Adjustable MCCB
4
Metasol
Adjustable Molded Case Circuit Breaker
Adjustable
Low voltage circuit breaker
•Ics = 100%×Icu
•Ui = 1,000V
•Uimp = 8kV
125 AF 250 AF
•0.7 … 1 × In •0.7 … 1 × In
•37kA @ 415/460 •37kA @ 415/460
•16 … 125A •100 … 250A
5
MCCB System overview
▒ Various installable Accessories
● Wider range of installable accessories compared to Meta MEC series.
● Composed of User Friendly Method.
6
System overview
Breaker
Internal auxiliaries
Rotary handle (direct)
Rotary handle (direct, key lock)
Rotary handle (extended)
Terminal cover (Short, Long)
Insulation barrier
Handle Lock
7
MCCB Internal accessories
● ●
8
Internal accessories
AX AL AL AX
AX AL AL AX
SHT/UVT
SHT/UVT
103 203 9
MCCB External accessories
▒ External accessories
Designed for various mount and user safety.
10
External accessories
Locking device
- Fixed padlock
- Removable padlock
- Key lock device on direct handle
Insulation barrier
These allow the insulation characteristics between the phases at the
connections to be increased.
11
Marking and configuration
MCCB
MCCB model
•ABS: Standard type
Standardized
characteristics
i: Rated insulation voltage
U
Uimp: Impulse withstand
voltage
Ue: Rated operational voltage
Icu: Ultimate breaking capacity
Ics: Service breaking capacity
MCCB
Upstream connections
Fixing hole
Product name
Brand name
Certification mark
Company logo
Adjustable dial
Fixing hole
Downstream connections
12
External configuration
MCCB
① Handle
•Function of indications
- “ON” “OFF” “TRIP”
•Resetting
When the handle indicates "tripped" position
it must first be reset by moving the handle to
the “OFF” position and then closing is
possible
•Trip-Free even if the handle is held at “ON”,
Terminal
the breaker will trip if an over current flows
•Suitable for Verification of the main contact
position under abnormal conditions because Arc-
the handle doesn’t indicate open position Extinguishing
unit
② Arc-Extinguishing unit
LS patent technique PASQ Contact
Arc-Extinguishing unit
Handle
PASQ : Puffer Assisted Self-Quenching Mechanism
•Reduction of arc voltage for a short time
Trip button
Hybrid Grid
chamber Ass’y
Trip
13
Quick selection table
Molded Case Circuit Breakers
MCCBs
AF 125AF
Type S-Type
3-pole ABS103c
4-pole ABS104c
Rated current, In A 16, 20, 25, 32, 40, 50, 63, 80, 100, 125
Adjustable Range 0.7 ...1 × In Note) 1
Rated operational
AC(V) 415/460
voltage, Ue
Rated insulation voltage, Ui V 1,000
Rated impulse withstand
kV 8
voltage, Uimp
14
AF 250AF
Type S-Type
3-pole ABS203c
4-pole ABS204c
Rated current, In A 100, 125, 160, 200, 250
Adjustable Range 0.7 ...1 × In
Rated operational
AC(V) 415/460
voltage, Ue
Rated insulation voltage, Ui V 1,000
Rated impulse withstand
kV 8
voltage, Uimp
15
125AF MCCB
ABS125c
Ratings
ABS103c c1 Note1) 60
b
c2 Note1) 64
d 82
Weight, kg Standard 1
Certification Pole 3p 4p
CE marking ○
Note) 1. Depth by door cut size: c1 for large cut, c2 for small cut
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
3. Adjustable range of 16A MCCB : 0.8~1×In
4. Life cycle means not guarantee but limitation
ABS104c (Quality guarantee: On/Off frequency on the basis of IEC60947-2 within the term of guarantee.)
16
Ordering types
S type (37kA@415/460V)
Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL or AX+AL
Note) For more detail see 21 page
External accessories
ABS125c Name
17
250AF MCCB
ABS250c
Ratings
c2 Note1) 64
ABS203c
d 87
Weight, kg Standard 1.2 1.6
Certification Pole 3p 4p
CE marking ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
3. Life cycle means not guarantee but limitation
(Quality guarantee: On/Off frequency on the basis of IEC60947-2 within the term of guarantee.)
