Professional Documents
Culture Documents
Mim SPC GN Mep - FF 001 00
Mim SPC GN Mep - FF 001 00
TABLE OF CONTENTS
FIREFIGHTING WORKS
1 INDEX
24 OFFICE BLDG, EGYPT Fire fighting
No. Valves
m Piping
GENERAL
24 OFFICE BLDG, EGYPT Fire fighting
Sprinklers
GENERAL
24 OFFICE BLDG, EGYPT Fire fighting
Control
Panel
No. Alarm Ball, Flashing Lamp, Manual Release and Abort Switch
Same as strobe-horn unit above.
No. Nozzles
GENERAL
24 OFFICE BLDG, EGYPT Fire fighting
TYCO USA
Viking Corp USA
Sprinklers and Accessories Globe Fire Sprinkler Corp. USA
Victaulic USA
Triple R USA
Test and Drain Connection
AGF USA
Bavaria Egypt
Fire Extinguishers Naffco UAE
Bavaria Egypt
Fire Cabinets and Fire Hose Reels Naffco UAE
Giacomini Italy
Kennedy UK
Hose Valves Potter-Roemer USA
GENERAL
24 OFFICE BLDG, EGYPT Fire fighting
GENERAL
24 OFFICE BLDG, EGYPT Fire fighting
PART 1 GENERAL
Products furnished but not installed: Include sprinkler head cabinet with
spare sprinkler heads.
15100 Valves
15145 Hangers and Supports
220000 Plumbing Works
210700 Steel Pipes and Fittings for Fire Protection Systems
1.5 DEFINITIONS
1.5.1 Pipe Sizes: used in this Specification are Nominal Pipe Size (NPS).
1.5.2 Other Definitions for fire protection systems are listed in NFPA 13 and 14
Section 210000
24 OFFICE BLDG, EGYPT Fire fighting
Standards.
1.5.3 Working Plans as used in this Section means those documents (including
drawings and calculations) prepared pursuant to the requirements contained
in NFPA 13 for obtaining approval of the Engineer.
1.6 SUBMITTALS
Product Data for each type of sprinkler head, valve, piping specialty, fire
protection specialty, fire department connection, hose valves, hose reel
and hose cabinet.
Computer Calculation for sprinkler system.
Shop Drawings prepared in accordance with NFPA 13 identified as
"Working Plans", showing layout and connections
Record Drawings: At project close-out, submit drawings of installed
systems in accordance with requirements of Division-1.
Maintenance Data for each type of sprinkler head, valve, piping
specialty, fire protection specialty, fire department connection, hose
valves, hose reel and hose cabinet, for inclusion in operation and
maintenance manual specified in Division-1.
Samples: Submit catalogs and representative samples of all materials to
be used in the work.
Install W elder’s Quali ficati on Certi ficates
1.7.2 Qualifications for Welding Processes and Operators: Comply with the
requirements of AWS D10.9, Specifications for Qualifications of Welding
Procedures and Welders for Piping and Tubing, Level AR-3".
Section 210000
24 OFFICE BLDG, EGYPT Fire fighting
1.10.1 Valve Wrenches: Furnish to Employer, 2 valve wrenches for each type of
valves installed.
1.10.2 Sprinkler Heads and Cabinets: Furnish extra sprinkler heads of each
style included in the project as indicated on drawings. Furnish each style
with its own sprinkler head cabinet and special wrenches as specified in
this Section.
PART 2 PRODUCTS
2.1 MANUFACTURERS
Manufacturers are subject to compliance with the specification
requirements of this section.
Section 210000
24 OFFICE BLDG, EGYPT Fire fighting
2.3.1 Welding Materials: Comply, with Section II, Part C, ASME Boiler and
Pressure Vessel Code for welding materials appropriate for the wall
thickness and chemical analysis of the pipe being welded.
2.3.2 Gasket Materials: Thickness, material and type suitable for design
temperatures and pressures.
2.3.3 Sealing Ring Materials: Shall be rubber sealing rings conforming to
ISO 2531 Standard.
