You are on page 1of 4

adaTECH OSC

The adaTECH OSC is an Overhead


Switch Controller, specially designed
to monitor and telecontrol of Load
Break Switch (LBS).

APPLICATIONS MAIN FEATURES


The adaTECH OSC is a compact design for  Control and supervising primary equipment
monitoring and controlling a Load Break Switch, and line status:
with the following functionalities:  Switch commands.
 Remote Terminal Unit (RTU).  Remote - Local operation.
 Line position automation.  Fault detection according to
 Medium Voltage Supervision: overcurrent protection functionalities
 Directional fault detection. (50/51 + 50N/51N).
 Automatic fault isolation, or  Fault isolation.
automatic switch.  Voltage presence and absence.
 Instantaneous current and voltage  Voltage and current measurement.
measurement.  Friendly local HMI design, allowing
 Primary equipment supervision. command execution and easy viewing of
 Alarms management (supply failure, status and alarms.
batteries status, etc.).  Communication protocols under IEC
60870-5-104.
 Web server for data display and remote
device governance.
 Web Services for information exchange
and remote management, compatible with
SOAP 1.2 and WSDL 1.1.
 Users management under LDAP, for
access credential validation, compatible
with OpenLDAP 2.4x.
1.2

www.arteche.com 1
TECHNICAL SPECIFICATIONS

Technical Characteristics
Voltage range 12 Vdc (+30%, -20%)
Power supply
Digital input voltage range 12 Vdc (+30%, -20%)
adaTECH OSC
Consumption <6 W
L0324422H11
Ratio error ± 0.5 % or 0,5 A
Current analog input Phase 15´
between 5 and 4000 A and -10 ºC and +60ºC
± 0.5% between 10% and
Accuracy Voltage analog input Ratio error 100% voltage range
according to 36 kV full scale
Repetition ±0,3%
Definite-time ±1% or 0,03 s.
Inverse-time s/BS 142
Current setting 500/1 A
15000/230 V
Voltage setting 21000/230 V
33000/230 V
1.2

www.arteche.com 2
Functional characteristics
These devices present the following features:
Communication under IEC 60870-5-104 protocol
Installation representation, with measurements, alarms status and position
information.
Measurements, events and adjustment parameters display
Configurable adjustment parameters
Remote access through HTTP
Events and procedures record
FW version history
Load configuration through XML file
SNTP synch
Remote access from SSH server
Configuration status
Remote configuration
Remote configuration modification
Remote events file
Web Services. Information exchange
and remote management systems, Remote software load
compatible with SOAP 1.2 and WSDL Remote configuration load
1.1, such as
First configuration setting
Instant report on any issue
Completed software load
IP petition
User management under LDAP, for access credential validation under OpenLDAP 2.4.x.
1.2

www.arteche.com 3
DIMENSIONS

 Dimensions in mm
1.2

www.arteche.com 4

You might also like