You are on page 1of 7

Designing laboratory

ventilation systems
Proper ventilation in labs is required to promote and maintain safety
and protection to life and property.

BY J. PATRICK BANSE, PE, and CHRIS ST. CYR, Smith Seckman Reid Inc., Houston

P
roper ventilation of laboratory set- logical observation of laboratory animals
Learning tings is required to promote and and also include animal holding rooms.
objectives maintain laboratory safety and pro- 4. Physical laboratories are spaces
 Understand the codes and tection to life and property. Items such as associated with physics and include
standards that guide labora- fume containment, worker safety, proper lasers, optics, high- and low-temperature
tory ventilation design. cleanliness through pressure relation- materials, and analytical instruments.
 Learn how to design labora- ships, filtration, air changes per hour Biological laboratories commonly
tory ventilation systems to (ACH), point of fume capture, tempera- have chemical fume hoods and Class I
meet system requirements. ture, and relative humidity requirements and Class II bio-safety cabinets. Chemi-
 Understand key equipment are elements necessary to design the ven- cal labs generally have a number of fume
functions.
tilation system depending on the labora- hoods.
tory type. Codes identify ventilation mea- This article will provide information on
sures to provide minimum requirements hood types and ventilation criteria primar-
for the protection of life and property ily on the first three types of labs, with
through prevention and control discussion on contaminant containment,
of fumes and containment of airflow practices, comfort conditioning,
Fume hood—bypass constant hazardous fumes and contami- and the codes that govern the lab ventila-
volume (sash open) nants for worker safety. tion systems.
There are four general types
Ceiling of laboratories noted in the Applicable codes and standards
Exhaust duct
ASHRAE Handbook—HVAC The 2011 edition of NFPA 45: Standard
Applications: on Fire Protection for Laboratories Using
1. Biological: Contains bio- Chemicals applies to laboratory buildings,
Fume logically active materials and units, and work areas in which defined
hood
includes areas such as biochem- chemicals are handled or stored. Chap-
Open sash istry, cell biology, immunology, ter 8, Laboratory Ventilating System and
pharmacology, microbiology, Hood Requirements, defines criteria and
Air flow
and related fields. Clinical lab- considerations for exhaust air and supply
oratories fall into this category. air systems including requirements for
2. Chemical laboratories that fume hood exhaust.
Floor support both organic and inor- ANSI/AIHA Z9.5-2012 - Laboratory
ganic synthesis and analytical Ventilation describes required and recom-
functions. mended practices for the design and opera-
Figure 1: Standard constant volume fume hood 3. Animal labs that include tion of lab ventilation systems for control
shows a typical airflow pattern. All graphics cour- areas for the observation, of exposure to airborne contaminants. It
tesy: Smith Seckman Reid manipulation, and pharmaco- does not apply to animal facilities, laminar

