Professional Documents
Culture Documents
Resistances and reactances of transformer, which are described above, can be imagined
separately from the windings (as shown in the figure below). Hence, the function of
windings, thereafter, will only be the transforming the voltage
The no load current I0 is divided into, pure inductance X0 (taking magnetizing components
Iμ) and non-induction resistance R0 (taking working component Iw) which are connected
into parallel across the primary. The value of E1 can be obtained by subtracting I1Z1 from
V1. The value of R0and X0 can be calculated as, R0 = E1 / Iw and X0 = E1 / Iμ.
But, using this equivalent circuit does not simplifies the calculations. To make calculations
simpler, it is preferable to transfer current, voltage and impedance either to primary side or
to the secondary side. In that case, we would have to work with only one winding which is
more convenient. From the voltage transformation ratio, it is clear that,
E1 / E2 = N1 / N2 = K
Now, lets refer the parameters of secondary side to primary. Z2 can be referred to primary
as Z2'
where, Z2' = (N1/N2)2Z2 = K2Z2. ............where K= N1/N2.
that is, R2'+jX2' = K2(R2+jX2)
equating real and imaginary parts,
R2' = K2R2 and X2' = K2X2 .
And V2' = KV2
The following figure shows the equivalent circuit of transformer with secondary
parameters referred to the primary.
Now, as the values of winding resistance and leakage reactance are so small that, V1 and
E1 can be assumed to be equal. Therefore, the exciting current drawn by the parallel
combination of R0 and X0 would not affect significantly, if we move it to the input
terminals as shown in the figure below.
TRANSFORMER TESTS
Open and short circuit tests are performed on a transformer to determine the:
The ammeter reading gives the no load current. As no load current is quite small compared
to rated current of the transformer, the voltage drops due to this current that can be taken
as negligible.
Since voltmeter reading V1 can be considered equal to the secondary induced voltage of
the transformer, wattmeter reading indicates the input power during the test. As the
transformer is open circuited, there is no output, hence the input power here consists of
core losses in transformer and copper loss in transformer during no load condition.
But as said earlier, the no-load current in the transformer is quite small compared to the
full load current so, we can neglect the copper loss due to the no-load current. Hence, can
take the wattmeter reading as equal to the core losses in the transformer
Vo = Rated voltage
Wo = Input power
Io = Input current = no load current
As transformer secondary is open, it is on no load. So current drawn by the primary is no
load current Io. The two components of this no load current are,
I 𝜇 = Io sin Φo
Iw = Io cos Φo
where cos Φo = No load power factor
And hence power input can be written as,
Wo = V1 Io cos Φo
As secondary is open, I2 = 0. Thus its reflected current on primary is also zero. So we have
primary current I1 =Io. As I2 = 0, secondary copper losses are zero.
And I1 = Io is very low hence copper losses on primary are also very very low. Thus the
total copper losses in O.C. test are negligibly small. As against this the inputvoltage is rated
at rated frequency hence flux density in the core is at its maximum value.
Hence iron losses are at rated voltage. As output power is zero and copper losses are very
low, the total input power is used to supply iron losses. This power is measured by the
wattmeter i.e. Wo. Hence the wattmeter in O.C. test gives iron losses which remain constant
for all the loads.
... Wo = Pi = Iron losses
Calculations : We know that,
Wo = Vo Io cos Φ
cos Φo = Wo /(Vo Io ) = no load power factor
Once cos Φo is known we can obtain,
Iw = Io cos Φo
and I 𝜇 = Io sin Φo
Once Ic and Im are known we can determine exciting circuit parameters as,
Ro = Vo /Iw Ω
and Xo = Vo /I 𝜇 Ω
The connection diagram for short circuit test on transformer is shown in the figure. A
voltmeter, wattmeter, and an ammeter are connected in HV side of the transformer
The connection diagram for short circuit test or impedance test on transformer is as
shown in the figure below. The LV side of transformer is short circuited and wattmeter
(W), voltmere (V) and ammeter (A) are connected on the HV side of the transformer.
Voltage is applied to the HV side and increased from the zero until the ammeter reading
equals the rated current. All the readings are taken at this rated current.
