MAXIMUM VOLTAGE DROP CALCULATION

PROJECT : RDP High mast - Parking area OWNER : SGP


CONTRACTOR : STE
AREA :Parking

mV = Appropriate voltage Drop ( in mV/amp/meter )


I = Current per phase (in amp)
L = Route Length (in meter) mV X I X L mV X P X L X10 3
Vd= or Vd=
P = Connected load (in KW's) 1000 1000 X 1.732 X V X P.F

V = Rated voltage
380
in volts
V
Vd = Total voltage drop in volts mV X P X L
or Vd=
Vd3 = Voltage drop in volts ( from Pole to Poles ) 1.732 X V X P.F

Pole 20 C) calculation
Circuit Details Cable size mV P L Vd3 Vd
F.P to 1st Pole 4CX 35 mm2 Cu 1.1 0.15 37 0.0103 0.01
1st Pole to 2nd Pole 4CX 25 mm2 Cu 1.5 0.15 52 0.0198 0.03
2nd Pole to 3rd Pole 4CX 25 mm2 Cu 1.5 0.15 29 0.0110 0.04
3rd Pole to 4th Pole 4CX 25 mm2 Cu 1.5 0.15 29 0.0110 0.05
4th Pole to 5th Pole 4CX 25 mm2 Cu 1.5 0.15 46 0.0175 0.07
5th Pole to 6th Pole 4CX 25 mm2 Cu 1.5 0.15 29 0.0110 0.08
6th Pole to 7th Pole 4CX 16 mm2 Cu 2.2 0.15 20 0.0111 0.09
7th Pole to 8th Pole 4CX 16 mm2 Cu 2.2 0.15 16 0.0089 0.10
8th Pole to 9th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.12
9th Pole to 10th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.15
10th Pole to 11th Pole 4CX 16 mm2 Cu 2.2 0.15 49 0.0273 0.17
11th Pole to 12th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.20
12th Pole to 13th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.22
13th Pole to 14th Pole 4CX 16 mm2 Cu 2.2 0.15 36 0.0201 0.24
14th Pole to 15th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.26
15th Pole to 16th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.29
16th Pole to 17th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.31
17th Pole to 18th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.33
18th Pole to 19th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.35
19th Pole to 20th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.38
% Voltage drop 0.17%
MAXIMUM VOLTAGE DROP CALCULATION

PROJECT : RDP High mast - Parking area OWNER : SGP


CONTRACTOR : STE
AREA :Parking

mV = Appropriate voltage Drop ( in mV/amp/meter )


I = Current per phase (in amp)
L = Route Length (in meter) mV X I X L mV X P X L X10 3
Vd= or Vd=
P = Connected load (in KW's) 1000 1000 X 1.732 X V X P.F

V = Rated voltage
220 V in volts
Vd = Total voltage drop in volts mV X P X L
or Vd=
Vd3 = Voltage drop in volts ( from Pole to Poles ) 1.732 X V X P.F

Pole 12 C) calculation
Circuit Details Cable size mV P L Vd3 Vd
F.P to 1st Pole 4CX 35 mm2 Cu 1.1 0.15 54 0.0150 0.02
1st Pole to 2nd Pole 4CX 16 mm2 Cu 2.2 0.15 37 0.0206 0.04
2nd Pole to 3rd Pole 4CX 16 mm2 Cu 2.2 0.15 34 0.0189 0.05
3rd Pole to 4th Pole 4CX 16 mm2 Cu 2.2 0.15 25 0.0139 0.07
4th Pole to 5th Pole 4CX 16 mm2 Cu 2.2 0.15 31 0.0173 0.09
5th Pole to 6th Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.11
6th Pole to 7th Pole 4CX 16 mm2 Cu 2.2 0.15 40 0.0223 0.13
7th Pole to 8th Pole 4CX 25 mm2 Cu 1.5 0.15 39 0.0148 0.15
8th Pole to 9th Pole 4CX 25 mm2 Cu 1.5 0.15 35 0.0133 0.16
9th Pole to 10th Pole 4CX 25 mm2 Cu 1.5 0.15 35 0.0133 0.17
10th Pole to 11th Pole 4CX 25 mm2 Cu 1.5 0.15 35 0.0133 0.19
11th Pole to 12th Pole 4CX 25 mm2 Cu 1.5 0.15 35 0.0133 0.20
% Voltage drop 0.09%
MAXIMUM VOLTAGE DROP CALCULATION

