You are on page 1of 1

ROOM TO BE PROPERLY VENTILATED & TEMPERATURE SHOULD BE MODERATE.

INTER ROW CONNECTOR


INTER ROW CONNECTOR
INTER BANK CONNECTOR INTER BANK CONNECTOR 376 368 ±3 585 ±3

2500 MIN HT REQ.


PLYWOOD
DECK

267
11

682 ±5
2080 585 75 585 800 585 75 585 1230 1700 585 75 585 750 585 75 585 1708 10152 1500
6600 18500
VIEW AT "A" VIEW AT "B"

1454 10152 1594


4
1 2 3
6000 6800
CELL OUTLINE INTER CELL CONNECTION
D-LINE

D
1700

900
800

400

7
BEAM

85
12
27 CELLS STILLAGE
1245

27 CELLS STILLAGE
5400

SET 1
750

585
27 CELLS STILLAGE

75
1245

585
27 CELLS STILLAGE
460

0
80
BILL OF MATERIAL (PER SET)
860

D4

SL. No. ITEM DESCRIPTION CAT No. QTY.


848

1. YHP 39 Cell 108 Nos.


2. 7 Cell Steel Stillage with plywood deck 12 No.
3. 6 Cell Steel Stillage with plywood deck 4 No.
6500

4. Inter Cell Connector SBL922 312 Nos.


18500

C- LINE
5. Inter Bank Connector SBL1197 2 Nos.
6. Inter Row Connector SBL926 4 Nos.
Terminal Shroud (Right) SP 4118 324 Nos.
7. Terminal Shroud (Left)
27 CELLS STILLAGE

27 CELLS STILLAGE

27 CELLS STILLAGE

27 CELLS STILLAGE

SP 4119 324 Nos.


SET 2

Fastener (MS - Lead Plated) SSL901 24 Sets


8.
10152

Fastener (MS - Lead Plated) SSL959 624 Sets


B4
9. Microporous Vent Plug SP973 108 Nos.

200
10. End Cell Take-Off SBL930 2 Nos.
11. Petroleum Jelly 4400 Gms.
12. Numbering Sticker (1-108) 1 Set.
780 Cell electrolyte (Sp. Gr. 1.205) with 10% extra
780
13. 9000 Lts.
for initial filling in non-returnable plastic jerrican
5400

14. Stillage Insulator SP4212 192 Nos.


930

NOTE :-
200

EACH 27 CELL ROW CONTAINES 3 NOS. 7 CELL STILLAGE


1500

B-LINE
& 1 NO. 6 CELL STILLAGE.
ESCAPE GALLERY
2080 1245 800 1245 1230
6600

ROOM LAYOUT FOR 108 YHP 39 (2 SETS)

A3 SIZE