Supply, store, installation, Floor mounted testing & commissioning of double skin
Air Handling Units with thermal break profile with a minimum panel thickness of
40 mm or more , AHRI / Eurovent certified unit complete with cooling coil( DX
cooling coil) ,DIDW centrifugal fan with IE3 motor with minimum W/cfm, VFD
with enclosure box ( IP 21 rated for indoor and IP 55 rated for out door
applications). The VFDs must have active harmonic filters to limit the harmonic
distortion to 3%, cleanable fabric filters of MERV 7 and fine filters of MERV 14, strip
heaters of following capacity condensate drain pan, coil piping connections,
condensate drain connections, mixing box with dampers inbuilt flexible duct
1 connectors. The fan should deliver the design cfm at 50 Hz or lower. The electrical
power wiring from the Isolator to the unit upto 5m shall be included.Isolator shall be
in electrical contractors scope. HVAC contractor to check the ahu room/location sizes
during the AHU selections/sizing, and shall strictly follow the AHU room/location
sizing, as no changes whatsoever shall be acceptable. Air balancing to be done as per
the approved shop drawings at the time of commissioning. The AHUs should meet
the sound pressure levels recommended by ASHRAE. The system shall be
complete in all respects of commissioning.The supplier should visit the site before
procurement and shall confirm the suitability of the particular unit for particular area
and confirm the external static pressure after checking the drawings. The supplier also
should vouch for the performance guaranty.
1.1 5TR1800 CFM, 12 mm ESP, 6RD, 7.5 kw Strip Heater(Medical ICU) Nos 1 192750 7,500.00 2,00,250.00 2,00,250.00
1.2 7 TR,2800 CFM, 12 mm ESP, 6RD, 7.5 kw Strip Heater(Surgical ICU,Medical ICU) Nos 2 254250 10,500.00 2,64,750.00 5,29,500.00
1.3 9 TR,2400 CFM,65 mm ESP, 8RD, 15 kw Strip Heater, with mixing box ( OT-1 & OT-2) Nos 2 378875 13,500.00 3,92,375.00 7,84,750.00
1.4 6.5 TR,1800 CFM,55 mm ESP, 8RD, 10 kw Strip Heater, with mixing box (OT-3) Nos 1 280750 9,750.00 2,90,500.00 2,90,500.00
7.5 TR,2100 CFM,60 mm ESP, 8RD, 12 kw Strip Heater, with mixing box (TRANSPLANT
1.5 Nos 2 320250 11,250.00 3,31,500.00 6,63,000.00
OT-1&2)
7.5 TR,3000 CFM,15 mm ESP, 6RD, 12 kw Strip Heater, with mixing box
1.6 Nos 2 268688 11,250.00 2,79,937.50 5,59,875.00
(POST ANESTHETIA CARE & ICU)
1.7 6TR,2200 CFM, 12 mm ESP, 6RD, 9 kw Strip Heater, ICCU Nos 1 221625 9,000.00 2,30,625.00 2,30,625.00
1.8 5TR1800 CFM, 12 mm ESP, 6RD, 7.5 kw Strip Heater, OBSICU Nos 1 221625 7,500.00 2,29,125.00 2,29,125.00
1.9 7.5TR,2800 CFM, 12 mm ESP, 6RD, 7.5 kw Strip Heater, RICU Nos 1 284156 11,250.00 2,95,406.25 2,95,406.25
2.1 9.5TR, 3200 CFM, 16 mm ESP, 6RD, 15kw Strip Heater, NICU Nos 1 324906 14,250.00 3,39,156.25 3,39,156.25
SL. NO DESCRIPTION UNIT Total Qty Rate Rate
3.1 11.5 TR (OT-1 & OT-2 including stand by) Nos 5 12000 11,250.00 23,250.00 1,16,250.00
3.2 8.5 TR (OT, ICU, Post Anesthetia Care, Isolation -2) Nos 14 9313 7,500.00 16,812.50 2,35,375.00
4.1 4 TR,8RD, 800cfm,8kW Strip Heater, 10mm ESP(For Isolation -1) Nos 4 143375 10,500.00 1,53,875.00 6,15,500.00
4.2 6 TR, 1200 cfm, 8RD, 10kW Strip Heater, 10mm ESP(For Isolation -2) Nos 1 192750 15,750.00 2,08,500.00 2,08,500.00
4.3 5TR,8RD, 900cfm,8kW Strip Heater, 10mm ESP,(ISOLATION 1) Nos 1 179469 13,125.00 1,92,593.75 1,92,593.75
4.4 3.5TR,700cfm,8kW Strip Heater, 10mm ESP,(ISOLATION 2) Nos 1 131344 9,187.50 1,40,531.25 1,40,531.25
Supply, Installation testing and commissioning of Ducted type split/package air cooled
Air-conditioners each complete with air cooled condenser and evaporator with copper
