3 - CPS Pump Design Calculation 1
3 - CPS Pump Design Calculation 1
ENGINEERING CONSULTANCY
Designed By : RSA Checked By : RSA
Subject : PUMP DESIGN CALCULATION
Date : 07-21-18 Date : 07-21-18
DAILY FLOWRATE :
= 13,500.00 GALLONS
= 51.10 cu. M
II. DAILY VOLUMETRIC FLOWRATE DEMAND 51.10 cu. M say 50.00 cu. M
III. HOURLY PEAK VOL. FLOWRATE 15.00 cu. M / Hr say 15.00 cu. M / Hr
~ 66.05 GPM
Hor. Run 30 M
DOMESTIC PUMP MOTOR :
Res. Pressure 20 PSI
14.08 M TPm = 4.94 HP (Approx. @ 60% Efficiency)
156.39 FT
P @ 68 PSI
NOTE:
Motor rating must be validated to the pump manufacturer.