The FloBoss S600 Panel-Mount Flow Computer

TM

Remote Automation Solutions


1
The FloBoss S600 is ™

designed to be the
most advanced flow
computer in the world!

The FloBoss S600 Flow Manager


is a panel-mount flow computer
designed specifically for
hydrocarbon liquid and gas
measurement where versatility and
accuracy matter.

The standard features of the unit


make it ideal for fiscal measurement,
custody transfer, batch loading and
meter proving applications. The unit
allows multi-stream multi-station
applications to be configured for
simultaneous metering of both
liquids and gases.

The FloBoss S600 offers multiple communications interfaces including:


■ One or two LAN ports for Ethernet 10 base T connectivity.

■ HART communication through a 12 channel HART board.

■ An embedded web server supports remote access through a

TCP/IP connection.
■ Two RS-232 ports for connection to a printer, RTU, Modbus device, or

distributed control system.


■ Three RS-422/485 ports for connection to a Modbus network or

DCS system.
■ One dedicated configuration port.

2
Power and flexibility

■ Distributed processing ■ Liquid and gas measurement


■ High accuracy ■ Up to 6 meter runs
■ Windows-based setup ■ Connects to most flowmeter types
■ Easily-expandable modular I/O ■ Prover capability
■ Flexible communications ■ API and ISO calculations
■ Compact size
■ Remote I/O capability

Display — 20 Characters by 8 Lines The FloBoss S600 uses a 50MHz


Intel 486 microprocessor,
Function Keys
math coprocessor, and six
Alarm LED microprocessors on each I/O board
for fast, accurate calculations. Its
modular design and
exceptional connectivity give you
Navigation Button superb adaptability.

The S600 can be used either as


a stand-alone solution or as a
system component. The Intelligent
Data Entry Keys
I/O board fits both gas and liquid
applications and supports two
streams and a header. Using
additional I/O boards, up to six
streams and two headers can
be configured using all common
flowmeter types including orifice,
ultrasonic, turbine, positive
displacement and Coriolis. There
is no need for multiple cards for
different applications.

The HART interface supports HART-


compatible smart instrumentation,
The S600 features a user interface The FloBoss S600 is easily configured increasing the number of instruments
that is robust and easy to use. using Config 600 software that can be connected to the S600.

3
Enhanced productivity through ease of use

■ Configuration automation ■ I/O assignments


■ Modbus map ■ Measurement constants
■ Communications allocation ■ Device types
■ Communications protocols ■ Report editor
■ Reports ■ Display editor
■ Front screen alarms ■ Modbus editor
■ Scaling units

In addition to its computing power


and extended capabilities, the
FloBoss S600 is extremely easy to set
up and use. The available Config 600
configuration package gives you fast,
intuitive control from a PC. Featuring
Windows compatibility, Config 600
allows you to implement a wide
range of time-saving options, such as
instant configuration and automatic Typical Communication Setup Window
generation of documentation,
reports, modbus registers and front
panel displays.

The FloBoss S600 allows both the


novice and expert user to develop
a configuration to meet specific
needs. It has all of the capabilities you
would expect from a high-end flow
computer: scaling, I/O assignment,
constants, communications, etc.

Using IPL 600, the Interactive


Program Loader (a component of
Config 600), the user can upload
existing configurations for additional
customization or to clone
additional S600s. Typical Gas Stream Setup Window

4
Connecting for the future

■ Five configurable ports ■ Chromatograph (Danalyzer/ABB/Siemens)


■ TCP/IP Ethernet interface ■ Modbus/TCP (ASCI & RTU)
■ Dual Ethernet Options ■ Coriolis (Micromotion)
■ EFM Modbus ■ Ultrasonic (Daniel/Instromet/SICK/Caldron)
■ HART

Supervisory Computer
Additional MMI
(PC w/Windows NT)

The modular design of the FloBoss


S600, and its wide range of
communication and expansion
options, lets it be easily adapted to
your requirements however they
might change.

The FloBoss S600 offers two RS232


ports with handshake signals and TCP/IP Ethernet Network
three differential communications
ports. Each of these three ports can
be independently configured point-
to-point (RS-422) or multi-dropped
(RS-485), supporting both two-wire
and four wire protocol. In addition,
there is a 10BaseT (Twisted Pair)
Ethernet interface utilizing TCP/IP
protocols for flexibility and
network connectivity.

