Professional Documents
Culture Documents
Distance Protection
Distance Protection
A Comprehensive Overview
of
Distance Protection
Compiled By:
Shahzad Azam Hashmi
Assistant Manager Electrical
Central Power House,
Bahria Town Karachi, Pakistan
Contact: +92-311-7418463
Email: engineer.hashmi99@gmail.com 1
Shahzad Azam Hashmi Protection Central Power House
Table of Contents
1. Basic Concepts .......................................................................................................................................... 4
1.1. Resistance of Transmission Line........................................................................................................ 4
1.2. Inductance of Transmission Line ....................................................................................................... 4
1.3. Reactance of Transmission Line ........................................................................................................ 4
1.4. Impedance .......................................................................................................................................... 4
1.5. Justification of Impedance for Protection .......................................................................................... 4
1.6. Impedance of Normal Line ................................................................................................................ 5
1.7. Impedance in Case of Fault ................................................................................................................ 5
2. Measuring Principal .................................................................................................................................. 6
2.1. Normal System................................................................................................................................... 6
2.2. Faulty System..................................................................................................................................... 6
2.3. Comparison of Impedance Angle ....................................................................................................... 7
3. Impedance in 3 – Phase System ................................................................................................................ 7
3.1. 3 – Phase Faults ................................................................................................................................. 7
3.2. Phase – Phase Fault ............................................................................................................................ 8
3.3. Phase – Ground Fault ......................................................................................................................... 9
3.4. Compensating Factor (𝑍𝐿𝑁) ............................................................................................................ 10
4. CT Classification..................................................................................................................................... 13
5. Zone of Protection................................................................................................................................... 13
5.1. Inaccuracies...................................................................................................................................... 14
6. Distance Protection Characteristics ........................................................................................................ 15
6.1. Impedance Relay .............................................................................................................................. 15
6.2. MHO or Admittance Relay .............................................................................................................. 15
6.3. Quadrilateral Characteristics ............................................................................................................ 16
7. Polarization Method ................................................................................................................................ 18
7.1. Types of Polarization ....................................................................................................................... 19
8. Source Impedance Ratio (SIR) ............................................................................................................... 19
8.1. SIR Challenges in Short Lines ......................................................................................................... 20
9. Directional Comparison Schemes ........................................................................................................... 20
9.1. Distance Protection Directional Comparison Schemes.................................................................... 21
2
Shahzad Azam Hashmi Protection Central Power House
Table of Figures
Figure 1: Impedance in Transmission Line ................................................................................................... 5
Figure 2: Fault Occur on Transmission Line ................................................................................................ 5
Figure 3: Impedance after Fault Occur ......................................................................................................... 5
Figure 4: Impedance Characteristics of Normal System............................................................................... 6
Figure 5: Impedance Characteristics During Fault ....................................................................................... 6
Figure 6: Comparison of Impedance Characteristics .................................................................................... 7
