designed to be the
most advanced flow
computer in the world!
TCP/IP connection.
■ Two RS-232 ports for connection to a printer, RTU, Modbus device, or
DCS system.
■ One dedicated configuration port.
2
Power and flexibility
3
Enhanced productivity through ease of use
4
Connecting for the future
Supervisory Computer
Additional MMI
(PC w/Windows NT)
5
High performance, accurate measurement
Approvals
■ CE
■ OMH – Hungarian Weights & Measures
■ CMI – Czech Weights & Measures
■ OMNL – Algerian Weights & Measures
■ EN 12405 – Electronic Gas Volumetric Measurement Devices
■ OIML R117 – Measuring Systems for Liquids other than Water
■ SMU – Slovak Republic
■ SDM – France
■ NMI – Netherlands
■ BRML – Romania
6
Outstanding access and security
7
Count on Emerson
Doing business with Emerson Process Management gives you the confidence that the products, services and
solutions you buy are backed by our unmatched global support. And, Emerson’s industry expertise will help
you achieve the performance and profitability goals you are measured by.
The information and support you need can be as close as your telephone or web browser, or right around the
corner. With over 600 locations in more than 85 countries, chances are we have an office near you.
Technical support for your ROC, FloBossTM, and related products is also available directly from the Internet with
SupportNetTM Technical Services. Whether you need software or firmware updates, or just have a technical
question, SupportNet can make your job easier. And best of all, SupportNet is available to you 24 hours a day,
seven days a week.
SupportNet gives you an easy and convenient means to get answers to technical questions or solutions to
product problems. You have access to our extensive knowledge base of information, as well as to our factory-
trained technical support team. You also have access to e-learning modules that provide audio-visual training
on a variety of topics.
You can enjoy even more benefits with SupportNet Express or SupportNet Plus, subscription services that let
give you valuable on-line tools designed to meet your technical support needs.
Bristol, Inc., Bristol Babcock Ltd, Bristol Canada, BBI SA de CV and the Flow Computer
Division , are wholly owned subsidiaries of Emerson Electric Co. doing business as
Remote Automation Solutions (“RAS”), a division of Emerson Process Management.
ROC, FloBoss, ROCLINK, Bristol, Bristol Babcock, ControlWave, TeleFlow and Helicoid
are trademarks of RAS. AMS, PlantWeb and the PlantWeb logo are marks of Emerson
Electric Co. The Emerson logo is a trademark and service mark of the Emerson Electric
Co. All other marks are property of their respective owners.
The contents of this publication are presented for informational purposes only. While
every effort has been made to ensure informational accuracy, they are not to be
Remote Automation Solutions construed as warranties or guarantees, express or implied, regarding the products or
Pickering, North Yorkshire, UK services described herein or their use or applicability. RAS reserves the right to modify
Phone: +44 (0) 1751 471 818 or improve the designs or specifications of such products at any time without notice.
Fax: +44 (0) 1751 471 801 All sales are governed by RAS’ terms and conditions which are available upon request.
E-mail: fcd.tech-support@emersonprocess.com RAS does not assume responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use and maintenance of any RAS product remains
www.EmersonProcess.com/remote solely with the purchaser and end-user.
8
7:S600
Specification Sheet June 2009
Communication Specifications
COMMUNICATION RS232 Ports (Ports 3 & 4)
Connector: FCC-68 RJ45.
Configuration Port (located on the bottom of the
front panel) Communication Standard: RS232D.
Connector: 6-pin RJ12. Signals Supplied: Tx, Rx, RTS, CTS, DTR,
Communication Standard: RS232D. DSR, GND, DCD.
Signals Supplied: Tx, Rx, CTS, GND. Baud Rate:300, 600, 1200, 2400, 4800, 9600,
19200, 38400.
Baud Rate: 300, 600, 1200, 2400, 4800, 9600,
Format: Software configurable.
19200, 38400.
Format: Config600 Protocol. Data Protocol: ASCII, MODBUS (ASCII,
RTU).
Ethernet (Ports 1 & 2)
RS422/RS485 Ports (Ports 5, 6, & 7)
Port 1: Standard.
Connector: standard screw terminals, 3.5 mm
Port 2: Optional, with P190 board installed. pitch, 13-pin.
Speed: 10 Mbit/second. Communications: RS422 - point-to-point - 4
Media Connectivity: 10baseT, twisted pair wire RS422 – multidrop (RS485 4 wire) - 4
utilizing standard RJ45. wire RS485 - multimaster - 2 wire.
Protocol: Modbus/TCP or Modbus over Signals Supplied: Tx+, Tx-, Rx+, Rx-,
Ethernet. common shield.
Baud Rate: 300, 600, 1200, 2400, 4800, 9600,
19200, 38400.
Format: Software controlled on each channel.
