Professional Documents
Culture Documents
Prepared by :
Eng.Elmamoun Ibrahim Mustafa
Low Voltage Switchgear
1- Introduction to the switchgear
LV Switchgear Functions
LV-Switchgear protection
Switchgear control
Incomers.
Feeders
6-Motor Overloads relays
Low Voltage Switchgear
7- Circuit Breaker
Air circuit breaker(ACB).
Utilization categories.
ACB features .
ACB components.
8-MCCB
Accessories of MCCB
Types of MCCB
Selection of MCCB
9-Fuses
Fuse type (rewirable,t otally eclosed)
Let through energy
Selection parameter
Coordination type1&2
Capability
Utilization category
Low Voltage Switchgear
11- SWGR Main common part
Incomers
Feeders
Bus-section
Standard color code and numbers of Control wires
Enclosure degree of protection (Ingress protection)
12-SWGR Types
Main Distribution Boards(MDB)
Sub distribution Board (SDB)
Motor control Center(MCC)
Automatic Transfer switch (ATS)
Definitions Switchgear
A general Term covering Switching devices &
their combination with associated control
,measuring ,protective and regulating
equipment ,also assemblies of such devices and
equipment with associated interconnects
,accessories, enclosures and supporting
structure, intended in principle for use in
connection with generation , transmission ,
distribution& conversion of electric energy.
Exemplar LV -SWGR
Introduction to the switchgear
The term switchgear, used in association with the
electric power system, or grid, refers to the
combination of electrical disconnects, fuses and/or
circuit breakers used to isolate electrical
equipment.
Switchgear is used both to de-energize equipment
to allow work to be done and to clear faults
downstream.
This type of equipment is important because it is
directly linked to the reliability of the electricity
Exemplar LV -SWGR
supply.
Introduction to the switchgear
Applications
Low voltage switchgear exist in
Upstream of components Critical power
Downstream of transformers
Industrial facilities
Exemplar LV -SWGR
Utilities
Oil and gas
Introduction to the switchgear
LV Vr < 1
MV 1 < Vr < 35
Control Device.
Switchboards
LV Switchgear Functions
LV Switchgear Functions
Electrical protection
Protection of circuit elements against the thermal and
mechanical stresses of short-circuit currents
Protection of persons in the event of insulation failure
Protection of appliances and apparatus being supplied
(e.g. motors, etc.)
Electrical isolation of sections of an installation
Local or remote switching
Over-voltage protection
Exemplar LV -SWGR
Under-voltage protection
Switchgear Functions
Switchgear
Switching Protection
On/Off Close/Open Abnormal Condition
Connect / Dis-connect Over current E/F
Start / Stop O/L S/C
Make /Carry/ Break
Exemplar LV -SWGR
10. EL+MCB.
LV Switchgear Product Features & Ranges
Contactor 9 to 550 A (ON/OFF)
Relay 0.6 to 450 A (O/L +Single Phasing )
Fuse 2 to 800 A (S/C)
ACB 400 to 6300 A (ON/OFF+ O/L+ S/C)
MCCB 16 to 1600 A (ON/OFF+ O/L+ S/C)
MPCB 0.16 to 63 A (ON/OFF+O/L+ S/C+ Single Phasing)
VOLTAGES
Currents
Conventional Free Air Thermal Current (Ith).
Rated Current(In).
Exemplar LV -SWGR
Low Voltage Switchgear Terminology-Currents
Rated Current(In).
Contactors
Switchgear Products & components
Contactors
A mechanical Switching Device having only one position
of rest operated otherwise than hand, capable of making
,carrying and breaking currents under normal circuit
condition including overload condition.
