Professional Documents
Culture Documents
H O S T E D BY
Alexandria University
ORIGINAL ARTICLE
KEYWORDS Abstract Static Var Compensators (SVC) have been widely used to separately improve each of
Motor starting; voltage variation performance and steady state power factor of industrial substations. However,
ETAP; these two functions are interdependent, power factor improvement tends to do better voltage reg-
Induction motor; ulation. In this paper, a newly starting method with SVC for large induction motors is suggested.
Power factor; This method provides a controllable amount of reactive power precisely according to the require-
Stativ var compensator; ment of the load. A combined controller consists of slow susceptance control besides fast acting
Voltage regulation voltage control will give SVC the ability to achieve power factor correction, and will present a con-
stant voltage characteristic during large induction motor starting. An ideal compensator approach
is proposed for both power factor correction and optimum voltage regulation. A case study of
1.4 MW large induction motor starting is presented with different starting methods. A comparative
study is conducted to simulation results using Electrical Transient Analyzer Program (ETAP) for
different starting cases. Finally, the simulation results provide bases for the safe and reliable oper-
ation and would insure a robust design of practical substation.
Ó 2018 Faculty of Engineering, Alexandria University. Production and hosting by Elsevier B.V. This is an
open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).
1. Introduction the utility and the motor itself can’t be neglected. When volt-
age is applied on induction motor, a bulk of current is drawn
Large Induction Motors are widely used in all industrial from the utility that momentarily causes a dip in system volt-
plants, and the international production of induction motors age, where the magnitude of this dip is proportional to the
is significantly increased. Self-starting advantage for induction magnitude of the current and the impedance of the system.
motor used to be focused for research. Induction motors start- Because of the highly inductive nature of the motor circuit at
ing is simple due to the absence of external circuit for starting, rest, the power factor of induction motor at starting is quite
it’s a merit, on the other hand the effect of induction motor on low, usually on the order of 10 to 20 percent [1,2]. This means
that the effective component at starting is reactive power due
to relatively low power factor and the voltage sag momentarily
* Corresponding author.
occurs till magnetizing circuit fulfills with its demand of reac-
E-mail addresses: ahmed.omran@sidpec.com (A.S. Omran), nabil. tive component.
abbasi@alexu.edu.eg (N.H. Abbasy), rhamdy@alexu.edu.eg (R.A.
In recent years, many researches and studies have been
Hamdy).
implemented regarding to induction motors starting. Various
Peer review under responsibility of Faculty of Engineering, Alexandria
University.
starting methods such as Direct On-Line (DOL), reduced
https://doi.org/10.1016/j.aej.2018.10.009
1110-0168 Ó 2018 Faculty of Engineering, Alexandria University. Production and hosting by Elsevier B.V.
This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).
4060 A.S. Omran et al.
voltage Auto-transformer, and soft starter are traditionally teristics in DOL, Auto-transformer, and soft starter starting
used [3]. In some papers the starting behavior of induction methods respectively. The dynamic curves of motor speed,
motors was discussed through comparison between conven- motor torque, motor current and bus bar voltages in three dif-
tional starting methods [4–6]. A few researches discussed ferent starting categories are obtained through ETAP simula-
motor starting with unconventional voltage support devices tion. A transient analysis is conducted for DOL starting as a
like SVC and static synchronous compensator (STATCOM) base case. Section 4 shows the suggested technique of induc-
[7,8], these devices have been widely described to overcome tion motor starting with (SVC), In the last section, the contrast
the voltage sag problem during large induction motor starting, between mentioned methods is highlighted and its correspond-
and without effecting motor dynamics during starting. While ing results are obtained.
