Operation qualification protocol for air handling unit & air distribution system
Purpose:
To verify the operational attributes of the Heating Ventilation and Air Conditioning system, critical to serve
To establish the suitability of the draft SOP prepared for the operation of System.
Requalification:
ABBREVIATIONS:
2 DQ Design Qualification.
3 IQ Installation Qualification
4 OQ Operational Qualification
5 GI Galvanized Iron
6 SS Stainless Steel.
7 Temp Temperature
8 RH Relative Humidity
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 1/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
12 Cont. Continued
13 WC Water column
15 0C Degree centigrade
16 m Micron
18 Min Minimum
19 Max Maximum
22 NA Not Applicable
24 DX Direct Expansion
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 2/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
33 AL. Aluminium
34 NR Not Required
36 DB Dry Bulb
38 KW Kilo Watt
39 HP Horse Power
40 Ph Phase
42 Pa Pascal
System Description
Control System
Safety System
FUNCTION: The AHU is designed to circulate the air in the area after passing it over cooling coils to
maintain the required environmental conditions and passing it through the series of filters to maintain
desired cleanliness level in the area. The air in-take and out-take of the system is designed to maintain
certain degree of pressure gradient, temperature and Relative Humidity in the area as per the
requirement.
The major components of the air-handling unit are briefly described as below:
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 3/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
Blower: – Blower is provided in the unit to supply air in the working area. This blower is direct driven by a
motor. The blower takes the air from the atmosphere and / or from the rooms as return air and delivers it
to the working areas through air distribution network
Cooling Coil: –The air Temperature and RH should be controlled by cooling coil. It has Coated Al.fins and
Chilled water circulated through coil by copper tubes. The Dry air passing through coil before entering in
room via ducting system.
Hot water Coil: –The air Temperature and RH should be controlled by HW coils. It has Coated Al.fins and
Chilled water circulated through coil by copper tubes. The Dry air passing through coil before entering in
room via ducting system.
Air Distribution Network. An air distribution network is provided to supply the air, delivered by the
blowers, into the working areas. By using the same network, return air flows back to the air handling unit
to maintain certain pressure gradient and other parameters like Temperature & RH.
10 micron Pre Filters: – Fresh air filters having filtration efficiency upto 90% down to 10m are provided in
the Fresh air intake of the AHU to filter out dust particles from the service area air.
0.3 micron HEPA Filters: – HEPA filters having filtration efficiency up to 99.99% down to 0.3m are
provided in the Air Handling Unit for bleed air.
10+5 micron combo Pre Filters: –Combo pre filters having filtration efficiency up to (90% down to 10 m
+ 95% down to 5m) are provided before cooling coil in the return air of the Air Handling Unit to filter out the
dust particles.
3 micron Fine Filters: – Fine filters having filtration efficiency up to 99% down to 3m are provided after
the cooling coil and blower to remove fine particles from the treated air.
CONTROL SYSTEM
Instrumentation and Control System: – For the purpose of controlling of various parameters,
AREA DETAILS
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 4/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
The Air Handling unit is designed to provide and maintain the following conditions in the area where it
caters
AHU Capacity of air filtration – ______________ CFM.
Temperature – NMT 25 ºC
R H – NMT 60 %
Equipment should be installed properly as defined in Installation Qualification Protocol of the equipment.
Test Equipment
Calibration Calibration
Test Equipment Purpose Done on Due on
Required Confirmed By
of the motors.
Reported by
Verified by
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 5/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
The execution team should be qualified for conducting Operational Qualification of the equipment
Date of Training:
Title:
Inspection checklist
The SOP shall be drafted and verified for operation during Operational Qualification testing. If any
changes / modifications are found SOP shall be revised considering all changes.
Prior to the Qualification test, the Personnel shall be trained by the competent Engineer from the supplier /
user on the operational features of the equipment / system and method of qualification protocol.
The trained personnel shall carry out the Operational Qualification for key functionality and safety
features. Record the observations in the individual test data sheets. Checkpoints designed for the purpose
of OQ are also aimed at verification of existing and drafted SOPs.
Report the deficiency from the specified function, if any in the protocol.
Operational Qualification
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 6/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
Instrument Calibration
Magnehelic
gauges
Checked by
Verified by
(Name) (Sign.) (Date)
(Quality Assurance)
Key Functionality
The critical components of the Air Handling System shall be checked to ensure that these are operating to
meet the desired design specification, as given by the supplier.
Safety Function
Operational Checks
Specified
S. No. Test Particulars Observations Checked By
Function
1 Primary Checks
1.1 Check for the Supply Blower and Motor of Air Handling Unit
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 7/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
Specified
S. No. Test Particulars Observations Checked By
Function
Blower and Motor
Check the Supply
should be
Blower and Motor
properly fitted on
1.1.1 assembly for proper
base frame and
fitment on base
tightened with
frame.
bolts and nuts.
Motor shaft
Check the motor
should rotate
1.1.2 shaft rotation,
smoothly when
manually.
rotated manually.
Blower should
Check the Blower rotate smoothly
1.1.3
rotation, manually. when rotated
manually.
Motor should be
Check the motor
tightened with
1.1.4 shaft key and hub
shaft key and hub
screws.
screws.
Blower should be
Check the Blower
tightened with
1.1.5 shaft key and hub
shaft key and hub
screws.
screws.
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 8/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
Specified
S. No. Test Particulars Observations Checked By
Function
Open and close the
Fresh Air damper of
the Air Handling Unit
for its operation,
Damper should
manually.
1.2.1 open and close
Note: Adjust the smoothly.
damper in full open
condition after the
checking.
2 Operational Checks
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 9/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
filters 12-15mm of wc
Checked by
Verified by
(Name) (Sign.) (Date)
(Engineering)
SOP VERIFICATION
Title : _____________________
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 10/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
The System was operated as per the SOP and details are recorded as under:
Verified By : ____________________
Date : ____________________
Acceptance Criteria
https://pharmaguidances.com/operation-qualification-protocol-for-air-handling-unit-air-distribution-system/ 11/13
27/11/2022, 08:30 Operation qualification protocol for air handling unit & air distribution system - Pharmaceutical Guidance
Operational Qualification shall be considered acceptable when all the conditions specified in various test
data sheets.
Any deviation from the acceptance criteria of the specific checkpoint shall be reported and decision should
be taken for the rejection, replacement or rectification of the equipment / component.
SUMMARY
———————————————————————————————————————
CONCLUSION
———————————————————————————————————————
Not Applicable
Distribution
History
– 00 New SOP