Data Protocol: ASCII, MODBUS (ASCII,
RTU).
7:S600
Specification Sheet Page 5
Expansion Boards
The FloBoss S600 is supplied with one P144 I/O board and one P148 Pulse Mezzanine as standard. There
are two additional slots available to accept additional expansion boards, these can be the following:
P144 I/O Board – Provides the S600 with additional analog and digital I/O.
P148 Pulse Mezzanine – Provides pulse input capability. Fits on P144 and P154 boards and does not
use an additional slot.
P154 Prover board – For applications with a prover.
P188 HART board – For applications with HART transmitters.
P190 2nd Ethernet board – Provides a second Ethernet port.
Details of these optional boards are as follows:
P144 I/O BOARD (1 standard, additional boards are P154 PROVER BOARD (continued)
optional) Digital Outputs
Analog Inputs Quantity: 12
Quantity: 12 Pulse Inputs-Flow/Turbine (requires Pulse
Analog Outputs Mezzanine board)
Quantity: 4 Quantity: 2 dual pulse or 4 single pulse.
Digital Inputs Frequency Density Inputs:
Quantity: 16 Quantity: 2
Digital Outputs Pulse Outputs
Quantity: 12 Quantity: 4
Pulse Inputs-Flow/Turbine (requires Pulse Raw Pulse Input
Mezzanine board): 2 dual pulse or 4 single Quantity: 3
pulse. Phase Loop Lock Input
Frequency Density Inputs: 3. Quantity: 2
PRT (RTD) Inputs: 3, 4-wire. Switch Detect
Pulse Outputs: 5. Quantity: 4
Raw Pulse Output: 1, Raw pulse output for
proving, 0 to 5 kHz. P188 HART BOARD (optional)
Supports dual master (primary or secondary), read
P148 PULSE MEZZANINE (1 standard, additional only (can not be used to change constants on the
boards are optional) HART board). Does not support burst mode.
Fits on P144 and P154 boards to provide pulse Quantity: 12 Channels. Each channel can be
input capability. configured for point-point or multi-drop
Quantity: 2 dual pulse or 4 single pulse. communications. In multi-drop mode, each
Note: The P148 Pulse Mezzanine board fits on channel can support up-to 8 transmitters
a P144 or P154 board and does not use an Max. Number of HART Transmitters: 50.
additional slot.
P190 ETHERNET BOARD (optional)
P154 PROVER BOARD (optional)
Compact, uni-directional, bi-directional, master Adds a second Ethernet port to the S600. Refer to
meter, dual chronometry. Up to 4 sphere switch. the Ethernet section of the Communication
Specifications table for more information.
Digital Inputs
Quantity: 32
7:S600
Specification Sheet Page 6
Input Specifications
ANALOG INPUTS PULSE INPUTS-FLOW/TURBINE
Type: 1 to 5 V, 0 to 5 V, 4 to 20 mA, or 0 to 20 Requires Pulse Mezzanine board to be fitted to a
mA, opto-isolated. Two groups of 5 single- P144 or P154 board.
ended voltage or current inputs with each Type: Dual pulse or single pulse train, opto-
group sharing a common return; channels 11 isolated.
and 12 are current input only. Signal Level: ±3.5 V to ±24 V, minimum 5 mA.
Signal Level: 0 to 5.125 V or 0 to 22 mA. Frequency Range: 0 to 10 kHz.
Scan Rate: All channels can be acquired in less Security Monitoring: IP 252/76 (ISO 6551),
than 1 second. level A or B.
Resolution: 24 bits, auto-zero, auto-calibrate.
Conversion Time: Less than 100 ms per DIGITAL STATUS INPUTS
channel. Type: 16 opto-isolated inputs, arranged in 4
groups of 4 with common positive connection
Series Mode Rejection: >100 dB at 50 Hz and
to allow simple interface to open collector
60 Hz.
outputs.
Voltage Common Mode Range: ±50 V as a
Max Input Voltage: 30 V.
group relative to computer ground.
Min Input On Voltage: 12 V.
Common Mode Rejection: >100 dB at 50 Hz
and 60 Hz. Max Input Off Voltage: 3 V.
Input Impedance: >10 MΩ (voltage mode), Input Impedance: 2-2.5 kΩ typical.
approx 250 Ω (current mode). Protection: Reverse voltage protection.
Calibration Period: 2 years to 0.005% of PRT (RTD) INPUTS
voltage; 5 years to 0.01% of voltage. Type: 4 wire connection using Pt 100
A/D Converter Inputs Voltage Mode transducers, opto-isolated.
Type of Inputs: Single-ended voltage inputs. PRT (RTD) Resistance: 100 Ω [Pt 100 to IEC
Input Range: 0 to 5.2 V. 751/DIN 43760 (Europe 0.00385), IPTS68
Accuracy: ±0.005% of FSD at 23°C (73°F). (American 0.00392), Calendar-Van Dusen].