STATCOM gives better dynamic performance with different
under voltage levels [9–11], the SVC is the preferred device 2. System topology and reactive power calculation
in this case because of its cost effectiveness. In previous
research in this field the SVC reacted at motor starting as a 2.1. Utility and substation
voltage support device, and not required to perform any power
factor correction. In [7] and [12] a straightforward control
The plant substation is fed from two separately incomer at
topology was implemented for motor starting method using
11 kV as a typical double ended substation. Under normal
only voltage reference to SVC controller, while in [13] SVC
conditions, the secondary side arrangement is operated as
controller was using only susceptance control. An alternative
two separate radial systems. The load served from a secondary
control technique was described for modern static Var system
substation should be divided equally between the two bus
(SVS) installation in a utility grid using susceptance control
sections, detailed single line diagram (SLD) for plant
besides voltage reference [14]. The SVS consists of SVC and
substation is shown in Fig. 1. Plant substation Incomer A
switched capacitor banks like in industrial substation. The
and B fed from existing generation switchgear (utility section)
slow susceptance control is used to act when the voltage refer-
consists of one gas turbine generator (G1) with total active
ence is slightly displaced due to small disturbance. In this case,
power generation of 27 MW (36 MVA) and one steam turbine
the slow susceptance control gives enough time for the
generator (GS) with total active power generation of 36 MW
mechanically switched capacitor to compensate reactive power
(45 MVA). The existing loads of utility section is 47.7 MW,
as a supplementary source [15,16]. In this paper the SVC con-
the utility had the following constraints for the 11 kV
trol technique described for SVS was suggested in this case
substation during front-end engineering design:
study, a susceptance control is added besides the voltage regu-
lation control to improve the substation power factor and volt-
Strict medium voltage motor starting requirements:
age profile by SVC. This proposed control scheme will be used
Requested starting device for medium voltage motor above
to perform voltage support during induction motor starting
1 MW. This rule limited the ability to start the large com-
and substation power factor improvement during steady state.
pressor motors without special starting method, therefore
This paper illustrates information on a 1.4 MW induction
the Nitrogen compressor was designed with Auto-
motor case study at 11 kV consuming 8920 MWh per annum
transformer starting.
with about 10% of total energy consumption for the entire
Limited available reactive power capacity to plant substa-
plant. A substation power flow and induction motor starting
tion, therefore 92% power factor (PF) is requested (by the
case study will be conducted through simulation. The induc-
utility contract). A bonus is given in case of sustaining the
tion motor in this case study was originally designed with
PF above certain limits (0.5% reduction in the total cost
embedded Auto-transformer. The Auto-transformer was
for every 0.01 increase in the PF from 0.92 to 0.97).
replaced with soft starter later after a short circuit accident
was occurred to the Auto-transformer. DOL starting was used
in the period between Auto-transformer and soft starter instal-
2.2. Load classification for 11 kV switchgear Bus A
lation. In this case study starting methods can be broken down
into four basic categories: full voltage starting DOL, electro-
mechanical reduced voltage starting (Auto-transformer), A 4.4 MW motor at 11 kV coupled with twin screw extru-
solid-state reduced voltage starting (soft starter), and the sug- der application fed from variable speed drive through an
gested motor starting with SVC. The first three methods are 11/4.4 kV step-down transformer.
applied practically in different field circumstances as men- A 1.4 MW induction motor drives a Nitrogen air compres-
tioned, however many problems were recorded for both motor sor application. It represents this paper case study. It’s con-
performance and substation dynamic behavior. The effect of nected to 11 kV bus bar through voltage controlled soft
different startup methods on motor start-up time, starting tor- starter module. The original design for motor starting was
que and substation voltages are further analyzed through Auto-transformer, but it faced serious damage due to a
ETAP platform. The starting with SVC is proposed to avoid short circuit accident. Starting medium voltage motor
the drawbacks for the earlier methods, and to solve some above 1 MW directly is not allowed as mentioned before
issues in utility side. The effect of SVC on substation power therefore, a soft starter module has been installed instead
factor has further investigation with suggested advanced sus- of Auto-transformer. These two starting methods are classi-
ceptance control. fied as reduced voltage motor starting. These methods have
This paper is organized as follows: Section 2 presents the negative impact on motor starting torque therefore, some
topology of the plant substation, as well as load classification, process arrangement is considered for starting without fac-
and basic calculations for necessary reactive power compensa- ing motor stall. reducing compressor feeds at starting was
tion. Section 3 presents the dynamic curves of motor charac- mandatory in these starting methods. Prior to soft starter
Enhanced performance of substation dynamics 4061
installation DOL starting was the only option with the util- The substation impedance of Bus A 11 kV is given as
ity side approval, but it wasn’t straightforward and it ZSubA ¼ ð6:5 þ j3) PU at 100 MVA Base.
