Section 6 - Employer’s Requirements 6-191

v. The installation shall be topped up and more sterilizer added.

vi. The installation shall then be left for three hours and shall then be tested for residual
chlorine; if none is found, the installation shall be drained and the process repeated.

vii. The installation shall be finally drained and flushed with potable water before use.

h) Measurement And Rates

I. GI and CPVC pipes


i. GI pipes above ground shall be measured per linear metre along the centre line of
the pipe and shall be inclusive of all fittings e.g. couplings, tees, bends, elbows,
unions, flanges, etc. Deduction for valves shall be made. Rates quoted shall be
inclusive of all fittings, clamps, cutting holes chases and making good the same and
all other items mentioned in the specifications and Schedule of Quantities.

ii. GI pipes below ground shall be measured per linear metre along the centre line of
the pipe and shall be inclusive of all fittings e.g. couplings, tees, bends, elbows,
unions and flanges, etc. Deduction for valves shall be made. Rates quoted shall be
inclusive of all fittings, cutting holes and chases and making good the same and all
other items mentioned in the specifications and Schedule of Quantities. Excavation,
filling, back filling with selected excavated earth, compaction and disposal of surplus
earth, fine sand filling around GI pipes, in external work shall be measured
separately, as per respective items.

II. Valves, Bib cocks and stop cocks


Gunmetal and cast iron valves, Bib cocks and stop cocks shall be measured by numbers.

III. Flanges for Nozzles


Flanges for nozzles shall be measured by numbers and the quoted rate shall include welding of
the flanges to the pipe nozzles.

IV. Painting/ pipe protection/ insulation


Unless otherwise specified painting/ pipe protection/ insulation for pipes shall be measured and
paid upon completion. These shall be measured per linear metre along the centre line of the
pipe, over the finished surface and shall include all valves and fittings for which no deduction
shall be made.

1.7 Mechanical Works For Water Bodies

There are many fountains in the garden of Ujjayanta Palace and the water demand of these
fountains will be catered by the existing Ponds.
There are two Ponds in the Ujjayanta Place where the natural water is stored, the same water
will be used for fountains. Two water treatment plants are proposed (one for each Pond).

Bidding Document for Renovation of Ujjayanta Palace Complex Procurement of Works Single-Stage: Two-Envelope
Section 6 - Employer’s Requirements 6-192

Two submersible pump sets (1W+1S) will be placed in the pond itself to feed the Water
Treatment plant consisting of Dual Media Filter & dosing system.
Each fountain will be having its individual inlet from the main header line coming from water
treatment plant with automation like water level sensor & solenoid valves.
For cleaning and maintenance purpose a drainage network is also proposed, and the drained
water will be collected in the Ponds.

1.7.1 Pump Details


Pump Details

Item Description Design Specifications

Type of Pump Submersible Pump Set

Capacity 90 m3/hr

Working Hours 3 hrs

Head 35 Meter

Purpose To feed WTP

Quantity 1W+1S

Pump Header 100 mm

Header MOC MSEP

1.7.2 Water Treatment Plant:


The proposed Water Treatment Plant based on Filter Technology is designed to produce
product water at the flow rate of 90.0 m3/hr. A dual media filter followed by chlorine dosing
system is proposed in the system. Detail description of water treatment plant are as follows:
The Proposed Water Treatment system is based on assumptions of inlet water parameter which
are subjected to change based on the actual water parameters of pond.

1.7.3 Inlet water parameters


Inlet water parameters

Total Suspended Solids (TSS) <100 mg/l

Turbidity <50 NTU

Bidding Document for Renovation of Ujjayanta Palace Complex Procurement of Works Single-Stage: Two-Envelope
Section 6 - Employer’s Requirements 6-193

1.7.4 Outlet water parameters


Outlet water parameters

Total Suspended Solids (TSS) < 50 mg/l

Turbidity < 5 NTU

1.7.5 Dual Media Filter


Dual Media Filter

Item Description Design Specifications

Type of Filter Vertical Downstream Pressure Vessel

Capacity 90 m3/hr

Working Hours 3 hrs

Mode of operation Manual

Filtration Rate 12m2/m3/hr

Size of Vessel 2750 mm Dia x 1800 mm HOS

Height 3M

Valves 5 Valves Battery, Butterfly Type

MOC MSEP outside, MSRL inside

Rubber Lining 3mm

Vessel Thickness 6mm

Dish & Strainer plates 9mm

Operating Pressure 3.5 kg/cm2

Design Pressure 5.25 kg/cm2

Internal Water Distribution Common header with Inverted Bell Mouth

Internal Water Collection Header Laterals

Filter Media Fine Sand, Coarse Sand, Pebbles, Gravels,

Bidding Document for Renovation of Ujjayanta Palace Complex Procurement of Works Single-Stage: Two-Envelope
Section 6 - Employer’s Requirements 6-194

Activated Carbon Granules

Activated Carbon Iodine value 900 IV

Valves Six valve Operation

Valve Type Butterfly

Service Cycle Whenever pressure drop exceeds 0.8 Kg/cm2.

Backwash Duration 15-30 minute

Backwash Mode Manual

Frontal Piping MSEP

All Inter Connecting Piping MSEP

Pressure Gauge 01 No. at Inlet & 01 No. at Outlet

Pressure Gauge Make Micro / Equivalent

Rota Meter 01 No. at Inlet & 01 No. at Outlet

Rota Meter Make Aster / Equivalent

1.7.6 Chlorine Dosing System


Chlorine Dosing System

Item Description Design Specifications

Dosing Pump

Capacity 0 - 6 LPH

MOC PP

Make E-Dose/ Equivalent

Dosing Tank

MOC HDPE

Capacity 100 Litre

Bidding Document for Renovation of Ujjayanta Palace Complex Procurement of Works Single-Stage: Two-Envelope