Exemplar LV -SWGR
Exemplar LV -SWGR
Contactors
Exemplar LV -SWGR
Left – Vacuum Contactor 6kV 400A; Right – 12 kV, 40 kA Indoor Vacuum Circuit Breaker
Contactors
Working principle
When power is supplied to the coil from the control
circuit, a magnetic field is produced, magnetizing the
electromagnet. The magnetic field attracts the armature
to the magnet, which in turn closes the contacts. With
the contacts closed, current flows through the power
circuit from the line to the load. When current no longer
flows through the control circuit, the electromagnet’s coil
is de-energized, the magnetic field collapses and the
movable contacts open under spring pressure.
Exemplar LV -SWGR
Contactors
Contactors circuits
Power circuit
Control circuit
Auxiliary Circuit
Notice:
No electrical connection between them, and all can have
different supply.
Exemplar LV -SWGR
Contactors
Power circuit
Consists of main contacts.
Make, carry & break load Current.
Control circuit
Consists of coil of contactor.
For operating the contactor.
Pick up: at 85% & withstand up to 110% of Uc.
Definition ( the Min voltage at which the contactor picks up satisfactorily)
Drop off :75 to 20% of Uc.
Exemplar LV -SWGR
Definition:(the Max voltage at which the contactor will droop off completely)
Contactors
Auxiliary Circuit
Accessory part.
Consist of NO or NC contacts.
Does not affect the contactor operation.
Gets affected by contactor operation.
Used for indication, interlocking ..ect.
Exemplar LV -SWGR
Contactors
Limits of operation :
Pick Up – 85% to 110% of Uc.
Drop Off - 75% to 20% Of Uc(For A.C)
75% to 10% Of Uc(For D.C)
Terms:
Power contactor.
Control contactor.
Capacitor Duty contactor.
AC contactor.
DC Contactor.
Exemplar LV -SWGR
Vacuum Contactor
Contactors
Application Area:
Switching Of Motors.
Switching Of Lighting Loads.
Switching Of Heating loads.
Switching Of Capacitor.
Features :
Long operational Life.
High frequency of Operation.
Can operated from remote.
Can be used for Automatic switching operation.
Can offer no volt protection
Exemplar LV -SWGR
Contactors
Utilization Categories
What is the meaning of the utilization categories for
the contactors?
The standard utilization categories defines the current
making and breaking values for contactors. They depend
on the following:
1. The type of load to be controlled (squirrel cage or slip
ring motor, resistors)
2. The operating cycle conditions (motor running, stalled
or starting, reverse operation, …ect)
Exemplar LV -SWGR
Contactors
Utilization Categories
AC1:Non –Inductive/ Slightly Inductive Loads &
Resistance Furnaces.
AC2: Slip ring motors : Starting/ Switching off.
AC3:Squirrel Cage Motors : Starting /Switching Off
during Running.
AC4:Squirrel Cage Motors : Starting Plugging &Inching.
DC1:Non-Inductive or Slightly Inductive loads,
Resistance Furnaces.
DC3:Shunt Motors: Starting Plugging and Inching.
Exemplar LV -SWGR
Terminal Size.
Easy of maintenance.
Availability of Spares.
Contactors
Selection of Guidelines:
Study the Application & find out Utilization Category.
Select a contactor with current rating for that particular
Utilization Category equal or more than full load current.
Contactor should have Sufficient making capacity to
close on in rush currents.
No of operations required should be fulfilled by contactor
for that Utilization Category.
Exemplar LV -SWGR
RELAY
Protective relaying is
the Science or Art of
detecting faults on
power systems and
clearing those faults
from the power
system as quickly as
possible.
Exemplar LV -SWGR
Protection relays
Classification of Relays:
Classification can be done by different ways, such as by
function, input and performance characteristics …etc. so
it can be divided into following types:
(i) Protective Relays:
Protective relays and fuses operate on the intolerable
power system conditions. They are applied to all parts of
the power system; generators, busbars, transformers ,
transmission lines , distribution lines , feeders, motors
loads, capacitors banks and reactors.
Exemplar LV -SWGR
(ii) Regulating Relays:
Regulating relays are associated with tap changer of
transformers , on governor of generating equipment to
control the voltages level with varying load (used during
normal conditions).