required many arrangements to start the motor. Motor locked rotor impedance
Three units of capacitor bank (750 kVar each), supported
VLðratedÞ
with single tuned internal reactor for harmonic filtration. ZMLR ¼ pffiffiffi ð1Þ
At first the three capacitor banks were controlled by auto- 3ILRA
matic controller but due to 6.6 kV induction motors start- The base impedance of the system
ing, capacitor banks suffered from continuous switching,
and because of vacuum circuit breaker (VCB) connected ðBase KVÞ2
ZSys Base ¼ ð2Þ
with capacitor bank, there was unwanted overvoltage dur- Base MVA
ing switching over medium voltage buses. Manual switching Converting the motor impedance to reactance and resis-
capacitor bank was a simple solution to overcome the prob- tance respectively in per unit at 100 MVA
lems due to using automatic controller for Power Factor
correction. The sequence of capacitor bank switching is XMLR P:U ¼ ZMLR =ZSys Base sinðtan1 X=RÞ ð3Þ
simple, the operator read the power factor every two hours.
If the power factor is lower than 92% a single capacitor RMLR P:U ¼ ZMLR =ZSys Base cosðtan1 X=RÞ ð4Þ
bank unit is switched on service by the operator, and if Motor per unit locked rotor impedance
the power factor is higher than 98% a single unit is switched
off to avoid leading power factor. This method for power ZMLR P:U ¼ RMLR P:U þ J XMLR P:U ð5Þ
factor correction was direct but it depends on the operator The equivalent parallel impedance of the motor and reac-
action, therefore a SVC device is suggested as a solution for tive power compensator impedance (Fig. 2) is:
unwanted capacitor bank switching.
ZMLR ZCom
8 MVA 11/6.6 kV step-down transformer feeds Bus A ZEq ¼
P:U P:U
ð6Þ
ZMLR P:U þ ZCom P:U
(6.6 kV switchgear) with about 50% loading factor.
Four 11/0.4 kV step-down transformer feeds 4 sections The voltage drops across Bus A 11kV when the motor and
in low voltage switchgears with the same loading compensator are initially energized is represented in voltage
factor 50%. divider to achieve a maximum 1 percent voltage drop in sub-
station as follows:
ZEq Voltage sag during motor starting will not exceed accept-
V% ¼ 100 ¼ 99% ð7Þ
ZEq þ ZSub A able limits for remote bus bar (5% for Medium and low
voltages switchgears as a marginal limit and 10% as critical
By getting ZEq the only unknown in (6) is ZComP:U
limit).
Base MVA
ZCom P:U ¼ j ð8Þ
compensator MVA
3.1. Direct online starting method
The calculated value for reactive power compensation dur-
ing 1.4 MW motor starting is 8.7 MVar according to (8). This A DOL start is the simplest, most common, and least expen-
capacitance aims to decrease voltage drop to 1% [17]. The sive method of starting squirrel cage Induction motors.
total substation compensator capacity for both power factor Direct-on line starting offers high-acceleration torque and
correction and voltage support is 10.95 MVar. reduced acceleration time [3,18]. The DOL starting is repre-
sented by two models. The first one is modeled by Simulink
2.4. Substation load flow simulation to show the transients during starting as a base case for the
other starting methods. The second one is modeled by ETAP
The following load flow simulation presents bus voltages in as a normal motor acceleration case study.
percentage, apparent power and power factor as it appears
in Fig. 3. The load flow analysis aims to show the power factor Simulink model.
for Bus A 11 kV substation switchgear without capacitor
banks connected to 11 kV switchgear. The load flow analysis It’s well known that when the rated terminal voltage is sud-
shows that power factor for substation is 90% without any denly applied to the induction motor at rest, an oscillating
power factor correction, and the voltage drop across bus bars transient torque appears. However, this fact is not unexpect-
for medium voltages (11 kV & 6.6 kV) and low voltage edly considered by many industrial users. Excessive transient
(0.4 kV) is between 1% and 3% for full load as an extreme torque of oscillatory occurs when power supply voltage
condition for loading which is acceptable limits for voltage applied suddenly to start an induction motor. As this phe-
drop. nomenon is clarified for a long time, industrial user is not con-
scious unexpectedly because there are no clear descriptions in
the general standard. Depending on a case, transient torque
3. Conventional large induction motor starting takes a very big value and there is a case to cause axis fatigue
and damage of compressor side gear. In this case a Simulink
The Case study criteria for every starting method will consist dynamic model is conducted in DOL starting to observe this
of three major requirements: phenomenon. The results from this model can give a roughly
figure for the transient torque in the other starting methods.