tubes, GSS casing, filters, cooling coils, fan motors, control wiring, refrigerant controls
and accessories, including MICROPROCESSOR CONTROL with indication lamps for the
operation of the system with thermostat fixed in the respective rooms to adjust the
temperature according to the equipments requirements with Micro- processor control
panel for each machine. Bidder to elaborate the features of Microprocessor panel.This
shall facilitate all functions such as ON / OFF thermostat to compressor control, fan
5 interlocks, HP/LP & AFT controls etc. The remote control for the unit shall be
considered. The refrigerant shall be ecofriendly like R410a, R407c,R32 etc.The power
cabling from local isolator / panel , to the machine shall be considered along with this
line item.The control wiring between indoor unit and out door unit shall not be
considered under this lineitem. Length of power cabling shall be inferred from the
drawings. The system shall be complete with all respects of commissioning. The
supplier should visit the site before procurement and shall confirm the suitability of
the particular unit for particular area and confirm the external static pressure after
checking the drawings. The supplier also should vouch for the performance guaranty.
5.1 1 TR, 2 mm ESP, 400 cfm Nos 1 7000 1,875.00 8,875.00 8,875.00
5.2 1.5 TR, 4 mm ESP, 600 cfm Nos 1 7000 1,875.00 8,875.00 8,875.00
5.3 2.5TR, 5 mm ESP, 1000 cfm Nos 3 7000 2,500.00 9,500.00 28,500.00
5.4 3 TR, 5 mm ESP, 1200 cfm Nos 5 8375 3,125.00 11,500.00 57,500.00
5.6 6 TR, 15 mm ESP, 2400 cfm Nos 1 11438 6,250.00 17,687.50 17,687.50
5.7 7.5TR, 10mm ESP, 3000 cfm Nos 2 11438 7,500.00 18,937.50 37,875.00
5.9 8.5 TR, 11 mm ESP, 3400 cfm Nos 1 13438 8,750.00 22,187.50 22,187.50
SL. NO DESCRIPTION UNIT Total Qty Rate Rate
5.12 11.5 TR, 10 mm ESP, 4600 cfm Nos 1 14750 12,500.00 27,250.00 27,250.00
5.13 12.5 TR, 11 mm ESP, 5000 cfm Nos 1 14750 14,375.00 29,125.00 29,125.00
Supply, Installation, Testing and Commissioning of Hi-wall type split air conditioners,
air cooled type with evaporator coil made of copper tubes, fan and fan motor air
cooled condenser with copper tubes and inverter type scroll compressor , cordless
remote control, GSS casing, filters, cooling coils, fan motors, and control panel. Bidder
to elaborate the features of Micro- processor panel.The quote should be inclusive of
control cabling from machine out door to indoor or from control panel to indoor and
power cabling along with earthing.This shall facilitate all functions such as ON OFF
6.0 thermostat to compressor control, fan interlocks, HP/LP & AFT controls etc. And MS
base frame for outdoor units complete with epoxy painting, vibration isolation pads,
supports, hangers, railing, brackets etc including civil works. Note: Apply 2 coats of
epoxy primer and 2 coats of black paint, The air conditioner unit should be provided
with a required voltage stabilizer and up to 5Rmt.copper piping between indoor and
outdoor unit as specified. Condenser and evaporator coils shall be equipped with
copper tubes. Minimum 5 star rated if not specified. The refrigerant shall be eco-
friendly gasses like R-410A /R 407C/ R32. The capacities are as under
Supply & installation of 18G, hard drawn copper Refrigerant piping, duly insulated
complete with elbows, T joints, sleeves etc., with GSS slotted rail supporting
arrangement and GI clamp for individual pipes, 19mm Thick nitrile rubber
7 Rm 1480 1698 312.50 2,010.63 29,75,725.00
sleeves with polyshield coating oblique/IC clad insulation. Liquid line and Gas line
shall not be measured seperately (including the piping of standby split and DX type
units.)
