MOTOR SIZE AND PROTECTION AND FEEDER SIZE

TYPE OF MOTOR: STARTING CONTROL: WYE-DELTA STARTING


MOTOR RATING: 0 HP Voltage: 220 3 PHASE
RATING KW: #N/A KW RATED VA : #N/A VA PER PHASE VA:
A MOTOR FULL LOAD CURRENT: #N/A AMPS
B CIRCUIT BREAKER (RATING): #N/A AT, 3 Pole,60Hz.
C SAFETY SWITCH (RATING): #N/A AT, 3 Pole,60Hz, NEMA 3R, ENCLOSURE. NFDS
D HEATER RANGE #N/A AMPS
E WIRE SIZE (750C) 3 #N/A mm.sq. THHN + 1- #N/A mm.sq. TW GND WIRE
F CONDUIT SIZE (MAX. 3-WIRE): #N/A mm.sq. CDT

MOTOR SIZE AND PROTECTION AND FEEDER SIZE

TYPE OF MOTOR: STARTING CONTROL: WYE-DELTA STARTING


MOTOR RATING: 10 HP Voltage: 380 3 PHASE
RATING KW: 7.50 KW RATED VA : 9,375 VA PER PHASE VA:
A MOTOR FULL LOAD CURRENT: 17.71 AMPS
B CIRCUIT BREAKER (RATING): 30 AT, 3 Pole,60Hz.
C SAFETY SWITCH (RATING): 60 AT, 3 Pole,60Hz, NEMA 3R, ENCLOSURE. NFDS
D HEATER RANGE 8-16 AMPS
E WIRE SIZE (750C) 3 5.5 mm.sq. THHN + 1- 3.5 mm.sq. TW GND WIRE
F CONDUIT SIZE (MAX. 3-WIRE): 15 mm.sq. CDT

MOTOR SIZE AND PROTECTION AND FEEDER SIZE

TYPE OF MOTOR: STARTING CONTROL: WYE-DELTA STARTING


MOTOR RATING: 150 HP Voltage: 440 3 PHASE
RATING KW: 110.00 KW RATED VA : 137,500 VA PER PHASE VA:
A MOTOR FULL LOAD CURRENT: 180.00 AMPS
B CIRCUIT BREAKER (RATING): 250 AT, 3 Pole,60Hz.
C SAFETY SWITCH (RATING): 600 AT, 3 Pole,60Hz, NEMA 3R, ENCLOSURE. NFDS
D HEATER RANGE 85-125 AMPS
E WIRE SIZE (750C) 3 100.0 mm.sq. THHN + 1- 30 mm.sq. TW GND WIRE
F CONDUIT SIZE (MAX. 3-WIRE): 65 mm.sq. CDT
#N/A VA

3,125 VA

45,833 VA
PROJECT:
SUBJECT:
DATE:

MOTOR SIZE AND PROTECTION AND FEEDER SIZE

TYPE OF MOTOR: STARTING CONTROL


MOTOR RATING: 0 HP Voltage: 220 3 PHASE
RATING KW: #N/A KW RATED VA : #N/A VA PER PHASE VA: #N/A
A MOTOR FULL LOAD CURRENT: #N/A AMPS
B CIRCUIT BREAKER (RATING): #N/A AT, 3 Pole,60Hz.
C SAFETY SWITCH (RATING): #N/A AT, 3 Pole,60Hz, NEMA 3R, ENCLOSURE. NFDS
D HEATER RANGE #N/A AMPS
E WIRE SIZE (750C) 3 #N/A mm.sq. THHN + 1- ### mm.sq. TW GND WIRE
F CONDUIT SIZE (MAX. 3-WIRE): #N/A mm.sq. CDT

