PUMPING MAIN DESIGNS

NAME OF WORK :- CONSTRUCTION PROPOSED MEDICAL COLLEGE AT MACHILIPATNAM IN KRISHNA DISTRICT,


ANDHRAPRADESH .
FLUSH WATER ( HOSPITAL & ANCILLARIES

Maximum Height Of Building 11.90 M ( 2.0 m Additional Consider for below ground )
Height of Roof Tank above Terrace Floor 2.00 M
Suction Head 3.00 M
RCC Tank side wall Height/ Syntex Tank 2.00 M
Tank Inlet Residual Head 5.00 M
Ground Level Difference 2.00 M
Frictional Losses 6.00 M
Additional Losses 6.00 (Safety Factor)
Static Head Discharge Head -Suction Head
Sump Possitive suction 4.00
Static Head 21.90

Total Dyanimic Head Static Head+Frictional Losses

33.90
SAY 33.90
Daily Pumping Hours 3 Hours
Daily water Requirement 125000.00 Liters
Pumping rate 31250.00 Liters
8.68 l/sec
0.009 cum/sec
H.P of pump = ¡W . Q . H
0.735 h

Where n = Efficiency of Pump


H.P 6.04

H.P 7.50

Twp Pumps of 7.50 H.P Pumps (1 working+1 stand by)

Pump Company Groundfous


Hydro System (Filling Tanks )
PUMPING MAIN DESIGNS
NAME OF WORK :- CONSTRUCTION PROPOSED MEDICAL COLLEGE AT MACHILIPATNAM IN KRISHNA DISTRICT,
ANDHRAPRADESH .
QUARTERS

Maximum Height Of Building 11.90 M ( 2.0 m Additional Consider for below ground )
Height of Roof Tank above Terrace Floor 2.00 M
Suction Head 3.00 M
RCC Tank side wall Height/ Syntex Tank 2.00 M
Tank Inlet Residual Head 5.00 M
Ground Level Difference 2.00 M
Frictional Losses 5.00 M
Additional Losses 5.00 (Safety Factor)
Static Head Discharge Head -Suction Head
Sump Possitive suction 4.00
Static Head 21.90

Total Dyanimic Head Static Head+Frictional Losses

31.90
SAY 31.90
Daily Pumping Hours 3 Hours
Daily water Requirement 30400.00 Liters
Pumping rate 10133.33 Liters
2.81 l/sec
0.003 cum/sec
H.P of pump = ¡W . Q . H
0.735 h

Where n = Efficiency of Pump


H.P 1.84

H.P 3.00

Twp Pumps of 3.00H.P Pumps (1 working+1 stand by)

Pump Company Groundfous


Hydro System (Filling Tanks )
PUMPING MAIN DESIGNS

NAME OF WORK :- CONSTRUCTION PROPOSED MEDICAL COLLEGE AT MACHILIPATNAM IN KRISHNA DISTRICT,


ANDHRAPRADESH .
MEDICAL COLLEGE , LT HALL &GUEST HOUSE

Maximum Height Of Building 12.98 M ( 2.0 m Additional Consider for below ground )
Height of Roof Tank above Terrace Floor 2.00 M
Suction Head 3.00 M
RCC Tank side wall Height/ Syntex Tank 2.00 M
Tank Inlet Residual Head 5.00 M
Ground Level Difference 2.00 M
Frictional Losses 4.00 M
Additional Losses 4.00 (Safety Factor)
Static Head Discharge Head -Suction Head
Sump Possitive suction 4.00
Static Head 22.98

Total Dyanimic Head Static Head+Frictional Losses

30.98
SAY 30.98
Daily Pumping Hours 3 Hours
Daily water Requirement 92500.00 Liters
Pumping rate 30833.33 Liters
8.56 l/sec
0.009 cum/sec
H.P of pump = ¡W . Q . H
0.735 h

Where n = Efficiency of Pump


H.P 5.45

H.P 7.50

Twp Pumps of 7.50 H.P Pumps (1 working+1 stand by)

Pump Company Groundfous


Hydro System (Filling Tanks )
PUMPING MAIN DESIGNS
NAME OF WORK :- CONSTRUCTION PROPOSED MEDICAL COLLEGE AT MACHILIPATNAM IN KRISHNA DISTRICT,
ANDHRAPRADESH .
HOSTEL BLOCKS

Maximum Height Of Building 11.90 M ( 2.0 m Additional Consider for below ground )
Height of Roof Tank above Terrace Floor 2.00 M
Suction Head 3.00 M
RCC Tank side wall Height/ Syntex Tank 2.00 M
Tank Inlet Residual Head 5.00 M
Ground Level Difference 2.00 M
Frictional Losses 5.00 M
Additional Losses 5.00 (Safety Factor)
Static Head Discharge Head -Suction Head
Sump Possitive suction 4.00
Static Head 21.90