(iii) Monitoring Relays:
This type of relays are used in energizing or restoring lines
to service after an outage and in interconnecting pre-
energizing parts of the systems.
(iv) Auxiliary Relay:
There are two categories:
Exemplar LV -SWGR
8. Others.
SWGR panel Sections Protection
Protection applied for different sections of the SWGR:-
1- Incomer section which could be:-
a- Transformer.
b – Public utility supply.
c – Generator (emergency Gen Set).
2-outgoing feeders
Loads (Motor feeder) , sub distribution boards
A - Motors
B - Lighting
C- Heating loads
D-Air conditioning.
Exemplar LV -SWGR
Hospitals Process
Public building(bank, etc.) cement works (furnace,
Computer Centre motor….etc)
Incomers
Generator protection
Electrical protections
1- Over current & earth fault.
2-Over /under voltage.
3-Over/Under Frequency.
4- Reverse active power.
Mechanical protections
1-Over /under speed.
2-Lub oil Temp
3-Oil pressure.
Exemplar LV -SWGR
Electronic overloads:-
are the newest form of overloads. They replace thermal
based protection with electrical measurements.
Electronic overloads can be simple and inexpensive or
quite sophisticated, premium priced devices.
Exemplar LV -SWGR
Tripping class
Tripping classes of the thermal overload relays
Overload relays typically operate on an inverse time
curve where the tripping time becomes less as the
current increases. They are rated by trip class. Trip class
specifies the length of time it will take for the relay to
open in an overload condition.
Standard tripping classes are10, 20, 30. The tripping
class indicates according to IEC 60947-4-1 the
maximum tripping time in seconds under specified
conditions of test at 7.2 times the setting current and
specifics tripping and non tripping times for 1.5 and 7.2
times the setting current.
Exemplar LV -SWGR
Tripping classes
Tripping classes
Exemplar LV -SWGR
Circuit Breakers
Circuit Breaker
Circuit Breaker is :
A switching Device.
Capable Of making , Carrying & breaking normal or fault
currents.
Must offer short circuit current.
Circuit Breaker Types:
MCB(Miniature Circuit Breaker) UP to 125 A.
MCCB (Molded Case Circuit Breaker) Up to 1600 A.
MPCB (Motor protection Circuit Breaker) Up to 63 A.
ACB (Air Circuit Breaker) Up to 6300 A.
Exemplar LV -SWGR
Air Circuit Breaker
Exemplar LV -SWGR
Exemplar LV -SWGR
Air Circuit Breaker
Methods
Method of operation
Manual operated
Electrically operated.
Method of Installation
Fixed
Draw out
Exemplar LV -SWGR
Air Circuit Breaker
Applications
As a switching & protection Device for Power
Distribution ( As incomer, Bus-coupler & out going
feeder).
For Transformer protection.
For Bus bar / Cable protection.
Switching protection of motors ,lighting loads, heating
loads, capacitor etc.
Exemplar LV -SWGR
Air Circuit Breaker
Specifications
Rated operational Voltage Ue .
Nominal Rated current In .
Rated Ultimate S/C Breaking capacity Icu.
Rated Service S/C Breaking capacity Ics.
Rated S/C Making capacity Icm.
Rated Short time withstand current Icw.
Utilization category B.
Exemplar LV -SWGR
Air Circuit Breaker
Rated Ultimate S/C Breaking capacity Icu.
Circuit Breaker can break two faults of claimed Value and
can make one fault of the claimed value .
in other words: the circuit breaker must be able to break this
current two times without causing damage, the breaker must
be replaced or tested sub-sequently after two short circuits
(Test sequence: Icu: O-t-CO)
The test is use to see the performance of the contacts (Fix &
Moving) of a circuit breaker (as per standard), earlier it was
called as P1 duty (O-CO)
O=open
Exemplar LV -SWGR
T=relaxation
C=close
Test of Performance of the contacts
Rated Service S/C Breaking capacity Ics.