MOTOR SIZE AND PROTECTION AND FEEDER SIZE

TYPE OF MOTOR: STARTING CONTROL


MOTOR RATING: 0 HP Voltage: 380 3 PHASE
RATING KW: #N/A KW RATED VA : #N/A VA PER PHASE VA: #N/A
A MOTOR FULL LOAD CURRENT: #N/A AMPS
B CIRCUIT BREAKER (RATING): #N/A AT, 3 Pole,60Hz.
C SAFETY SWITCH (RATING): #N/A AT, 3 Pole,60Hz, NEMA 3R, ENCLOSURE. NFDS
D HEATER RANGE #N/A AMPS
E WIRE SIZE (750C) 3 #N/A mm.sq. THHN + 1- ### mm.sq. TW GND WIRE
F CONDUIT SIZE (MAX. 3-WIRE): #N/A mm.sq. CDT

MOTOR SIZE AND PROTECTION AND FEEDER SIZE

TYPE OF MOTOR: STARTING CONTROL


MOTOR RATING: 0 HP Voltage: 440 3 PHASE
RATING KW: #N/A KW RATED VA : #N/A VA PER PHASE VA: #N/A
A MOTOR FULL LOAD CURRENT: #N/A AMPS
B CIRCUIT BREAKER (RATING): #N/A AT, 3 Pole,60Hz.
C SAFETY SWITCH (RATING): #N/A AT, 3 Pole,60Hz, NEMA 3R, ENCLOSURE. NFDS
D HEATER RANGE #N/A AMPS
E WIRE SIZE (750C) 3 #N/A mm.sq. THHN + 1- ### mm.sq. TW GND WIRE
F CONDUIT SIZE (MAX. 3-WIRE): #N/A mm.sq. CDT
VA

VA

VA
TABLES: 220 V,3phase,60Hz FVNR-STARTING

MOTOR MOTOR MOTOR CIRCUIT SAFETY HEATER WIRE SIZE WIRE SIZE CONDUIT
RATING RATING FULL LOAD BREAKER SWITCH RANGE THHN XLPE/PVC SIZE
HP KW CURRENT RATING RATING (90deg.c) (90deg.c) (MAX.4-W)
0.25 0.18 1.1 15 30 .98-1.45 3.5 4.0 15
0.3 0.25 1.5 15 30 1.4-2.2 3.5 4.0 15
0.5 0.37 2 15 30 1.7-2.6 3.5 4.0 15
0.75 0.55 2.8 15 30 2.2-3.4 3.5 4.0 15
1 0.75 3.6 15 30 2.8-4.2 3.5 4.0 15
1.5 1.1 5.2 15 30 4-6 3.5 4.0 15
2 1.5 6.8 15 30 5-8 3.5 4.0 15
3 2.2 9.6 20 30 7-11 3.5 4.0 15
4 3 11 30 30 9-13 3.5 4.0 15
5 3.7 15.2 30 60 8-16 5.5 6.0 15
5.5 4 18.5 30 60 12-18 5.5 6.0 15
7.5 5.5 22 50 60 16-24 5.5 6.0 15
10 7.5 28 50 100 24-36 8.0 10.0 20
15 11 42 75 100 28-40 14.0 16.0 25
20 15 54 100 100 45-67 22.0 25.0 32
25 18.5 68 125 200 54-80 22.0 25.0 32
30 22 80 150 200 54-80 30.0 35.0 32
40 30 104 200 200 85-125 50.0 70.0 50
50 37 130 225 400 110-160 60.0 70.0 50
60 45 154 300 600 125-185 80.0 95.0 50
75 55 192 400 600 125-185 125.0 120.0 65
100 75 248 400 800 200-300 200.0 185.0 80
125 90 312 500 1200 240-360 250.0 240.0 80
150 110 360 600 1200 300-450 250.0 240.0 80
200 150 480 800 1200 400-600 2-150 2-150 100

