp-1 - (Q+W)
Tp-1
Q+W
Interval p-1
W
Tp
Qp = 0
Q
Interval p
Tp+1
Qp+1 - Q
Qn - Q
Tn
Interval n
Tn+1
Qn+1 - Q
6 - 15
Integration of Distillation Columns into a HEN
Q cond
(Tcond )
Qreb
Feed Col
Qcond
Qreb
(Treb )
6 - 16
Integration of Columns above the PINCH
6 - 17
Integration of Columns above the PINCH
Col
Q cond
PINCH
Q C,min
6 - 18
Integration of Columns below the PINCH
T1 Q1 = Q H,min
Interval 1
T2 Q2
Interval 2
T3 Q3
Interval 3
T4 Q4
Interval 4
PINCH Q5 = 0
Tp = T5
Interval 5 Q reb
T6 Q6 - Qreb Col
Interval 6 Q cond
T7 Q 7 + (Q cond - Q reb )
Interval 7
T8 Q8 = Q C,min + (Q cond - Q reb )
6 - 19
Integration of Columns below the PINCH
Q H,min
PINCH
Q reb
Col
6 - 20
Integration of Columns across the PINCH
T1 Q 1 = Q H,min + Q reb
Interval 1
T2 Q 2 + Q reb
Interval 2
T3 Q3 + Qreb
Interval 3
T4 Q4
Q reb
Interval 4
PINCH Q5 = 0
Tp = T5 Col
Interval 5
T6 Q6 Q cond
Interval 6
T7 Q7 + Q cond
Interval 7
T8 Q8 = Q C,min + Q cond
6 - 21
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Worksheet 1
The composite curves of the hot and cold process streams are constructed with the
•
T, H - diagram. The required procedure has been postulated as follows:
1. Enter the temperature enthalpy profile of the hot and cold streams, which are to
be combined.
Corresponding to the above algorithm, the heat capacity flow rate is constant
within all temperature intervals.
3. The beginning and end temperatures of all individual hot and cold streams
indicate the temperature range within each temperature interval of the plot.
These intervals are highlighted by dotted lines.
4. The next step consists of the addition of the individual hot heat capacity flow
rates within each temperature interval.
5. Simultaneously the same is done for all cold heat capacity flow rates within
each interval.
• •
6. For each temperature interval a T, H - curve results. The slope of the T, H -
interval is determined by the sum of individual heat capacity flow rates occurring
in each interval. The slope algorithm is postulated as follows:
∆T 1
tan α = •
= •
∆H i ∑ Cpi
•
7. The complete hot composite curve is set together by joining the individual T, H -
curves.
9. The hot and cold composite curve show how the individual streams would
behave if they were a single stream.
worksheet_1_03-04-02.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Worksheet 2
1. The hot and cold streams are numbered separately. The use of the declarations
cold and hot for the numbering is recommended.
2. All individual cold streams are marked by horizontal lines running from right to
left on the schematic. The inlet and outlet temperature values should be entered
at each end of the streams.
3. Simultaneously all individual hot streams are marked by horizontal lines running
from left to right on the schematic.
4. A heat exchanger always indicates the coupling of two streams (hot and cold).
The couplings should be marked by circles, which connect a hot with a cold
stream. The heat duty of the exchanger should be entered on the schematic
too.
5. Coolers and heaters are shown by circles with the corresponding heat duty.
7. It is always helpful to enter all enthalpy differences and heat capacity flow rates
within the HEN design grid.
•
C p - table
•
C p tables are produced separately for the process streams below and above the
PINCH. They each consist of two columns.
•
1. Arrange the hot streams with decreasing C p - value in the left column.
•
2. Arrange the cold streams with decreasing C p - value in the right column.
•
It is helpful to designate the C p table with the corresponding stream type.
worksheet_2_03-04-02.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Worksheet 3
Rule 1: Split the process into two independent subsystems at the PINCH.
Rule 2: Design the HEN above and below the PINCH independently.
Rule 3: Above the PINCH the use of cold utility must be avoided, and no hot utility
can be placed below the PINCH.
Rule 4: The designer should start at the PINCH, because the PINCH is the most
constrained part of the problem.
Rule 5: The design must be checked against the arguments and criteria, which
were postulated before. Using the stream-splitting concept is a good tool
to simplify the design.
Rule 6: The streams which are to be combined, must be coupled in the order with
decreasing heat capacity flow rates, because these can best be matched
at the beginning of the design.
Rule 10: The placement of coolers and heaters should be done as the final step in
the design. Note that the heat duties of the cold and hot utilities must
conform to the values from the energy analysis (heat cascade or graphical
setting).
worksheet_3_03-04-02.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Worksheet 4/1
The table algorithm for the cascade can be used to calculate energy targets. The
calculation can be done in four steps (use worksheet 5).
step 1:
4. Determine the temperature intervals and enter them into the corresponding
column.
step 2:
The second step includes the energy balancing for each interval. The heat capacity
flow rates of hot streams count negative and those of cold streams count positive.
• •
2. Determine the enthalpy flow rates ∆ H i by multiplying the C pi with the
temperature difference ∆Ti.
3. Positive values for enthalpy flow rates indicate a deficit and negative values a
surplus.
step 3:
The heat duty in each interval is solved by removing or adding heat from external
heat sinks or sources (see column “Balanced Energy ...”). The heat balance allows
maximum heat recovery within each interval. However, heat recovery can also be to
carry out between intervals.
The surplus heat can now be cascaded down the temperature scale from interval to
interval. The point where the heat flow approaches the minimum corresponds to the
PINCH.
worksheet_4_03-04-02.doc
University of Applied Sciences
Oldenburg/Ostfriesland/Wilhelmshaven Energy Recovery Prof. Dr. G. Kleemann
Department of
Applied Natural Sciences PINCH Method Worksheet 4/2
step 4:
The cascade is solved by adding the amount of heat with which the energy flow
becomes zero at the PINCH to the hot utility at the top of the cascade. This does not
change the heat balance of the heat cascade but increases all the heat flows
between the intervals. This permisses an energy flow from high temperatures to low
temperatures.
The energy flow can now be cascaded down the intervals till the energy goes to zero
at the PINCH (column “cascade 2”). At the top of the cascade the smallest amount of
heat can be seen which must be added to the hot utility. The amount of heat to be
removed shows the value at the bottom of the cascade. The results correspond with
the graphical setting of the composite curves. Finally the heat cascade concludes
with “cascade 3” in which the enthalpy differences are shown as surpluses and
deficits.
worksheet_4_03-04-02.doc
Worksheet 5: Heat Cascade
( Please Note: Hot and cold streams must be shifted by ∆Tmin /2. Hot streams: - ∆Tmin /2. Cold streams: + ∆Tmin /2. )
Balanced energy
number
Σ Cp i
Interval
Hi
Surplus
Deficit /
Streams within the interval
Cascade 1 Cascade 2 Cascade 3
[K] [ kW/K ] [ kW ] Hi
T1 = °C
1
T2 = °C
2
T3 = °C
3
T4 = °C
4
T5 = °C
5
T6 = °C
6
T7 = °C