Circuit Breaker can break three faults of claimed Value and
can make two fault of the claimed value.
in other words: the circuit breaker must be able to break this
current three times without causing damage, the breaker
must sub-sequently be able to conduct its rated current
without prior maintenance (Test sequence: Ics: O-t-CO-t-CO)
Also earlier this test was called P2 duty (O-CO-CO).
O=open
T=relaxation
C=close
Rated Shorted time Withstand Capacity Icw.
Exemplar LV -SWGR
1. Releases.
2. CTs
3. Micro-switches.
4. Lock & Interlocks.
Exemplar LV -SWGR
ACB component
1-Releases
Fault diagnostics Units(O/L,S/C,U/V,E/F).
Generate mechanical tripping command.
Magnetic ,thermal, semiconductor ,Microprocessor
principles.
Releases
Exemplar LV -SWGR
Bimetal
Settings
Exemplar LV -SWGR
Short Circuit
Coil +Plunger
Instantaneous operated
Setting
M1 M2
500% 700%
Exemplar LV -SWGR
Exemplar LV -SWGR
ACB component
ACB component
Shunt Release
Versions : AC coil,DC coil
240 VAC 415 VAC Operating voltages.
24VDC,48VDC,110VDC,220VDC.
Operating 70% to 110% Of Vn of AC coil.
Used for remote tripping.
Electrical Interlocking.
Exemplar LV -SWGR
ACB component
ACB component
Exemplar LV -SWGR
ACB component
ACB component
Instantaneous 2 to 16 -
Microswitches Applications:
Are Nothing but limited switch
They are auxiliary switches for position sensing.
Used of various indication :-
i) Service position.
ii) Test or lsolated position.
Exemplar LV -SWGR
Exemplar LV -SWGR
Micro switches
4-Lock & Interlocks
Tighten
Test
Molded Case Circuit Breaker
MCCB
(Molded Case Circuit Breaker)
Exemplar LV -SWGR
Molded Case Circuit Breaker
Exemplar LV -SWGR
Molded Case Circuit Breaker
Why using MCCBs.
Lower Downtime.
Reduced Running cost.
Low inventory.
Accessories e.g
Trip indiction.
Remote Tripping.
UV Protection.
Auxiliary contact.
In built O/L + S/C Protection.
Occupies less space.
Exemplar LV -SWGR
Types
Conventional type
Operating time :15 to 20 msec.
Higher let though Energy.
Current Let though energy.
Current limiting MCCB
Lower Let through energy
Exemplar LV -SWGR
Molded Case Circuit Breaker
Selection of MCCBs
Current rating.
Overload & short circuit release settings.
Breaking Capacity.
Fault level at the point of the installation.
Mechanical & electrical life.
Exemplar LV -SWGR
Molded Case Circuit Breaker
Exemplar LV -SWGR
Molded Case Circuit Breaker
Fuses
Fuses
1. REWIREABLE FUSES
The most commonly used fuse in 'house wiring' and
small current circuit is the semi-enclosed or rewireable
fuse.(also sometime known as KIT-KAT type fuse).
fuse wire may be of lead, tinned copper, aluminum or an
alloy of tin-lead. The actual fusing current will be about
twice the rated current.
such fuses have the advantage of easy removal or
replacement without any danger of coming into the
contact with a lie part and negligible replacement cost
Exemplar LV -SWGR
Fuses
fault levels.
Fuses
HRC Fuse
Contacts for
Cylindrical Contact Blade Contacts bolted
Cap
connection
Size 0 A1,A2,A3,A4
Size 10X38
Size 1 B1,B2,B3,B4
Size 14X51
Size 2 C1,C2,C3
Size 22X58
Size Diameter X D1
Size 3
length
Size
Exemplar LV -SWGR
4
Fuses
160 amperes.
Fuses
Fuses
Fuses
Type 1 coordination:
type 1 coordination requires that, under short circuit
conditions, the contactor or starter shall cause no danger
to persons or installations and may not be suitable for
further service without repair and replacement of parts.