PROJECT : RDP High mast - Parking area OWNER : SGP


CONTRACTOR : STE
AREA :Parking

mV = Appropriate voltage Drop ( in mV/amp/meter )


I = Current per phase (in amp)
L = Route Length (in meter) mV X I X L mV X P X L X10 3
Vd= or Vd=
P = Connected load (in KW's) 1000 1000 X 1.732 X V X P.F

V = Rated voltage
220 V in volts
Vd = Total voltage drop in volts mV X P X L
or Vd=
Vd3 = Voltage drop in volts ( from Pole to Poles ) 1.732 X V X P.F

Pole 3 C) calculation
Circuit Details Cable size mV P L Vd3 Vd
F.P to 1st Pole 4CX 35 mm2 Cu 1.1 0.15 54 0.0150 0.02
1st Pole to 2nd Pole 4CX 16 mm2 Cu 2.2 0.15 24 0.0134 0.03
2nd Pole to 3rd Pole 4CX 16 mm2 Cu 2.2 0.15 54 0.0301 0.06
1.833333 % Voltage drop 0.03%
MAXIMUM VOLTAGE DROP CALCULATION

PROJECT : RDP High mast - Parking area OWNER : SGP


CONTRACTOR : STE
AREA :Parking

mV = Appropriate voltage Drop ( in mV/amp/meter )


I = Current per phase (in amp)
L = Route Length (in meter) mV X I X L mV X P X L X10 3
Vd= or Vd=
P = Connected load (in KW's) 1000 1000 X 1.732 X V X P.F

V = Rated voltage
220 V in volts
Vd = Total voltage drop in volts mV X P X L
or Vd=
Vd3 = Voltage drop in volts ( from Pole to Poles ) 1.732 X V X P.F

Pole 3 C) calculation
Circuit Details Cable size mV P L Vd3 Vd
F.P to 1st Pole 4CX 35 mm2 Cu 1.1 0.15 59 0.0164 0.02
1st Pole to 2nd Pole 4CX 25 mm2 Cu 1.5 0.15 39 0.0148 0.03
2nd Pole to 3rd Pole 4CX 25 mm2 Cu 1.5 3.20 62 0.5024 0.53
% Voltage drop 0.24%
MAXIMUM VOLTAGE DROP CALCULATION

PROJECT : RDP High mast - Parking area OWNER : SGP


CONTRACTOR : STE
AREA :Parking

mV = Appropriate voltage Drop ( in mV/amp/meter )


I = Current per phase (in amp)
L = Route Length (in meter) mV X I X L mV X P X L X10 3
Vd= or Vd=
P = Connected load (in KW's) 1000 1000 X 1.732 X V X P.F

V = Rated voltage
220 V in volts
Vd = Total voltage drop in volts mV X P X L
or Vd=
Vd3 = Voltage drop in volts ( from Pole to Poles ) 1.732 X V X P.F