TABLES: 220 V,3phase,60Hz YWE-DELTA STARTING

MOTOR MOTOR MOTOR CIRCUIT SAFETY HEATER WIRE SIZE WIRE SIZE CONDUIT
RATING RATING FULL LOAD BREAKER SWITCH RANGE THHN XLPE/PVC SIZE
HP KW CURRENT RATING RATING (90deg.c) (90deg.c) (MAX.4-W)
7.5 5.5 22 50 60 8-16 5.5 6.0 15
10 7.5 28 50 100 12-18 8.0 10.0 20
15 11 42 75 200 18-26 14.0 16.0 25
20 15 54 100 200 24-36 22.0 25.0 32
25 18.5 68 125 200 28-40 22.0 25.0 32
30 22 80 150 400 34-50 30.0 35.0 32
40 30 104 200 400 45-67 50.0 50.0 50
50 37 130 225 400 54-80 60.0 70.0 50
60 45 154 300 600 65-85 80.0 95.0 50
75 55 192 400 600 85-125 125.0 120.0 65
100 75 248 400 800 110-160 200.0 185.0 80
125 90 312 500 1200 125-185 250.0 240.0 80
150 110 360 600 1200 160-240 250.0 240.0 80
200 150 480 800 1200 200-300 2-150 2-150 100
GROUNDING AMP
WIRE DERAT
FACTOR
2.0 1.22 1.51
2.0 1.63 2.06
3.5 2.00 2.75
3.5 2.80 3.85
3.5 3.73 4.95
3.5 5.22 7.15
3.5 6.96 9.35
3.5 9.79 13.20
3.5 11.52 15.13
3.5 15.30 20.90
3.5 19.14 25.44
3.5 21.59 30.25
5.5 28.79 38.50
5.5 41.67 57.75
8.0 54.20 74.25
8.0 67.74 93.50
8.0 81.29 110.00
14.0 102.37 143.00
22.0 127.96 178.75
22.0 153.55 211.75
22.0 191.94 264.00
30.0 255.92 341.00
38.0 319.90 429.00
38.0 363.68 495.00
38.0 484.90 660.00

GROUNDING AMP
WIRE DERAT
FACTOR
3.5 36.71 30.25
5.5 54.38 38.50
8.0 59.93 57.75
8.0 74.58 74.25
8.0 93.23 93.50
8.0 104.42 110.00
14.0 139.22 143.00
14.0 163.15 178.75
22.0 172.75 211.75
22.0 229.43 264.00
30.0 348.05 341.00
38.0 359.89 429.00
38.0 431.87 495.00
38.0 166.69 660.00
TABLES: 380 V,3phase,60Hz FVNR-STARTING

MOTOR MOTOR MOTOR CIRCUIT SAFETY HEATER WIRE SIZE WIRE SIZE CONDUIT GROUND
RATING RATING FULL LOAD BREAKER SWITCH RANGE THHN XLPE/PVC SIZE WIRE
HP KW CURRENT RATING RATING (90deg.c) (90deg.c) (MAX.4-W)
0.25 0.18 0.71 15 30 .48-.72 3.5 4.0 15 2.0
0.3 0.25 0.94 15 30 .64-.96 3.5 4.0 15 2.0
0.5 0.37 1.16 15 30 .95-1.45 3.5 4.0 15 3.5
0.75 0.55 1.62 15 30 .95-1.45 3.5 4.0 15 3.5
1 0.75 2.16 15 30 1.4-2.2 3.5 4.0 15 3.5
1.5 1.1 3.02 15 30 2.2-3.4 3.5 4.0 15 3.5
2 1.5 4.03 15 30 2.8-4.2 3.5 4.0 15 3.5
3 2.2 5.67 15 30 4-6 3.5 4.0 15 3.5
4 3 6.67 15 30 5-8 3.5 4.0 15 3.5
5 3.7 8.86 15 30 6-9 3.5 4.0 15 3.5
5.5 4 11.08 20 30 6-9 3.5 4.0 15 3.5
7.5 5.5 12.50 30 30 8-16 3.5 4.0 15 3.5
10 7.5 17.71 30 60 12-18 5.5 6.0 15 5.5
15 11 23.53 40 60 16-24 8.0 6.0 15 5.5
20 15 31.38 50 100 24-36 8.0 10.0 20 8.0
25 18.5 39.22 60 100 28-40 14.0 10.0 20 8.0
30 22 47.06 80 100 34-50 14.0 16.0 25 8.0
40 30 59.27 100 200 45-67 22.0 25.0 25 8.0
50 37 74.08 125 200 54-80 30.0 35.0 32 14.0
60 45 88.90 125 200 65-95 38.0 50.0 32 14.0
75 55 111.12 175 200 85-125 60.0 50.0 40 22.0
100 75 148.17 225 400 110-160 80.0 70.0 50 22.0
125 90 185.21 300 600 125-185 100.0 95.0 50 30.0
150 110 210.55 300 600 160-240 125.0 120.0 65 30.0
200 150 280.73 400 600 200-300 150.0 150.0 100 30.0