Type 2 coordination:
type 2 coordination requires that, under short circuit
conditions, the contactor or starter shall cause no danger
to persons or installations and shall be suitable for further
use. The risk of contact welding is recognized, in which
case the manufacturer shall indicate the measures to be
Exemplar LV -SWGR
RCCB designed to
disconnect quickly enough
to mitigate the harm caused
by such shocks although
they are not intended to
provide protection against
overload or short-circuit
conditions.
Exemplar LV -SWGR
A two-pole residual current device wiring
L =live conductor
N =neutral
A two-pole residual current device wiring
The most widely used are 30 mA (milliamp) and 100 mA
devices. A current flow of 30 mA (or 0.03 amps) is
sufficiently small that it makes it very difficult to receive a
dangerous shock. Even 100 mA is a relatively small figure
when compared to the current that may flow in an earth
fault without such protection (hundred of amps)
A 300/500 mA RCCB may be used where only fire
protection is required. eg., on lighting circuits, where the
risk of electric shock is small
RCDs are an extremely effective form of shock protection
Exemplar LV -SWGR
RCCB - sensitivity ∆In
Isolation
The function intended to cut off the supply
from all or discrete section of installation
by separating installation or section from
every source of electrical energy for
reasons of safety.
Isolation Distance between contacts.
Clearance And Creepage.
Exemplar LV -SWGR
Switches ,Dis-connecter ,Isolator
Switch
A manual Switching device.
Shall make, break and carry current under normal
&Specified overload condition.
Shall be capable of carrying for A specified time, short
circuit currents.
Shall withstand short circuit till S.C.P.D clear the fault
( With A minimum of 12 Ie for 1 sec)
Exemplar LV -SWGR
Switches ,Dis-connecter ,Isolator
Switch-Switching capability
Dis-connecter
A mechanical Switching Device.
In open position complies with requirements specified for isolating.
Carry normal and over load.
Carry short circuit currents for specified time.
Switching on and off in no load.
Exemplar LV -SWGR
Switches ,Dis-connecter ,Isolator
Switch- Dis-connecter
For Isolating the motor feeder for any maintenance
work.
Can be used as back-up switching device in case of
emergencies (like contactor welding).
Positive opening of main contacts.
Additional facilities like door interlock and padlocking.
A switch which in opening condition satisfies the
isolating requirements specified for disconnector.
Exemplar LV -SWGR
Positive Opening Mechanism
Exemplar LV -SWGR
Switches ,Dis-connecter ,Isolator
Exemplar LV -SWGR
Utilization categories of LV AC switches
according to IEC 60947-3
Exemplar LV -SWGR
Utilization categories of LV AC switches
Exemplar LV -SWGR
Fuse combination units
Design Example
Switchgear common main parts
Exemplar LV -SWGR
Low voltage switchgear common main parts
The most common use of LV switchgear is in LV Distribution
Board so This systems has the following parts
(1) Incomer
The incomer feeds incoming electrical power to the
incomer bus. The switchgear used in the incomer
section should have a main switching device.
The switchgear devices attached with incomer
should be capable of withstanding abnormal current
for a short specific duration in order to allow
downstream devices to operate. But it also be
Exemplar LV -SWGR
(2)Feeders
Different feeders are connected to the bus to feeds
different loads like, motor loads, lighting loads, industrial
machinery loads, air conditioner loads, transformer
cooling system loads etc.
All feeders are primarily protected by switch fuse unit & in
addition to that, depending upon the types of load
connected to the feeders, the different switchgear devices
are chosen for different feeders. Let’s discuss in details
Exemplar LV -SWGR
Low voltage switchgear common main parts
Standard
color codes &numbers
for control wires
Exemplar LV -SWGR
Control wires
[figure (a)]
Exemplar LV -SWGR
Low Voltage Switchgear -types
1/2 changeover sequence
[figure (b)]
Exemplar LV -SWGR
[figure (d)]
automatic changeover modes
Limitations:
Difficult to change resistance.
