vi. The installation shall then be left for three hours and shall then be tested for residual
chlorine; if none is found, the installation shall be drained and the process repeated.
vii. The installation shall be finally drained and flushed with potable water before use.
ii. GI pipes below ground shall be measured per linear metre along the centre line of
the pipe and shall be inclusive of all fittings e.g. couplings, tees, bends, elbows,
unions and flanges, etc. Deduction for valves shall be made. Rates quoted shall be
inclusive of all fittings, cutting holes and chases and making good the same and all
other items mentioned in the specifications and Schedule of Quantities. Excavation,
filling, back filling with selected excavated earth, compaction and disposal of surplus
earth, fine sand filling around GI pipes, in external work shall be measured
separately, as per respective items.
There are many fountains in the garden of Ujjayanta Palace and the water demand of these
fountains will be catered by the existing Ponds.
There are two Ponds in the Ujjayanta Place where the natural water is stored, the same water
will be used for fountains. Two water treatment plants are proposed (one for each Pond).
Bidding Document for Renovation of Ujjayanta Palace Complex Procurement of Works Single-Stage: Two-Envelope
Section 6 - Employer’s Requirements 6-192
Two submersible pump sets (1W+1S) will be placed in the pond itself to feed the Water
Treatment plant consisting of Dual Media Filter & dosing system.
Each fountain will be having its individual inlet from the main header line coming from water
treatment plant with automation like water level sensor & solenoid valves.
For cleaning and maintenance purpose a drainage network is also proposed, and the drained
water will be collected in the Ponds.
Capacity 90 m3/hr
Head 35 Meter
Quantity 1W+1S
Bidding Document for Renovation of Ujjayanta Palace Complex Procurement of Works Single-Stage: Two-Envelope
Section 6 - Employer’s Requirements 6-193
Capacity 90 m3/hr
Height 3M
Bidding Document for Renovation of Ujjayanta Palace Complex Procurement of Works Single-Stage: Two-Envelope
Section 6 - Employer’s Requirements 6-194
Dosing Pump
Capacity 0 - 6 LPH
MOC PP
Dosing Tank
MOC HDPE
Bidding Document for Renovation of Ujjayanta Palace Complex Procurement of Works Single-Stage: Two-Envelope