The processor bus meets IEEE


standards allowing easy upgrades
when it becomes necessary. Code
is written in ANSI C for the Intel FloBoss S600 Flow Computers
Processor for maximum portability.

Typical Network Diagram

5
High performance, accurate measurement

Approvals
■ CE
■ OMH – Hungarian Weights & Measures
■ CMI – Czech Weights & Measures
■ OMNL – Algerian Weights & Measures
■ EN 12405 – Electronic Gas Volumetric Measurement Devices
■ OIML R117 – Measuring Systems for Liquids other than Water
■ SMU – Slovak Republic
■ SDM – France
■ NMI – Netherlands
■ BRML – Romania

In today’s oil and gas industry,


speed, accuracy and stability are
key requirements, which is why we
incorporated advanced technology
into the FloBoss S600.

By using multiple processors, very


high calculation speeds are achieved
(e.g. AGA8 in 40mS), while a high
Typical liquid multi-stream application accuracy analogue-to-digital
converter autocalibrates every cycle
against a high-stability reference.

Distribution of the processing


workload means that performance is
maintained, even with a full loading
of six streams. Local processing also
means that fast PID loops can be
implemented for control purposes.

Typical gas orifice application

6
Outstanding access and security

In addition to front panel operation, the FloBoss S600


can be accessed over the internet through its Ethernet
port. This gives users the ability to remotely view
reports, displays, and diagnostics as well as read and
change data from almost anywhere in the world.

Advanced security protocols control user access or


limit the number of viewable and changeable items
according to the user’s security access level.

Navigation is made simple through a logical menu


system and many of the screens present the data points
in a format identical to the front panel display.

This offers great consistency between all types of user


interface and makes the FloBoss S600 easy to use.

7
Count on Emerson
Doing business with Emerson Process Management gives you the confidence that the products, services and
solutions you buy are backed by our unmatched global support. And, Emerson’s industry expertise will help
you achieve the performance and profitability goals you are measured by.

The information and support you need can be as close as your telephone or web browser, or right around the
corner. With over 600 locations in more than 85 countries, chances are we have an office near you.

Technical support for your ROC, FloBossTM, and related products is also available directly from the Internet with
SupportNetTM Technical Services. Whether you need software or firmware updates, or just have a technical
question, SupportNet can make your job easier. And best of all, SupportNet is available to you 24 hours a day,
seven days a week.

SupportNet gives you an easy and convenient means to get answers to technical questions or solutions to
product problems. You have access to our extensive knowledge base of information, as well as to our factory-
trained technical support team. You also have access to e-learning modules that provide audio-visual training
on a variety of topics.

You can enjoy even more benefits with SupportNet Express or SupportNet Plus, subscription services that let
give you valuable on-line tools designed to meet your technical support needs.

© 2001 - 2007, Remote Automation Solutions, division of Emerson Process


Management. All rights reserved.

Bristol, Inc., Bristol Babcock Ltd, Bristol Canada, BBI SA de CV and the Flow Computer
Division , are wholly owned subsidiaries of Emerson Electric Co. doing business as
Remote Automation Solutions (“RAS”), a division of Emerson Process Management.
ROC, FloBoss, ROCLINK, Bristol, Bristol Babcock, ControlWave, TeleFlow and Helicoid
are trademarks of RAS. AMS, PlantWeb and the PlantWeb logo are marks of Emerson
Electric Co. The Emerson logo is a trademark and service mark of the Emerson Electric
Co. All other marks are property of their respective owners.

The contents of this publication are presented for informational purposes only. While
every effort has been made to ensure informational accuracy, they are not to be
Remote Automation Solutions construed as warranties or guarantees, express or implied, regarding the products or
Pickering, North Yorkshire, UK services described herein or their use or applicability. RAS reserves the right to modify
Phone: +44 (0) 1751 471 818 or improve the designs or specifications of such products at any time without notice.
Fax: +44 (0) 1751 471 801 All sales are governed by RAS’ terms and conditions which are available upon request.
E-mail: fcd.tech-support@emersonprocess.com RAS does not assume responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use and maintenance of any RAS product remains
www.EmersonProcess.com/remote solely with the purchaser and end-user.