Supply, store, installation, testing & commissioning of PVC drain piping and
insulated with 9mm thick aluminium foil face XLPE Aluminium foil faced
8
Sleeve,section should be open and Gum pasted with PVC Pipe, All joints laminated
with 3mm thick XLPE Tape with 3M Gum,
Supply, store, installation, testing & commissioning of GI duct work using 120 gsm GI
sheets with all accessories, supports, jointing materials, flanges complete all inline
8 0 3383 - 3,383.25 -
with the DW 144 or SMACNA and in line with the specifications, drawings etc.
The system shall be complete in all respects forcommissioning.
8.1 Ductwork complete (24 Gauge) Sq.m 2830 792 300.00 1,092.22 30,90,970.68
8.2 Ductwork complete (22 Gauge) Sq.m 346 892 310.00 1,201.87 4,15,848.42
Supply, store, installation, Testing and commissioning of Supply and return Duct
insulation which is closed cell elastomeric nitrile foam rubber insulation class stuck to
duct as per specifications.The thermal conductivity of the insulation material shall not
exceed 0.035 W/m K at an average temperature of of 30 degC. Density of nitrile
rubber shall be 40-60 Kg/m3. The product shall have temperature range of -40 deg C
to 105 deg C. The insulation material and the outer layer of vapor barrier should have
10 antimicrobial properties. The insulation should have fire rating of Class O. Water vapor
permeability shall not less then 0.024 per inch ( 2.48x10-14 Kg/m.s Pa ) as per
DIN 53122 part DIN 52615.The system shall be complete in all respects for
commissioning. Required thicknesses as mentioned below. The duct insulation
measured in the line item is considered as per the duct dimention. The measurement
shall be taken according to that any material wastage shall not be considered during
measurement.
10.1 13 mm thick for conditioned areas Sqm. 3381 378 162.50 540.31 18,26,796.56
10.2 19 mm thick for non conditioned areas with glass cloth and two coats of vapor barrier Sqm. 50 860 377.50 1,237.68 61,884.09
25 mm thick for exposed areas and cladded with glass cloth and two coats of vapor
10.3 Sqm. 280 989 377.50 1,366.81 3,82,707.50
barrier
Supply, store, installation, testing & commissioning of Acoustic Insulation for ducts
and the return plenum using nitrile rubber, open cell foam, fibre free, minimum
density of 140 kg/cu.m should have microban, as per ASTM G-21, ASTM E-2180,
thermal conductivity not exceeding 0.047 W/m.K at 20 C, conform to class 1 rating for
flame spread in accordance to BS 476 part 7, to thickness of minimum of 10mm all
11
inline with the specificatoin and to meet the design noise criteria. The system shall be
complete in all respects for commissioning. The duct insulation measured in the line
item is considered as per the duct dimention. The measurement shall be taken
according to that any material wastage shall not be considered during measurement.
Not to be applied in OT and ICU & Isolation units.
11.1 Acoustic liner 10mm Sq.m 375 789 162.50 951.13 3,56,671.88
Supply, store, installation, testing & commissioning of Grilles, Diffusers with plenums
13 and Dampers as specified below. The system shall be complete in all respects
forcommissioning.
13.1 4 Way Supply Air Square Diffusers with opposed blade dampers Sq.m 89 12219 1,187.50 13,406.25 11,93,156.25
13.2 4 Way Return Air Square Diffusers Sq.m 90 10063 1,125.00 11,187.50 10,06,875.00
13.3 Supply Linear Bar Grille Sq.m 2 12923 937.50 13,860.63 20,790.94
13.4 Return Linear Bar Grille Sq.m 3 6735 875.00 7,609.69 22,829.06
Supply, store, installation, testing & commissioning of Fire dampers quick release
fusible link , louver type, constructed out of 18 Gauge galavanised steel casing etc., in
accordance with BS 476, DW 144, DW 151, DW 154 as appropriate and have Fire
17 Sq.m 9 15094 2,187.50 17,281.25 1,55,531.25
resistance rating equal to the Fire barrier it penerates all inline with the specifications
relevant statuatory authority regulations on all Fire rated walls, Barriers, Floors
whether indicated on the HVAC drawings or not.