Motor starting with appropriate terminal voltage drop. The transient torque values should be investigated as they
Motor starting within acceptable start-up time and motor are with acceptable limits. Fig. 4 shows the simulation layout,
torque therefore, further information about mechanical Figs. 5 and 6 show the dynamic behavior of the motor during
load is entered in ETAP motor model. entire period of starting, while Figs. 7 and 8 give the simulation
pu
Real power pu
pu o PS S Scope 1
0.5
pu o PS S
PF
0
I pu o PS S
T
n ~ ~1 ~2 ~1
-0.5
~2 -0.05 0 0.05 0.1 0.15 0.2 0.25
Current Sensor
f(x) = 0
Voltage Source RLC
Time (sec)
Solver
Configuration
pu
R Fig. 8 Motor transient behavior DOL.
~1
C
~2
Asynchronous Machine
Squirrel Cage Mechanical
Transient torque oscillation of this induction motor occurs
R
~
97
1
A
V bus
kv
93
0.5
89
0
85
-0.5 0 1 2 3 4 5 6 7 8 9 10
0 1 2 3 4 5 6 7 8 9 10 Time (sec)
Time (sec)
% of motor torque
250
150
B
50
0
0 1 2 3 4 5 6 7 8 9 10
Phase currents (A)
Time (sec)
600
400
Fig. 9 (A: 11 kV bus terminal voltage % at DOL starting, B:
200
motor torque % at DOL starting).
0
-200
8000
-400
reactive power
kvar Motor
6000
-600
-0.05 0 0.05 0.1 0.15 0.2 0.25 4000 A
Time (sec) 2000
0
0 1 2 3 4 5 6 7 8 9 10
Fig. 7 Motor transient starting current DOL. Time (sec)
4000
kW Motor real
3000
power
% of bus nominl kv
100
Vt (% of bus nominl 100
voltage) 0.4 Kv Bus 6.6 Kv Bus 97
V bus
97
93
93
89
89 85
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
85
Time (sec)
0 1 2 3 4 5 6 7 8 9 10
Time (Sec)
Fig. 13 11 kV bus terminal voltage % at Auto-transformer
Fig. 11 Voltage sag across 6.6 kV and 0.4 kV switchgears at starting.
DOL starting.
% of motor torque
200
Motor torque Load torque
150
Torque
600
I (% of FLA)
500 100
400
50
300
200
0
100 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
0 Time (sec)
0 1 2 3 4 5 6 7 8 9 10
Time(sec)
Fig. 14 Motor and load torque during Auto-transformer
Fig. 12 Motor starting current during DOL starting. starting.
The previous DOL curves show the basic data about bus Motor torque almost is halved with significant reduction with
voltages associated with motor starting case study, motor respect to DOL method starting torque. Great care should be
speed, starting current and torque characteristics. Fig. 9 shows taking to make sure that there will be sufficient accelerating
the terminal voltage across the motor and torque speed char- torque available from the motor. An acceptable torque value
acteristics. Instead of slip-torque relation the time-torque rela- is checked, the higher acceleration torque, the shorter starting
tion gives clear image about starting time for motor which is time. The motor torque should adequate full load torque of the
about 6 secs. The motor terminal voltage drops through start- motor at all curve points as shown in Fig. 14. The acceleration
ing period to 91% which is lower than the marginal limit. In time should be evaluated to make sure that the motor has suf-
Fig. 10 the relation between starting period, active and reactive ficient thermal capacity to handle the heat generated due to the
power consumption is illustrated, it’s clear that the largest por- longer acceleration time.
tion of starting power is reactive part. The bus voltages for The dynamic curves for bus voltages in ETAP show great
0.4 kV and 6.6 kV buses are suffer from critical voltage drop improvement in both medium and low voltage buses. Fig. 15
during DOL starting as shown in Fig. 11, the 6.6 kV bus has represents one bus from each switchgear, which is first concern
the largest voltage drop, where bus voltage is 89%. The in this case study criteria. The torque result was not as good as
0.4 kV voltage is beyond 90%. Fig. 12 shows starting current the buses voltages. Fig. 14 shows that maximum torque value
during DOL starting and its value is almost five times from at starting is reduced significantly from over than 200% in
its rated value. The DOL starting was applied for the motor DOL starting into lower than 150%. In fact, this result was
for a long time after Auto-transformer was removed. The expected however, the setting is 75% of rated voltage which
remote buses faced some difficulties in voltage fluctuation dur- is almost the higher value for Auto-transformer voltage.
