Downlight Econ 8XS White 8W 4000K 006
First always disconnect the mains of the LED drivers before connect to the DecaLED downlights
! Set the positions of the six dip-switches to the on position like shown in below drawings!
Other settings possible wil damage the DecaLED downlights!
!
1 2 3 4 5 6
21 94000067
103 TCI DC JOLLY
ON
93,5
- -
+
+
SYNC
67 57,5
8W
+ +
SEC -
1-10V - 94506305
PUSH L
94506308
PRI N
L
93,5
- -
+
+
SYNC
57,5
67
16W
+ +
SEC -
1-10V -
94506315
PUSH L 94506318
PRI N
L
124
TCI DC MAXI JOLLY
ON
112
+- +-+- +-
SEC
69 1-10V
79
1 NTC
24W
sync
+- +-
VAUX
94506325
94506328
PUSH L
PRI
LN
124
TCI DC MAXI JOLLY
ON
112
+- +-+- +-
SEC
69 1-10V
79
1 NTC
32W
sync
+- +-
VAUX
94506335
94506338
PUSH L
PRI
LN
1 2 3 4 5 6
ON
+- +-+- +-
SEC
1-10V
NTC
sync
+- +-
VAUX
PUSH
PRI N
L
1-10V Regulator
220-240V AC
1) Max. 10 drivers can be controlled by one 1-10V Regulator (when use link/sync cable between the drivers!)
2) Max. length of link/sync cable from first driver to last driver = 15 meters!
3) In case of using a potentiometer 100KB is recommended!
1 2 3 4 5 6
ON
+- +-+- +-
SEC
1-10V
sync
+- +-
NTC
VAUX
PUSH
PRI
LN
220-240V AC
1 2 3 4 5 6
ON
+- +-+- +-
SEC
1-10V
sync
+- +-
NTC
VAUX
220-240V AC
pulse switch
94000083 / 94000084 1) Max. 10 drivers can be controlled by one pulse switch (when use link/sync cable between the drivers!)
Link/Sync cable
to next LED driver 2) Max. length of link/sync cable length from first driver to last driver = 15 meters!
- + 3) Use normally open push button with no incorporated warning on-off light!