Dissipate a lot of heat.
Limited number of starts per hours.
Start characteristics change between starts if
the resistance have not totally cooled.
Hard to start high inertia loads
Exemplar LV -SWGR
Auto transformer Starting method
Draw Backs:-
Requires frequent maintenance &
Inspection.
Voltage applied to motor is in steps
& not continues, hence voltage
Flickers & mechanical jerks.
Produces a very dangerous current
spikes.
Exemplar LV -SWGR
Star-Delta Starting Method
Star-Delta Starting
Method
The motor initial connected
in star configuration and
then ,after preset time, the
motor is disconnected for
the supply and
reconnected in delta
configuration
Exemplar LV -SWGR
Star-Delta Starting Method
Exemplar LV -SWGR
Star-Delta Starting Method
When compared to DOL starting current and toque
reduces by 1/3rd .
Open transition form star to delta cause high current &
torque transient.
Sequence
Star-ON
Main-ON
Starting time (Seconds)
Star-OFF
Pause time (msec).
Delta -ON
Exemplar LV -SWGR
Exemplar LV -SWGR
Electronic soft starter
Introduction
Soft starters use a combination of power electronics and
electronic control circuitry to slow increase the voltage
on the motor during starting; ensuing a smooth
acceleration.
Soft starters use thyristors-SCR- (Silicon Controlled
Rectifier) to control the energy delivered to the motor. A
thyristor is a device which turns on when a pulse is
applied to its gate and will continue to conduct until the
current drops to zero (at which time it turns off). In an
AC sine wave current goes to zero each half cycle,
Exemplar LV -SWGR
Loads
Exemplar LV -SWGR
Induction motors
synchronous motors.
Shunt capacitors
FAULT LEVEL CALCULATIONS
CALCULATION ASSUMPTIONS
WHY ?
Simplifies calculation.
Accuracy is not much affected.
Calculated values will be higher than actual & hence
safe.
Exemplar LV -SWGR
FAULT LEVEL CALCULATIONS
CALCULATION ASSUMPTIONS
WHAT ?
Type of short circuit : three phase bolted short circuit
Impedances of busbar /switchgear / c.T. /Joints are
neglected.
Fault current from the transformer would be limited by the
source fault level
Transformer tap is in the main position.
Short circuit current waveform is a pure sine wave.
Exemplar LV -SWGR
Step 1:
Prepare a single line diagram of the electrical power
supply and distribution network, clearly indicating all the
significant network elements, fault current contributors,
short circuit protective devices, etc.
(iii) Cable Resistance (RC) & Cable Reactance (XC) per unit
length and the actual length of the cable used.
(iv) Motors’ rated voltages (UrM), rated currents (IrM) and
locked rotor currents (ILR).
Step 3:
Convert %R into Ohmic values, to obtain RT.
10 x (%R) x (kV)2
RT (in Ω) = ------------------------ {multiple by10 to change from PU}
Exemplar LV -SWGR
kVA
FAULT LEVEL CALCULATIONS
Step 4:
Similarly, convert %X into Ohmic values, to obtain XT.
10 x (%X) x (kV)2
XT (in Ω) = ------------------------ {multiple by 10 to change from PU}
kVA
Step 5:
Similarly, convert %x”d of the generator into Ohmic
values, to obtain XG.
10 x (%x”d ) x (kV)2
Exemplar LV -SWGR
Step 6:
Now, the resistance of the generator, ‘RG’ is normally
given as a % of ‘XG’. For LV Generators, it is:
RG (in Ω) = 0.15 XG.
Step 7:
Calculate a correction factor ‘KG’.
