Performance Data

Model: TC-120
Tag/Reference #: TCV120 460V /
Qty: 1
General Information
Unit Configuration: Vertical Upflow
Operating Weight: 698 lbs.
Unit Length/Width/Height: 29.0/41.0/69.8 inches
Systems Information
Fluid Flow F/P: 25.00 / 0.00 GPM Altitude: 0 Feet
Fluid Type: Water Antifreeze Percent: 0 %
Entering Conditions
Cooling Heating
Entering Air Dry Bulb: 80.0 °F 68.0 °F
Selected Options
Entering Air Wet Bulb: 67.0 °F
Top Discharge, PSC Motor
Entering Water/Fluid: 85.0 °F 70.0 °F
Standard RPM & Standard Motor
Operating Performance
Uncoated Air Coil, Copper Water Coil
Cooling
Total Capacity: 121.9 MBH 168.0 MBH
Sensible Capacity: 88.9 MBH
Input Power: 9.47 kW 10.56 kW
Effeciency: 12.9 EER 4.7 COP
Part Load %: %
Full Load %: %
Unit Performance
Full Cooling Full Heating
Air Flow: 4000 CFM 4000 CFM
Total Capacity: 121.9 MBH 168.0 MBH
Sensible Capacity: 88.9 MBH
Heat of Rejection: 154.2 MBH
Heat of Absorption: 131.9 MBH
Leaving Air Dry Bulb: 59.4 °F 106.9 °F
Leaving Air Wet Bulb: 57.2 °F
Leaving Fluid Temp: 97.3 °F 59.5 °F
Fluid Pressure Drop: 15.1 ft. H2O 16.0 ft. H2O
Input Power: 9.5 kW 10.6 kW
Efficiency: 12.9 EER 4.7 0.0 COP
Unit Electrical Data
Unit Amps - FLA Min. Cir. Amps - MCA Max. Fuse Size - MFS
460/60/3 19.7 21.7 25
Fan Performance
Fan Motor BHP: 2.27 BHP
Fan Motor RPM: 1085 RPM
Sheave: A
Turns: 2.00
External Duct Static: 0.8 in. H2O
Motor / Compressor Data
Qty FLA (ea.) RLA (ea.) LRA (ea.)
Fan Motor 1 4.10
Compressor 2 7.80 52.00