Valves used within the fire protection systems shall be UL listed, rated
1200 kPa working pressure.
2.4.1 Gate Valves - 50 mm and Smaller: Body and bonnet of cast bronze,
1200 kPa cold water working pressure-non-shock, threaded ends, solid
wedge, outside screw and yoke, rising stem, screw-in bonnet, and malleable
iron handwheel. Valves shall be capable of being repacked under pressure,
with valve wide open. UL listed.
2.4.2 Gate Valves - 65 mm and Larger: Iron body; bronze mounted, 1200 kPa
cold water working pressure-non-shock. Valves shall have solid taper
wedge; outside screw and yoke, rising stem; flanged bonnet, with body and
bonnet conforming to ASTM A 126 Class B; replaceable bronze wedge
facing rings; flanged ends; and a packing assembly consisting of a cast iron
gland flange, brass gland, packing, bonnet, and bronze bonnet bushing.
Valves shall be capable of being repacked under pressure, with valve wide
open. UL listed.
2.4.3 Swing Check Valves: 1200 kPa cold water working pressure, cast iron
body and bolted cap conforming to ASTM A 126, Class B; non slamming
horizontal swing, with a malleable iron disc and flanged ends. Valve shall
be capable of being refitted while the valve remains in the line. UL listed.
2.5.1 Interior Automatic Air Vent: Float type hot pressed brass MS58 consists
of two halves screwed together and fitted with O-ring seal, with rubber valve
seal, plastic float, vacuum breaker complete with automatic self-sealing
spring loaded brass check valve stainless steel spring and catch ring rated for
1200 kPa working pressure.
Section 210000
24 OFFICE BLDG, EGYPT Fire fighting
2.6 SPRINKLERS
2.6.2 Sprinkler Head Cabinet and Wrench: Finished steel cabinet suitable for
wall mounting, with hinged cover and space for spare sprinkler heads plus
sprinkler head wrench. Provide separate cabinets for each style sprinkler
head on the project.
Flush fire department inlet connection, UL listed, cast brass body with drop
clappers, size shall be 100 mm outlet and two 65 mm female inlets each
provided with BS 336 instantaneous adaptor supplied by the fire
department connection manufacturer.
Section 210000
24 OFFICE BLDG, EGYPT Fire fighting
2.9.1 General: Types and sizes shall mate and match piping and equipment
connections.
Provide brackets for extinguishers not located in cabinets and for those
located in cabinets, where indicated or required.
General: Provide fire cabinets for locations indicated, of suitable size for
housing fire extinguishers, hose reels, valves, fire department connections and
accessories of types and a capacity indicated, in colors and finishes approved by
the Engineer from manufacturer's standard, which comply with Drawings.
Type FC1: Cabinet box fully recessed in walls of sufficient depth to suit style
of trim indicated, sized to contain fire hose reel and two fire extinguishers.
Type FC2: Cabinet box fully exposed and mounted directly on wall,
painted red, sized to contain fire hose reel and two fire extinguishers.
Type FC3: Cabinet box fully recessed in wall, with full glass door, sized
to contain fire hose valve, fire hose and branch pipe.
Trim Style: Fabricate trim in one piece with corners mitred, welded and
ground smooth.
Exposed Trim: One-piece combination trim and perimeter door frame
overlapping surrounding wall surface with exposed trim face and wall
return at outer edge (backbend).
Trim Metal: Same metal as door.
Baked Enamel Finish: Immediately after cleaning and pre- treatment, apply
two-coat baked enamel finish consisting of prime coat and thermosetting
topcoat complying with paint manufacturer for application and baking to have a
dry thickness of 2.0 mils.
General: Provide fire extinguishers for each extinguisher cabinet and other
locations indicated, in colors and finishes approved by the Engineer from
manufacturer's standard, which comply with requirements of governing
authorities.
PART 3 EXECUTION
3.1 EXAMINATION
Examine rough in for fire cabinets and sprinklers to verify actual locations
of piping connections prior installing.
