Professional Documents
Culture Documents
CAT 500kva
CAT 500kva
PRIME
400 ekW 500 kVA
50 Hz 1500 rpm 400 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.
FEATURES
FUEL/EMISSIONS STRATEGY CAT® C15 ATAAC DIESEL ENGINE
• Low Fuel consumption • Utilizes ACERT™ Technology
• Reliable, rugged, durable design
FULL RANGE OF ATTACHMENTS • Field-proven in thousands of applications
• Wide range of bolt-on system expansion worldwide
attachments, factory designed and tested • Four-stroke diesel engine combines consistent
• Flexible packaging options for easy and cost performance and excellent fuel economy with
effective installation minimum weight
• Electronic engine control
SINGLE-SOURCE SUPPLIER
• Fully prototype tested with certified torsional CAT GENERATOR
vibration analysis available • Matched to the performance and output
characteristics of Cat engines
WORLDWIDE PRODUCT SUPPORT
• Load adjustment module provides engine relief
• Cat dealers provide extensive post sale support
upon load impact and improves load acceptance
including maintenance and repair agreements
and recovery time
• Cat dealers have over 1,800 dealer branch stores
• UL 1446 Recognized Class H insulation
operating in 200 countries
• The Cat® S•O•SSM program cost effectively detects CAT EMCP 4 CONTROL PANELS
internal engine component condition, even the • Simple user friendly interface and navigation
presence of unwanted fluids and combustion • Scalable system to meet a wide range of
by-products customer needs
• Integrated Control System and Communications
Gateway
PRIME 400 ekW 500 kVA
50 Hz 1500 rpm 400 Volts
SPECIFICATIONS
TECHNICAL DATA
Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1349 standard conditions.
CSA, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22, These ratings also apply at ISO3046 standard conditions.
NEMA MG 1-33, UL508A, 72/23/EEC, 98/37/EC,
2004/108/EC
Prime - Output available with varying load for an
unlimited time. Average power output is 70% of the
prime power rating. Typical peak demand is 100% of
prime rated ekW with 10% overload capability for
emergency use for a maximum of 1 hour in 12. Overload
operation cannot exceed 25 hours per year.
DIMENSIONS
Package Dimensions
NOTE: For reference only - do not use for
Length 3775.1 mm 148.63 in installation design. Please contact
Width 1110.0 mm 43.7 in your local dealer for exact weight
and dimensions. (General
Height 2091.0 mm 82.32 in Dimension Drawing #2781052).
www.Cat-ElectricPower.com
Performance No.: DM8494
2013 Caterpillar
All rights reserved.
Feature Code: C15DEC2
Materials and specifications are subject to change without notice.
Gen. Arr. Number: 2351211 The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," the
Source: U.S. Sourced "Power Edge" trade dress, as well as corporate and product identity used
herein, are trademarks of Caterpillar and may not be used without
permission.
February 11 2013 21372090
6