ing motor starting. The soft starter module was the suggested Fig. 14 shows very low offset between motor torque and load
solution after Auto-transformer failure. torque between second 10 and second 20 period. This case
enforces some process arrangement for starting without facing
3.2. Auto-transformer starting method problems like reducing compressor feeds at starting. The start-
ing period is increased to 22 secs, therefor, the remote switch-
This method is classified as reduced voltage starting method gear will suffer from voltage sag longer than DOL starting.
using electro-mechanical device where the motor terminals The starting current in Fig. 16 is 400%, and it is pushing ther-
are connected to the lower voltage side of the Auto- mal state for the motor during starting to its thermal capacity.
transformer. The most common taps that are used are 80%,
65%, and 50%. In this case 75% voltage is determined for
motor starting voltage, the current in the primary is reduced
Vt (% of bus nominl
100
to 70% from its original locked rotor current, the motor is 0.4 Kv Bus 6.6 Kv Bus
97
voltage)
started with this reduced voltage, and then after 25 secs, the
connection is switched to line voltage with external vacuum 93
% of motor torque
500 150
Motor torque Load torque
I (% of FLA)
400
Torque
300 100
200
50
100
0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
0
Time (Sec) 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Time (sec)
Fig. 16 Motor starting current during Auto-transformer
starting. Fig. 18 Motor and load torque during soft starting.
Vt (% of bus nominl
100
dents and was replaced with soft starter device. 97
0.4 Kv Bus 6.6 Kv Bus
voltage)
93
3.3. Soft-starter starting method
89
band is 175% to 500% of full load current and its setting for I (% of FLA) 300
the motor is 350% of full load current. It then will ramp up 200
the applied voltage until it reaches the limiting value, and will
100
then hold that current as the motor accelerates.
In soft starting method, the motor is given an initial torque 0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
100
93
Time (sec) grids and it has implemented for industrial application success-
fully in many cases [19]. The SVC regulates voltage at its ter-
Fig. 17 11 kV bus terminal voltage % at soft starting. minal by controlling the amount of reactive power injected
4066 A.S. Omran et al.
SVC supplies
reactive power I
V¼ SVC is inductive ½B ¼ BL max ð11Þ
BL max
Fig. 22 TSC-TCR reactive power contribution for the suggested This control scheme is developed for the SVC that will
SVC. operate in a coordinated manner with the switching scheme
of the existing power capacitor banks at the other substations
in company, or improve power factor by susceptance setpoint
into or absorbed from the power system by set a reference volt- with slow response. The strategy chosen to accomplish suscep-
age or susceptance. When system voltage is low, the SVC gen- tance regulation by providing a ‘‘dead band” in the SVC’s V-l
erates reactive power (capacitive mode), and when system characteristic. The function compares the actual power factor
voltage is high, it absorbs reactive power (inductive mode). value to the power factor set point, and from this error signal
The variation of reactive power is performed by switching generates a susceptance contribution to the total voltage refer-
capacitor banks and controlling inductor banks. The suggested ence of the SVC. The limits of the regulator are set such that
topology for the SVC is consists of thyristors switched capac- the voltage reference may be adjusted a maximum of 0.08 p.
itor (TSC) as a capacitive source, and thyristors controlled
reactor (TCR) as an inductive source. The TCR is controlled
linearly to generate inductance or to smooth the output capac-
itance using phase control. In this case study, a TCR with TSC V-I SVC linear operation
type is used to overcome the voltage sag during large motor regon
V
ref
starting and to improve power factor instead of fixed capacitor
bank, The TSC-TCR compensator single line diagram shows B L. MAX
in Fig. 21. The TSC is splitted into three equal units, each unit
has a 4 MVar capacity, while the TCR is one unit 4 MVar.