Un c
KG = ------- -------------------------------
Exemplar LV -SWGR
where,
KG = Generator Correction Factor
Un = Nominal System Voltage, in Volts
URG = Generator Rated Voltage, in Volts
c = Voltage Correction Factor = 1.05
x”d = Sub-transient Reactance of the Generator, in p.u.
form Sin φrG = √(1 – Cos2φrG)
CosφrG = Rated Power Factor of the Generator
Exemplar LV -SWGR
FAULT LEVEL CALCULATIONS
Step 8:
Now find out the Corrected Generator Resistance (RGK)
& the Corrected Generator Reactance (XGK):
RGK = KG x RG
XGK = KG x XG
Step 9:
Now find out the cable resistance & reactance for the
actual length of cable used up to the point of fault:
Exemplar LV -SWGR
RL = RC x LC
XL = XC x LC
FAULT LEVEL CALCULATIONS
Where,
RL = Line or Lead Resistance, in Ω
XL = Line or Lead Reactance, in Ω/meter
RC = Cable Resistance per km, in Ω/meter
XC = Cable Reactance per km, in Ω
LC = Actual length of cable up to the point of fault, in m
Exemplar LV -SWGR
FAULT LEVEL CALCULATIONS
Step 10:
Now add all ‘R’ & all ‘X’ values; find out ‘Zk’.
Zk = √[(Re)2 + (Xe)2]
Re = RT or RGK + RL
Xe = XT or XGK + XL
Step 11:
Now find out the initial symmetrical short circuit current, I”k:
c Un
Exemplar LV -SWGR
I” k = -------
√3 Zk
FAULT LEVEL CALCULATIONS
where,
I”k = Initial Symmetrical short circuit current, in Amperes
Un = Nominal System Voltage, in volts
c = Voltage Correction factor = 1.05 for LV (for HV it is 1.10)
Zk = Equivalent Impedance up to the point of fault, in Ω
Exemplar LV -SWGR
FAULT LEVEL CALCULATIONS
Cosϕrg=0.8
Fault level Calculation
Step 2: System Data
Cable : R= 0.062 Ώ/Km
X=0.079 Ώ/Km
Length of the cable 21 to 31 =100 M
Induction Motors : M1 Irt =70 A
M2 Irt =135 A
M3 Irt =40 A
M4 Irt =200 A
Exemplar LV -SWGR
Fault level Calculation
RG = 0.004134 Ohms
Exemplar LV -SWGR
Fault level Calculation
Step 6
Calculation of RMS Value at the point of the fault.
Ik “ At the fault location F1
Step 7
Calculation of X/R up the point of the fault F1,F2,F3.
X/R up the point of the fault location F1
Step 10:
Calculate the aggregate of the rated full load currents of
all the motors at a particular location (ΣIrM).
If (ΣIrM) at a particular location is less than 1% of the
short circuit current contributed by other sources for a
fault at that particular location, then contribution to the
short circuit, from the motors need not be considered.
Or else, the motors’ contribution to short circuit has to
be calculated. So for this case contribution by induction
motors to the RMS S/C current at the fault location
Exemplar LV -SWGR
Step 11:
contribution by induction motors to the Peak S/C
current at the fault location F1,F2 &F3
the peak current contribution from the motor group would
be:
IpM = χM √2 I”kM
Where:χM = 1.3 for an R/X ratio of 0.42 (Given as per IEC60909),
as in the case of LV Induction motors
{R/X of 0.2 in the case of LV asynchronous motors(Given as per IEC60909)}
Exemplar LV -SWGR
Step 11:
Calculate the total fault level, both R.M.S. (I” KT ) and
the Peak (IpT) at the fault location:
I” KT = I”K + I” KM & IpT = Ip + IpM
Fault location F1
R.M.S Value (I” KT) =38.77 + 2.34=41.11 KA
Peak value (IpT )=87.71+4.3= 92.01 KA ( Peak)
Fault location F2
R.M.S Value (I” KT) =9.63 + 2.34=11.97 KA
Exemplar LV -SWGR
Fault location F3
R.M.S Value (I” KT) =15.67 + 2.34=18.01 KA.