Now the current flowing through the windings are rated current hence the total copper
loss is full load copper loss. Now the voltage supplied is low which is a small fraction of
the rated voltage. The iron losses are function of applied voltage. So the iron losses in
reduced voltage test are very small. Hence the wattmeter reading is the power loss which
is equal to full load copper losses as iron losses are very low.
... Wsc = (Pcu) F.L. = Full load copper loss
Calculations : From S.C. test readings we can write,
Wsc = Vsc Isc cos Φsc
... cos Φsc = Vsc Isc /Wsc = short circuit power factor
Wsc = Isc2 R02 = copper loss
... R02 =Wsc /Isc2
while Z02=Vsc /Isc = √(R022 + X022)
... X02 = √(Z022 - R022)
Thus we get the equivalent circuit parameters R02, X02and Z02. Knowing the transformation ratio
K, the equivalent circuit parameters referred to secondary also can be obtained.
During no-load condition, V1 is approximately equal to El and V02 = E2 where V02 indicates
no-load terminal voltage of the secondary. When secondary is loaded, let the secondary
terminal voltage be V2. The difference between V2 and V02 is the voltage drop across
equivalent impedance in secondary, i.e., I2Z02 shown in Figure (a).
Total approximate voltage drop =AG=AF+FG
= I2R02cosθ–I2X02sinθ
This approximate voltage drop is for lagging power factor only.
For leading power factor, the approximate voltage drop will be
= I2R02cosθ–I2X02sinθ
where ‘+’ sign is for lagging power factor and ‘-’ sign is for leading power factor.
The above calculation is referred to as secondary. It may be noted that voltage drop referred
to as primary is
I1R01cosθ±I1X01sinθ
∴% voltage drop in secondary is=
=vrcosθ±vxsinθ (1.42)
where
and
REGULATION OF A TRANSFORMER
Definition: The voltage regulation is defined as the change in the magnitude of receiving
and sending the voltage of the transformer. The voltage regulation determines the ability
of the transformer to provide the constant voltage for variable loads.
Voltage Regulation of Transformer Formula
The percentage change in output voltage from no-load to full-load is termed the voltage regulation
of the transformer. Ideally, there should be no change in Vo from no-load to full-load (i.e.,
regulation = 100%). For the best possible performance, the transformer should have the lowest
possible regulation. Mathematically, voltage regulation can be expressed as
Where Vo(NL) is the transformer no-load output voltage, and Vo(FL) is the full load output voltage.
When the transformer is loaded with continuous supply voltage, the terminal voltage of the
transformer varies. The variation of voltage depends on the load and its power factor.
EFFICIENCY OF TRANSFORMER
Just like any other electrical machine, efficiency of a transformer can be defined as the
output power divided by the input power. That is efficiency = output / input .
Transformers are the most highly efficient electrical devices. Most of the transformers have
full load efficiency between 95% to 98.5% . As a transformer being highly efficient, output
and input are having nearly same value, and hence it is impractical to measure the
efficiency of transformer by using output / input. A better method to find efficiency of a
transformer is using, efficiency = (input - losses) / input = 1 - (losses / input).
Hence, efficiency of a transformer will be maximum when copper loss and iron losses are equal.
That is Copper loss = Iron loss.
But in some types of transformers, their performance can not be judged by this efficiency. For
example, distribution transformers have their primaries energized all the time. But, their
secondaries supply little load all no-load most of the time during day (as residential use of
electricity is observed mostly during evening till midnight).That is, when secondaries of
transformer are not supplying any load (or supplying only little load), then only core losses of
transformer are considerable and copper losses are absent (or very little). Copper losses are
considerable only when transformers are loaded. Thus, for such transformers copper losses are
relatively less important. The performance of such transformers is compared on the basis of energy
consumed in one day.
All day efficiency of a transformer is always less than ordinary efficiency of it.
1. Firstly, if one transformer fails, the continuity of supply can be maintained through other
transformers.
2. Secondly, when the load on the substation becomes more than the capacity of the existing
transformers, another transformer can be added in parallel.
3. Thirdly, any transformer can be taken out of the circuit for repair/routine
maintenance without interrupting supply to the consumers.
In order that the transformers work satisfactorily in parallel, the following conditions should be
satisfied:
This condition is absolutely essential because wrong connections may result in dead short-circuit.