Total Dyanimic Head Static Head+Frictional Losses

31.90
SAY 31.90
Daily Pumping Hours 3 Hours
Daily water Requirement 81890.00 Liters
Pumping rate 27296.67 Liters
7.58 l/sec
0.008 cum/sec
H.P of pump = ¡W . Q . H
0.735 h

Where n = Efficiency of Pump


H.P 4.97

H.P 7.50

Twp Pumps of 7.50H.P Pumps (1 working+1 stand by)

Pump Company Groundfous


Hydro System (Filling Tanks )
PUMPING MAIN DESIGNS
NAME OF WORK :- CONSTRUCTION PROPOSED MEDICAL COLLEGE AT MACHILIPATNAM IN KRISHNA DISTRICT,
ANDHRAPRADESH .
HOSPITAL BLOCKS & ANCILLARIES

Maximum Height Of Building 12.80 M ( 2.0 m Additional Consider for below ground )
Height of Roof Tank above Terrace Floor 2.00 M
Suction Head 3.00 M
RCC Tank side wall Height/ Syntex Tank 2.00 M
Tank Inlet Residual Head 5.00 M
Ground Level Difference 2.00 M
Frictional Losses 5.00 M
Additional Losses 5.00 (Safety Factor)
Static Head Discharge Head -Suction Head
Sump Possitive suction 4.00
Static Head 22.80

Total Dyanimic Head Static Head+Frictional Losses

32.80
SAY 32.80
Daily Pumping Hours 3 Hours
Daily water Requirement 275000.00 Liters
Pumping rate 68750.00 Liters
19.10 l/sec
0.019 cum/sec
H.P of pump = ¡W . Q . H
0.735 h

Where n = Efficiency of Pump


H.P 12.86

H.P 7.50

Twp Pumps of 7.50H.P Pumps (2 working+1 stand by)

Pump Company Groundfous


Hydro System (Filling Tanks )
PUMPING MAIN DESIGNS

NAME OF WORK :- CONSTRUCTION PROPOSED MEDICAL COLLEGE AT MACHILIPATNAM IN KRISHNA DISTRICT,


ANDHRAPRADESH .
COLLEGE , HOSTELS & QUARTERS

Maximum Height Of Building 11.90 M ( 2.0 m Additional Consider for below ground )
Height of Roof Tank above Terrace Floor 2.00 M
Suction Head 3.00 M
RCC Tank side wall Height/ Syntex Tank 2.00 M
Tank Inlet Residual Head 5.00 M
Ground Level Difference 2.00 M
Frictional Losses 6.00 M
Additional Losses 6.00 (Safety Factor)
Static Head Discharge Head -Suction Head
Sump Possitive suction 4.00
Static Head 21.90

Total Dyanimic Head Static Head+Frictional Losses

33.90
SAY 33.90
Daily Pumping Hours 3 Hours
Daily water Requirement 70400.00 Liters
Pumping rate 23466.67 Liters
6.52 l/sec
0.007 cum/sec
H.P of pump = ¡W . Q . H
0.735 h

Where n = Efficiency of Pump


H.P 4.54

H.P 5.00

Twp Pumps of 5.00 H.P Pumps (1 working+1 stand by)

Pump Company Groundfous


Hydro System (Filling Tanks )
PUMPING MAIN DESIGNS

NAME OF WORK :- CONSTRUCTION PROPOSED MEDICAL COLLEGE AT MACHILIPATNAM IN KRISHNA DISTRICT,


ANDHRAPRADESH .
MEDICAL COLLEGE & LT HALL
Suction Head 3.00 M
Residual Head 5.00 M
Ground Level Difference 2.00 M
Frictional Losses 2.00 M
Additional Losses 2.00 (Safety Factor)
Static Head Discharge Head -Suction Head
Sump Possitive suction 4.00
Static Head 6.00

Total Dyanimic Head Static Head+Frictional Losses

10.00
SAY 10.00
Daily Pumping Hours 1Hours
Daily water Requirement 50000.00 Liters
Pumping rate 50000.00 Liters
13.89 l/sec
0.014 cum/sec
H.P of pump = ¡W . Q . H
0.735 h

Where n = Efficiency of Pump


H.P 2.85

H.P 3.00

Twp Pumps of 3.00 H.P Pumps (1 working+1 stand by)

Pump Company Groundfous


Hydro System