You are on page 1of 1

Project : SELAHPADS R.S. ALCALA JR.

ENGINEERING CONSULTANCY
Designed By : RSA Checked By : RSA
Subject : PUMP DESIGN CALCULATION
Date : 07-21-18 Date : 07-21-18

DAILY FLOWRATE :

I. DAILY VOLUMETRIC FLOWRATE DEMAND ( 8th, 9th & 10th)

= 11,070.00 GALLONS
= 41.90 cu. M

II. DAILY VOLUMETRIC FLOWRATE DEMAND 41.90 cu. M say 40.00 cu. M

III. HOURLY PEAK VOL. FLOWRATE 12.00 cu. M / Hr say 12.00 cu. M / Hr
~ 52.84 GPM

say 1x 50.00 GPM


TOTAL RUNNING CAPACITY

HOT Water Recir PUMP CONFIGURATION

2 x 50 GPM (DUPLEX TYPE / N+1)

IV. HYDRAULIC CALCULATION

TOTAL DYNAMIC HEAD: WATER HP :

Static Head 31.6 M WP = Q ɤ TDH = 1.98 HP

Friction Head 2.00 M

Hor. Run 30 M
HW PUMP MOTOR :
Res. Pressure 20 PSI
14.08 M TPm = 3.30 HP (Approx. @ 60% Efficiency)

TDH = 47.68 M say 4.0 HP

156.39 FT

P @ 68 PSI

NOTE:
Motor rating must be validated to the pump manufacturer.