Figure 7: 3 - Phase Fault (All 3 Phases Shorted Together) ........................................................................... 7
Figure 8: Impedance Characteristics of 3 - Phase Fault ................................................................................ 8
Figure 9: Phase - to - Phase Fault Scenario .................................................................................................. 8
Figure 10: Impedance Characteristics of Phase - Phase Fault ...................................................................... 8
Figure 11: Phase – Ground Fault Scenario.................................................................................................... 9
Figure 12: Impedance Characteristics of Phase - Ground Fault ................................................................... 9
Figure 13: Protection Analysis .................................................................................................................... 10
Figure 14: Single Line Diagram to the Fault Point ..................................................................................... 10
Figure 15: Sequence Network Equivalent Circuit ...................................................................................... 11
Figure 16: Trip Option ................................................................................................................................ 13
Figure 17: Distance Relay Zone Development ........................................................................................... 13
Figure 18: Distance Relay Protection Zone – 1 .......................................................................................... 14
Figure 19: Distance Relay Protection Zone – 2 .......................................................................................... 14
Figure 20: Impedance Relay Characteristics............................................................................................... 15
Figure 21: MHO/Admittance Relay Characteristics ................................................................................... 15
Figure 22: Configuration of MHO Characteristics (PowerDB Software)................................................... 16
Figure 23: Three Zone MHO Relay Setup (PowerDB Software) ............................................................... 16
Figure 24: Quadrilateral Characteristics ..................................................................................................... 17
Figure 25: Three Zones Quadrilateral Characteristics MHO Relay (PowerDB Software) ......................... 17
Figure 26: Testing of Relay Across the Quad Points (PowerDB Software) ................................................ 18
Figure 27: Ground Compensation Option (PowerDB Software) ................................................................ 18
Figure 28: Source Impedance Ratio (SIR) .................................................................................................. 19
Figure 29: Directional Comparison Schemes ............................................................................................. 21
Figure 30: Direct-Underreaching Transfer Trip (DUTT) ............................................................................ 22
Figure 31: Permissive-Underreaching Transfer Trip (PUTT) ..................................................................... 22
Table of Tables
Table 1: Classification of Lines as Per SIR................................................................................................. 20
Table 2: Distance Protection Directional Comparison Schemes ................................................................. 21
3
Shahzad Azam Hashmi Protection Central Power House
1. Basic Concepts
1.1. Resistance of Transmission Line
Resistance of conductor is directly proportional to its length
𝜌
𝑅= ∗ 𝑑=𝑟∗ 𝑑
𝐴
𝜌
𝑟= = 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 𝑙𝑒𝑛𝑔𝑡ℎ 𝑜𝑓 𝑙𝑖𝑛𝑒
𝐴
1.2. Inductance of Transmission Line
(𝐺𝑀𝑀)
𝐿 = 2 𝑥 10−7 ∗ 𝑑
(𝐺𝑀𝑅)
1.4. Impedance
In short transmission line (less than 50 miles) the effect of shunt capacitance can be neglected,
So,
𝑍 = 𝑅 + 𝑗𝑋
𝑍 = 𝑟 ∗ 𝑑 + 𝑗𝑥 ∗ 𝑑 = 𝑑 (𝑟 + 𝑗𝑥)
𝑧 = 𝑟 + 𝑗𝑥
𝑍 =𝑑∗𝑧
𝑍 = 𝐼𝑚𝑝𝑒𝑑𝑒𝑛𝑐𝑒 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 𝑙𝑒𝑛𝑔𝑡ℎ 𝑜𝑓 𝑙𝑖𝑛𝑒
4
Shahzad Azam Hashmi Protection Central Power House
𝑉𝑠 − 𝑉𝑅
𝑍𝐿 =
𝐼𝐿
In case of fault the line divided into two impedances i.e impedance at fault and impedance of
normal line as shown in Fig.3.
𝑉𝑠
𝐼𝑚𝑝𝑒𝑑𝑎𝑛𝑐𝑒 𝑎𝑡 𝐹𝑎𝑢𝑙𝑡 = 𝑍𝑓 =
𝐼𝑓
• Using the relation below the location of the fault can be calculated
𝑍𝑓 = 𝑑𝑓 (𝑟 + 𝑗𝑥) = 𝑑𝑓 ∗ 𝑧
𝑉𝑠
𝑑𝑓 =
𝑧 ∗ 𝐼𝑙
5
Shahzad Azam Hashmi Protection Central Power House
2. Measuring Principal
2.1. Normal System
If we measuring the impedance of the line from some point ‘M’, the RX diagram in Fig.4 shows
the impedance line is close to resistance axis.
6
Shahzad Azam Hashmi Protection Central Power House
7
Shahzad Azam Hashmi Protection Central Power House
𝑉𝑎𝑏 = 𝑉𝑎 − 𝑉𝑏
𝑉𝑎𝑏
𝐼𝑎 = − 𝐼𝑏 =
𝑍𝐿1𝑓
𝑉𝑎
𝑍𝐿1𝑓 =
𝐼𝑎
8
Shahzad Azam Hashmi Protection Central Power House
𝐼𝑎 = 3𝐼0
𝑉𝑎 = 𝐼𝑎 (𝑍𝐿1𝑓 + 𝑍𝐿𝑁 )
𝑉𝑎
= 𝑍𝐿1𝑓 + 𝑍𝐿𝑁
𝐼𝑎
From Fig.10, it can be observed that due to phase to ground fault the impedance angle got shifted.
9
Shahzad Azam Hashmi Protection Central Power House
It can be observed that the actual protection is at point ‘A’ but in phase – ground fault the value
of impedance is high at point B so, there need a compensation from point A to B for the
protection to be operated. Otherwise, the protection will not operate at point B due to higher
value of impedance.
10
Shahzad Azam Hashmi Protection Central Power House
Voltage at the fault 𝑉𝑓 is ‘0’, so we connect the three networks in series. We know from figure 15
that positive sequence impedance and negative sequence impedance is same.