ABS204c
18
Ordering types
S type (37kA@415/460V)
Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL or AX+AL
Note) For more detail see 21 page
External accessories
ABS250c Name
19
Accessories
SHT
Shunt Trip
AX
Auxiliary UVT
Switch
Undervoltage
trip
AL
Left-hand seat Right-hand seat
Alarm Switch
AX
Auxiliary
Switch
AX+AL
AL
Alarm
Combination switch Switch
Maximum possibilities
Position Type 3/4p
AX 1
Left-hand
AL 1
seat
AX+AL 1
AX 1
Right-hand AL 1
seat AX+AL 1
SHT/UVT 1
20
Combinations of accessories
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker
AX AX+SHT(UVT)2
AX2 AX2+SHT(UVT)
AL AX3(4)+SHT(UVT)
AL2 AX3(4)+SHT(UVT)2
AL3(4) AL+SHT(UVT)
SHT(UVT) AL+SHT(UVT)2
SHT(UVT)2 AL2+SHT(UVT)
AX+AL AL2+SHT(UVT)2
AX+AL2 AL3(4)+SHT(UVT)
AX+AL3(4) AL3(4)+SHT(UVT)2
AX2+AL AX+AL+SHT(UVT)
AX2+AL2 AX+AL+SHT(UVT)2
AX2+AL3(4) AX2+AL2+SHT(UVT)
AX3(4)+AL AX2+AL2+SHT(UVT)2
AX3(4)+AL2 AX3(4)+AL3(4)+SHT(UVT)
AX3(4)+AL3(4) AX3(4)+AL3(4)+SHT(UVT)2
AX+SHT(UVT)
21
Accessories
Contact (AX+AL)
AX
AL
Rating (AX+AL)
Conventional thermal current, Ith 5A
22
Accessories
The shunt trip opens the mechanism in response to an externally applied voltage signal. The releases include
coil clearing contacts that automatically clear the signal circuit when the breaker has tripped.
DC 12V - 1.5
AC/DC 24~30V 1.5 1.5
AC/DC 48~60V 1.5 1.5
Voltage AC/DC 100~130V 1.5 1.5
Metasol MCCB
AC/DC 200~250V 1.5 1.5
Terminal block type (TBT) ABS125c, ABS250c
AC 380~450V 1.5 -
AC 440~500V 1.5 -
Max.opening time 50ms (max.)
Tightening torque of terminal screw 8.2 kgf·cm
Note: 1. Range of operational voltage: 0.7 ~ 1.1Vn
Frequency (Only AC): 45Hz ~ 65Hz
23
Accessories
The undervoltage release automatically opens a circuit breaker when voltage drops to a value ranging between
20% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be
re-closed again until the voltage returns to 85% of line voltage.
Continuously energized, the undervoltage release must be operating before the circuit breaker can be closed.
24
Adjustable Mold Case Circuit Breaker
Adjustable to
Three level
0.85×In
0.7×In 1.0×In
25
Accessories
External accessories
Wide range of external accessories provides user-friendly solution for mounting, cable connection, insulation, safety lock and remote control.
Insulation barrier
Terminal cover
Breaker
Rotary handle
(Direct, Key lock)
Rotary handle
Terminal cover (Extended)
Insulation barrier
26
Rotary handles
Direct type The rotary handle operating mechanism is available in either the direct version or in the extended version on
the compartment door. It is always fitted with a compartment door lock and on a request it can be supplied
with a key lock in the open position.
Type
Direct type Breaker type
Direct type Extended type
Key lock (Key lock) MCCB
(DH 125~250AF)
N-40c - -
ABS125c
DH125 DHK125 EH125
N-50c - -
ABS250c
DH250 DHK250 EH250
Note: Padlock type for N-handle
- On or OFF state type - Only OFF state type
(N 125~250AF)
LINE
LINE LOAD LOAD LINE
(125~250AF)
LOAD
ON ON
27
Accessories
D-handle
MCCB and D-handle
ABS125c ABS250c
Tripped
Push to trip
LINE
LOAD
ON ON ON
28
Installing the D-handle
ABS125c ABS250c
Cutting Panel
29
Accessories
LOCKED
UNLOCKED
D-handle
Operating
OFF position test
CAUTION
Remove the key if you operate the handle.