Figure (i) shows the correct method of connecting two single-phase transformers in parallel.
It will be seen that round the loop formed by the secondaries, the two secondary e.m.f.s EA and
EB oppose and there will be no circulating current.
Transformer Connection Based on Polarity (i) Correct Connections (ii) Wrong Connections
Figure (ii) shows the wrong method of connecting two single-phase transformers in parallel. Here
the two secondaries are so connected that their e.m.f.s EA and EB are additive. This may lead to
short-circuiting conditions and a very large circulating current will flow in the loop formed by the
two secondaries.Such a condition may damage the transformers unless they are protected by fuses
and circuit breakers.
If this condition is not met, the secondary e.m.f.s will not be equal and there will be circulating
currentin the loop formed by the secondaries. This will result in the unsatisfactory parallel
operation of transformers.
Let us illustrate this point. Consider two single-phase transformer A and B operating in parallel as
shown in the figure.
Let Ea and Eb be their no-load secondary voltages and Za and Zb be their impedances referred to
the secondary. Then at no-load, the circulating current in the loop formed by the secondaries is
Even a small difference in the induced secondary voltages can cause a large circulating current in
the secondary loop because impedances of the transformers are small. This secondary circulating
current will cause current to be drawn from the supply by the primary of each transformer.These
currents will cause copper losses in both primary and secondary. This creates heating with no
useful output.
When the load is connected to the system, this circulating current will tend to produce unequal
loading conditions i.e., the transformers will not share the load according to their kVA ratings. It
is because the circulating current will tend to make the terminal voltages of the same value for
both transformers.
Therefore, the transformer with a smaller voltage ratio will tend to carry more than its proper share
of the load.
Thus, one transformer would tend to become overloaded than the other and the system could not
be loaded to the summation of transformer ratings without overloading one transformer.
This condition is also desirable for proper parallel operation of single phase transformers.
If this condition is not met, the transformers will not share the load according to their kVA ratings..
In that case, it can be corrected by inserting proper amount of resistance or reactance or both in
series with either primary or secondary circuits of the transformers where the impedance is below
the value required to fulfill this condition.
If the reactance/resistance ratios of the two transformers are not equal, the power factor of the load
supplied by the transformers will not be equal.
In other words, one transformer will be operating with a higher and the other with a lower power
factor than that of the load.
LOAD SHARING BY TRANSFORMER
∴
Equation (1.73) suggests that if two transformers with different kVA ratings are connected in
parallel, the total load will be divided in proportion to their kVA ratings if their equivalent
impedances are inversely proportional to their respective ratings.
Since
i.e.,
i.e.,
Similarly,
Similarly, load shared by transformer A,
Similarly,
Total S=SA+SB=V2I×10-3 kVA
Three phase transformers are used to step-up or step-down the high voltages in various
stages of power transmission system. The power generated at various generating stations
is in three phase nature and the voltages are in the range of 13.2KV or 22KV. In order to
reduce the power loss to the distribution end, the power is transmitted at somewhat higher
voltages like 132 or 400KV.
Hence, for transmission of the power at higher voltages, three phase step-up transformer is
used to increase the voltage. Also at the end of the transmission or distribution, these high
voltages are step-down to levels of 6600, 400, 230 volts, etc. For this, a three phase step
down transformer is used.
A three phase transformer can be built in two ways; a bank of three single phase
transformers or single unit of three phase transformer.The former one is built by suitably
connecting three single phase transformers having same ratings and operating
characteristics. In this case if the fault occurs in any one of the transformers, the system
still retained at reduced capacity by other two transformers with open delta connection.
Hence, continuity of the supply is maintained by this type of connection. These are used in
mines because easier to transport individual single phase transformers.
Construction of Three Phase Transformers
A three phase transformer can be constructed by using common magnetic core for both primary
and secondary windings. As we discussed in the case of single phase transformers, construction
can be core type or shell type. So for a bank of three phase core type transformer, three core type
single phase transformers are combined. Similarly, a bank of three phase shell type transformer is
get by properly combining three shell type single phase transformers. In a shell type transformer,
EI laminated core surrounds the coils whereas in core type coil surrounds the core.