Provide pressure gauges with a connection not less than 6 mm and having a
soft metal seated globe valve, arranged for draining pipe between gauge
and valve.
Paint piping with two (2) coats of red lead and three (3) coats of red paint.
3.3.2 Threaded Joints: Conform to ANSI B1.20.1, tapered pipe threads for
field cut threads. Join pipe, fittings, and valves as follows:
Note the internal length of threads in fittings or valve ends, and proximity
of internal seat or wall, to determine how far pipe should be threaded into
joint. Align threads at point of assembly. Apply appropriate tape or thread
compound to the external pipe threads. Assemble joint to appropriate
thread depth. When using a wrench on valves place the wrench on the
valve end into which the pipe is being threaded. Do not use pipe with
threads which are corroded, or damaged. If a weld opens during cutting or
threading operations, that portion of pipe shall not be used.
Section 210000
24 OFFICE BLDG, EGYPT Fire fighting
Groove pipe and assemble joints with grooved coupling, gasket, lubricant,
and bolts according to coupling and fitting of manufacturers written
instructions.
Where there is more than one control valve, provide permanently marked
identification signs indicating the portion of the system controlled by each
valve.
Examine walls for thickness and framing for cabinets to verify cabinet
depth and mounting prior to cabinet installation. Cabinets shall be built
into walls unless otherwise indicated on Drawings.
Install items included in this section in locations and at mounting heights
indicated, or if not indicated, at heights to comply with applications of
governing authorities.
Prepare recesses in walls for fire cabinets as required by type and size of
cabinet and style of trim and to comply with manufacturer's instructions.
Securely fasten mounting brackets and fire cabinets to structure, square and
plumb, to comply with manufacturer's instructions.
Section 210000
24 OFFICE BLDG, EGYPT Fire fighting
Provide a frame and glazed block plan showing the areas protected and
positions of alarm valve. Locate the block plan as directed by the Engineer.
Ensure that the components of the systems include for the necessary
provisions to transfer visual and audible remote alarm signals. Carry out
connections to the remote alarm contacts.
Flush, test, and inspect sprinkler and hose reel piping systems in
accordance with NFPA 13.
Replace piping system components, which do not pass the test procedures
specified, and retest repaired portion of the system.
Hand over to the Employer the spare parts and tools required for operation
and maintenance as recommended by the manufacturer to cover a working
period of two years. In addition, submit to the Employer, for approval, a
priced list of the above recommended spare parts and tools for an additional
period of three years. The list should nominate the above-required items.
The approved list shall be part from the operation and maintenance
manuals.
SECTION
210700
PART 1 GENERAL
This section specifies black or galvanized steel pipes, malleable iron fittings
and welded fittings as required by the Contract.
Steel pipes shall be installed and tested as part of integrated fire protection
systems.
Section 210700
24 OFFICE BLDG, EGYPT Fire fighting
ASTM No.
B 16.3 Malleable-Iron Screwed Fittings
B 16.5 Cast-Steel Flanged Fittings
B 16.9 Wrought-Steel Butt-Welding Fittings
B 16.11 Forged-Steel Socket-Welding Fittings
1.4 SUBMITTALS
1.5.1 Inspection and Test by the Manufacturer: Pipe and fittings shall be
thoroughly inspected by the manufacturer before delivery. The manufacturer
shall make all tests as specified herein and the results of the tests shall be
furnished to the Engineer upon request. The manufacturer may use his own
or other suitable facilities for the performance of the inspection and test
requirements specified herein. Fittings shall be suitably inspected for
soundness and brittleness.
1.5.2 Testing: Materials and installed work may require testing and retesting at any
time during the progress of the Works. Tests, including retesting of rejected
materials or installed works, shall be done at the Contractor's expense.
Section 210700
24 OFFICE BLDG, EGYPT Fire fighting
Section 210700
24 OFFICE BLDG, EGYPT Fire fighting
PART 2 PRODUCTS
2.1 MATERIALS
Steel pipes shall be tested for flattering, bending, and internal hydrostatic
pressure of 50 kg/cm2 in accordance with the requirements of ASTM A 53.