Remote Automation Solutions


D350857X012 / Printed in USA / 4-07

8
7:S600
Specification Sheet June 2009

FloBoss™ S600 Flow Manager


The FloBoss S600 Flow Manager is a panel-mount All metering calculations are performed using 64-
flow computer designed specifically for bit (double) precision floating point numbers for the
hydrocarbon liquid and gas measurement where highest accuracy. Cumulative totals are stored in
versatility and accuracy matter. The standard three separate memory locations (Tri-reg format)
features of the unit make it ideal for fiscal for maximum integrity. The user language
measurement, custody transfer, batch loading, and Logicalc™ also allows double precision
meter proving applications. The unit allows mathematical functions to be performed on the
configuration of multi-stream, multi-station database objects.
applications, enabling you to simultaneously meter
The reliability of the analog performance of the
liquids and gasses.
FloBoss S600 allows longer intervals between
The FloBoss S600 Flow Manager is designed for calibration checks.
use either as a stand alone Flow Computer or as a
The FloBoss S600 Flow Manager offers multiple
system component. The base unit is supplied with
communication interfaces:
a single Input/Output (I/O) board and can be used
for both gas and liquid applications. The I/O ƒ One or two Ethernet 10baseT ports. An
capability of the single I/O board is detailed on optional second Ethernet port can be added if
Page 5, but is generally suitable for 2 of 3 streams required.
and a header. Additional I/O boards can be added
ƒ HART communication is facilitated using a 12-
(maximum of 3) to enable a single FloBoss S600
to handle up to 10 streams and up to 2 headers, channel HART board, supporting point-to-point
with both Gas & Liquid in a single machine. Orifice, and multi-drop architectures (up to 50
transmitters).
ultrasonic, turbine, positive displacement, Coriolis,
Annubar, Venturi, and V-Cone flow meter types ƒ An embedded webserver allows remote
are all supported. access to the flow computer. Security is
provided by way of user name and password
The Floboss S600 uses distributed processing to protection with a detailed event log for audit
achieve maximum performance. The main CPU ®
purposes. Supports Windows Internet
incorporates a hardware floating point processor. ®
Explorer version 5 or greater.
Each additional card also has local processing to
ƒ Two configurable EIA-232 (RS-232) serial
convert inputs and output from engineering units to
ports for connection to a printer or RTU.
field values and vice-versa, as well as running
background tests and PID loops. ƒ Three EIA-422/485 (RS-422/RS-485) serial
ports (up to 38400 bps baud) for connection to
intelligent meters, Modbus SCADA data
networks, or a DCS Supervisory System.
ƒ One dedicated configuration port for
connection to the Config600 configuration
software.
Use the software interface (Config600 Lite,
Config600 Lite+, or Config600 Pro) to upload and
download configurations. You can also create or
edit configuration files using Config600 Lite+ and
Config600 Pro (refer to the Config600 specification
sheet, 4:C600). Finally, the keypad interface on
the S600/webserver enables you to review or
modify system parameters.
Continued on Page 2
D301151X412

