Professional Documents
Culture Documents
Contactors DIL
Motor-protective
circuit-breakers PKZ
Motor starters MSC
Soft starters DS 4
Frequency inverters
DF, DV
Rapid Link
For Klockner Moeller Sales and Support call KMparts.com (866) 595-9616
The way to safe machines integrated and applied in the field of tactor contacts. If the control voltage
mechanical engineering. The classifica- on the contactor coil is removed by an
During the engineering design phase of
tion in specific cases is not always easy, Emergency-Stop and there is a fault
a machine, every design engineer – in
but the basic steps to be applied remain involving “welded contactor contacts”,
addition to considering the functional
transparent in all cases. further measures for maintaining the
aspects of the machine – is confronted
safety function in controls of safety
eventually with the issue of safety fea-
Using the tree structure (Figure 1) it is category 3 or 4 must be provided. Gen-
tures, and is posed with the following
possible to appraise what can happen if erally, a connection of two contactors
question: How dangerous is the machine
the control fails. First of all the serious- in series (Figure 2) is provided. With the
that they are designing? The potential ness of the injury is assessed, followed rare exception that both contactors have
dangers posed by the machine can be by the time spent in the danger area and not welded at the same time, the safety
identified by a risk assessment. A por- finally the perceptibility of the danger. function is maintained as the second
tion of the danger can be suppressed by The assessment results in the safety cat- contactor will bring the drive which is
mechanical modifications or extensions egories to which the control must com- the source of danger to a standstill.
(no sharp edges, bulkheads in front of ply. The safety categories are a measure
moving parts, etc.). If an electrical control of the reliability of the control during a This expensive solution, which requires
is engineered, safety tasks are shifted to malfunction. The fundamental difference significantly more space in the control
the control. Typical safety tasks are the between controls of safety category 1 or panel and additional time and expense
Emergency-Stop or monitoring of safety 2 to controls of categories 3 or 4 is that for manufacturing the main wiring har-
doors, contact mats or photoelectric the controls in safety categories 1 and ness, is not always acceptable in the
barriers. The question of the reliability of 2 may lose their safety function during engineering design. This is where Moel-
the control during a malfunction should a fault scenario. Controls of safety cat- ler uses the CMD Contactor Monitoring
be considered in order to delegate the egory 3 or 4 must maintain their safety Device. Not a second, expensive and
control of safety-relevant tasks to the function even in a fault scenario. large contactor to maintain the safety
control.
function, but rather a small attractively
Contactor control circuits conform to
priced relay. This continuously compares
The EN 954-1 EN 954-1
the specified state of the contactor
The European standard EN 954-1 can If the electrical circuits for control of based on the control voltage with the
easily claim to be simple to apply. Based motors are now examined, the motors actual state which is signalled with the
on the simplicity of its fundamental are switched by contactors. A typical assistance of an auxiliary contact. In a
design, the standard can be easily contactor fault is welding of the con- fault scenario, the CMD switches the
Risk graph S1
P1
F1
Starting point for P2 Category selection
risk assessment
S2
P1
F2
P2
2
For Klockner Moeller Sales and Support call KMparts.com (866) 595-9616
PL – Performance Level DC – Diagnostic Coverage
The assessment of the consequences of The Diagnostic Coverage enables a
a control failure using a tree structure quantitative statement with regard to
no longer results directly in a safety cat- detected faults. This involves the assump-
egory, but rather in a Performance Level tion principle that a control that detects
in accordance with the EN ISO 13489. a large number of faults is more reliable
This can result in PLs ranging from “a” to than a control that hardly detects any
“e” (Figure 3). faults.
DC < 60% r no error detection
The PL reflects the level of danger that 60% ≤ DC < 90% r low error
exists due to the failure of a control. detection
On machines featuring a control of PL 90% ≤ DC < 99% r medium error
“a”, there is only a low level of danger, detection
whereas machines with a control catego- 99% ≤ DC r high error
rised as PL “e” are categorised as very detection
dangerous
Common cause failure
The actual Performance Level that a
In order to avoid a “failure burst“
control complies with no longer depends
measures must be undertaken to avoid
solely on the design of the control. Addi-
common cause failures. For this purpose,
tionally, qualitative declarations regard-
a range of measures is provided by the
ing the service life and fault detection
standard to assist the users.
must also be considered.
Interaction between PL, DC, MTTFd
MTTF – Mean time to failure
The Performance Level to which the
Figure 2: Redundant power section The MTBF time (mean time between
control complies can be read off of a bar
failure) is a measure of the reliability of a
chart (Figure 4).
component or a control which has been
upstream contactor or switch-disconnec- in use for a long time with electronic
tor off using the undervoltage coil. components. As the electromechanical Operating principle
components of an assembly no longer
Enhancements of the EN 954-1 in the function after the first fault, the MTTF
of the CMD
EN ISO 13849 time (mean time to failure) is taken into The CMD relay has the task of moni-
consideration here. It is a measure of toring the high-power contacts of the
The simple handling of the EN 954-1
how long the component or control motor contactor for welding. For this
described at the outset has the disadvan-
will function reliably. As only the faults, purpose, the control voltage of the con-
tage that it fails to make any mention
which can cause dangerous failures need tactor coil is applied as the specified on
of the reliability of the control in the
to be examined from the safety techno- the CMD. On the other side the actual
scheduled service life. This circumstance
logy perspective, the MTTFd (Mean time state of the contactor is signalled via a
has lead to the EN 954-1 only being
to failure dangerous) is considered for reliable auxiliary N/C contact. The CMD
valid for a transitional period. The suc-
assessment of the Performance Level. compares the nominal and actual state.