Acceptable tolerances for thickness and weights shall not exceed those
specified by ASTM A 53.
2.1.2 Fittings: Screwed fittings, white core malleable cast iron conforming to
ASA B 16.3, Class 150 standard pattern.
PART 3 EXECUTION
Section 210700
24 OFFICE BLDG, EGYPT Fire fighting
Installation of steel pipes and fittings shall comply with requirements of the
Division 15 Sections.
3.2.1 Threaded Joints: Tapered pipe threads for field-cut threads. Join pipe
fittings and valves as follows:
Note the internal length of threads in fittings or valve ends, and proximity of
internal seat or wall, to determine how far pipe should be threaded into joint.
Align threads at point of assembly.
Assemble joint and wrench tight. Wrench on valve shall be on the valve end
into which the pipe is being threaded.
3.2.2 Flanged Joints: Flanged joints shall be furnished with bolts, nuts, gaskets and
all necessary accessories. Bolts shall be of the best quality of steel with
hexagonal head, washers and hexagonal nuts. Bolt lengths shall be so that, after
erection, the bolt shall not protrude through the nut more than one to three
threads. Gaskets shall be one piece, full-face type of best quality cloth inserted
sheet rubber at least 3 mm thick. Align surfaces of flanges parallel. Assemble
joints by sequencing bolt tightening to make initial contact of flanges and gaskets
as flat and parallel as possible. Use suitable lubricants on bolt threads. Tighten
bolts gradually and uniformly with a torque wrench.
3.2.3 Welded Joints: Employ, qualified welders and submit welders qualification
certificate to the Engineer. Comply with the requirements of the ASME
Boiler and Pressure Vessel Code. Submit welding procedures and the
technical data and specification for electrodes.
Prepare end of parts to be welded in compliance with the joint design set up
Section 210700
24 OFFICE BLDG, EGYPT Fire fighting
Use proper machine tools for cutting. Thoroughly clean rust, scale, paint, oil or
grease from welding faces and adjoining surfaces for a distance of 20 mm from
edge of the welding groove or from the toe of the fillet in the case of socket-
welded or fillet-welded joints. In addition, remove any contaminating or surface-
coating material that may reach the weld area as a result of weld heat.
Layout and assemble various component parts. Carefully space, align and
tack-weld together the parts to be jointed so that final welded assembly will
conform to the required dimensions within acceptable tolerances (± 3 mm
maximum end-to-end tolerance). Ensure that a sufficient number and
suitable proportions of tack welds are provided to hold the parts in place
during ordinary handling.
Apply sufficient number of weld passes to suit the material, thickness and
position of parts to be welded. Start welding at the bottom and progress
upward, except for thin-walled material.
Section 210700
24 OFFICE BLDG, EGYPT Fire fighting
SECTION
212000
CARBON DIOXIDE EXTINGUISHING SYSTEMS
PART 1 GENERAL
1.2 DESCRIPTION
This section covers the carbon dioxide fire extinguishing systems in the main
electric equipment rooms.
Comply with the applicable requirements set forth in the latest edition of the
listed standards for the design, equipment, installation, testing and
maintenance of extinguishing agent:
1.4 SUBMITTALS
1.4.1 Field installation layout detailing the location of agent storage tanks,
directional valves, pipe runs including pipe sizes and lengths, control
panel(s), detectors, manual pull stations, abort stations, audible and visual
alarms, etc.
1.4.2 Auxiliary details and information such as maintenance panels, door holders,
special sealing requirements and equipment shutdowns.
1.4.3 Separate layouts and isometric details for each protected area.
1.4.4 Electrical layout drawings showing the locations of devices and include
point-to-point conduit runs.
1.4.5 Internal control panel wiring diagram including power supply requirements
SECTION 212000
24 OFFICE BLDG, EGYPT Fire fighting
1.4.8 Calculations for battery standby power supply taking into consideration the
power requirements of alarms, initiating devices and auxiliary components
under full load conditions.