36 Consulting-Specifying Engineer • JANUARY/FEBRUARY 2014 www.csemag.com


minimum ventilation rates in volume exhaust airflow) shown in Figure
Fume hood—bypass constant the breathing zone (Table 6-1) 2; variable volume fume hood (constant
volume (sash closed) and minimum exhaust rates face velocity); and auxiliary air fume
(Table 6-4) for laboratories and hood (constant volume exhaust airflow
Ceiling Exhaust duct other spaces. (Standard 62.1- with 50% to 70% makeup air directly to
Louvered 2013 was released in Novem- hood).
bypass
opening
ber 2013.) Additionally, there are biological
The International Building safety cabinets used in clinical lab set-
Air flow
Code (IBC) in the occupancy tings that include Class I, which is simi-
Fume chapter 304 defines testing and lar to a chemical fume hood (see Figure
hood Closed sash research laboratories as a Busi- 3); and a Class II A1 bio-safety cabinet
ness Group “B” occupancy. The that includes high-efficiency particulate
Low bypass
opening International Mechanical Code absorption (HEPA) supply filters and
(IMC) in Table 403.3 identifies HEPA exhaust filters that allow air to
Air flow minimum ventilation rates for be re-circulated to the lab or exhausted
Floor science laboratories, and sec- directly outside (see Figure 4).
tion 510 explains the require- A Class II B1 bio-safety cabinet is simi-
ments for laboratory exhaust lar; however, all air is removed through
Figure 2: A bypass constant volume fume hood systems. a HEPA filter and exhausted directly
shows a typical airflow pattern with sash closed. There are other standards as outside. A Class III bio-safety cabinet is
well, such as OSHA 29 CFR completely enclosed and the work is done
flow hoods, or bio-safety cabinets. Chap- 1910.1450: Occupational exposure to through gloves attached to the cabinet.
ter 5 of this standard discusses laboratory hazardous chemicals in laboratories and This cabinet is exhausted directly outside
ventilation system designs. 21 CFR 58: Good Laboratory Practice with no recirculation allowed. The figures
In the 2011 ASHRAE Handbook— Regulations, which while giving guid- illustrate the differing airflow patterns and
HVAC Applications, Chapter 16 pro- ance, do not specifically require or specify filtration requirements.
vides detailed descriptions of laboratory ventilation rates or practices. Generally, when working in a required
airflow, fume hood types, hazard assess- The more recent editions of several clean environment such as when mixing
ments, exhaust systems, and applications codes and standards have less focus on medications (pharmacy) or working with
to various lab types. minimum or required air change rates and infectious bacteria (research), airflow direc-
NFPA 99: Health Care Facilities Code, more focus on proper capture of fumes tion and air cleanliness are requirements.
2012 edition, has deleted the previously and contaminants, protection
included chapter pertaining to laborato- of workers, proper hood design
ries and has added a new Chapter 4, which and sash face velocity, supply Bio-safety cabinet, Class I
establishes four “Categories of Risk.” Also air distribution, and pressure
included is Chapter 9 outlining HVAC relationships. As with any
Ceiling
requirements for health care facilities. Ref- project design, it is appropri- Exhaust duct
erences are made in this chapter to NFPA ate to determine which codes
45 and ASHRAE Standards 90.1, 90A, and and standards are officially HEPA
170. This code will pertain primarily to adopted by the authority hav- filter
clinical labs and related spaces whether ing jurisdiction (AHJ) so that
Bio-cabinet
within a hospital or separate building. the correct and more stringent
The 2010 edition of FGI Guidelines requirements can be incorpo-
for Design and Construction of Health- rated into the design. Air flow
care Facilities incorporates ASHRAE
170-2008 (with addenda): Ventilation of Fume hood types Air flow
Health Care Facilities, which has spe- Some common types of
cific requirements for laboratory ventila- fume hoods used in clinical and Floor
tion including pressure relationships, air chemical labs include standard
change rates, and temperature and relative fume hoods (constant volume
humidity requirements. exhaust airflow with variable Figure 3: This Class I bio-safety cabinet shows a
ASHRAE Standard 62.1: Ventilation for face velocity) shown in Figure typical airflow pattern and HEPA filter location and
Acceptable Indoor Air Quality identifies 1; bypass fume hood (constant laminar airflow.