𝑍𝐿1𝑓 = 𝑍𝐿2𝑓
11
Shahzad Azam Hashmi Protection Central Power House
So,
1
𝑍𝐿𝑁 = (𝑍 − 𝑍𝐿1𝑓 )
3 𝐿𝑜𝑓
𝑍𝐿𝑁 𝑐𝑎𝑙𝑙𝑒𝑑 𝑡ℎ𝑒 "𝐺𝑟𝑜𝑢𝑛𝑑 𝑅𝑒𝑡𝑢𝑟𝑛 𝑜𝑟 𝑅𝑒𝑠𝑖𝑑𝑢𝑎𝑙 𝐼𝑚𝑝𝑒𝑑𝑒𝑛𝑐𝑒
Doing some complex mathematics using that base equation we have compensation factor
𝑍𝐿𝑜 − 𝑍𝐿1
𝐾𝑁 = ( )
3𝑍𝐿1
𝐾𝑁 = 𝑅𝑒𝑠𝑖𝑑𝑢𝑎𝑙 𝐶𝑜𝑚𝑝𝑒𝑛𝑠𝑎𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟
𝑍𝐿𝑜 = 𝐴𝑏𝑠𝑜𝑙𝑢𝑡𝑒 𝑍𝑒𝑟𝑜 𝑆𝑒𝑞𝑢𝑒𝑛𝑐𝑒 𝐼𝑚𝑝𝑒𝑑𝑒𝑛𝑐𝑒
𝑍𝐿1 = 𝐴𝑏𝑠𝑜𝑙𝑢𝑡𝑒 𝑃𝑜𝑠𝑖𝑡𝑖𝑣𝑒 𝑆𝑒𝑞𝑢𝑒𝑛𝑐𝑒 𝐼𝑚𝑝𝑒𝑑𝑒𝑛𝑐𝑒
𝑍𝑔 = 𝑍𝐿1𝑓 (1 + 𝐾𝑁 )
𝑉𝑎
= 𝑍𝐿1𝑓 (1 + 𝐾𝑁 )
𝐼𝑎
𝑍𝐿𝑜 − 𝑍𝐿1
𝑃𝑜𝑠𝑖𝑡𝑖𝑣𝑒 𝑆𝑒𝑞𝑢𝑒𝑛𝑐𝑒 𝐶𝑜𝑚𝑝𝑒𝑛𝑠𝑎𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟 = 𝐾𝑜 = ( )
𝑍𝐿1
𝑉𝑎
𝑃𝑜𝑠𝑖𝑡𝑖𝑣𝑒 𝑆𝑒𝑞𝑢𝑒𝑛𝑐𝑒 𝐶𝑜𝑚𝑝𝑒𝑛𝑠𝑎𝑡𝑖𝑜𝑛 𝐹𝑎𝑐𝑡𝑜𝑟 = 𝐾𝑜 = 𝑍𝐿1𝑓 = ( )
𝐼𝑎 + 𝐼𝑜 𝐾𝑁
12
Shahzad Azam Hashmi Protection Central Power House
4. CT Classification
• The most common relaying accuracy class for the CTs is C designation, which reflects if
value of current is 20 times the nominal value, the CT will give the error not more than
10 % when nominal burden is connected to CT.
• The C designation is followed by a number, which is a secondary terminal voltage that
the CT will support while meeting the error limit (≤ 10 %) at 20 times rated primary
current.
• It is not very simple to say that if 𝑍𝑓 < 𝑍𝐿𝑖𝑛𝑒 the trip will be initiated. Instead there
needed to have consider various factors otherwise will not have secure protection.
• So, to overcome this we use safety factors.
5. Zone of Protection
The zones of protections needed to be developed to compensate the error (10 % to 20 %)
• There does not require the instantaneous trip if the fault occur beyond 80 – 90 % of the
total distance of the line because those 10 – 20 % are the errors and inaccuracies that go
into the calculations of those impedances. There are errors in measurements and the
assumptions we taken about the line.
13
Shahzad Azam Hashmi Protection Central Power House
• Line impedance is erroneous that changes with the time so also contribute to error so 10 –
20 % safety factor is good
• Zone – 2 covers complete line including some part of other line. For zone – 2 tripping
there use to give intentional delay.
• Zone -1 must not reach beyond the remote bus
• Use 10 – 20 % safety factors
5.1. Inaccuracies
• Relay measurement accuracies (relays have typically 3% of error)
• CT and PT errors and transients
• Line impedance values are approximation
• CVT transients
14
Shahzad Azam Hashmi Protection Central Power House
• If the impedance value lies with in the circle or range the relay will trip the line
• The reach on the resistance axis is uniform along the edge of circle
• The problem is that it is non – directional so need to supervise it after making it
directional somehow
• It is directional
• Admittance circle passes through the origin which use to be compensated with offset
• The reach along the resistance axis is not uniform as can be assessed from the edge of
circle
• Line ‘S’ is the load line and it is clear that sometimes the load become so high that it
drops the impedance which can operate the relay false.
• To overcome this issue the load blinders are used
15
Shahzad Azam Hashmi Protection Central Power House
16
Shahzad Azam Hashmi Protection Central Power House
Figure 25: Three Zones Quadrilateral Characteristics MHO Relay (PowerDB Software)
17
Shahzad Azam Hashmi Protection Central Power House
Figure 26: Testing of Relay Across the Quad Points (PowerDB Software)
7. Polarization Method
• Comparator-based distance elements require a polarization quantity to provide a reliable
angle reference for directional discrimination
• In previous methods we have voltage that compare with the current to asses the
directionality
• It means if we do not have proper voltage, we will have the trouble in determining the
direction of fault
• Polarization means which voltage to be used to determine the direction of the fault
18
Shahzad Azam Hashmi Protection Central Power House
𝑍𝑠
𝑆𝐼𝑅 =
𝑍𝐿
𝐼𝑎 depends upon the distance of fault from measuring point (Green Box) because less impedance
of the line between the fault point and 𝑍𝐿
19
Shahzad Azam Hashmi Protection Central Power House
SIR Classification
>4 Short Lines
> 0.5 and < 4 Medium Lines
<0.5 Long Lines
• The length of line cannot be used as the criterion for the classification of lines
• It might be possible that a line in length is short but through SIR calculation it is long due
to line impedance
20
Shahzad Azam Hashmi Protection Central Power House
In this both relays looking, at the same fault and take permission from each other through
communication to trip.
21
Shahzad Azam Hashmi Protection Central Power House
22