1- Cold water booster pump/ To serve the fixtures which require
S.NO TYPE OF FIXTURE Frequency of use NUMBER OF FIXTURES LOADING UNITS
PER FIXTURE TOTAL LOADING (COLD WATER) UNITS (COLD WATER) 1 BATH Low 131.00 4 524 2 WB Low 186.00 1 186 3 SHOWER Low 0.00 2 0 4 WC Low 186.00 1 186 5 HAND SPR Low 186.00 1 186 6 KITCHEN SINK Low 124.00 2 248 7 WASHING MACHINE Low 124.00 2 248 8 DISHWASH Low 0.00 2 0 9 Bibtaps,Provisions & etc L.U Low 8.00 2.00 16 Total Loading Units 1594 Flow rate (L/s) 9.5 Selected Booster pump set ( 1 duty & 1 assist ) with flow rate per each (L/s) 4.75
BOOSTER PUMP HEAD CALCULATION COLD WATER BOOSTER PUMP DCWP-E-01
ITEM DESCRIPTION DBCWP-01 Unit
NO. A PUMP CAPACITY 1 Total flow rate 4.75 L/s 2 Velocity of the Fluid 1.80 m/s 0.040 m/m 3 Friction rate 400.000 pa/m B PUMP HEAD 1 Vertical Height (m) 6.80 m 2 Pipe Friction Rate m/m 0.0400 m/m 3 Horizontal Length of Pipe (m) 95.00 m 4 Fitting Losses 50% Supply length (m) 47.50 m 5 Total Length Of Pipes (m) 149.30 m 6 Total Pipe Friction Loss (m) 5.97 m 8 residual pressure (m) 15.00 m 9 Total Pressure required (m) 27.77 m B PUMP Selection 1 Flow rate ( 1 Duty + 1 assist) Pump for each 4.75 l/s 2 Head ( 1 Duty + 1 assist) Pump for each 28.00 m 2 Estimated Power for each 2.50 kw
PRESSURE VESSEL(PV) Tank Volume
Pump Capacity in (LPM) 285.00
Considering 10% of total capacity for 10mins for PV
Pressure Vessel = 10% of pump capacity in LPM x 10Min