www.csemag.com Consulting-Specifying Engineer • JANUARY/FEBRUARY 2014 37


Laboratory ventilation
Bio-safety cabinets provide that cleanli- Canopy hoods are open on the sides and air change rates, pressure relationships,
ness and direction with placement of the primarily used to remove heat and water and temperature and relative humidity
HEPA filters at the point of air delivery and vapor from work areas. This hood type is requirements.
removal. HEPA filters carry a minimum not a true fume hood and should not be Functions associated with clinical labs
efficiency reporting value—commonly used as a substitute for one. include bacteriology, biochemistry, cytol-
known as MERV—rating of 17 or higher. Open sash face velocities are between ogy, glass washing, histology, microbiol-
75 ft per minute (fpm) and ogy, pathology, and serology, as well as
120 fpm, with 100 fpm being general lab functions. Many of these func-
Bio-safety cabinet, Class II A1 an average velocity or rule of tions occur in smaller separate rooms due to
thumb for preliminary air cal- odors, space temperature, and local capture
culations depending on what requirements—as well as worker safety.
Ceiling
chemicals are stored or used Supply airflow arrangement, airflow
HEPA filter in the hood. A velometer is velocity, and point of capture are all
attached to the fume hood to extremely important to the overall func-
measure face velocity and tion and successful containment of con-
Air flow inform users if the hood is safe taminants, odors, and gas vapors. Supply
Bio-cabinet to use. The hood sensors may air devices of Group A (outlets mounted
alarm locally or be connected in or near the ceiling that discharge air
Air flow to the building automation sys- horizontally) or E (outlets mounted in or
tem (BAS). near the ceiling that project primary air
ASHRAE Standard 110: vertically) should be located in the ceil-
Method of Testing Perfor- ing where practical and deliver air so the
Floor mance of Laboratory Fume velocity near a fume hood is approxi-
Hoods, defines the criteria for mately 50% of the hood face velocity or
containment performance of a in most cases about 50 fpm. Hoods should
Figure 4: Class II A1 bio-safety cabinet has a typi- fume hood using a tracer gas be located out of the general walkway to
cal airflow pattern and HEPA filter location with and instruments to measure minimize air currents and disruption of
laminar airflow with clean supply and discharge air. the amounts of tracer gas that airflow. The HVAC design engineer must
enters the breathing zone of a be involved in the lab planning to provide
mannequin. This test simulates input to make the airflow and ventilation
General lab—negative the containment capability of system functional without sacrificing
Fume exhaust hood the hood. A face velocity test, safety. Computational fluid dynamics
exhausted to outside
flow visualization test, large (CFD) may be a consideration in special
volume visualization test, trac- cases or for complex HVAC/lab designs.
er gas test, and sash movement According to ASHRAE 62.1-2010, air
test are all performed under (return, transfer, exhaust) shall be clas-
this standard. The standard has sified and its recirculation limited in
specific requirements that must accordance with its classification. There
Pressure
sensor be met for the hood to comply. are four classes of air according to the
General lab standard.
Lab considerations Class 1: Air with low contaminant con-
Clinical (biological) labs centration, low sensory-irritation inten-
are generally located in hos- sity, and inoffensive odor. Class 1 air may
pitals but are sometimes sepa- be recirculated or transferred to any space.
rate, independent, and located Class 2: Air with moderate contami-
Negative to adjacent corridor away from the patient care nant concentration, mild sensory-irrita-
and treatment areas. The lab tion intensity, or mildly offensive odors.
Figure 5: This general lab layout shows pressure may be classified as a business Class 2 air may be recirculated within the
relationship, typical fume hoods, and pressure sen- (B) occupancy, but if located space of origin, but not to a Class 1 space.
sor location. Airflow should be balanced to create within the hospital, it is subject Class 3: Air with significant contami-
a constant airflow offset resulting in the negative to hospital licensing require- nant concentration, significant sensory-
pressure relationship. ments, which include proper irritation intensity, or offensive odor.