FloBoss S600 Flow Manager

Remote Automation Solutions


Website: www.EmersonProcess.com/Remote
7:S600
Specification Sheet Page 2

Base Unit Specifications


ENCLOSURE DISPLAY-KEYPAD
Painted, welded steel outer case with plastic front Graphics Display: LCD 128 x 64 pixel (8 lines of
panel. 20 alpha-characters) with LED backlight, using
Classification: IP50 from front panel. a Toshiba T6963 LCD controller.
Dimensions Alarm/Status: 3 color LED: green, amber, red.
Case: 84.5 mm W by 270 mm H by 303.8 mm Keyboard: 29 self-colored silicon rubber keys
D (3.327 in. W by 10.63 in. H by 11.94 in. D). with tactile feel.
Display Keypad Moulding: 85 mm W by 269 Configuration Port: RJ12 connector for the
mm H by 28 mm D (3.35 in. W by 10.59 in. H Config600 package on the bottom of the front panel
by 1.10 in. D). moulding.
Panel Cutout: 66 mm W x 150 mm H (2.6 in.
W by 5.9 in. H) with ±1 mm tolerance. POWER REQUIREMENTS
Supply Voltage: 20-32 V dc, 24 W nominal, 48 W
Pitch Between Cases: 110 mm (4.33 in.)
maximum.
giving 25 mm (0.98 in.) air gap.
Typical: 18 W with 1 I/O board.
Max Panel Thickness: 10 mm (0.39 in.).
24 W with 2 I/O boards.
Weight: 4.3 kg (9.48 lb) approximate with a 36 W with 3 I/O boards.
single I/O board space configuration.
Protection: 2.5 A anti-surge fuse.
Circuit Boards: Eurocard-compatible, slide in and
Inrush Current: Thermistor protection providing 6
out from the rear.
A at 25ºC.
Access: Allow 300 mm (11.81 in.) clearance
Supply Isolation: Three-way, galvanically
directly behind case for maintenance.
isolated from input to computer, supply and
Operating Temperature: 0°C to 60°C (32°F to ground, 50 V.
140°F).
Hold-up Period: 4 ms after power fail flag.
Storage Temperature: –40°C to 70°C (–40°F to
Maximum Input Ripple: 2 V pk-pk.
158°F).
Input Power Fail Flag: 17-19 V dc.
Relative Humidity: 90% non-condensing.
Power Outputs: 24 V dc, 500 mA; 15 V dc,
Safety Classification: For use in a classified safe
100 mA. 50 V dc isolation. The outputs are
electrical area.
together isolated from the supply voltage and
EMC: Complies with the following European Union from the computer.
EMC regulations.
Emissions: EN55022-B.
Immunity: EN61000-4, IEC-EN 61000-6-2.

Continued from Page 1


The FloBoss S600 Flow Manager provides the ƒ K factor or Meter Factor linearization.
following functions through the Config600 ƒ Valve monitor/control.
configuration tool:
ƒ Sampler control.
ƒ Stream and station totalization.
ƒ Station densitometer.
ƒ Batch totalization and correction.
ƒ Station gas chromatograph.
ƒ 3-term PID control.
ƒ Forward, reverse and error totals.
ƒ Flow balancing.
ƒ Comprehensive maintenance mode.
ƒ Flow scheduling.
ƒ Coriolis meter interface.
ƒ Automatic proving sequence.
ƒ Ultrasonic meter interface.
ƒ Supports Modbus/TCP or Modbus over
Ethernet.
7:S600
Specification Sheet Page 3

CPU and Calculation Specifications


CPU CAPABILITY CALCULATIONS
Processor: 50 MHz. Gas: AGA 3 (Volume and Mass), AGA 5, AGA 7,
Memory: 16 MB DRAM, 2 MB SRAM (battery- AGA 8, AGA 10, GPA 2172 & 2145, ISO 5167,
backed), 4 MB Flash. ISO 6976, ISO12213 – 2 & 3,
Real-Time Operating System: Wind River GOST 8.563.1 & 2 (97), GOST 8.586,
VxWorks. GOST 30319, PR 50.2.019, NX 19,
Battery Backup (SRAM) NX 19 Mod, S-GERG, M-GERG,
VDI/VDE 2040, PTZ, Annubar, V-Cone.
Charging time: 48 hours (20%-80%).
Hold-up Time (without recharge): 3 months at Liquid: API 2540 (Tables 5, 5A, 5B, 5D, 6, 6A,
20°C, 1 month at 40°C. 6B, 6C, 6D, 23, 23A, 23B, 23D, 23E, 24, 24A,
Battery Life (Typical): 5-7 years. 24B, 24C, 24D, 24E, 53, 53A, 53B, 54, 54A,
54B, 54C, 54D, 59A, 59B, 60A, 60B), API 11.1,
Battery Backup Hold Time (after battery has
API 11.2.1, API 11.2.1M, API 11.2.2,
failed its load test): 6 weeks at 20°C.
API 11.2.2M, API 11.2.4, API 12.2.1,
Form ‘C’ Watchdog Relay API 12.2.1M, API 12.2.2, API 12.2.2M,
Contact Form: Change-over contacts. ASTM D1555 & D1555M, GPA TP15, GPA
Max Current: 1 A. TP15M, GPA TP16, GPA TP25, GPA TP27,
Max Voltage: 50 V dc. Steam & Water IAPSW 1967, NPD, Propylene
Maximum Power: 30 VA. API 11.3.2.2, Ethylene IUPAC, NIST 1045 &
API 11.3.2.1, Downer, ISO 91/1 (IP2), ISO 91/2
Control: Released on de-power, or watchdog (IP3).
restart, or software-controlled.
Clock Facilities Solartron/MicroMotion densitometer algorithms,
Type: Battery-backed calendar clock. Sarasota/PEEK densitometer algorithms.
Watchdog Period: 2.5 seconds maximum. Prover: Compact, uni-directional, bi-directional,
Clock Accuracy master meter, dual chronometery. Support for
Powered On: 0.5 seconds per day. 1, 2, or 4 sphere switches. Each S600 can
support up to two provers.
Battery Supported: 10 seconds per day.
APPROVALS AND COMPLIANCES
Available with European CE Mark.
MID MI-002 (Gas) & MI-005 (Liquid) of European
Directive 2004/22/EC
OIML R117 & OIML R117-1
EN12405 For EFM devices compliant.
Approved by NMI (Netherlands Measurement
Institute, CMI (Czech Metrology Institute), OMH
(Hungarian National Office of Measure), BRML
(Romania), SDM (France) GOST (Russia) SMU
(Slovak Republic), CSA (Canada), PAC (China),
DMDM (Serbia), INMETRO (Brazil), GOST-K
(Kazakhstan) and OMNL (Algeria).
7:S600
Specification Sheet Page 4

