40'

DESIGN: Column Plan


TOILET STORE
8'0" X 5'0" UTILITY / WASH 7'0" X 5'0" AREA STATEMENT:
11'3" X 5'0" Plot Area :
Ground Floor Area :
SHOP First Floor Area :
11'0" X 9'0"
NOTE:
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
KITCHEN STEEL REINFORCEMENT
12'8" X 11'0" Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.

M7.5 = 1:4:8 ( USED AS P.C.C. )


M. BEDROOM SHOP M10= 1:3:6
14'0" X 11'0" 11'0" X 9'0" M15= 1:2:4
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )

BASIN
M25= 1:1:2
LIVING + CLEAR COVER TO MAIN
DINING PUJA
18'8" X 10'0" REINFORCEMENT:

ROAD
8'0" X 6'0" 1.FOOTINGS : 50 mm
2.RAFT FOUNDATION.TOP : 50 mm
50'

3.RAFT FOUNDATION.
C. TOILET BOTTOM/SIDES : 75 mm
8'0" X 5'0" 4.STRAP BEAM : 50 mm
5.GRADE SLAB : 20 mm
6.COLUMN : 40 mm
7.SHEAR WALL : 25 mm
GUEST 8.BEAMS : 25 mm
BEDROOM 9.SLABS : 15 mm
11'0" X 8'10"
BEDROOM 10.STAIRCASE : 15 mm
12'0" X 12'0" DRAWING
11.WATER RETAINING
14'8" X 12'0" STRUCTURES : 20/30 mm

Client Name: Mr.Arvind singh


Project Type: Residential
Date: 21-09-2023
Sheet No.: S-01
SHEET NO. : S-01
PARKING
11'0" X 14'0"

C. TOILET
4'1" X 6'6" UP

ROAD
GF COLUMN PLAN
This drawing is the property of makemyhouse.com It may not be used for any purpose other than the owner.
makemyhouse.com does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
2 3
1 4 5
DESIGN: Column Centerline Plan

AREA STATEMENT:
1'-5" 1"
13'-22 1"
12'-12 Plot Area :
13'-3"
Ground Floor Area :
First Floor Area :
NOTE:
J J SOIL BEARING CAPACITY
C1 C2 C2 C2 Foundations have been designed

1"
6'-12
According to given site soil condition.
STEEL REINFORCEMENT
I C2
I Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.

1"
4'-12
M7.5 = 1:4:8 ( USED AS P.C.C. )
H C2
H M10= 1:3:6
C2

1"
6'-112
M15= 1:2:4
1 M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
C132"
M25= 1:1:2
G G

1"
2"

1'-102
G C2 CLEAR COVER TO MAIN
F F REINFORCEMENT:
C2 F C1 1.FOOTINGS : 50 mm
2.RAFT FOUNDATION.TOP : 50 mm

9'
3.RAFT FOUNDATION.
50'

BOTTOM/SIDES : 75 mm
1"

121"
43'-102

2
E E 4.STRAP BEAM : 50 mm
39'-9"

C2 C2 C2 5.GRADE SLAB : 20 mm

6'-10"
6.COLUMN : 40 mm
1"

7.SHEAR WALL : 25 mm
32'-92

30'-11"

C1 8.BEAMS : 25 mm
D D 9.SLABS : 15 mm

1"
5'-52
21'-11"

10.STAIRCASE : 15 mm
121"
121" 4 11.WATER RETAINING
C C STRUCTURES : 20/30 mm
15'-1"

C2
C
C2 C2

1"
7'-12
Client Name: Mr.Arvind singh
9'-72"
1

C2 B
Project Type: Residential
C2
B B Date: 21-09-2023
2'-6"

2'-6"
121" 2 121" 121" 4 C2
C3 C3 Sheet No.: S-01
A C2
A SHEET NO. : S-02
13'-3"

C3 COLUMN IS FOR BOUNDARY


14'-8"
PROVISION G+1
WALL WITH 6' DEEP PILE
1"
27'-102

40'

1 4 5
2 3
ROAD
COLUMN CENTERLINE PLAN
This drawing is the property of makemyhouse.com It may not be used for any purpose other than the owner.
makemyhouse.com does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
2 3
1 4 5
DESIGN: Foundation Plan

1'-5" 1" 1" AREA STATEMENT:


13'-3" 13'-22 12'-12
Plot Area :
Ground Floor Area :
First Floor Area :
J C1 C2 C2 C2 J NOTE:

4'-10"
4'-4"