1.4.10 Operation and Maintenance Manual for the systems and equipment.
1.6 APPROVALS
All basic equipment shall be formally approved by at least one international
recognized testing laboratory such as: VDS, CNPP, LPC, UL or FM.
PART 2 PRODUCTS
2.1 PIPES AND FITTINGS
2.1.1 Pipes: Comply with NFPA 12, section 2-2.1, seamless steel pipes to ASTM
A53 Grade B. Sch. 40 for ¾" and smaller, Sch. 80 for 1" and larger.
Nonmetalic pipes are not allowed.
2.1.2 Fittings: Comply with NFPA 12, fittings up to 2" shall be malleable iron
fittings rated 2000 kPa (300 lb class) to ASTM A-197. Fittings rated 1000
kPa are not allowed. Forged steel fittings shall be used for larger sizes.
2.1.3 Jointing: Threaded, welded and flanged as long as they conform to the
above requirements. Do not use hole-cut fittings.
2.4 DETECTORS
Provide optical smoke detectors in protected areas. Except for the generator
room where flame and heat detector are to be used.
Each detector base or the detector it self shall have a flashing status
indicating LED for visual supervision. When the detector is activated, the
flashing LED will latch on steady and at full brilliance until it is reset by the
reset switch, from the control panel.
The optical smoke detectors shall be sensitive to visible and invisible products of
combustion.
Provide wall mounted, 18 gauge metal cabinet suitable for electrical circuits with
a hinged, locked door painted with approved finish, 220 VAC, 50 Hz, audible
and visual "Trouble" sign event a loss of A/C, rectified or battery power
occurred, self-contained 24 VDC emergency power supply including a battery
charger and rechargeable batteries with a minimum rating of 6 Amp hours.
SECTION 212000
24 OFFICE BLDG, EGYPT Fire fighting
Dual action device for manual discharge of the agent. The manual actuation
shall bypass the time delay and abort functions, shall cause the system
discharge and shall cause all alarm and shutdown devices to operate in the
same manner as if the system had operated automatically.
PART 3 EXECUTION
3.1 INSTALLATION
All installation shall be in accordance with manufacturer's written
instruction, and NFPA Standards.
used in the system. Include in the manual checklists and procedures for
emergency situations, troubleshooting techniques and maintenance
operations and procedures.
Upon completion of each system, provide six (6) copies of system "Record"
drawings to the Engineer. The drawings shall show actual installation details
including all equipment locations (i.e. control panel(s), agent container(s),
detectors, alarms, manuals and aborts, etc.), as well as piping and conduit
routing details. Show all room or facilities modifications, including door
and/or damper installations completed. Provide one (1) copy of reproducible
engineering drawings plus one (1) copy of electronic files reflecting all
actual installation details.
The tests shall demonstrate that the entire control system functions as
designed and intended. All circuits shall be tested: automatic actuation,
manual actuation, HVAC and power shutdowns, audible and visual alarm
devices, and manual override of agent container weight supervision.
Supervision of all panel circuits, including AC power and battery power
supplies, shall be tested and qualified.
3.8 WARRANTY
All system components furnished, and installed under this contract, shall be
SECTION 212000
24 OFFICE BLDG, EGYPT Fire fighting
guaranteed against defects in design, materials and workmanship for the full
warranty period which is standard with the manufacturer, but in no case less
than one (1) year from the date of system acceptance.
Hand over to the Employer the spare parts and tools required for operation
and maintenance as recommended by the manufacturer to cover a working
period of two years. In addition, submit to the Employer, for approval, a
priced list of the above recommended spare parts and tools for an additional
period of three years. The list should nominate the above-required items.
The approved list shall be part from the operation and maintenance manuals.
Hand over to the Employer the spare parts and tools required for operation
and maintenance as recommended by the manufacturer to cover a working
period of two years. In addition, submit to the Employer, for approval, a
priced list of the above recommended spare parts and tools for an additional
period of three years. The list should nominate the above-required items.
The approved list shall be part from the operation and maintenance manuals.
