TECHNICAL REPORT
Technician :
Banyak
JOB NO : XF-0039/319/32/2023
TECHNICAL REPORT
No. -----/--/SRV/PTK/I/-----
TSR Number:
Customer Name PT. PALMDALE AGROASIA LESTARI MAKMUR
Customer Group
Contact Person Mr. Manro H Munthe Email
Address Desa teluk bakung, kec. Telephone
Sungai ambawang, Fax
kab. Kubu raya,
kalimantan barat
Customer Complaint
- Service genset
- Synchron genset
Action repair/swervice
- replace Alternator
- replace control, Governor
- magnetic pick up
- Kit fuel selenoid
-cover shut off valve
-PCB Assy-Eng Interface
-Switch Magnetic
- Fuel water separator
-Lube filter
-Water filter
3. Test load genset manual mode synchron OK, Genset cummins to genset caterpillar OK, ganset
cummis to turbine OK, “load adjusting from potentio”
4. Test load genset Auto mode synchron OK, genset cummins to ganset caterpillar LOAD HUNTING
not stable share load,
- adjusting High limit speed value from 1- 10
- adjusting low limit speed value from 1-10
- adjusting bias limit speed value from 1-10
- adjusting frequency gain value from 1-13
- adjusting frequency in value from 1-100
- adjusting angle gain value 1-13
- adjuting load gain value 1- 13
- adjusting load in value 1-100
- adjusting load share gain value 1-13
- adjusting load share in 1-100
Note “ when adjusting from value low to high and test load synchron genset, genset cummins and
genset caterpillar load hunting
5. Test load genset Auto mode synchron OK, genset cummmins to TURBINE- LOAD HUNTING not
stable share load
- adjusting High limit speed value from 1- 10
- adjusting low limit speed value from 1-10
- adjusting bias limit speed value from 1-10
- adjusting frequency gain value from 1-13
- adjusting frequency in value from 1-100
- adjusting angle gain value 1-13
- adjuting load gain value 1- 13
- adjusting load in value 1-100
- adjusting load share gain value 1-13
- adjusting load share in 1-100
Note “ when adjusting from value low to high and test load synchron genset, genset cummins and
turbine load hunting
Result test
Genset cummins support for manual synchron with potentio to adjusting load share genset
to genset and genset to turbine. when auto synchron with COMAP and load genset, hunting for
load share and make ganset caterpillar hunting and turbine hunting not support to AUTO LOAD
SHARE.
Acknowledged by Reported By,
(Supervisor) (Technician)
Model : C700D5
SN : G10S101247
640 KVA Prime Rating
HOURS METER :
Pt. ALTRAK1978
Cummins Power Generation
Photographmade
View from
Left genset
View from
Right
genset
Pt. ALTRAK1978
Cummins Power Generation
Photographmade
1. SERVICE GANSET
- Replace Alternator
New Alternator
chager Battery
Pt. ALTRAK1978
Cummins Power Generation
Photographmade
- Control Governor
Old control governor
Pt. ALTRAK1978
inspection CPG
Photographmade
- PICK UP Magnetic
Pt. ALTRAK1978
Cummins Power Generation
Photographmade
- Switch Magnetic
Pt. ALTRAK1978
inspection CPG
Photographmade
Adjust speed governor low limit in Adjust speed governor bias in panel
panel
Pt. ALTRAK1978
inspection CPG
Photographmade
Voltage Engine
Pt. ALTRAK1978
inspection CPG
Photographmade
Voltage Engine
Pt. ALTRAK1978
inspection CPG
Photographmade
Pt. ALTRAK1978
inspection CPG
Photographmade
Load Turbine
Pt. ALTRAK1978
inspection CPG
Photographmade
Genset Hunting
Pt. ALTRAK1978
inspection CPG