TABLES: 380 V,3phase,60Hz YWE-DELTA STARTING

MOTOR MOTOR MOTOR CIRCUIT SAFETY HEATER WIRE SIZE WIRE SIZE CONDUIT GROUND
RATING RATING FULL LOAD BREAKER SWITCH RANGE THHN XLPE/PVC SIZE WIRE
HP KW CURRENT RATING RATING (90deg.c) (90deg.c) (MAX.4-W)
7.5 5.5 12.50 20 30 5-8 3.5 4.0 15 3.5
10 7.5 17.71 30 60 8-16 5.5 6.0 15 3.5
15 11 23.53 50 60 8-16 5.5 6.0 15 3.5
20 15 31.38 70 100 12-18 8.0 10.0 20 3.5
25 18.5 39.22 70 100 18-26 8.0 10.0 20 5.5
30 22 47.06 75 200 18-26 14.0 16.0 25 5.5
40 30 59.27 100 200 24-36 14.0 16.0 25 5.5
50 37 74.08 100 200 34-50 22.0 25.0 32 8.0
60 45 88.90 125 400 34-50 22.0 25.0 32 8.0
75 55 111.12 125 400 45-67 38.0 50.0 40 22.0
100 75 148.17 175 400 65-95 60.0 70.0 50 22.0
125 90 185.21 225 600 65-95 80.0 95.0 50 22.0
150 110 210.55 250 600 85-125 100.0 120.0 65 30.0
200 150 280.73 350 800 125-185 150.0 150.0 60 30.0
AMP
DERAT
FACTOR
0.97
1.30
1.59
2.23
2.97
4.16
5.54
7.79
9.17
12.18
15.24
17.19
24.35
32.36
43.14
53.93
64.71
81.49
101.86
122.24
152.80
203.73
254.66
289.51
386.01

AMP
DERAT
FACTOR
12.50 10.80 17.19
17.71 15.30 24.35
23.53 20.32 32.36
31.38 27.10 43.14
39.22 33.87 53.93
47.06 40.65 64.71
59.27 51.18 81.49
74.08 63.98 101.86
88.90 76.78 122.24
111.12 95.97 152.80
148.17 127.96 203.73
185.21 159.95 254.66
210.55 181.84 289.51
280.73 242.45 386.01
TABLES: 440 V,3phase,50Hz FVNR-STARTING (DOL)