END OF SECTION212000
SECTION 212000
24 OFFICE BLDG, EGYPT Fire fighting
SECTION
212200
PART 1 GENERAL
1.2 DESCRIPTION
This section covers the clean agent fire extinguishing systems in the IT rooms and
the control rooms.
Comply with the applicable requirements set forth in the latest edition of the
listed standards for the design, equipment, installation, testing and
maintenance of clean agent extinguishing agent:
1.4 SUBMITTALS
1.4.1 Field installation layout detailing the location of agent storage tanks, pipe
runs including pipe sizes and lengths, control panel(s), detectors, manual pull
stations, abort stations, audible and visual alarms, etc.
1.4.2 Auxiliary details and information such as maintenance panels, door holders,
special sealing requirements and equipment shutdowns.
1.4.3 Separate layouts and isometric details for each protected area.
1.4.4 Electrical layout drawings showing the locations of devices and include
point-to-point conduit runs.
1.4.5 Internal control panel wiring diagram including power supply requirements
and field wiring termination points.
SECTION 212200
24 OFFICE BLDG, EGYPT Fire fighting
1.4.8 Calculations for battery standby power supply taking into consideration the
power requirements of alarms, initiating devices and auxiliary components
under full load conditions.
1.4.10 Operation and Maintenance Manual for the systems and equipment.
SECTION 212200
24 OFFICE BLDG, EGYPT Fire fighting
Energize an alarm horn/strobe device located outside protected areas,
Start time-delay sequence (not to exceed 30 second),
Enable system abort sequence,
Shut down the HVAC system and/or close dampers.
After completion of the time-delay sequence, the agent shall be
discharged and the following shall occur:
PART 2 PRODUCTS
2.1.1 Pipes: Comply with NFPA 2001, section 2-2.1; seamless galvanized steel pipes
schedule 40 to ASTM A53 Grade B. Nonmetalic pipes are not allowed.
2.1.2 Fittings: Comply with NFPA 2001, section 2-2.3, malleable iron fittings rated
2000 kPa (300 lb class) to ASTM A-197. Fittings rated 1000 kPa are not allowed.
2.1.3 Jointing: Threaded, welded, flanged and grooved as long as they conform
to the above requirements. Do not use hole-cut fittings.
SECTION 212200
24 OFFICE BLDG, EGYPT Fire fighting
switch for visual and electric supervision of the cylinder pressure. Wire the
low pressure switch to the control panel to provide an audible and visual
"Trouble" alarm in the event of the cylinder pressure drops below 18 bars.
Provide for each cylinder an automatic pressure relief which operates when
internal temperature exceeds 65º C.
Provide for each protected area separate cylinder bank or single cylinder as
indicated on Drawings with a separate agent pipe work.
2.5 DETECTORS
Provide wall mounted, 18 ga. metal cabinet suitable for electrical circuits with a
hinged, locked door painted with approved finish, 220 VAC, 50 HZ, audible and
visual "Trouble" signals event a loss of A/C, rectified or battery power occurred,
self-contained 24 VDC emergency power supply including a battery charger and
rechargeable batteries with a minimum rating of 6 Amp hours.
SECTION 212200
24 OFFICE BLDG, EGYPT Fire fighting
Verified detection
Parallel wired agent release modules
Class "A" wiring of detection and agent release circuits.
Roll up type, fiber glass installed in such a manner that upon receiving a
signal from the control panel, in case of fire, the holding mechanism will let
loose the curtain to fall through a "U" channel guide.
Seal all openings in walls, floors or ceilings within the protected areas with 2
hours rated fireproof sealant.
SECTION 212200
24 OFFICE BLDG, EGYPT Fire fighting
PART 3 EXECUTION
3.1 INSTALLATION
Check the entire system after the system installation has been completed by
qualified, trained personnel in accordance with the manufacturer's recommended
procedures and NFPA standards:
Check for proper mounting and installation all containers and distribution
piping.
Test for proper connection, continuity and resistance to ground all
electrical wiring.
Functionally test the complete system in the presence of the Engineer or
his representative and all functions, including system and equipment
interlocks, must be operational at least five (5) days prior to the final
acceptance tests.