Communication Specifications
COMMUNICATION RS232 Ports (Ports 3 & 4)
Connector: FCC-68 RJ45.
Configuration Port (located on the bottom of the
front panel) Communication Standard: RS232D.
Connector: 6-pin RJ12. Signals Supplied: Tx, Rx, RTS, CTS, DTR,
Communication Standard: RS232D. DSR, GND, DCD.
Signals Supplied: Tx, Rx, CTS, GND. Baud Rate:300, 600, 1200, 2400, 4800, 9600,
19200, 38400.
Baud Rate: 300, 600, 1200, 2400, 4800, 9600,
Format: Software configurable.
19200, 38400.
Format: Config600 Protocol. Data Protocol: ASCII, MODBUS (ASCII,
RTU).
Ethernet (Ports 1 & 2)
RS422/RS485 Ports (Ports 5, 6, & 7)
Port 1: Standard.
Connector: standard screw terminals, 3.5 mm
Port 2: Optional, with P190 board installed. pitch, 13-pin.
Speed: 10 Mbit/second. Communications: RS422 - point-to-point - 4
Media Connectivity: 10baseT, twisted pair wire RS422 – multidrop (RS485 4 wire) - 4
utilizing standard RJ45. wire RS485 - multimaster - 2 wire.
Protocol: Modbus/TCP or Modbus over Signals Supplied: Tx+, Tx-, Rx+, Rx-,
Ethernet. common shield.
Baud Rate: 300, 600, 1200, 2400, 4800, 9600,
19200, 38400.
Format: Software controlled on each channel.
Data Protocol: ASCII, MODBUS (ASCII,
RTU).
7:S600
Specification Sheet Page 5

Expansion Boards
The FloBoss S600 is supplied with one P144 I/O board and one P148 Pulse Mezzanine as standard. There
are two additional slots available to accept additional expansion boards, these can be the following:
P144 I/O Board – Provides the S600 with additional analog and digital I/O.
P148 Pulse Mezzanine – Provides pulse input capability. Fits on P144 and P154 boards and does not
use an additional slot.
P154 Prover board – For applications with a prover.
P188 HART board – For applications with HART transmitters.
P190 2nd Ethernet board – Provides a second Ethernet port.
Details of these optional boards are as follows:

P144 I/O BOARD (1 standard, additional boards are P154 PROVER BOARD (continued)
optional) Digital Outputs
Analog Inputs Quantity: 12
Quantity: 12 Pulse Inputs-Flow/Turbine (requires Pulse
Analog Outputs Mezzanine board)
Quantity: 4 Quantity: 2 dual pulse or 4 single pulse.
Digital Inputs Frequency Density Inputs:
Quantity: 16 Quantity: 2
Digital Outputs Pulse Outputs
Quantity: 12 Quantity: 4
Pulse Inputs-Flow/Turbine (requires Pulse Raw Pulse Input
Mezzanine board): 2 dual pulse or 4 single Quantity: 3
pulse. Phase Loop Lock Input
Frequency Density Inputs: 3. Quantity: 2
PRT (RTD) Inputs: 3, 4-wire. Switch Detect
Pulse Outputs: 5. Quantity: 4
Raw Pulse Output: 1, Raw pulse output for
proving, 0 to 5 kHz. P188 HART BOARD (optional)
Supports dual master (primary or secondary), read
P148 PULSE MEZZANINE (1 standard, additional only (can not be used to change constants on the
boards are optional) HART board). Does not support burst mode.
Fits on P144 and P154 boards to provide pulse Quantity: 12 Channels. Each channel can be
input capability. configured for point-point or multi-drop
Quantity: 2 dual pulse or 4 single pulse. communications. In multi-drop mode, each
Note: The P148 Pulse Mezzanine board fits on channel can support up-to 8 transmitters
a P144 or P154 board and does not use an Max. Number of HART Transmitters: 50.
additional slot.
P190 ETHERNET BOARD (optional)
P154 PROVER BOARD (optional)
Compact, uni-directional, bi-directional, master Adds a second Ethernet port to the S600. Refer to
meter, dual chronometry. Up to 4 sphere switch. the Ethernet section of the Communication
Specifications table for more information.
Digital Inputs
Quantity: 32
7:S600
Specification Sheet Page 6

Input Specifications
ANALOG INPUTS PULSE INPUTS-FLOW/TURBINE
Type: 1 to 5 V, 0 to 5 V, 4 to 20 mA, or 0 to 20 Requires Pulse Mezzanine board to be fitted to a
mA, opto-isolated. Two groups of 5 single- P144 or P154 board.
ended voltage or current inputs with each Type: Dual pulse or single pulse train, opto-
group sharing a common return; channels 11 isolated.
and 12 are current input only. Signal Level: ±3.5 V to ±24 V, minimum 5 mA.
Signal Level: 0 to 5.125 V or 0 to 22 mA. Frequency Range: 0 to 10 kHz.
Scan Rate: All channels can be acquired in less Security Monitoring: IP 252/76 (ISO 6551),
than 1 second. level A or B.
Resolution: 24 bits, auto-zero, auto-calibrate.
Conversion Time: Less than 100 ms per DIGITAL STATUS INPUTS
channel. Type: 16 opto-isolated inputs, arranged in 4
groups of 4 with common positive connection
Series Mode Rejection: >100 dB at 50 Hz and
to allow simple interface to open collector
60 Hz.
outputs.
Voltage Common Mode Range: ±50 V as a
Max Input Voltage: 30 V.
group relative to computer ground.
Min Input On Voltage: 12 V.
Common Mode Rejection: >100 dB at 50 Hz
and 60 Hz. Max Input Off Voltage: 3 V.
Input Impedance: >10 MΩ (voltage mode), Input Impedance: 2-2.5 kΩ typical.
approx 250 Ω (current mode). Protection: Reverse voltage protection.
Calibration Period: 2 years to 0.005% of PRT (RTD) INPUTS
voltage; 5 years to 0.01% of voltage. Type: 4 wire connection using Pt 100
A/D Converter Inputs Voltage Mode transducers, opto-isolated.
Type of Inputs: Single-ended voltage inputs. PRT (RTD) Resistance: 100 Ω [Pt 100 to IEC
Input Range: 0 to 5.2 V. 751/DIN 43760 (Europe 0.00385), IPTS68
Accuracy: ±0.005% of FSD at 23°C (73°F). (American 0.00392), Calendar-Van Dusen].
Ambient Temperature Effect: ± 7 ppm/°C (± 4 Excitation Current: 1 mA nominal.
ppm/°F) from 23°C (73°F) in the range 0 to Measuring Range: 60 to 216 Ω (–100°C to
45°C (32 to 113°F). +300°C) (–148°F to +572°F).
A/D Converter Inputs Current Mode Resolution: 0.01°C (0.018°F).
Type of Inputs: Single-ended current inputs. Accuracy: –100°C to 200°C (–148°F to 392°F) ±
Input Range: 0 to 22 mA. 0.01% –200°C to 300°C (392°F to 572°F) ±
Accuracy: ± 0.02% of FSD at 23°C (73°F). 0.02%.
Ambient Temperature Effect PRT (RTD) Cables: Core resistance up to 600 Ω.
± 10 ppm/°C (± 5.5 ppm/°F) from 23°C in the Barriers: 9 V, 100 Ω are satisfactory.
range 0 to 45°C (32 to 113°F). Security: Continuous cable/PRT (RTD)
integrity tests for earths/open circuits.
FREQUENCY/DENSITY INPUTS
Type: dc coupled, opto-isolated.
Signal Level: 3 V min pk-pk.
Maximum Input Voltage: 12 V pk-pk.
Current Limit: Internally limited to 3 mA.
Frequency Range: 0 to 10 kHz.
Accuracy of Frequency Measurement: 10
ppm.
Resolution: 5 nanoseconds.
7:S600
Specification Sheet Page 7