4'-4"
SOIL BEARING CAPACITY

5'-4"
F7 F8

1"
6'-12
F2 5'-8" F7 Foundations have been designed
According to given site soil condition.
F5 5'-8" 4'-10" STEEL REINFORCEMENT
I 5'-4" I
5'-2" Steel Reinforcement confirming to IS 1786-1985 code,

1"
4'-12
C2 FE - 500 grade should be used.
F5

5'-8"
5'-2"
5'-2"
H F6 H M7.5 = 1:4:8 ( USED AS P.C.C. )
C2 C2 M10= 1:3:6

1"
6'-112
5'-2" 4'-4" M15= 1:2:4
5'-2" M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
F5

6'-2"

5'-2"
G C1 G

1"
M25= 1:1:2

1'-102
F1 C2 F5

6'-2"
5'-2"
CLEAR COVER TO MAIN
F F1 F
4'-10" C2 C1 REINFORCEMENT:
1.FOOTINGS : 50 mm
4'-10"
2.RAFT FOUNDATION.TOP : 50 mm

9'
5'-2" 5'-2"
50'

3.RAFT FOUNDATION.
F5 F5
1"

BOTTOM/SIDES : 75 mm
43'-102

5'-8"

5'-2"

5'-2"
E F6 E 4.STRAP BEAM : 50 mm
39'-9"

C2 C2 C2 5.GRADE SLAB : 20 mm

6'-10"
4'-4" 6.COLUMN : 40 mm
1"
32'-92

30'-11"

7.SHEAR WALL : 25 mm

6'-2"
D C1 D 8.BEAMS : 25 mm
4'-4"
F1 9.SLABS : 15 mm

1"
5'-2" 5'-2"

5'-52
21'-11"

10.STAIRCASE : 15 mm
F5 F5 4'-10"
5'-8"

5'-2"

5'-2"
F6 11.WATER RETAINING
C C STRUCTURES : 20/30 mm
15'-1"

C2 C2
C2

1"
7'-12
4'-4" 4'-10" Client Name: Mr.Arvind singh
9'-72"

5'-2"
1

(BOX) 5'-8"
4'-10"
Project Type: Residential

4'-10"
C2 C2(BOX)
5'-4"

4'-4"
B F3 F7 F8 B Date: 21-09-2023
2'-6"

2'-6"
F4 C2 C2
C3 C3
A A Sheet No.: S-01
SHEET NO. : S-03
13'-3"

C3 COLUMN IS FOR BOUNDARY


14'-8"
PROVISION G+1
WALL WITH 6' DEEP PILE
1"
27'-102

40'

1 4 5
2 3
ROAD

FOUNDATION PLAN
This drawing is the property of makemyhouse.com It may not be used for any purpose other than the owner.
makemyhouse.com does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
DESIGN: Foundation & Column Schedule

AREA STATEMENT:
Plot Area :
Ground Floor Area :
First Floor Area :
SCHEDULE OF REINFORCEMENT FOR FOOTINGS AND COLUMNS NOTE:
REINFORCEMENTREINFORCEMENT SOIL BEARING CAPACITY

TYPE EXCAVATION L (IN) B (IN) D (IN) t (IN) IN 'L' DIRECTION IN 'B' DIRECTION COL NO. COLUMN SECTION Foundations have been designed
According to given site soil condition.
STEEL REINFORCEMENT

F1 6'-2" X 4'-10" 5'-6" 4'-6" 1'-10" 10" 10 TMT 6" C/C 10 TMT 6" C/C 16" 3"
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.

M7.5 = 1:4:8 ( USED AS P.C.C. )

9"
M10= 1:3:6
F2 5'-4" X 5'-4" 5'-0" 5'-0" 1'-10" 10" 10 TMT 6" C/C 10 TMT 6" C/C C1 M15= 1:2:4
8 NOS 12 TMT M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
M25= 1:1:2
8 TMT @ 6" C/C (DOUBLE RING)
F3 5'-4" X 4'-4" 5'-0" 4'-0" 1'-8" - 10 TMT 6" C/C 10 TMT 6" C/C CLEAR COVER TO MAIN
(BOX) REINFORCEMENT:
1.FOOTINGS : 50 mm
F4 4'-10" X 5'-2" 4'-6"
12" 3" 2.RAFT FOUNDATION.TOP : 50 mm
4'-6" 1'-8" - 10 TMT 6" C/C 10 TMT 6" C/C 3.RAFT FOUNDATION.
(BOX)