Pole 8 C) calculation
Circuit Details Cable size mV P L Vd3 Vd
F.P to 1st Pole 4CX 35 mm2 Cu 1.1 0.10 41 0.0076 0.01
1st Pole to 2nd Pole 4CX 25 mm2 Cu 1.5 0.15 65 0.0247 0.03
2nd Pole to 2nd Pole to4CX 25 mm2 Cu 1.5 0.15 39 0.0148 0.05
3rd Pole to 4th Pole 4CX 25 mm2 Cu 1.5 0.15 37 0.0141 0.06
4th Pole to 5th Pole 4CX 25 mm2 Cu 1.5 0.15 41 0.0156 0.08
1st Pole to 2nd Pole 4CX 16 mm2 Cu 2.2 0.10 37 0.0137 0.09
2nd Pole to 2nd Pole to4CX 16 mm2 Cu 2.2 0.10 37 0.0137 0.10
3rd Pole to 4th Pole 4CX 16 mm2 Cu 2.2 0.15 19 0.0106 0.11
% Voltage drop 0.05%
MAXIMUM VOLTAGE DROP CALCULATION

PROJECT : RDP High mast - Parking area OWNER : SGP


CONTRACTOR : STE
AREA :Parking

mV = Appropriate voltage Drop ( in mV/amp/meter )


I = Current per phase (in amp)
L = Route Length (in meter) mV X I X L mV X P X L X10 3
Vd= or Vd=
P = Connected load (in KW's) 1000 1000 X 1.732 X V X P.F

V = Rated voltage
380 V in volts
Vd = Total voltage drop in volts mV X P X L
or Vd=
Vd3 = Voltage drop in volts ( from Pole to Poles ) 1.732 X V X P.F

Pole 17 C) calculation
Circuit Details Cable size mV P L Vd3 Vd
F.P to 1st Pole 4CX 35 mm2 Cu 1.1 0.15 9 0.0025 0.00
1st Pole to 2nd Pole 4CX 16 mm2 Cu 2.2 0.15 41 0.0228 0.03
2nd Pole to 3rd Pole 4CX 16 mm2 Cu 2.2 0.15 29 0.0162 0.04
3rd Pole to 4th Pole 4CX 16 mm2 Cu 2.2 0.15 42 0.0234 0.06
4th Pole to 5th Pole 4CX 16 mm2 Cu 2.2 0.15 42 0.0234 0.09
5th Pole to 6th Pole 4CX 16 mm2 Cu 2.2 0.15 42 0.0234 0.11
6th Pole to 7th Pole 4CX 16 mm2 Cu 2.2 0.15 27 0.0150 0.13
7th Pole to 8th Pole 4CX 16 mm2 Cu 2.2 0.15 31 0.0173 0.14
8th Pole to 9th Pole 4CX 16 mm2 Cu 2.2 0.15 54 0.0301 0.17
9th Pole to 10th Pole 4CX 16 mm2 Cu 2.2 0.15 54 0.0301 0.20
10th Pole to 11th Pole 4CX 16 mm2 Cu 2.2 0.15 42 0.0234 0.23
11th Pole to 12th Pole 4CX 16 mm2 Cu 2.2 0.15 42 0.0234 0.25
12th Pole to 13th Pole 4CX 16 mm2 Cu 2.2 0.15 42 0.0234 0.27
13th Pole to 14th Pole 4CX 16 mm2 Cu 2.2 0.15 20 0.0111 0.29
14th Pole to 15th Pole 4CX 16 mm2 Cu 2.2 0.15 54 0.0301 0.32
15th Pole to 16th Pole 4CX 16 mm2 Cu 2.2 0.15 54 0.0301 0.35
16th Pole to 17th Pole 4CX 16 mm2 Cu 2.2 0.15 54 0.0301 0.38
2.135294 % Voltage drop 0.17%
MAXIMUM VOLTAGE DROP CALCULATION

PROJECT : RDP High mast - Parking area OWNER : SGP


CONTRACTOR : STE
AREA :Parking

mV = Appropriate voltage Drop ( in mV/amp/meter )


I = Current per phase (in amp)
L = Route Length (in meter) mV X I X L mV X P X L X10 3
Vd= or Vd=
P = Connected load (in KW's) 1000 1000 X 1.732 X V X P.F