MOTOR MOTOR MOTOR CIRCUIT SAFETY HEATER WIRE SIZE WIRE SIZE CONDUIT
RATING RATING FULL LOAD BREAKER SWITCH RANGE THHN XLPE/PVC SIZE
HP KW CURRENT RATING RATING (90deg.c) (90deg.c) (MAX.4-W)
0.25 0.18 0.6 15 30 .48-.72 3.5 4.0 15
0.3 0.25 0.8 15 30 .64-.96 3.5 4.0 15
0.5 0.37 1 15 30 .95-1.45 3.5 4.0 15
0.75 0.55 1.4 15 30 .95-1.45 3.5 4.0 15
1 0.75 1.8 15 30 1.4-2.2 3.5 4.0 15
1.5 1.1 2.6 15 30 2.2-3.4 3.5 4.0 15
2 1.5 3.4 15 30 2.8-4.2 3.5 4.0 15
3 2.2 4.8 15 30 4-6 3.5 4.0 15
4 3 5.5 15 30 5-8 3.5 4.0 15
5 3.7 7.6 15 30 6-9 3.5 4.0 15
5.5 4 9.25 15 30 6-9 3.5 4.0 15
7.5 5.5 11 20 30 8-16 3.5 4.0 15
10 7.5 14 30 60 12-18 5.5 6.0 15
15 11 21 40 60 16-24 5.5 6.0 15
20 15 27 60 100 24-36 8.0 10.0 20
25 18.5 34 70 100 28-40 8.0 10.0 20
30 22 40 80 200 34-50 14.0 16.0 25
40 30 52 100 200 45-67 14.0 16.0 25
50 37 65 100 200 54-80 22.0 25.0 32
60 45 77 125 400 65-95 22.0 25.0 32
75 55 96 125 440 85-125 38.0 50.0 40
100 75 124 175 400 110-160 60.0 70.0 50
125 90 156 225 600 125-185 80.0 95.0 50
150 110 180 250 600 160-240 100.0 120.0 65
200 150 240 350 600 200-300 150.0 150.0 100

TABLES: 440 V,3phase,50Hz WYE-DELTA STARTING

MOTOR MOTOR MOTOR CIRCUIT SAFETY HEATER WIRE SIZE WIRE SIZE CONDUIT
RATING RATING FULL LOAD BREAKER SWITCH RANGE THHN XLPE/PVC SIZE
HP KW CURRENT RATING RATING (90deg.c) (90deg.c) (MAX.4-W)
7.5 5.5 11 20 30 5-8 3.5 4.0 15
10 7.5 14 30 60 8-16 5.5 6.0 15
15 11 21 50 60 8-16 5.5 6.0 15
20 15 27 70 100 12-18 8.0 10.0 20
25 18.5 34 70 100 18-26 8.0 10.0 20
30 22 40 75 200 18-26 14.0 16.0 25
40 30 52 100 200 24-36 14.0 16.0 25
50 37 65 100 200 34-50 22.0 25.0 32
60 45 77 125 400 34-50 22.0 25.0 32
75 55 96 125 400 45-67 38.0 50.0 40
100 75 124 175 400 65-95 60.0 70.0 50
125 90 156 225 600 65-95 80.0 95.0 50
150 110 180 250 600 85-125 100.0 120.0 65
200 150 240 350 800 125-185 150.0 150.0 60
GROUNDING AMP
WIRE DERAT
FACTOR
2.0 0.83
2.0 1.10
3.5 1.38
3.5 1.93
3.5 2.48
3.5 3.58
3.5 4.68
3.5 6.60
3.5 7.56
3.5 10.45
3.5 12.72
3.5 15.13
5.5 19.25
5.5 28.88
5.5 37.13
5.5 46.75
8.0 55.00
8.0 71.50
8.0 89.38
8.0 105.88
14.0 132.00
14.0 170.50
14.0 214.50
22.0 247.50
30.0 330.00

GROUNDING AMP
WIRE DERAT
FACTOR
3.5 15.13
3.5 19.25
3.5 28.88
3.5 37.13
5.5 46.75
5.5 55.00
5.5 71.50
8.0 89.38
8.0 105.88
22.0 132.00
22.0 170.50
22.0 214.50
30.0 247.50
30.0 330.00
TABLES: 440 V,3phase,50Hz FVNR-STARTING (DOL)