If the door is opened with much
pressure when the position of ON
handle is ON or TRIP, the
handle lock lever will be
demaged.
PUSH TO
OFF Tripped TRIP
Locking system
KEY LOCK
Open Panel Door
LOCKED
UNLOCKED
OFF position
30
E-handle
MCCB and E-handle
ABS125c ABS250c
Tripped
Push to trip
LOAD
ON ON ON
31
Accessories
E-handle
Installing the E-handle
ABS125c ABS250c
32
LOCKED
UNLOCKED
Operating
OFF position Test
CAUTION
Remove the key if you operate the handle.
If the door is opened with much
pressure when the position of
Reset ON
handle is ON or TRIP, the
handle lock lever will be
demaged.
OFF
Locking System
Releasing
33
Accessories
Terminal covers
The terminal covers are applied to the circuit-breaker to prevent accidental contact with live parts and thereby guarantee
protection against direct contacts.
Two types by length are available and provide IP20 degree of protection.
Also, covers ara classified in to 2 different type: Independent, Attachable and detachable with D or N Handle
TCS(Short type)
TCL(Long type)
Long type construction
34
Accessories
Insulation barriers
Insulation barrier allows the insulation characteristics between the phases at the connections to be increased.
They are mounted from the front, even with the circuit-breaker already installed, inserting them into the
corresponding slots.
They are incompatible with both the insulating terminal covers.
It is possible to mount the phase separating partitions between two circuit-breakers side by side.
Breaker
Type
MCCB
ABS125c
IB-23
ABS250c
35
Dimensions
MCCB ABS125c
(mm)
30 30 30 59
Insulation barrier Insulation barrier
80
80
Fixing hole Fixing hole
Ø8.2
Ø5
50
22 22
16.5
16.5
100
135
155
100
135
155
50
50
37 37
120 68
82
3P 4P
M8×14
8
Ø9
16
18 24 8 t≤5
10
52
52
132
30 30 92 122
3P 4P 3P 4P
36
Dimensions
MCCB ABS250c
59
(mm)
80
Mounting Hole Mounting Hole
C
L C
L
Ø4.5
Ø8.2
47
22 22
14.5 14.5
59.4
102
126
144
165
59.4
102
126
144
165
50
C C
50
L L
19.6
19.6
44.5 44.5
Trip Button
Trip Button
35 35 35 60
70 70 64
105 140 68.5
86.85
3P 4P
28 24
Ø9
C C C C
126
52
52
L L L L
53.5
35 35 35 107 142
3P 4P 3P 4P
37
Characteristics curves
Minute
20
10
8
6
4
Compensation curves 2
1
40
Operating time
Ambient temp. 40 ℃ 20
150
10
8
6
4
compensation ratio(%)
2
100
Second
125A 1
Rated current
0.8
0.6
0.4
Instantaneous tripping In=16A, Im=400A
characteristic In=20A, Im=400A
0.2 In=25A, Im=400A
16~32A : Im=400A±20% In=32A, Im=400A
50 40~125A : Im=12×In±20% In=40~125A, Im=12×In
0 10 20 30 40 50 0.1
0.08
0.06
Ambient temperature Max.total fault
0.04 clearing time
0.02
Rated current: 125A 0.01
1 1.5 2 3 4 5 6 7 8 910 15 20 30 40 50 60 80 100
20
10
8
6
Compensation curves
4
2
Max.value
1
Operating time
40
Ambient temp. 40 ℃
20
150
10
8
6 Min.value
compensation ratio(%)
2
100
Second
Rated current
1
0.8
0.6
0.4 Instantaneous
tripping
0.2 characteristic
50
0 10 20 30 40 50 (Im=12xIn±20%)
0.1
0.08
Ambient temperature 0.06 Max.total fault
0.04 clearing time
0.02
Rated current: 250A 0.01
1 1.5 2 3 4 5 6 7 8 910 15 20 30 40 50 60 80 100
38
Dimensions
Rotary handles
t1.2~3.2
t1.2~3.2 2-Ø6
4-Ø5
℃
A
D
E
B
60
104 B A
C
105105
43 43
39
Dimensions
Rotary handles
t1.2~3.2
~3.2 2-Ø6
4-Ø5
℃
B
D
E
B A
C
40
Technical Information
Standard accessories
The following accessories for mounting, connection and insulation are standard
items and are packed with Metasol series circuit breakers.