V = Rated voltage380
in volts
V
Vd = Total voltage drop in volts mV X P X L
or Vd=
Vd3 = Voltage drop in volts ( from Pole to Poles ) 1.732 X V X P.F

Pole 14 C) calculation
Circuit Details Cable size mV P L Vd3 Vd
F.P to 1st Pole 4CX 35 mm2 Cu 1.1 0.15 15 0.0042 0.00
1st Pole to 2nd Pole 4CX 25 mm2 Cu 1.5 0.15 33 0.0125 0.02
2nd Pole to 3rd Pole 4CX 25 mm2 Cu 1.5 0.15 33 0.0125 0.03
3rd Pole to 4th Pole 4CX 25 mm2 Cu 1.5 0.15 56 0.0213 0.05
4th Pole to 5th Pole 4CX 25 mm2 Cu 1.5 0.15 14 0.0053 0.06
5th Pole to 6th Pole 4CX 25 mm2 Cu 1.5 0.15 55 0.0209 0.08
6th Pole to 7th Pole 4CX 25 mm2 Cu 1.5 0.10 29 0.0073 0.08
7th Pole to 8th Pole 4CX 25 mm2 Cu 1.5 0.10 29 0.0073 0.09
8th Pole to 9th Pole 4CX 25 mm2 Cu 1.5 0.10 29 0.0073 0.10
9th Pole to 10th Pole 4CX 25 mm2 Cu 1.5 0.10 29 0.0073 0.11
10th Pole to 11th Pole 4CX 25 mm2 Cu 1.5 0.10 29 0.0073 0.11
11th Pole to 12th Pole 4CX 25 mm2 Cu 1.5 0.10 29 0.0073 0.12
12th Pole to 13th Pole 4CX 25 mm2 Cu 1.5 0.10 29 0.0073 0.13
13th Pole to 14th Pole 4CX 25 mm2 Cu 1.5 0.15 29 0.0110 0.14
1.471429 % Voltage drop 0.06%
MAXIMUM VOLTAGE DROP CALCULATION

PROJECT : RDP High mast - Parking area OWNER : SGP


CONTRACTOR : STE
AREA :Parking

mV = Appropriate voltage Drop ( in mV/amp/meter )


I = Current per phase (in amp)
L = Route Length (in meter) mV X I X L mV X P X L X10 3
Vd= or Vd=
P = Connected load (in KW's) 1000 1000 X 1.732 X V X P.F

V = Rated voltage
380 V in volts
Vd = Total voltage drop in volts mV X P X L
or Vd=
Vd3 = Voltage drop in volts ( from Pole to Poles ) 1.732 X V X P.F

Pole 10 C) calculation
Circuit Details Cable size mV P L Vd3 Vd
F.P to 1st Pole 4CX 35 mm2 Cu 1.1 0.15 64 0.0178 0.02
1st Pole to 2nd Pole 4CX 16 mm2 Cu 2.2 0.15 24 0.0134 0.03
2nd Pole to 3rd Pole 4CX 16 mm2 Cu 2.2 0.15 37 0.0206 0.05
3rd Pole to 4th Pole 4CX 16 mm2 Cu 2.2 0.15 29 0.0162 0.07
4th Pole to 5th Pole 4CX 16 mm2 Cu 2.2 0.15 29 0.0162 0.08
5th Pole to 6th Pole 4CX 16 mm2 Cu 2.2 0.15 12 0.0067 0.09
6th Pole to 7th Pole 4CX 16 mm2 Cu 2.2 0.15 29 0.0162 0.11
7th Pole to 8th Pole 4CX 16 mm2 Cu 2.2 0.10 44 0.0163 0.12
8th Pole to 9th Pole 4CX 16 mm2 Cu 2.2 0.10 24 0.0089 0.13
9th Pole to 10th Pole 4CX 16 mm2 Cu 2.2 0.10 50 0.0186 0.15
2.09 % Voltage drop 0.07%