This combination makes the reactive power control smooth
with no sudden change in reactive power flow from SVC as
shown in Fig. 22. B C . MAX
Fig. 26 Load flow analysis for Bus A 11 kV switchgear with installed SVC.
% of bus nominl kv
101 600
500
97 I (% of FLA)
400
V bus
93
300
89 200
100
85
0 1 2 3 4 5 6 7 8 9 10 0
Time (sec) 0 1 2 3 4 5 6 7 8 9 10
Time (sec)
300
% of motor torque
% of bus voltage
200
V bus
kV
96
150 DOL
94 Auto trans
100 Soft starter
92 SVC
50
90
0
0 1 2 3 4 5 6 7 8 9 10 0 5 10 15 20 25 30
Time (sec) Time (sec)
Fig. 28 Motor and load torque during SVC starting. Fig. 31 11 kV bus terminal voltage % during different starting
methods.
97
200
Torque
150
Overall, in this paper, different starting methods of a particu-
lar induction motor are investigated by ETAP simulation soft-
100
ware, including DOL start, Auto-transformer start, soft starter
50
start, and motor starting using SVC. The influence of load and
0
0 5 10 15 20 25 30 power grid in each model is analyzed. Through simulation, the
Time (sec)
dynamic curves of the motor current and bus voltages in each
Fig. 32 Motor torque % during different starting methods. starting method can be visualized and analyzed. The advan-
tages and disadvantages of different starting methods are
explored. A combined reference control is proposed with
600
DOL
SVC. Under such scheme, the SVC starting method shows
Auto trans
500
Soft starter
SVC
superior performance relative to other starting methods.
I (% of FLA)
400
Motor starting with SVC increases accelerating torque, and
gives shorter starting time. Using SVC during motor starting
300
produces enhanced voltage profile for all substation voltage
200 levels, without affecting motor starting torque. The SVC with
100 combined references control can achieve power factor
0
improvement for slow susceptance control and voltage support
0 5 10 15 20 25 30
Time (sec)
for fast acting voltage regulation control. The substation
dynamics are improved for both voltage profile and power fac-
Fig. 33 Motor starting current % during different starting tor by using suggested combined reference control. The voltage
methods. drop during starting with SVC is reduced from 11% to 1%
with better motor performance. The power factor is improved
from 90% to 99% with SVC, the unwanted overvoltage due to
VCB with fixed capacitor bank is eliminated. The simulation
Table 2 Motor starting method comparison table.
results provide bases for the safe and reliable operation in
Start-up starting Tstð%Þ =I2 stð%Þ Max Voltage the design of practical substation.
model time (s) Torque drop (%)
(%)
Appendix A. A.1. 1.4 Mw Induction motor parameters
DOL 5.8 0.02 220 11
Auto- 22 0.028 125 7
P = 1470 KW, f = 50 Hz, V = 11000 V
transformer
Soft starter 26 0.03 100 8 I fl @2980 min1 = 89 A, J m ¼ 14:3 kg m2
SVC 4.6 0.06 230 1 J l @2980 min1 ¼ 44 kg m2
Rs = 0.941 O, X rðflÞ = 10.6 O
X s = 10.3 O, X rðlrÞ = 6.8 O
ing was at SVC starting Fig. 32, while the DOL starting gives a X m = 538 O, RrðflÞ = 0.9 O
close torque speed characteristic performance. The other two RrðlrÞ = 2.5 O, single cage with deep bars
methods were almost similar to each other, due to their classi-
T st = 70%, PF @2980 min1 = 90%
fication as reduced voltage starting. Fig. 33 shows that the lar-
gest starting current happened during SVC starting at 590%, top speed = 2980 min1
while the soft starter starting limiting the current at 350%,
the starting current at Auto-transformer method began with
400% and decayed 300% at the end of starting period.