In core type three phase transformer, core is made up of three limbs or legs and two yokes. The
magnetic path is formed between these yokes and limbs. On each limb both primary and secondary
windings are wounded concentrically. Circular cylindrical coils are used as the windings for this
type of transformer. The primary and secondary windings of one phase are wounded on one leg.
Under balanced condition, the magnetic flux in each phase of the leg adds up to zero. Therefore,
under normal conditions, no return leg is needed. But in case of unbalanced loads, high circulating
current flows and hence it may be best to use three single phase transformers.
In shell type, three phases are more independent because each phase has independent magnetic
circuit compared with core type transformer. The construction is similar to the single phase shell
type transformer built on top of another. The magnetic circuits of this type of transformer are in
parallel. Due to this, the saturation effects in common magnetic paths are neglected. However,
shell type constructed transformers are rarely used in practice.
Shell Type
Working of Three Phase Transformers
Consider the below figure in which the primary of the transformer is connected in star fashion on
the cores. For simplicity, only primary winding is shown in the figure which is connected across
the three phase AC supply. The three cores are arranged at an angle of 120 degrees to each other.
The empty leg of each core is combined in such that they form center leg as shown in figure.
working of a transformer
When the primary is excited with the three phase supply source, the currents IR, IY and IB are
starts flowing through individual phase windings. These currents produce the magnetic fluxes ΦR,
ΦY and ΦB in the respective cores. Since the center leg is common for all the cores, the sum of
all three fluxes are carried by it. In three phase system, at any instant the vector sum of all the
currents is zero. In turn, at the instant the sum of all the fluxes is same. Hence, the center leg
doesn’t carry any flux at any instant. So even if the center leg is removed it makes no difference
in other conditions of the transformer.
Likewise, in three phase system where any two conductors acts as return for the current in third
conductor, any two legs acts as a return path of the flux for the third leg if the center leg is removed
in case of three phase transformer. Therefore, while designing the three phase transformer, this
principle is used.
These fluxes induce the secondary EMFs in respective phase such that they maintain their phase
angle between them. These EMFs drives the currents in the secondary and hence to the load.
Depends on the type of connection used and number of turns on each phase, the voltage induced
will be varied for obtaining step-up or step-down of voltages.
As discussed above, either by a single three phase transformer or by three single phase transformers
combination, three phase transformations can be carried out. The way of connecting the windings
for three phase transformation is same whether the three windings of a three phase transformer or
three windings of three single phase transformers are used. The primary and secondary windings
are connected in different ways, such as in delta or star or combination of these two. The voltage
and current ratings of the three phase transformer is depends on suitable connection. The most
commonly used connections are
Star-delta
Delta-star
Delta-delta
Star-star
In this, the primary winding of the transformer is connected in star and secondary in delta
connection.
The neutral point on the primary or high voltage side can be grounded which is desirable in
most of the cases.
The line voltage ratio between secondary and primary is 1/√3 times the transformation ratio
of each transformer.
There exists 30 degrees phase difference between primary and secondary line voltages.
Since the actual primary coil voltage is 58% of the primary line voltage, the insulation
requirements for HV windings is reduced by using this winding.
In this connection balanced three phase voltage are obtained at the secondary or LV side,
even when the unbalanced currents are flowing the in the primary or HV side due to neutral
wire. The neutral wire grounding also provides lightning surge protection.
This connection is used to step-up the voltage level and is commonly employed in sending
end or starting of high tension transmission system.
In this, the primary is connected in delta fashion and secondary in star fashion so that three
phase 4 wire system at secondary is possible.
The secondary voltage to the load is √3 times the delta connected primary voltage. Also the
load and secondary currents will be the same due to the same series circuit.
This connection provides three single phase circuits at both lower and higher voltages and
one three phase circuit at higher voltage so that single and three phase loads can be supplied.
Dual voltages are obtained delta-star connection. Low single phase voltages are obtained by
wiring between any phase and ground. Higher single phase voltages are obtained by wiring
between any two phases. And by connecting all three phases to the load, three phase voltage
is obtained.
The insulation requirement on high voltage side is lowered due to the star (less number of
turns per phase) connected secondary.
Similar to star-delta, this connection causes to create a 30 degrees phase difference between
primary and secondary line voltages.
By using this connection, it is not possible to connect it parallel with delta-delta and star-
star transformers due to the primary and secondary voltage phase difference.