9"
BOTTOM/SIDES : 75 mm
C2 4.STRAP BEAM : 50 mm
F5 5'-2" X 5'-2" 4'-6" 4'-6" 1'-8" 8" 10 TMT 6" C/C 10 TMT 6" C/C 6 NOS 12 TMT
5.GRADE SLAB : 20 mm
6.COLUMN : 40 mm
8 TMT @ 6" C/C RING 7.SHEAR WALL : 25 mm
8.BEAMS : 25 mm
F6 5'-8" X 4'-4" 5'-0" 4'-0" 1'-8" 8" 10 TMT 6" C/C 10 TMT 6" C/C 9.SLABS : 15 mm
10.STAIRCASE : 15 mm
11.WATER RETAINING
F7 4'-4" X 5'-8" 4'-0" 5'-0" 1'-8" 8" 10 TMT 6" C/C 10 TMT 6" C/C 9" 3"
STRUCTURES : 20/30 mm

9''
Client Name: Mr.Arvind singh
C3 Project Type: Residential
F8 4'-10" X 4'-10" 4'-6" 4'-6" 1'-8" 8" 10 TMT 6" C/C 10 TMT 6" C/C Date: 21-09-2023
4 NOS 12 TMT
8 TMT @ 7" C/C RING Sheet No.: S-01
SHEET NO. : S-04
Note: The depth of foundation will be according to the site conditions.

This drawing is the property of makemyhouse.com It may not be used for any purpose other than the owner.
makemyhouse.com does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
G.L.

A A
REINFORCEMENT DESIGN: Foundation Schedule
IN 'L' DIRECTION

'L'
REINFORCEMENT
IN 'B' DIRECTION AREA STATEMENT:
Plot Area :

'D'
12" 12" Ground Floor Area :
'B'

't'

4"
First Floor Area :
P.C.C. 1:4:8
PLAN
TYPICAL FOOTING DETAIL OF COLUMN SECTION A-A NOTE:
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
G.L.
FE - 500 grade should be used.

COLUMN REINFORCEMENT M7.5 = 1:4:8 ( USED AS P.C.C. )


IN 'B' DIRECTION M10= 1:3:6
B B REINFORCEMENT M15= 1:2:4
IN 'L' DIRECTION

'L'
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
M25= 1:1:2
CLEAR COVER TO MAIN

'D'
REINFORCEMENT:
'B' 1.FOOTINGS : 50 mm

't'
P.C.C. 1:4:8 2.RAFT FOUNDATION.TOP : 50 mm
PLAN 3.RAFT FOUNDATION.
TYPICAL FOOTING DETAIL OF SECTION B-B BOTTOM/SIDES : 75 mm
CORNER WALL COLUMNS 4.STRAP BEAM : 50 mm
5.GRADE SLAB : 20 mm
G.L. 6.COLUMN : 40 mm
7.SHEAR WALL : 25 mm
COLUMN REINFORCEMENT 8.BEAMS : 25 mm
IN 'B' DIRECTION 9.SLABS : 15 mm
B
B REINFORCEMENT 10.STAIRCASE : 15 mm
IN 'L' DIRECTION
'L'

11.WATER RETAINING
STRUCTURES : 20/30 mm

'D'
Client Name: Mr.Arvind singh
'B' Project Type: Residential

't'
P.C.C. 1:4:8
Date: 21-09-2023
PLAN
TYPICAL FOOTING DETAIL OF SECTION B-B Sheet No.: S-01
CORNER WALL COLUMNS SHEET NO. : S-04

G.L. G.L.

REINFORCEMENT
A A IN 'L' DIRECTION REINFORCEMENT
'L'

IN 'B' DIRECTION
'D'

12" 12" 12" 12"

4"
'B' P.C.C. 1:4:8 P.C.C. 1:4:8
PLAN
SECTION A-A
TYPICAL DETAIL OF COMBINED
FOOTING OF COLUMN FOUNDATION SCHEDULE

This drawing is the property of makemyhouse.com It may not be used for any purpose other than the owner.
makemyhouse.com does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect
SCHEDULE OF PLINTH BEAM
REIN. AT REIN. AT EXTRA AT EXTRA AT RINGS
NAME SIZE (IN)
TOP BOTTOM BOTTOM TOP UP TO L/3 AFTER L/3

PB1/GB1 9" x 16" 2-12 TMT 3-12 TMT 2-12 TMT 2-12 TMT
DESIGN: Plinth Beam Plan
8 # @ 5" C/C 8 # @ 6" C/C