MOTOR MOTOR MOTOR CIRCUIT SAFETY HEATER WIRE SIZE WIRE SIZE CONDUIT
RATING RATING FULL LOAD BREAKER SWITCH RANGE THHN XLPE/PVC SIZE
HP KW CURRENT RATING RATING (90deg.c) (90deg.c) (MAX.4-W)
0.25 0.18 0.6 15 30 .48-.72 3.5 4.0 15
0.3 0.25 0.8 15 30 .64-.96 3.5 4.0 15
0.5 0.37 1 15 30 .95-1.45 3.5 4.0 15
0.75 0.55 1.4 15 30 .95-1.45 3.5 4.0 15
1 0.75 1.8 15 30 1.4-2.2 3.5 4.0 15
1.5 1.1 2.6 15 30 2.2-3.4 3.5 4.0 15
2 1.5 3.4 15 30 2.8-4.2 3.5 4.0 15
3 2.2 4.8 15 30 4-6 3.5 4.0 15
4 3 5.5 15 30 5-8 3.5 4.0 15
5 3.7 7.6 15 30 6-9 3.5 4.0 15
5.5 4 9.25 15 30 6-9 3.5 4.0 15
7.5 5.5 11 20 30 8-16 3.5 4.0 15
10 7.5 14 30 60 12-18 5.5 6.0 15
15 11 21 40 60 16-24 5.5 6.0 15
20 15 27 60 100 24-36 8.0 10.0 20
25 18.5 34 70 100 28-40 8.0 10.0 20
30 22 40 80 200 34-50 14.0 16.0 25
40 30 52 100 200 45-67 14.0 16.0 25
50 37 65 100 200 54-80 22.0 25.0 32
60 45 77 125 400 65-95 22.0 25.0 32
75 55 96 125 440 85-125 38.0 50.0 40
100 75 124 175 400 110-160 60.0 70.0 50
125 90 156 225 600 125-185 80.0 95.0 50
150 110 180 250 600 160-240 100.0 120.0 65
200 150 240 350 600 200-300 150.0 150.0 100

TABLES: 440 V,3phase,50Hz WYE-DELTA STARTING

MOTOR MOTOR MOTOR CIRCUIT SAFETY HEATER WIRE SIZE WIRE SIZE CONDUIT
RATING RATING FULL LOAD BREAKER SWITCH RANGE THHN XLPE/PVC SIZE
HP KW CURRENT RATING RATING (90deg.c) (90deg.c) (MAX.4-W)
7.5 5.5 11 20 30 5-8 3.5 4.0 15
10 7.5 14 30 60 8-16 5.5 6.0 15
15 11 21 50 60 8-16 5.5 6.0 15
20 15 27 70 100 12-18 8.0 10.0 20
25 18.5 34 70 100 18-26 8.0 10.0 20
30 22 40 75 200 18-26 14.0 16.0 25
40 30 52 100 200 24-36 14.0 16.0 25
50 37 65 100 200 34-50 22.0 25.0 32
60 45 77 125 400 34-50 22.0 25.0 32
75 55 96 125 400 45-67 38.0 50.0 40
100 75 124 175 400 65-95 60.0 70.0 50
125 90 156 225 600 65-95 80.0 95.0 50
150 110 180 250 600 85-125 100.0 120.0 65
200 150 240 350 800 125-185 150.0 150.0 60

General notes on HVAC

to compute tonner take the area and divide it with 16, 17, 18
GROUNDING AMP
WIRE DERAT
FACTOR
2.0 0.83
2.0 1.10
3.5 1.38
3.5 1.93
3.5 2.48
3.5 3.58
3.5 4.68
3.5 6.60
3.5 7.56
3.5 10.45
3.5 12.72
3.5 15.13
5.5 19.25
5.5 28.88
5.5 37.13
5.5 46.75
8.0 55.00
8.0 71.50
8.0 89.38
8.0 105.88
14.0 132.00
14.0 170.50
14.0 214.50
22.0 247.50
30.0 330.00

GROUNDING AMP
WIRE DERAT
FACTOR
3.5 15.13
3.5 19.25
3.5 28.88
3.5 37.13
5.5 46.75
5.5 55.00
5.5 71.50
8.0 89.38
8.0 105.88
22.0 132.00
22.0 170.50
22.0 214.50
30.0 247.50
30.0 330.00