Test each detector in accordance with the manufacturer's recommended
procedures, and test values recorded.
All system and equipment interlocks, such as door release devices,
audible and visual devices, equipment shutdowns, local and remote
alarms, etc., shall function as required and designed.
Test each control panel circuit for trouble by inducing a trouble
condition into the system.
SECTION 212200
24 OFFICE BLDG, EGYPT Fire fighting
Upon completion of each system, provide six (6) copies of system "Record"
drawings to the Engineer. The drawings shall show actual installation details
including all equipment locations (i.e. control panel(s), agent container(s),
detectors, alarms, manuals and aborts, etc.), as well as piping and conduit
routing details. Show all room or facilities modifications, including door
and/or damper installations completed. Provide one (1) copy of reproducible
engineering drawings plus one (1) copy of electronic files reflecting all
actual installation details.
The tests shall demonstrate that the entire control system functions as
designed and intended. All circuits shall be tested: automatic actuation,
A.R.M., manual actuation, HVAC and power shutdowns, audible and visual
alarm devices, manual override of abort functions and agent container
pressure supervision. Supervision of all panel circuits, including AC power
and battery power supplies, shall be tested and qualified.
SECTION 212200
24 OFFICE BLDG, EGYPT Fire fighting
computer program. All testing shall be in accordance with NFPA 2001.
Copies of the successful test results shall be submitted to the Engineer for
record.
Provide two (2) inspections of each system, installed under this contract,
during the one-year warranty period. The first inspection shall be at the six-
month interval, and the second inspection at the twelve-month interval, after
system acceptance. Inspections shall be conducted in accordance with the
manufacturer's guidelines and shall comply with the recommendations of
NFPA 2001.
3.8 WARRANTY
All system components furnished, and installed under this contract, shall be
guaranteed against defects in design, materials and workmanship for the full
warranty period which is standard with the manufacturer, but in no case less
than one (1) year from the date of system acceptance.
SECTION 212200
Fire fighting 24 OFFICE BLDG, EGYPT
B)GROOVED FITTINGS:
1. Victaulic (U.S.A)
2. Grinnell (U.S.A)
3. Smith COOPER (U.S.A)
4. Lede (CHINA)
5.Mech (CHINA)
6. 4.WPT (UL/FM) (CHINA)
7. Junt (CHINA) UL/FM
Or Approved Equal
C)THREADED FITTINGS:
1. TM (THAILAND)
2. Siam (THAILAND)
3. BIS (THAILAND)
Or Approved Equal
2-VALVES
1. Nibbco (U.S.A)
2. Kennedy (U.S.A)
3. CLA-VAL (U.S.A)
4. Viking (U.S.A)
5. Reliable (U.S.A)
6.Victaulic (U.S.A)
7.FIREWALL (U.S.A)
8.Schield (UL/FM) (UK)
9.WEFLO(UL/FM) (UK)
Or Approved Equal
3-AUTOMATIC SPRINKLERS
1. Reliable (U.S.A)
2. Viking (U.S.A)
3. Globe (U.S.A)
4. Tyco (U.S.A)
Or Approved Equal
4-SIAMESE CONNECTION
1. Giacomini (ITALY)
2. Potter (U.S.A)
Or Approved Equal
5-SUPERVISORY S.W
1. Potter (U.S.A)
2. System Sensor (U.S.A)
Or Approved Equal
6-PRESSURE GAUGE
1. Reliable (U.S.A)
2. AGF (U.S.A)
3.WEFLO(UL/FM) (UK)
Or Approved Equal
8-FIRE EXTINGUISHERS
1. Bavaria (EGYPT)
2. Naffco (U.A.E)
Or Approved Equal
9-PAINTING
1. Jotun (EGYPT)
2. Sika (EGYPT)
Or Approved Equal
B) DETECTION SYSTEM:
1. Simplex (U.S.A)
2. Hochiki (U.S.A)
3. Notifire (U.S.A)
Or Approved Equal