Supply, store, installation, testing & commissioning of Thermostats for indoor units.
21 No 22 0 1,250.00 1,250.00 27,500.00
The system shall be complete in all respects for commissioning.
Supply , installation and commissioning of power and control cabling with all
22 Rm 3600 219 50.00 268.75 9,67,500.00
necessary accessories for humidity control panel
Supply , installation and commissioning of power and control cabling with all
23 Rm 2000 156 50.00 206.25 4,12,500.00
necessary accessories for Dp transmitter
Supply, store, installation & commissioning of Stainless steel (SS304) Laminar flow
plenum with HEPA filter as per the specifications and drawings, all in line with the OT
27
standards.The system shall be complete in all respects forcommissioning. The sizes are
as follows
Supply, store, installation, testing & commissioning of wall mounted axial fans with
28 0 0 - - -
bird cowl
Supply, store, installation, testing & commissioning of centrifugal inline fans with
29
flexible connectors
29.1 150 cfm, 8mm ESP Nos 1 7484 1,875.00 9,359.25 9,359.25
29.2 100 cfm ,12mm ESP Nos 3 7229 1,875.00 9,104.44 27,313.31
29.3 100 cfm ,8mm ESP Nos 1 7229 1,875.00 9,104.44 9,104.44
29.4 100 cfm ,20mm ESP Nos 5 7484 1,875.00 9,359.25 46,796.25
29.8 600 cfm , 20mm ESP Nos 1 11661 1,875.00 13,535.81 13,535.81
SL. NO DESCRIPTION UNIT Total Qty Rate Rate
29.10 500 cfm, 20mm ESP (Mesh screen/filter shall be considerd, since it’s a fresh air fan) Nos 1 11136 1,875.00 13,011.00 13,011.00
29.11 750cfm, 20mm ESP (Mesh screen/filter shall be considerd, since it’s a fresh air fan) Nos 1 13475 2,500.00 15,974.88 15,974.88
30.1 1200 cfm,80mm ESP ( For isolation room exhaust fans placed at terrace) Nos 1 129583 3,125.00 1,32,707.50 1,32,707.50
30.2 1600 cfm,80mm ESP ( For isolation room exhaust fans placed at terrace) Nos 4 154273 3,125.00 1,57,397.75 6,29,591.00
30.3 1800 cfm , 85mm ESP ( For isolation room exhaust fans placed at terrace) Nos 1 154273 3,125.00 1,57,397.75 1,57,397.75
30.4 2300 cfm , 80mm ESP ( For isolation room exhaust fans placed at terrace ) Nos 1 172346 3,125.00 1,75,471.00 1,75,471.00
Supply, store, installation, testing & commissioning of drain pumps with 1m head. The
31 Nos. 0 11563 1,500.00 13,062.50 -
cabling provision of 3m for power supply shall be considered with this line item
Arranging and conducting 3rd Party OT validation procedure as per relevant ISO
33 standards and to the satisfaction of client. The procedure shall be included the 0 - -
following tests.
Air Velocity
Air Change
Defferential pressure LS 1 45000 15,000.00 60,000.00 60,000.00
Particle Count
HEPA Filter Integrity
TOTAL without GST ( GST EXTRA) 2,74,26,746.78
SL. NO DESCRIPTION UNIT Total Qty Rate Rate
Note: The ESP indicated in the BOQ. is intuitive. The contractor need to submit the ESP calculation for all the applicable items to the consultant and get approved before prequiement
1. For all the AC/ Ventilation equipment power cabling and containment from the nearest isolator/ socket to the equipment is in HVAC contractor’s scope. The cabling shall be of suitable rating
and as per OEM recommendation.
2. Any associated civil work shall be in civil contractor’s scope.
3. Any scaffolding works shall be in civil contractor’s scope.
4. All control and / or communication cabling shall be considered along with applicable items and will be in HVAC contractor’s scope.
6. In the BOQ, The indocated cappacities of units are design cappacities. It may be prodect specific, incase of inavailability, select next size available in the product range of the particular made.