You are on page 1of 2

Performance Summary for Soba za igru

Project:
Prepared By: 11:52PM

42NH Ductable in room Fan Coil with Multi Speed Motor


System Operation: 2 Pipe Changeover - System Fluid:1 Flow for Cooling and Heating

Selection Conditions 42NH425FE----- Heating Mode


Cooling Mode Room Air Temperature (db): 19.0 °C
Room Air Temperature (db): 24.0 °C Room Air Relative Humidity: 54.0 %
Room Air Relative Humidity: 65.3 % Entering Fluid Temperature: 65.0 °C
Entering Fluid Temperature: 7.0 °C Fluid Type: Water
Fluid Delta T: 5.0 °K
Fluid Type: Water System Curve Design
External Static Pressure: 50 Pa
Sound Attenuation External Static Pressure Apply To: R2
Room Attenuations: 9.00 dB
Ceiling and Duct Attenuations: 8.00 dB

Performance 42NH425FE-----

Fan Speed High Speed Medium Low Speed


Speed
Multi Speed units R1 R2 R3 R4 R5
Air Flow Rate m3/h 1006 939 801 590 397
External Static Pressure Pa 57 50 36 20 9
Cooling Mode
Total Capacity kW 4.59 4.42 4.01 3.22 2.32
Sensible Capacity kW 3.06 2.92 2.62 2.07 1.47
Supply Air Temperature °C 15.9 15.7 15.3 14.6 14.0
Fluid Flow Rate m3/h 0.79 0.76 0.69 0.55 0.40
Fluid Pressure Drop kPa 43 40 34 23 13
FCEER D
Heating Mode (water coil)
Total Capacity kW 10.10 9.63 8.55 6.59 4.52
Supply Air Temperature °C 49.8 50.4 51.7 53.1 53.8
Fluid Flow Rate m3/h 0.79 0.76 0.69 0.55 0.40
Fluid Pressure Drop kPa 33 31 26 18 10
FCCOP D
Electric Motor Consumption W 135 122 114 102 86
Noise Level
Lw : Sound power level dB(A) 63 62 60 55 48
Lp: Sound pressure level dB(A) 46 45 43 38 31
NR Level NR 41 40 38 34 28
Dimensions (HxWxD) mm 234x1115x511

Note:
Sound Power Levels according to ISO 3741. Sound pressure level, NR and NC are based upon hypothetical acoustic attenuation for the room and air diffusion sub-
system.
The accuracy of the above data is +/-2dB(A). All dimensions include Water valve factory fitted as maximum unit dimensions, for installation safety.
If the product is supplied without a Carrier control device, verification of EMC conformity is the responsibility of the installer or control integrator.

CARRIER participates in the ECP program for Fan Coil Units (Ducted and non Ducted). Check ongoing validity of certificate: http://www.eurovent-
certification.com

EMEA Fan Coil Builder 3.05 Page 1 of 2


Performance Summary for Soba za igru
Project:
Prepared By: 11:52PM

Accessories and Installed Options 42NH425FE-----

Option Description
Part Number 42NH425FE-----
Base Unit 42NH425
Coil 2 Pipe Changeover
Return Plenum: Without
Supply Plenum: Without
Coil Hand: Left
Power: None
Hydronic Fittings: None
Indoor Air Quality: G1
Return Spigot Diameter: Without
Control: Electrical box without control
Fresh Air: Without
Fresh Air Side: Without
Valve Actuators: Without Valve Actuators
Packaging: Individual Packaging
Supply Spigot Diameter: Without
Motor Drive: Multi-speed
Factory Speeds Wired: Standard (531)

EMEA Fan Coil Builder 3.05 Page 2 of 2