SI-WX-0213

File In/With: ECN LW12-0092


New 0413

Equipments Affected: LYS Heat Pumps


Service Information Subject: Software Enhancements for LYS-HP
(LYS-HP 10V15)

General
Beginning Mar. 16, 2012, enhanced software is supplied in new production LYS heat pumps.
New version number is LYS-HP 10V15.
Software Version No. Controller Equipments Micro-board P/N
LYS-HP 10V15 PLC LYS Heat Pumps 025W39725-001

Changes
I. Low Evaporator Pressure-Unload Pressure & Low Evaporator Pressure-Alarm
Pressure
When R134a refrigerant is used in LYS heat pump, low evaporator pressure-unload pressure and low
evaporator pressure-alarm pressure are changed from set value into fixed value.
Fixed values are as below:
Low Evaporator Pressure-Unload Pressure: 183 kPa
Low Evaporator Pressure-Alarm Pressure: 173 kPa
Note: When ITS mode is enabled, the unit does not execute unload logic when evaporator
pressure is low.
When R22 is applied, both parameters are still programmable and adopt original setting range.
II. Low Leaving Chilled Liquid Temperature Protection
When smart freeze protection is disabled, leaving chilled liquid temperature cannot be lower than
2.2℃.
When smart freeze protection is enabled, leaving chilled liquid temperature cannot be lower than
1.1℃.
In brine mode, leaving chilled liquid temperature cannot be lower than -14.4℃.

YORK(Wuxi) Air Conditioning & Refrigeration Co., Ltd. 1