38 Consulting-Specifying Engineer • JANUARY/FEBRUARY 2014 www.csemag.com


Class 3 air may be recirculated within the
space of origin, but not to any other space.
Class 4: Air with highly objectionable
fumes or gases or with potentially dan-
gerous particles, bioaerosols, or gases at
concentrations high enough to be con-
sidered harmful. Class 4 air shall not be
recirculated or transferred to any space
nor recirculated within the space of origin.
Fume hood exhaust air is defined by
Standard 62.1 in Table 5-2 as a Class 4.
NFPA 45, paragraphs 8.3 and 8.4, also
coincide with this requirement. Outdoor
air established as a minimum ventilation
rate in the Standard lists 10 cfm/person
and 0.18 cfm/sq ft as a minimum for the
breathing zone, which is defined as a Figure 6: This shows a bypass fume hood recessed into the lab wall on top of a flam-
space 3 to 72 in. above the floor. mable storage cabinet with workspace adjacent. Notice the airflow velocity meter on
Class 4 fume hood air discharge separa- the right of the hood.
tion from air intakes or operable windows
should be no closer than 30 ft but also ficient velocity (3000 fpm minimum) and each hood to its own fan or be manifolded
meet the requirements of NFPA 45 and with adequate stack height (7 ft minimum from several hoods to one fan. This latter
ANSI/AIHA Z9.5. Exhaust rates noted above roof level, 10 ft recommended) to arrangement requires careful air balancing
in ASHRAE 62.1 Table 6-4 for science allow fan observation and maintenance and possibly redundant discharge fans to
labs note a minimum exhaust rate of 1.00 without being exposed to the discharge avoid an entire lab being shut down upon
cfm/sq ft. With enough fume hoods this airstream. The stack height provides bet- a loss of airflow. Additionally, compatibil-
can usually be met, but localized exhaust ter opportunity for dilution as well. To ity of chemicals and contaminants must
for odor control and/or to meet minimum achieve sufficient air velocity, an exit cone be carefully evaluated before exhaust
ventilation rates, air change, or non- that reduces the outlet stack diameter and streams are combined to avoid potential
recirculation requirements may also be thus increases the air velocity may be nec- hazards or corrosion. Manifolded systems
needed. essary. Keep in mind this sudden diameter can be either constant volume or variable
volume. Pressure-dependent systems are
Localized exhaust for odor control and/or to constant volume only and usually employ
manual volume dampers for balancing.
meet minimum ventilation rates, air change, or Any changes to a system such as adding
non-recirculation requirements may also be needed. or removing a fume hood would require
re-balancing of the entire system.
One thing to note is that ventilation change can add a significant pressure drop Pressure-independent systems are either
air is defined in ASHRAE 62.1-2010 as by an average of 0.5 in. w.g. Redundant constant or variable volume and employ
that portion of supply air that is outdoor fans for critical applications are often pressure-independent air volume regula-
air plus any recirculated air that has been employed to provide constant airflow in tors or air valves with each fume hood
treated for the purpose of maintaining hoods and similar applications. Controls or exhaust device. Control of the airflow
indoor air quality (IAQ). While the major- for fan operation usually consist of cur- device can be from sash position sensors or
ity of ventilation air used for proper IAQ rent sensing relays on fan motors, airflow air velocity sensors at the fume hood (face
and makeup air is outdoor air, it may be switches, or differential pressure switches velocity determination). There are other
possible to filter and treat Class 2 and 3 that prove fan operation and airflow. Con- methods as well, but the goal is to provide
exhaust air for use as makeup air or route trol sequences of operation would identify constant minimum required hood face
the exhaust air through an energy recov- lead/lag fan operation, alarm status, and velocity for proper fume and vapor capture.
ery device with limited leakage, possibly proven airflow indication in a BAS and/ Large chemical labs such as teaching
saving energy. or locally at the fume hood. and science laboratories with many fume
Fume hood exhaust fans should be the Exhaust systems from chemical fume hoods may be able to take advantage of
type that discharge air vertically with suf- hoods may be ducted individually from differing usage factors that can reduce