Delta-delta
This type of connection is used when the supply source is delta connected and the secondary
load needs single voltage with high current. This is generally employed for three phase
power loads (like three phase motor).
In this, both primary and secondary windings are connected in delta fashion.
The voltage across the load is equal to the secondary voltage and voltage across the primary
winding is equal to source voltage. In this, the current flow through the load will be 1.732
times the secondary current and the feeder current will equal to the 1.732 times current
through the primary winding. Due to these high supply and load currents, it is recommended
to place transformer much closer to both source and load circuits.
In this, there exists no phase difference between the primary and secondary voltages.
The three phase voltages remains constant even with unbalanced load, thus allows
unbalanced loading.
The main advantage of this connection is if the one transformer is defective or removed for
service (open delta connection), then remaining two transformers continue to deliver thee
phase power at reduced load capacity.
Star – Star Connection
In this, both primary and secondary windings are connected in star fashion and also there
exist no phase difference between the primary and secondary voltages.
In this, current flowing through both primary and secondary windings are equal to the
currents of the lines to which they are connected (supply source and load). And voltages
between line phases on either end equal to 1.732 times respective winding voltages.
Due to neutral availability, it is well suited for three phase four wire system.
This type connection satisfactorily works if the load is balanced. But if the load is
unbalanced, the neutral point shift causes unequal phase voltages.
Large third harmonic voltages would appear in both primary and secondary windings
without the neutral tie. This may lead to the insulation failures.
This connection considerably generates interference with communication lines and hence
with this connection configuration, telephone lines cannot be run in parallel.
Due to these disadvantages, the star-star connection is rarely used and not employed in
practice.
Scott Connection
This connection is used to convert the three phase power into two phase power using two
single phase transformers.
One transformer called as main transformer having center or 50 percent tap and is connected
between the two lines of the three phase wires. The other transformer called as teaser
transformer having 86.6 tap and is connected between the third phase wire and 50 percent
tap of the main transformer.
The secondary winding of each transformer provides the phases of two phase systems.
The secondary voltages in the two transformers will be equal in magnitude if both
transformers are wound for equal number of turns on secondary. And produced voltages are
90 degrees out of phase with each other.
This connection is mainly used to supply the power to the two phase motor.
One of the transformers has centre taps both on the primary and secondary windings (Fig. 33.13)
and is known as the main transformer. It forms the horizontal member of the connection (Fig.
33.14).
The other transformer has a 0.866 tap and is known as teaser transformer. One end of both the
primary and secondary of the teaser transformer is joined to the centre taps on both primary and
secondary of the main trans- former respectively as shown in Fig. 33.14 (a). The other end A of
the teaser primary and the two ends B and C of the main transformer primary are connected to the
3-phase supply.
The voltage diagram is shown in Fig. 33.14 (a) where the 3-phase supply line voltage is assumed
to be 100 V and a transformation ratio of unity. For understanding as to how 3-phase
transformation results from this arrangement, it is desirable to think of the primary and secondary
vector voltages as forming geometrical TS¢ (from which this connection gets its name).
In the primary voltage T of Fig. 33.14 (a), EDC and EDB are each 50 V and differ in phase by
180°, because both coils DB and DC are on the same magnetic circuit and are connected in
opposition. Each side of the equilateral triangle represents 100 V. The voltage EDA being the
altitude of the equilateral triangle is equal to ( 3 / 2) ´ 100 = 86.6 V and lags behind the voltage
across the main by 90°. The same relation holds good in the secondary winding so that abc is a
symmetrical 3-phase system.
With reference to the secondary voltage triangle of Fig. 33.14 (b), it should be noted that for a load
of unity power factor, current Idb lags behind voltage Edbby 30° and Idc leads Edc by 30°. In other
words, the teaser transformer and each half of the main transformer, all operate at different power
factors.
Obviously, the full rating of the transformers is not being utilized. The teaser transformer operates
at only 0.866 of its rated voltage and the main transformer coils operate at cos 30° = 0.866 power
factor, which is equivalent to the main transformer’s coils working at 86.6 per cent of their kVA
rating. Hence the capacity to rating ratio in a T–T. connection is 86.6% — the same as
in V – V connection if two identical units are used, although heating in the two cases is not the
same.