cessor standard EN ISO 13849, has been
The undervoltage coil of the upstream
expanded in some aspects and makes 3 years <= MTTFd < 10 years r low
circuit-breaker or switch-disconnector is
statements regarding the occurrence of 10 years <= MTTFd < 30 years r medium
supplied via a relay output. In the event
malfunctions. 30 years <= MTTFd < 100 years r high
of a fault the circuit-breaker / switch-
disconnector is switched off via the
Legend
PL Performance Level
1 MTTFd every channel = low
2 MTTFd every channel = medium
3 MTTFd every channel = high
Risk parameters
S Severity of the injury
S1 Slight (generally a reversible injury)
S2 Severe (irreversible injury including F2 Frequent up to continuous exposure to Legend
death) the hazardous condition 1 Starting point to the assessment of the
F Frequency and/or exposure time to the P Possibility of avoiding the hazard or risk reduction
hazardous condition limiting the damage L Low contribution to risk reduction
F1 Seldom up to quite often and/or the P1 Possible under certain conditions H High contribution to risk reduction
DCavg none DCavg none DCavg low DCavg medium DCavg low DCavg medium DCavg High
exposure time is brief P2 Scarcely possible PLr Required Performance Level
Source: DIN EN ISO 13849-1 Source: DIN EN ISO 13849-1
Figure 3: Risk assessment graph according to EN ISO 13489 Figure 4: Performance Level
3
For Klockner Moeller Sales and Support call KMparts.com (866) 595-9616
L1 L1 L01 L01
L2 L2 -F1
L3 L3
L1 L2 L3 1.13
-Q1
1.14
-Q1 21
-Q11
I> I> I> 22
T1 T2 T3 a -K
33
-Q11
34
-S1
21 b
22
TEST
21 13
-S3
1 3 5 13 13 22 14
-Q11 -S2 -Q11
2 4 6 14 14
A2 D2
M
L02 L02
-M1 3 1 2
˜ 3
5
4
6
13 14
21 22
33 34
Permissible combinations
In order to guarantee a reliable func-
tioning of the combinations of circuit-
breaker/switch-disconnectors, contactors
Figure 7: Contactor auxiliary contact with mirror contact and CMD, only defined components are
approved for use. Other contactors fea-
turing other switching times or under-
is an auxiliary N/C contact that can only contact NHI2-11S-PKZ2, all the contact voltage releases with other voltage levels
close if all power contacts have opened. modules are positively-drive with respect can cause a loss of the safety function.
to each other.
All auxiliary N/C contacts on the three- Contactors
pole contactors DILM 7 to DILM 1600 CMD variants
and DILH 1400 to DILH 2000 and the The following contactors are approved
The supply voltage of the CMD must be for establishing safety relevant control
four-pole contactors DILM P comply with
identical to the control voltage of the sections:
the demands of a mirror contact (Figure
contactor to be monitored. The CMD is
7).
available for different control voltage The contactor must feature an auxiliary
variants in order to cover the largest pos- N/C contact with mirror contact func-
With the (high power) contact modules
sible range of applications: tions and a further auxiliary contact that
the side-mounted auxiliary contacts
NHI2-11S-PKZ2 comply with the
demands for a mirror contact.
Figure 9: Contactor with fitted auxiliary contacts Figure 10: Circuit-breaker with fitted undervoltage release
6
For Klockner Moeller Sales and Support call KMparts.com (866) 595-9616
Contactor B10d value at 400 V AC-3
DILM 7 to DILM 12 1.3 million switching operations
DILM 15 0.75 million switching operations
DILM 17 to DILM 65 1.3 million switching operations
DILM 72 0.75 million switching operations
DILM 80 to DILM 150 1.3 million switching operations
DILM 170 0.75 million switching operations
DILM 185 to DILM 820 1.3 million switching operations
DILM 1000 to DILM 1600 0.3 million switching operations
The MTTFd time of the CMD relay is Performance Level of the circuit
125 years under the condition that a
maximum switching frequency of nop = The parallel connection of the CMD and
350,400 switching operations / year is undervoltage release to a contactor com-
not exceeded. plies with Performance Level PL=e. The
calculation is subject to the following
The B10d values of the undervoltage preconditions:
release are:
Maximum operations of the contactor:
350,400 switching operations / year
Undervoltage B10d value
release Maximum switching operations of the
undervoltage release: 1095 switching
PKZ 2 10,000 switching operations / year
operations
NZM 1, NZM 2 10,000 switching In the calculation of the overall Perform-
operations ance Level for the control the upstream
safety components must be considered.
NZM 3 7,500 switching
Overall, controls that comply with Per-
operations
formance Level “d” can be established in
NZM 4 5,000 switching this way.
operations
Summary
Diagnostic coverage of the circuit The CMD is used in safety-relevant
current circuits. It monitors if the main
The Diagnostic Coverage is also calcu- contacts of the contactor have welded.
lated separately for both branches. As If welding is detected, it switches off the
the contactor is switched operationally supply of power to the application using
and the state with each switch operation the upstream circuit-breaker.
is checked by the auxiliary N/C contact
with mirror contact, the error detection Using the CMD, controls that comply
on the contactor is very high: DC contac- with Performance Level “d” can be set
tor: = 99 % up.
7
For Klockner Moeller Sales and Support call KMparts.com (866) 595-9616
Moeller addresses worldwide:
www.moeller.net/address
E-Mail: info@moeller.net
Internet: www.moeller.net
Xtra Combinations
It provides:
■ flexibility and simplicity
■ great system availability
■ the highest level of safety
For Klockner Moeller Sales and Support call KMparts.com (866) 595-9616