Fixing screw
Terminal bolt
Insulation barrier
Applied MCCB
Fixing screw(short) - -
Fixing screw(long) M4×85 M4×85
41
Technical Information
8.2
M5×14
8.2
Ø5.5
8.2
Ø5.5
M5×14 M5×14 Ø5.5 Ø5.5 Ø5.5 Ø5.5
8.2
18 24 12.5
7.5
M5×14 Ø5.5 Ø5.5 12.5 7
18 18 24 24 12.5 12.5
Connection 7
7.5
7.5
7 7
18 12.5 12.5
24 7
7.5
8.2
Ø9 Ø9
M8×14
8.2
8.2
Ø9 Ø9 Ø9 Ø9
M8×14 M8×14
Terminal Tightening torque Conductor 15
MCCB
8.2
18 24 Ø9 7
M8×14 7.5 (mm) (kgf·cm) Ø9 (mm)
15 15 15
18 18 24 24 7 7 7
7.5
7.5
M8 : 55 ~ 75 15
15
18 24 7 7
7.5
M8×14
8
M8×14 M8×14 Ø9 Ø9
125AF Ø9 Ø9 Ø9 Ø9
8
M8×14 18 24 16
Ø9 16 8
18 18 24 24 Ø9 16 16
10
8 8 8
10
10
18 24 16 16
8 8
10
M8 : 80 ~ 130
M8×20 Ø9 Ø9
M8×20 M8×20 Ø9 Ø9 Ø9 Ø9
21
≤25
21
≤25 10 ≤25
21
250AFM8×20 Ø9 Ø9
≤25
28 24 10 10 10
28 28 24 24
21
≤25 ≤25
10 10
28 24
42
Technical Information
Safety clearance
When installing a circuit breaker, safety clearances must be kept between the breaker and panels, bars
and other protection devices installed nearby. These safety clearances are depend on the ultimate
breaking capacity and are defined by tests carried out in accordance with standard IEC 60947-2.
When a short circuit interruption occur, high temperatures pressures are present in and above the arc
chambers of the circuit-breaker. In order to allow the pressure to be distributed and to prevent fire and
arcing or short-circuit currents, safety clearances are required.
Frame A(mm)
Description
size 415/460V 220/240V
A
125AF ABS125c 100 80
Frame C1 (mm) C
Description
size 415/460V 220/240V (mm)
The dimension
conduct + C1
C
C
C
C1
C1
C1
C1
C1
C1
C1
C1
C1
43
Technical Information
Safety clearance
D3
D1
D2
•D3: Connection by solderless terminal and using insulation barrier
•D4: Connection by busbar and using insulation barrier
Frame D1 D2 D3 D4
Description
size (mm) (mm) (mm) (mm)
D4
D3
D1
D2
The dimension
The dimension
conduct + 20
conduct + 20
125AF ABS125c 50 50
of bare
of bare
250AF ABS250c 50 50
E E
Frame E(mm)
Description
size 415/460V 220/240V
125AF ABS125c 50 20
250AF ABS250c 50 15
44
Technical Information
Safety clearance
Frame
Description F(mm)
size
F
125AF ABS125c 10
250AF ABS250c
10
Frame G
Description G(mm)
size
125AF ABS125c 0
250AF ABS250c 0
45
Technical Information
Metasol series circuit breakers and auxiliaries comply with the following
international standard:
•IEC 60947-1
Low-voltage switchgear and controlgear - Part 1: General rules
•IEC 60947-2
Low-voltage switchgear and controlgear - Part 2: Circuit-breakers
CE conformity marking
The CE conformity marking shall indicate conformity to all the obligations imposed on the
manufacturer, as regards his products, by virtue of the European Community directives providing
for the affixing of the CE marking.