Peak value (IpT ) =27.70+4.3= 32 KA ( Peak).
Result of the fault level calculation
Panel Structure
Structure contains the following:-
1. Front doors.
2. rear doors.
3. left and right side panels.
4. rear panels.
5. Basic compartment.
6. rear extensions.
7. Internal Sheet Metal
8. Instrument compartment,
breaker compartment.
protection panel.
Exemplar LV -SWGR
truck rail.
riser support
9. Shipping Frame
Construction Specifications
Panel housing description
1.General
The switchboard shall be an indoor, air insulated
and metal enclosed in accordance IEC/AS 62271-
200 classification with single bus bar system. It
shall be suitable for local and remote control, and
may communicate to the control system by field
bus connection. Switchboard shall be designed in
order to:
1. ensure service continuity to IEC 60439/61439
Exemplar LV -SWGR
Construction Specifications
2. guarantee high degree of operator safety
ensure easy installation and reduced
construction costs be easily adaptable to future
arrangement and extensions on both sides of
the switchboard,
3. Power cable connection preferably will be done
by cable from bottom front.
4. Bus-bar shall be copper and insulated.
5. All operations shall be performed with arc fault
contained door closed for maximum operator
Exemplar LV -SWGR
Doors:
Front doors - Semi-
concealed hinges
Rear doors – Bolted,
optional hinge (with Pad-
locking & handles)
Infrared Windows (Optional)
Paint
Electro static powder coat
(standard)
Exemplar LV -SWGR
f. Gas insulated bus bars. These are usually constructed as type (e) but use a
gas other than air such as SF6, (sulphur hexafluoride-SF6).
g. Totally enclosed bus bars using compound or oil as the insulation medium.
Exemplar LV -SWGR
(GIS) Gas Insulated Bus-bar
Exemplar LV -SWGR
Construction
Bus Design
The type of bus bar system selected for a specific duty is determined
by requirements of voltage, current, frequency, electrical safety,
reliability, short-circuit currents and environmental considerations.
Standard temperature rise Max 65ºC over 40ºC ambient
Platting
Insulation
Bare (standard)
Insulated bus (optional)
Bus bracing using steel supported polyester type fingerplates
Exemplar LV -SWGR
Comparison of typical design requirements for power generation and
industrial process systems
Feature Generation Industrial Processes
4 Jointing and Usually bolted but high current Usually bolted. Joint
connections applications are often fully welded. preparation very
Joint preparation very important important.
type
Construction
Riser Bus
Main Bus
Runbacks
Exemplar LV -SWGR
Construction-Type of structure/installation
1- Wall-mounted structures
Exemplar LV -SWGR
Construction-Type of structure/installation
2- Floor-mounted structures
Exemplar LV -SWGR
Construction
Control Wiring
Inter-cubical wiring made easy
Terminal strips
Located in wire way on
top of enclosure
Exemplar LV -SWGR
Construction
Instrumentation
Breaker door mounted lights, meters and control
Indicating Lights
Volt, amp, and watt meters
control switch (Selector switchs)
Multifunction Metering
Relays
Surge Protectors.
LCD Display
Exemplar LV -SWGR
Key features and benefits
Section Widths samples
E4 3200 Amp E2/E3 800 – 1600 E2 800 - 1600A
E6 4000 Amp E3 2500 Amp (65 & 100 kA) (65 kA)
Trip Units
Protection Features
LCD Display
Current Measurement
Contact Wear
Communications option
Harmonic Measurements
Communications option
Exemplar LV -SWGR
Key features and benefits
Safety Features
Safety shutters (standard)
Exemplar LV -SWGR
Key features and benefits
Safety Features
Padlocking provisions
• Anti-insertion lock
• Disconnect.
• connect, and test position
Painting: Satisfied Y , N
The painting is homogenous and correct in color, is free
from light reflection, scratches, flowing path, flaws and
disposals, and it has good adhesive strength