PB2 9" x 12" 2-12 TMT 2-12 TMT 2-12 TMT 2-12 TMT 8 # @ 5" C/C 8 # @ 6" C/C
AREA STATEMENT:
PB3/GB 9" x 12" 2-12 TMT 2-12 TMT 2-10 TMT 2-10 TMT 8 # @ 5" C/C 8 # @ 6" C/C
Plot Area :
PB4 9" x 12" 2-12 TMT 2-12 TMT - - 8 # @ 5" C/C 8 # @ 6" C/C Ground Floor Area :
NOTE-ALL GROUND BEAM AT CURRENT PLOT LEVEL. First Floor Area :
PB2/GB PB2 /GB PB2 /GB
NOTE:
7'-8" 11'-3" 6'-4" 10 T Ø @ 8" C/C SOIL BEARING CAPACITY
TOILET PB4 PB4 STORE 8T Ø @ 6" C/C Foundations have been designed
8'0" X 5'0" UTILITY / WASH 7'0" X 5'0" According to given site soil condition.
LVL+1'-6" 11'3" X 5'0"
LVL+1'-6" PB2 STEEL REINFORCEMENT

4"
PB2 LVL+1'-6" /GB Steel Reinforcement confirming to IS 1786-1985 code,
C C' FE - 500 grade should be used.
PB2 PB2 SHOP
11'0" X 9'0"
PB1 A A' M7.5 = 1:4:8 ( USED AS P.C.C. )
/GB1
KITCHEN
Plinth slab M10= 1:3:6
M15= 1:2:4
M. BEDROOM PB2 12'8" X 11'0" PB2 M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
14'0" X 11'0"
LVL+1'-6" M25= 1:1:2
LVL+1'-6" Brickwork
Plinth CLEAR COVER TO MAIN
PB2 PB2 Floor Finishing REINFORCEMENT:
LVL+1'-6" /GB Level(3'-0")lvl
PB2 SHOP 1.FOOTINGS : 50 mm
11'0" X 9'0" 2.RAFT FOUNDATION.TOP : 50 mm

4"
PB3 Brickwork
7'-8" 3.RAFT FOUNDATION.

12"
BASIN
4'-7"

Plinth Floor Finishing BOTTOM/SIDES : 75 mm


PB2 Level(1'-6")lvl 4.STRAP BEAM : 50 mm
Plinth Beam

ROAD
LIVING + PUJA 5.GRADE SLAB : 20 mm
PB2 PB4 PB3 8'0" X 6'0" Brickwork

4"
DINING
6'

/GB 18'8" X 10'0" 6.COLUMN : 40 mm


PB2

12"
LVL+1'-6"
LVL+1'-6" 7.SHEAR WALL : 25 mm
4'-8"

LVL+1'-6"
C. TOILET 8.BEAMS : 25 mm
8'0" X 5'0" Plinth Beam 9.SLABS : 15 mm
B 14'-9" B' PB1
PB3 /GB1 Brickwork

12"
10.STAIRCASE : 15 mm
Ground Beam 11.WATER RETAINING
PB2 PB2
8'-6"

GUEST Road Level Ground Level STRUCTURES : 20/30 mm


BEDROOM

BEDROOM
11'0" X 8'10"
LVL+1'-6"
Section AA' Section CC' Client Name: Mr.Arvind singh
12'0" X 12'0" PB2 DRAWING Project Type: Residential
PB2 14'8" X 12'0" PB2
/GB B Date: 21-09-2023
LVL+1'-6"
LVL+1'-6"
14'-9"
B' Sheet No.: S-01
PB3
SHEET NO. : S-05
2L/3 2Y12 1 L/3 2Y12

PB2 PB2 PARKING 2 Y12


11'0" X 14'0" PB2
L/4 2 Y12
L/4
/GB 2 8TMT @ 6" c/c RINGS 1
PB2 PB2 LVL+1'-6" LVL+1'-0"
/GB C. TOILET PB2
4'1" X 6'6" UP LVL+1'-0"
BEAM SECTION B-B'
PB2 PB2 PB2
4"

4"
/GB
PB2/GB PB2/GB ±0" LVL. PB2/GB
8"

8"
ROAD
9" 9"
PLINTH BEAM PLAN
SECTION 1 - 1 SECTION 2 - 2

This drawing is the property of makemyhouse.com It may not be used for any purpose other than the owner.
makemyhouse.com does not authorize the reproduction or conveyance of any information contained herein without prior written permission.

All dimensions in inches | Dimensions to be strictly followed |


Any discrepancy between the architectural/ structural or services drawings
must be brought to attention of Architect