www.csemag.com Consulting-Specifying Engineer • JANUARY/FEBRUARY 2014 39


Laboratory ventilation
ers should consult with lab users and safe-
ty personnel to obtain a list of the types
and quantities of chemicals proposed to be
used both in and outside of fume hoods,
along with storage quantities anticipated.
The chemical type will help the designer
choose the correct duct material and joint-
ing method to effect safe movement of the
vapors and contaminants.
Space temperature (70 to 75 F) and
relative humidity requirements are depen-
dent on the lab function and heat gain to
the space. Lab personnel wearing protec-
tive clothing may require temperatures in
the lower portion of the range in order
to remain comfortable. While a specific
relative humidity is not identified in the
Figure 7: These lab work counters have two bypass fume hoods at the back wall. various codes, it is usually maintained in
Notice the surface-mounted light fixtures indicating tight above-ceiling space. the 30% to 60% range. With the constant
volume air supply in most labs, tempera-
the amount of exhaust and makeup air these chemicals prepared by OSHA and ture control of occupied work areas is usu-
required, thus saving energy and increas- the Association for the Advancement of ally achieved through single duct reheat
ing equipment life. The usage factor must Medical Instrumentation (AAMI) recom- systems or double duct air terminal units.
be used prudently and generally takes the mend air change rates and point of vapor The MERV ratings are a measurement
following into consideration: total number release airflow guidelines. scale established by ASHRAE 52.2-2007
of fume hoods, available airflow diversity, Air balance and pressurization of lab that identifies the efficiency and cap-
type of fume hood controls, laboratory spaces can be tricky with controls and air ture capability of particle sizes from 10
makeup air and ventilation system type, system responses continually fluctuating microns to less than 0.3 microns. The
number of devices (hoods) that must oper- due to opening of doors to adjacent spaces MERV ratings range from 1 through 20
ate continuously, and hours per session/ or airflow volumes changing to accom- with the higher the value, the greater the
day hoods are actually in use. modate space temperature requirements. capture and efficiency. A MERV 8 filter
Some chemicals such as formalin, form- Accurate air measurements of supply air will trap greater than 90% of particles
aldehyde, and glutaraldehyde are used as devices and exhaust systems are needed sizes 3.0 to 10 microns. A MERV 13 filter
tissue preservatives and sterilants in clini- to balance the system. Strategic placement has a dust spot efficiency of 89% to 90%
cal labs and similar health care settings. of pressure sensors will help determine if and will capture droplet nuclei of 1.0 to
Many times these chemicals are used in the required pressure relationship is being 3.0 microns such as that from a sneeze.
operations performed in the open at coun- maintained. ANSI Z9.5 recommends that Higher MERV ratings of 16 will capture
ter level with the transfer of the liquid an air volume rate offset be used rather bacteria and particles as small as 0.30
from one container to another by pouring than controlling to a specific differential microns. Usually, a MERV 14 (90% to
or by gravity through a hose. This action pressure. However, this offset will typi- 95% efficiency) is used in an air system
allows fumes to become airborne and must cally result in a 0.01 to 0.02 in. w.g. differ- supplying air to a lab.
be captured near the point of use by proper ential. Figure 5 shows a general lab with Air supplied to labs requires filtration of
airflow direction. Airflow across the back pressure sensor locations. a MERV 13 minimum in central air sys-
of the worker with the point of capture Duct construction should be specified tems requiring either 1 or 2 filter beds in
and pickup at the counter level is a good and provided to achieve less than 1% order to provide relatively clean air for the
method. Air velocity at the work surface leakage of design airflow; however, the lab environment. Some functions, such as
needs to be slow enough to not evaporate design goal for both supply air (positive) pharmacological preparation, infectious,
the chemical, but yet adequate enough at and exhaust air (negative) duct systems or radioactive material use, require HEPA
the inlet (100 fpm minimum) to collect the should be for zero leakage. Exhaust duct filters on both the supply and exhaust
vapors and prevent them from permeating construction and materials should be airstreams. Sometimes the HEPA filters
the adjacent work stations. Best practice appropriate for the chemicals and fumes are installed at the point of air delivery
guides and standards for the safe use of that are to be captured. The HVAC design- into the room, but more often the work is

40 Consulting-Specifying Engineer • JANUARY/FEBRUARY 2014 www.csemag.com


Laboratory ventilation
isolated to a Class I or Class II bio-safety HVAC design for such spaces must con- n Biosafety in Microbiological and
cabinet with the HEPA filters installed in sider the temperature and relative humid- Biomedical Laboratories, Centers
the cabinet. Filters in the exhaust stream of ity ranges associated with not only the for Disease Control and Prevention
these cabinets must be designed to allow animals, but the research protocol for the (CDC)
the safe removal, disposal, and replace- particular study. Air distribution and air n Institute for Laboratory Animal
ment of these filters, such as with a bag-in/ movement are dependent on the hous- Resources (ILAR)
bag-out type of filter holding assembly. ing of the animals. Open cages, shoebox n The Animal Welfare Act with
Work in a bio-safety cabinet requires a cages, species type, number and size of authority vested in the U.S. Dept.
clean work surface but also allows for the animals, length of stay in primary or sec- of Agriculture (USDA)
dispersion of bacteria and related particles. ondary enclosures, and heat generation of n Guide for the Care and Use of
Proper capture of these particles through the animals are considerations that must Laboratory Animals, National
filtration is essential for safe operation. A be part of the HVAC design parameters. Research Council
bag-in/bag-out housing incorporates a bag The ASHRAE Handbook—HVAC Appli- n Code of Federal Regulations (CFR)
that completely covers the filter prior to cations has lab descriptions and is a good 21, Part 58: Good Laboratory Prac-
its removal so all particles are kept on the guide, along with references for design tices for Non-Clinical Laboratory
filter and not accidentally released into the considerations of animal facilities. Studies.
occupied environment or onto personnel Regulations, standards, and good prac-
changing the filter. tice design requirements from various Temperature and relative humidity in
organizations must be reviewed and fol- animal spaces must be flexible and closely
Animal facility considerations lowed as they would apply to the particu- controlled to match the research protocol.
Laboratory animals require comfort- lar application. These include: Temperature ranges between 64 to 85 F
able, clean, and temperature-controlled n American Association for Accredit- are common with a +/-2 F accuracy. Rela-
conditions that afford proper safety and ation of Laboratory Animal Care tive humidity ranges of 30% to 60% are
welfare of each animal species. The (AAALAC) considered acceptable.