When the CE marking is affixed on a product, it represents a declaration of the manufacturer or of
his authorized representative that the product in question conforms to all the applicable provisions
including the conformity assessment procedures.
46
Standard Use Environment
47
Technical Document
16 16 16 16 16 15 15 14
20 20 20 20 20 19 19 17
25 25 25 25 25 24 23 21
32 32 32 32 32 31 30 27
40 40 40 40 40 39 37 34
ABS125c
50 50 50 50 50 48 46 43
63 63 63 63 63 61 58 54
80 80 80 80 80 77 74 68
100 100 100 100 100 97 93 86
125 125 125 125 125 121 116 107
100 100 100 100 100 96 93 86
125 125 125 125 125 121 117 107
ABS250c 160 160 160 160 160 154 149 137
200 200 200 200 200 193 186 171
250 250 250 250 250 241 233 214
48
Technical Document
Impact of Altitude
If an MCCB is used in an elevated area higher than 2000m sea level, its operating performance is subject to
dramatic drop in atmospheric pressure and temperature. For example, the air pressure is reduced to 80% of
ordinary pressure at 2,200m and further 50% at 5,500m although the short-circuit performance is not affected.
If it is used in areas of high sea level, you can do correction based on the correction parameter table in high
altitude environment, as described below.
[Correction Parameter Table for Altitude]
Voltage Current
* Refer to the correction parameter table in high altitude Altitude Correction Correction
environment (ANSI C37. 29-1970) Parameter Parameter
1) How to Correct Voltage: 2,000m 1.00 1.00
- If the rated voltage is AC 600V at 4,000m above sea level, 3,000m 0.91 0.98
600V (rated voltage) × 0.82 (correction parameter) = 492V.
4,000m 0.82 0.96
2) How to Correct Current:
5,000m 0.73 0.94
- If the rated voltage is AC 800A at above 4,000m sea level,
800A (rated current) × 0.96(correction parameter) = 768A. 6,000m 0.65 0.92
49
Technical Document
Vibration
The magnitude of vibration is measured by double amplitude and frequency with the following equation with
accelerator.
αg=0.002×frequency(Hz)×double amplitude (mm)
* αg: multiple of gravitational acceleration (g=9.8m/sec2)
There are three types of vibration tests including resonance test, vibration endurance test, and malfunction test
as described below.
1) Resonant Test
Alter the frequency of sinusoidal wave within the range of 0~55Hz gradually with 0.5~1mm of double
amplitude applied to see if there is any occurrence of vibration on a specific part of MCCB.
2) Vibration Endurance Test
A sinusoidal wave with double amplitude of 0.5~1mm and frequency of 55Hz(resonant frequency obtained in
previous clause if there is a resonant point) is manually created to check the operational status.
3) Malfunction Test
Apply vibration for 10 minutes for each condition of altering double amplitude and frequency to check if there
is any malfunction in MCCB.
Impulse
The magnitude of impulse is denoted by the multiple of gravitational acceleration imposed on the equipment and
part. The test is conducted through a drop impulse test.
* Core loss: It refers to the electrical loss in a transformer caused by magnetization of the core that changes
over time and is categorized into hysteresis loss and eddy current loss.
* Hysteresis loss: It takes up the majority portion of no-load loss of electric equipment and is calculated like this.
Ph = σfBmn
Bm: maximum value of magnetic flux density, n: constant(1.6~2.0), f: frequency, σ: hysteresis constant
* Eddy current: It refers to an induced electric current formed within the body of a conductor when it moves
through a non-uniform or changing magnetic field. The eddy current that incurs at winding of
transformer or core is considered as one of the transformer losses as a part of exciting current. It
is also called ‘eddy current loss’.
50
Technical Document
Top-down ON ON
Top-down
ON ON
Status of (1) Non-conduction (ON or OFF status) Non-conduction (ON or OFF status)
MCCB (2) S
tatus where rated current is
conducted until the temperature of
MCCB becomes constant and
keeps being conducted
51