Professional Documents
Culture Documents
STANDBY
400 ekW 500 kVA
60 Hz 1800 rpm 480 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.
FEATURES
FUEL/EMISSIONS STRATEGY CAT® C15 ATAAC DIESEL ENGINE
• Low Fuel consumption • Utilizes ACERT™ Technology
• Reliable, rugged, durable design
DESIGN CRITERIA • Field-proven in thousands of applications
• The generator set accepts 100% rated load in one worldwide
step per NFPA 110 and meets ISO 8528-5 transient • Four-stroke diesel engine combines consistent
response. performance and excellent fuel economy with
minimum weight
UL 2200
• Electronic engine control
• UL 2200 listed packages available. Certain
restrictions may apply. Consult with your Cat® CAT GENERATOR
Dealer. • Matched to the performance and output
characteristics of Cat engines
FULL RANGE OF ATTACHMENTS
• Load adjustment module provides engine relief
• Wide range of bolt-on system expansion
upon load impact and improves load acceptance
attachments, factory designed and tested
and recovery time
• Flexible packaging options for easy and cost
• UL 1446 Recognized Class H insulation
effective installation
CAT EMCP 4 CONTROL PANELS
SINGLE-SOURCE SUPPLIER
• Simple user friendly interface and navigation
• Fully prototype tested with certified torsional
• Scalable system to meet a wide range of
vibration analysis available
customer needs
WORLDWIDE PRODUCT SUPPORT • Integrated Control System and Communications
• Cat dealers provide extensive post sale support Gateway•
including maintenance and repair agreements
• Cat dealers have over 1,800 dealer branch stores
operating in 200 countries
• The Cat® S•O•SSM program cost effectively detects
internal engine component condition, even the
presence of unwanted fluids and combustion
by-products
STANDBY 400 ekW 500 kVA
60 Hz 1800 rpm 480 Volts
Fuel • Primary fuel filter with integral water separator [ ] Integral single wall fuel tank base
• Secondary fuel filters [ ] Integral dual wall fuel tank base
• Fuel priming pump [ ] Fuel level switch
• Engine fuel transfer pump
• Fuel cooler*
• Flexible fuel lines
*Not included with packages without radiators
Generator • Class H insulation [ ] Oversize generators
• Self excited (SE) [ ] Permanent magnet excitation (PMG)
• Class H temperature rise [ ] Internal excited (IE)
• VR6 voltage regulator with 3-phase sensing with load [ ] Cat digital voltage regulator (CDVR) with kVAR/PF
adjustment module [ ] Anti-condensation space heaters
• IP23 protection [ ] Coastal Insulation Protection (CIP)
[ ] Reactive droop
Power Termination • Power Center houses EMCP controller and [ ] Power Center mounting option (right side)
power/control terminations (rear mounted) [ ] Multiple circuit breaker options
• Circuit breaker, UL listed, 3 pole (80% & 100% Rated) [ ] C.B. Shunt trips
• Circuit breaker, IEC compliant, 3-4 pole (100% Rated) [ ] C.B. Auxiliary contacts
• Segregated low voltage wiring termination panel
• IP22 protection
• Bottom cable entry
Governor • ADEM™A4 [ ] Load share module
SPECIFICATIONS
TECHNICAL DATA
Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1349 standard conditions.
CSA, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22, These ratings also apply at ISO3046 standard conditions.
NEMA MG 1-33, UL508A, 72/23/EEC, 98/37/EC, Fuel rates are based on fuel oil of 35º API [16º C (60º F)]
2004/108/EC gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
Standby - Output available with varying load for the when used at 29º C (85º F) and weighing 838.9 g/liter
duration of the interruption of the normal source power. (7.001 lbs/U.S. gal.). Additional ratings may be available
Average power output is 70% of the standby power for specific customer requirements, contact your Cat
rating. Typical operation is 200 hours per year, with representative for details. For information regarding Low
maximum expected usage of 500 hours per year. Sulfur fuel and Biodiesel capability, please consult your
Standby power in accordance with ISO8528. Fuel stop Cat dealer.
power in accordance with ISO3046. Standby ambients
shown indicate ambient temperature at 100% load which
results in a coolant top tank temperature just below the
shutdown temperature.
DIMENSIONS
Package Dimensions
NOTE: For reference only - do not use for
Length 3822.7 mm 150.5 in installation design. Please contact
Width 1110.0 mm 43.7 in your local dealer for exact weight
and dimensions. (General
Height 2166.0 mm 85.28 in Dimension Drawing #2781048).
Weight 3320 kg 7,319 lb
www.Cat-ElectricPower.com
Performance No.: DM8161
© 2011 Caterpillar
All rights reserved.
Feature Code: C15DEH4
Materials and specifications are subject to change without notice.
Gen. Arr. Number: 2351203 The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," the
Source: European Sourced "Power Edge" trade dress, as well as corporate and product identity used
herein, are trademarks of Caterpillar and may not be used without
permission.
June 01 2011 17795672