TECHNICAL REPORT

PT. Palmdale Agroasia Lestari Makmur

Technician :
Banyak

JOB NO : XF-0039/319/32/2023
TECHNICAL REPORT
No. -----/--/SRV/PTK/I/-----
TSR Number:
Customer Name PT. PALMDALE AGROASIA LESTARI MAKMUR
Customer Group
Contact Person Mr. Manro H Munthe Email
Address Desa teluk bakung, kec. Telephone
Sungai ambawang, Fax
kab. Kubu raya,
kalimantan barat

Job No Job Open Date


Make DIS/ Delivery date
Cummins Power
Equipment Type 07/11/2022
Generation Date of Failure
Model C700D5 Engine Made
Equipment S/N G10S101247 Engine Model VTA 28 – G5
Customer Unit No. 3 Engine SN
Location Kendawangan Hours meter
Application/ Use Prime Status operation

Customer Complaint
- Service genset
- Synchron genset

Action repair/swervice
- replace Alternator
- replace control, Governor
- magnetic pick up
- Kit fuel selenoid
-cover shut off valve
-PCB Assy-Eng Interface
-Switch Magnetic
- Fuel water separator
-Lube filter
-Water filter

Test Run Genset no load


1. Test run no load genset adjusting HZ/RPM frim potentio Manual mode OK, high 52 Hz-low 48 Hz
2. Test run no load gsnset adjusting VOLTAGE from potentio Manual mode OK, high 410 voltage –low
365 volt
3. Test run lo load genset adjusting HZ and Voltage Auto from module COMAP OK

Test Load Genset


1. Test load genset Manual mode single OK “not synchron”
2. Test load genset auto mode single OK “not synchron”
-- adjusting High limit speed value 5,85
- adjusting low limit speed value 1,96
- adjusting bias limit speed value 2,65
- adjusting frequency gain value 10
- adjusting frequency in value 50
- adjusting angle gain value 10
- adjuting load gain value 10
- adjusting load in value 50
- adjusting load share gain value 10
- adjusting load share in 50

3. Test load genset manual mode synchron OK, Genset cummins to genset caterpillar OK, ganset
cummis to turbine OK, “load adjusting from potentio”
4. Test load genset Auto mode synchron OK, genset cummins to ganset caterpillar LOAD HUNTING
not stable share load,
- adjusting High limit speed value from 1- 10
- adjusting low limit speed value from 1-10
- adjusting bias limit speed value from 1-10
- adjusting frequency gain value from 1-13
- adjusting frequency in value from 1-100
- adjusting angle gain value 1-13
- adjuting load gain value 1- 13
- adjusting load in value 1-100
- adjusting load share gain value 1-13
- adjusting load share in 1-100
Note “ when adjusting from value low to high and test load synchron genset, genset cummins and
genset caterpillar load hunting

5. Test load genset Auto mode synchron OK, genset cummmins to TURBINE- LOAD HUNTING not
stable share load
- adjusting High limit speed value from 1- 10
- adjusting low limit speed value from 1-10
- adjusting bias limit speed value from 1-10
- adjusting frequency gain value from 1-13
- adjusting frequency in value from 1-100
- adjusting angle gain value 1-13
- adjuting load gain value 1- 13
- adjusting load in value 1-100
- adjusting load share gain value 1-13
- adjusting load share in 1-100
Note “ when adjusting from value low to high and test load synchron genset, genset cummins and
turbine load hunting

Result test
Genset cummins support for manual synchron with potentio to adjusting load share genset
to genset and genset to turbine. when auto synchron with COMAP and load genset, hunting for
load share and make ganset caterpillar hunting and turbine hunting not support to AUTO LOAD
SHARE.
Acknowledged by Reported By,
(Supervisor) (Technician)

DEDY A S DIMAS SAPUTRA


CUMMINS POWER GENERATION

Engine model : VTA28-G5


Engine no : 25354224

Model : C700D5
SN : G10S101247
640 KVA Prime Rating

HOURS METER :

Pt. ALTRAK1978
Cummins Power Generation
Photographmade

GENSET 03 VIEW in POWER HOUSE

View from
Left genset

View from
Right
genset

Pt. ALTRAK1978
Cummins Power Generation

Photographmade

1. SERVICE GANSET
- Replace Alternator

New Alternator
chager Battery

Pt. ALTRAK1978
Cummins Power Generation
Photographmade

- Control Governor
Old control governor

Pt. ALTRAK1978
inspection CPG
Photographmade

- PICK UP Magnetic

Old pick up magnetic


NEW Pick up magnetic

- KIT, FUEL Selenoid and Cover Shut off valve

Pt. ALTRAK1978
Cummins Power Generation
Photographmade

- PCB ASSY-Eng Interface


A31 engine interface contrl genset

- Switch Magnetic

Pt. ALTRAK1978
inspection CPG
Photographmade

- Set the value in panel control


Adjust speed governor high limit in
panel

Adjust speed governor low limit in Adjust speed governor bias in panel
panel
Pt. ALTRAK1978
inspection CPG
Photographmade

Set Binary Input in Panel Control

- Test run no load

Voltage Engine

Pt. ALTRAK1978
inspection CPG
Photographmade

- Test synchron manual ( turbine – genset cummins – genset catterpillar )

Voltage Engine

Load Generator no.1

Pt. ALTRAK1978
inspection CPG
Photographmade

Load Generator no.2

Load Generator no.3 ( VTA 28 )

Pt. ALTRAK1978
inspection CPG
Photographmade
Load Turbine

Pt. ALTRAK1978
inspection CPG
Photographmade

- Test synchron auto


Auto synchron (OK)

Process auot synchrone

Genset Hunting
Pt. ALTRAK1978