If, however, both the teaser primary and secondary windings are designed for 86.6 volts only, then
they will be operating at full rating, hence the combined rating of the arrangement would become
(86.6 + 86.6)/(100 + 86.6)
= 0.928 of its total rating.* In other words, ratio of kVA utilized to that available would be 0.928
which makes this connection more economical than open-D with its ratio of 0.866.
Fig. 33.15 shows the secondary of the T – T connection with its different voltages based on a
nominal voltage of 100 V. As seen, the neutral point n is one third way up from point d. If
secondary voltage and current vector diagram is drawn for load power factor of unity, it will be
found that
1. current in teaser transformer is in phase with the voltage.
2. in the main transformer, current leads the voltage by 30° across one half but lags the voltage by
30° across the other half as shown in Fig. 33.14 (b).
Hence, when a balanced load of p.f. = cos f, is applied, the teaser current will lag or lead the voltage
by F while in the two halves of the main transformer, the angle between current and voltage will
be (30° – F) and (30° + F). The situation is similar to that existing in a V – V connection.
2. If main primary has N1 turns and main secondary has N2 turns, then main transformation ratio
is
3. If the load is balanced on one side, it is balanced on the other side as well.
4. Under balanced load conditions, main transformer rating is 15% greater than that of the teaser.
5. The currents in either of the two halves of main primary are the vector sum
MAGNETOSTRICTION
For parallel connection of transformers, primary windings of the Transformers are connected
to source bus-bars and secondary windings are connected to the load bus-bars.
Various conditions that must be fulfilled for the successful parallel operation of transformers:
1. Same voltage Ratio & Turns Ratio (both primary and secondary Voltage Rating is same).
2. Same Percentage Impedance and X/R ratio.
3. Identical Position of Tap changer.
4. Same KVA ratings.
5. Same Phase angle shift (vector group are same).
6. Same Frequency rating.
7. Same Polarity.
8. Same Phase sequence.
SPECIAL TRANSFORMER
AUTOTRANSFORMER
An autotransformer is a kind of electrical transformer where primary and secondary shares same
common single winding. So basically it’s a one winding transformer.
Autotransformer Theory
In an auto transformer, one single winding is used as primary winding as well as secondary
winding. But in two windings transformer two different windings are used for primary and
secondary purpose. A circuit diagram of auto transformer is shown below.
The primary winding AB from which a tapping at C is taken, such that CB acts as a secondary
winding. The supply voltage is applied across AB, and the load is connected across CB. The
tapping may be fixed or variable.When an AC voltage V1 is applied across AB, an alternating flux
is set up in the core, as a result, an emf E1 is induced in the winding AB. A part of this induced
emf is taken in the secondary circuit.
Let,
V1 = E1 and V2 = E2
As the secondary ampere-turns are opposite to primary ampere turns, so the current I2 is in phase
opposition to I1. The secondary voltage is less than the primary. Therefore current I2 is more than
the current I1. Therefore, the resulting current flowing through section BC is (I2 – I1)
Equation (1) and (2) shows that the ampere turns due to section BC and AC balance each other
which is characteristic of the transformer action.
The length of the conductor is proportional to the number of turns, and the cross section is
proportional to the product of current and number of turns.
Now, from the above figure (B) shown of the auto transformer, the weight of copper required in
an auto transformer is
Therefore
If the same duty is performed with an ordinary two winding transformer shown above in the
figure (A)
W0 = weight of copper on its primary winding + weight of copper on its secondary winding
Therefore,
Now, the ratio of the weight of the copper in an auto transformer to the weight of copper in an
ordinary transformer is given as
Therefore,
Saving of copper = K x weight of copper required for two windings of the transformer
Hence, saving in copper increases as the transformation ratio approaches to unity. Hence the auto
transformer is used when the value of K is nearly equal to unity.
Less costly
Better regulation
Low losses as compared to ordinary two winding transformer of the same rating.
Used only in the limited places where a slight variation of the output voltage from input voltage
is required.
It is used as a starter to give upto 50 to 60% of full voltage to the stator of a squirrel cage induction
motor during starting.
It is used to give a small boost to a distribution cable, to correct the voltage drop.