Transair robust piping system

Parker Hannifin manufacturers Transair, a robust piping system with superior operational efficiency perfectly suited for all industrial
applications. Transair is a fast, flexible and easy to modify aluminum pipe system for compressed air, vacuum and inert gas
applications. Transair components are reusable and interchangeable and enable manufacturing plant personnel to implement
many layout changes within minutes, instead of hours. This ease of use minimizes
downtime and increases plant productivity and efficiency. Transair’s innovative technology
offers significant savings on installation, maintenance and operating costs when
compared to traditional pipe.
For more information, please call 480-830-7764 or visit www.parkertransair.com.
input #21 at www.csemag.com/information
An air change rate is a calculation of layout will become and the better func- member of Consulting-Specifying Engi-
space volume and airflow which results tionality the lab will have. neer’s editorial advisory board. Chris St.
in the number of minutes it takes for the Cyr is a senior mechanical designer. He
air to “change.” An example: a 20x20-ft J. Patrick Banse has more than 35 years has more than 24 years of mechanical
room with a 9-ft ceiling height has a vol- of experience in the consulting engineer- design experience, with the past 15 years
ume of 3600 cubic feet (cf). If the space ing field, with the past 30 years in health in the design of health care facilities and
is supplied with 900 cfm of air, the air care design and engineering. He is a clinical labs.
would be “changed” every 4 minutes
(3600 cf/900 cfm = 4 minutes), which
then results in 15 ACH (60 min/hour/4 Construction
min). Placement of supply air and air Automotive
removal devices will determine if all of Industry
the air is actually changed. This is part of
the overall design challenge.
Air change rates of 10 to 15 ACH have
been accepted guidelines to keep odors
under control and provide adequate ven-
tilation for high respiration rate animals.
While the ACH may be suitable, other
factors such as animal heat gain, lights
and equipment heat gain, other exhaust
requirements (fume hoods), and quantity
of animals must be considered to deter-
mine correct airflow.
Air distribution device type and deliv-
ered air velocity, along with high or low
return/exhaust placement, may affect
actual ventilation rates or create drafts.
Fluctuating animal population may allow
for reduced airflow rates while maintain-
ing desired space conditions.
Other spaces and functions generally
associated with animal facilities—cage
washing, surgery rooms, food storage,
treatment rooms, refrigerated storage
rooms, and necropsy labs—require care-
ful design, air quantity, filtration, tem-
THE PATH TO NET-ZERO
perature, and relative humidity control. IT’s RIgHT UNDER YOUR FEET
Isolation or quarantine spaces are also
found in these facilities and are treated
similar to other airborne infectious isola- A Crucial Strategy For Maximum Efficiency
tion rooms. Hydronic radiant heating and cooling is used in 50% of net-zero
HVAC design for laboratories requires energy buildings. It’s a cost-effective way to downsize forced-air
team discussions and planning, identifi- HVAC systems, cutting energy use yet enhancing comfort. Our
cation of design parameters, and adher- experts can help you at every step – design, specification,
ence to applicable design codes and on-site installation support.
standards, along with a willingness to
agree on the ultimate goals—worker Take a walk toward greater efficiency.
safety, fume and vapor containment
and capture, product preservation, and Visit na.rehau.com/netzero to see our successful projects. Then request a lunch and
adherence to research protocol. HVAC learn or design assistance.
systems for labs cannot be designed in
a vacuum. The more you learn along the (800) 247-9445 ©2014 REHAU
way, the better the system design and
input #22 at www.csemag.com/information

You might also like