Figs. 31–33 give a brief comparison between different start-
ing method characteristics and the results of different motor
starting methods are summarized in Table 2 starting time,
Tst =I2 st ratio, max torque and max voltage drop are all calcu-
lated and tabulated in this table.Tst represents motor starting
torque while Ist represents substation consumed current during
motor starting. The close inspection of these results reveals
that the reduced voltage with Auto-transformer gives good
results in voltage drop and starting torque over the one with
soft starter. However, experience has proven that the perfor-
References
mance of soft starter could have been improved if the current
limiting has been increased from 350% to 450%. Also, the
[1] Z.M.S. El-Barbary, Fuzzy logic based controller for five-phase
table indicates that the Tst =I2 st ratio has been almost doubled induction motor drive system, Alexandria Eng. J. (AEJ) 51
in case of motor starting with SVC with respect to all other (2012) 263–268.
starting methods. In addition, the SVC starting method has [2] V. Sreeram, M.V. Supriya, Fault current discrimination during
successfully achieved the design criteria of 1% voltage drop induction motor starting, in: IEEE 6th International Conference
for the system. on Power Systems (ICPS), 2016, pp. 1–4.
4070 A.S. Omran et al.
[3] D.S. Padimiti, M.B. Christian, J. Jarvinen, Effective transient matrix converter in output stage, Alexandria Eng. J. (AEJ) 53
free capacitor switching (TFCS) for large motor starting on (2014) 563–572.
MVsystems, in: Petroleum and Chemical Industry Technical [11] Fahad Iqbal, Mohd T. Khan, Optimal placement of DG and
Conference (PCIC), 2017, pp. 113–124. DSTATCOM for loss reduction and voltage profile
[4] M. Habyarimana, D.G. Dorrell, Methods to reduce the starting improvement, Alexandria Eng. J. (AEJ) 57 (2018) 755–765.
current of an induction motor, in: IEEE International [12] E.P. da Silveira, R.C. Pires, A.T.L. de Almeida, A. José, J.
Conference on Power, Control, Signals and Instrumentation Rezek, Direct on line starting induction motor with Thyristor
Engineering (ICPCSI), 2017, pp. 34–38. Switched Capacitor based voltage regulation, in: Brazilian
[5] P.S. Patil, K.B. Porate, Starting analysis of induction motor: a Power Electronics Conference, 2009, pp. 1124–1129.
computer simulation by Etap Power Station, in: Second [13] R. Hadidi, I. Mazhari, A. Kazemi, Simulation of induction
International Conference on Emerging Trends in Engineering motor starting with SVC, in: IEEE Conference on Industrial
& Technology, 2009, pp. 494–499. Electronics and Applications, Harbin, 2007, pp. 1135–1140.
[6] H. Zhu, X. Liu, N.E. Mastorakis, The simulation analysis of [14] P. Pourbeik, A. Boström, Modeling and application studies for a
motor startup based on the ETAP platform, in: International modern static VAr system installation, IEEE Trans. Power
Conference on Mathematics and Computers in Sciences and in Delivery (1994) 229–240.
Industry, 2014, pp. 245–248. [15] Carson W. Taylor, Guy Scott, Adel Hammad, Static VAr
[7] M.Z. El-Sadek, N.H. Fetih, F.N. Abdelbar, Starting of compensator models for power flow and dynamic performance
induction motors by static VAR compensators, in: simulation, IEEE Trans. Power Syst. (1994) 229–240.
International Conference on Power Electronics and Variable- [16] G. Romegialli, H. Beeler, Reactive compensation. Problems and
Speed Drives, 1988, pp. 444–447. concepts of static compensator control, in: IEE Proceedings C -
[8] L.S. Patil, A.G. Thosar, Application of D-STATCOM to Generation, Transmission and Distribution, 1981, pp. 382–388.
mitigate voltage sag due to DOL starting of three phase [17] John H. Stout, Capacitor starting of large motors, IEEE Trans.
induction motor, in: International Conference on Control, Ind. Appl. (1978) 209–212.
Automation, Communication and Energy Conservation, 2009, [18] M. Abbas, M.A. Majeed, M. Kassas, F. Ahmad, Motor starting
pp. 1–4. study for a urea manufacturing plant, in: International
[9] A. Qatamin et al, SVC versus STATCOM for improving power Conference on Power Engineering, Energy and Electrical
system loadability: A case study, in: 8th International Drives, 2011, pp. 1–6.
Renewable Energy Congress (IREC), Amman, 2017, pp. 1–4. [19] V. Ambarani, Static VAr compensation system for industries,
[10] M.R. Banaei, E. Salary, Mitigation of voltage sag, swell and Power Qual. Hyderabad (1998) 177–194.
power factor correction using solid-state transformer based [20] ETAP 12.6 user guide ‘‘Control model type3” 24-p22.