It is also used as a voltage regulator
Used in power transmission and distribution system and also in the audio system and railways.
INSTRUMENT TRANSFORMERS
Instrument transformers are of two types –
Primary of C.T. is having very few turns. Sometimes bar primary is also used. Primary is connected
in series with the power circuit. Therefore, sometimes it also called series transformer. The
secondary is having large no. of turns. Secondary is connected directly to an ammeter. As the
ammeter is having very small resistance. Hence, the secondary of current transformer operates
almost in short circuited condition. One terminal of secondary is earthed to avoid the large voltage
on secondary with respect to earth. Which in turns reduce the chances of insulation breakdown
and also protect the operator against high voltage. More ever before disconnecting the ammeter,
secondary is short circuited through a switch ‘S’ as shown in figure above to avoid the high voltage
build up across the secondary.
Sl.
Current Transformer (C.T.) Potential Transformer (P.T.)
No.
1 Connected in series with power circuit. Connected in Parallel with Power circuit.
Primary current and excitation vary over wide range Primary current and excitation variation are
5
with change of power circuit current restricted to a small range.
One terminal of secondary is earthed to avoid the One terminal of secondary can be earthed
6
insulation break down. for Safety.
TRANSFORMER RATINGS
Manufacturer designs transformer based on required voltage and current and specified them on the
nameplate of the transformer in terms of VA called the rating. It can be also said that the maximum
voltage and current that can be safely applied to transformer called the rating. The rating of
transformer depends upon temperature rise which depends upon losses taking place in the
transformer. Although temperature can be maintained within permissible limits by using the proper
cooling system. If the effectiveness of the cooling system is more then the rating of the transformer
will be more and vice versa. For a given cooling system rating of an electrical machine is indirectly
determined by the losses present in the machine.
In a transformer, losses are of two types
For any transformer rated input in KVA at the primary = rated output in KVA at secondary +
losses.
As transformer runs on very high efficiency its losses can be neglected and hence rated input in
KVA at the primary = rated output in KVA at secondary. From here we can say that rated KVA
marked on the nameplate of transformer refers to both the windings. i.e KVA rating for both the
primary and secondary winding is same.
The KVA rating mentioned on the nameplate of the transformer is load side KVA but only at full
load condition.
No transformer is truly an 'ideal transformer' and hence each will incur some losses, most of which
get converted into heat. If this heat is not dissipated properly, the excess temperature in transformer
may cause serious problems like insulation failure. It is obvious that transformer needs a cooling
system. Transformers can be divided in two types as (i) dry type transformers and (ii) oil immersed
transformers. Different cooling methods of transformers are -
For dry type transformers
Air Natural (AN)
Air Blast
For oil immersed tranformers
Oil Natural Air Natural (ONAN)
Oil Natural Air Forced (ONAF)
Oil Forced Air Forced (OFAF)
Oil Forced Water Forced (OFWF)
COOLING METHODS FOR DRY TYPE TRANSFORMERS
Air Natural Or Self Air Cooled Transformer
This method of transformer cooling is generally used in small transformers (upto 3 MVA). In this
method the transformer is allowed to cool by natural air flow surrounding it.
Air Blast
For transformers rated more than 3 MVA, cooling by natural air method is inadequate. In this
method, air is forced on the core and windings with the help of fans or blowers. The air supply
must be filtered to prevent the accumulation of dust particles in ventilation ducts. This method can
be used for transformers upto 15 MVA.
This method is used for oil immersed transformers. In this method, the heat generated in the core
and winding is transferred to the oil. According to the principle of convection, the heated oil flows
in the upward direction and then in the radiator. The vacant place is filled up by cooled oil from
the radiator. The heat from the oil will dissipate in the atmosphere due to the natural air flow
around the transformer. In this way, the oil in transformer keeps circulating due to natural
convection and dissipating heat in atmosphere due to natural conduction. This method can be used
for transformers upto about 30 MVA.
Oil Natural Air Forced (ONAF)
The heat dissipation can be improved further by applying forced air on the dissipating surface.
Forced air provides faster heat dissipation than natural air flow. In this method, fans are mounted
near the radiator and may be provided with an automatic starting arrangement, which turns on
when temperature increases beyond certain value. This transformer cooling method is generally
used for large transformers upto about 60 MVA.