Ambient Temperature Effect: ± 7 ppm/°C (± 4 Excitation Current: 1 mA nominal.
ppm/°F) from 23°C (73°F) in the range 0 to Measuring Range: 60 to 216 Ω (–100°C to
45°C (32 to 113°F). +300°C) (–148°F to +572°F).
A/D Converter Inputs Current Mode Resolution: 0.01°C (0.018°F).
Type of Inputs: Single-ended current inputs. Accuracy: –100°C to 200°C (–148°F to 392°F) ±
Input Range: 0 to 22 mA. 0.01% –200°C to 300°C (392°F to 572°F) ±
Accuracy: ± 0.02% of FSD at 23°C (73°F). 0.02%.
Ambient Temperature Effect PRT (RTD) Cables: Core resistance up to 600 Ω.
± 10 ppm/°C (± 5.5 ppm/°F) from 23°C in the Barriers: 9 V, 100 Ω are satisfactory.
range 0 to 45°C (32 to 113°F). Security: Continuous cable/PRT (RTD)
integrity tests for earths/open circuits.
FREQUENCY/DENSITY INPUTS
Type: dc coupled, opto-isolated.
Signal Level: 3 V min pk-pk.
Maximum Input Voltage: 12 V pk-pk.
Current Limit: Internally limited to 3 mA.
Frequency Range: 0 to 10 kHz.
Accuracy of Frequency Measurement: 10
ppm.
Resolution: 5 nanoseconds.
7:S600
Specification Sheet Page 7
Output Specifications
ANALOG OUTPUTS PULSE OUTPUTS
Type: 4 to 21 mA outputs, opto-isolated. Type: Opto-isolated open-collectors.
Resolution: 12 bit minimum. Frequency Range: 0 to 100 Hz.
Accuracy: ± 0.1% at 23°C (73°F). Max Output Current: 100 mA.
Ambient Temperature Effect: 20 ppm/°C Max Output Saturation Voltage: 1.5 V @ 100
(11ppm/°F) from 23°C (73°F). mA.
Load Loop Resistance: 650 Ω maximum when Low Current Saturation Voltage: 600 mV @ 1
powered by local isolated source, 470W 1000W mA to suit TTL style input.
when powered from +24 V external supply. Max Output Standoff Voltage: 42 V (limited by
Maximum External Supply: 32 V. Transorb).
Output Form: Controlled active current sink to
RAW PULSE OUTPUTS
ground return of local floating supply.
Type: Digital ground-referenced open-collector.
Number of Field Connections: 3 terminals per
Gating: Software controlled.
channel.
Max Output Saturation: 1.5 V.
Update Time: 100 ms to within 1%.
Max Output Standoff Voltage: 26 V (limited by
DIGITAL OUTPUTS Transorb).
Type: 3 groups of 4 with common negative, Max Output Current: 100 mA.
opto-isolated. Frequency Range: 0 to 5 kHz.
Frequency Range: 0 to 0.5 Hz. Minimum On Period: 100 µs (microseconds).
Max Output Saturation Voltage: 1.5 V @ 100 Use: To bus together several streams to a
mA. common prover computer.
Low current Saturation Voltage: 600 mV @ 1
mA to suit TTL style input, with 4.7 kΩ pull up to
5 V.
Max Output Standoff Voltage: 42 V (limited by
Transorb).
Max Output Current: 100 mA.
Reset/Power on State: All digital outputs – OFF.
7:S600
Specification Sheet Page 8
Bristol, Inc., Bristol Canada, BBI SA de CV and Emerson Process Management Ltd, Remote Automation Solutions division (UK),
are wholly owned subsidiaries of Emerson Electric Co. doing business as Remote Automation Solutions (“RAS”), a division of
Emerson Process Management. FloBoss, ROCLINK, Bristol, Bristol Babcock, ControlWave, TeleFlow and Helicoid are trademarks
of RAS. AMS, PlantWeb and the PlantWeb logo are marks of Emerson Electric Co. The Emerson logo is a trademark and service
mark of the Emerson Electric Co. All other marks are property of their respective owners.
The contents of this publication are presented for informational purposes only. While every effort has been made to ensure
informational accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or
services described herein or their use or applicability. RAS reserves the right to modify or improve the designs or specifications of
such products at any time without notice. All sales are governed by RAS’ terms and conditions which are available upon request.
RAS does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use
and maintenance of any RAS product remains solely with the purchaser and end-user.
Emerson Process Management
Remote Automation Solutions
Marshalltown, IA 50158 U.S.A.
Houston, TX 77041 U.S.A.
Pickering, North Yorkshire UK Y018 7JA
© 2002-2009 Remote Automation Solutions, division of Emerson Process Management. All rights reserved.