Output Specifications
ANALOG OUTPUTS PULSE OUTPUTS
Type: 4 to 21 mA outputs, opto-isolated. Type: Opto-isolated open-collectors.
Resolution: 12 bit minimum. Frequency Range: 0 to 100 Hz.
Accuracy: ± 0.1% at 23°C (73°F). Max Output Current: 100 mA.
Ambient Temperature Effect: 20 ppm/°C Max Output Saturation Voltage: 1.5 V @ 100
(11ppm/°F) from 23°C (73°F). mA.
Load Loop Resistance: 650 Ω maximum when Low Current Saturation Voltage: 600 mV @ 1
powered by local isolated source, 470W 1000W mA to suit TTL style input.
when powered from +24 V external supply. Max Output Standoff Voltage: 42 V (limited by
Maximum External Supply: 32 V. Transorb).
Output Form: Controlled active current sink to
RAW PULSE OUTPUTS
ground return of local floating supply.
Type: Digital ground-referenced open-collector.
Number of Field Connections: 3 terminals per
Gating: Software controlled.
channel.
Max Output Saturation: 1.5 V.
Update Time: 100 ms to within 1%.
Max Output Standoff Voltage: 26 V (limited by
DIGITAL OUTPUTS Transorb).
Type: 3 groups of 4 with common negative, Max Output Current: 100 mA.
opto-isolated. Frequency Range: 0 to 5 kHz.
Frequency Range: 0 to 0.5 Hz. Minimum On Period: 100 µs (microseconds).
Max Output Saturation Voltage: 1.5 V @ 100 Use: To bus together several streams to a
mA. common prover computer.
Low current Saturation Voltage: 600 mV @ 1
mA to suit TTL style input, with 4.7 kΩ pull up to
5 V.
Max Output Standoff Voltage: 42 V (limited by
Transorb).
Max Output Current: 100 mA.
Reset/Power on State: All digital outputs – OFF.
7:S600
Specification Sheet Page 8

Bristol, Inc., Bristol Canada, BBI SA de CV and Emerson Process Management Ltd, Remote Automation Solutions division (UK),
are wholly owned subsidiaries of Emerson Electric Co. doing business as Remote Automation Solutions (“RAS”), a division of
Emerson Process Management. FloBoss, ROCLINK, Bristol, Bristol Babcock, ControlWave, TeleFlow and Helicoid are trademarks
of RAS. AMS, PlantWeb and the PlantWeb logo are marks of Emerson Electric Co. The Emerson logo is a trademark and service
mark of the Emerson Electric Co. All other marks are property of their respective owners.
The contents of this publication are presented for informational purposes only. While every effort has been made to ensure
informational accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or
services described herein or their use or applicability. RAS reserves the right to modify or improve the designs or specifications of
such products at any time without notice. All sales are governed by RAS’ terms and conditions which are available upon request.
RAS does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use
and maintenance of any RAS product remains solely with the purchaser and end-user.
Emerson Process Management
Remote Automation Solutions
Marshalltown, IA 50158 U.S.A.
Houston, TX 77041 U.S.A.
Pickering, North Yorkshire UK Y018 7JA

© 2002-2009 Remote Automation Solutions, division of Emerson Process Management. All rights reserved.