Professional Documents
Culture Documents
Abstract
Detailed information on drainage system design is included in the Civil and Struc-
tural Manual, Section 500. This section discusses design considerations for
drainage systems related to fire protection. A well designed drainage system:
• Contains spills, preferably in a closed system.
• Carries oil spills, rainwater, and fire water to a safe location where the spill can
be retained and recovered.
• Minimizes the spread and area of exposure from spills and fires in process
plants, tank fields, marketing terminals, chemical plants, production platforms,
etc.
This section covers drainage for process facilities. For other types of facilities, see
Sections 3100 to 4100. For drainage around tanks and in tank fields, see the Tank
Manual.
Contents Page
• Slopes should range from 3/16 inch per foot to 1/4 inch per foot for paved
areas. Absolute minimum and maximum slopes are 1/8 inch per foot and 1/2
inch per foot. Around pumps and other areas where leaks are anticipated, 1/4
inch per foot is preferred.
• Drainage patterns should minimize ponding of runoff near equipment and
prevent drainage from unpaved areas from entering drain hubs in paved areas.
• All areas under process equipment should be paved to assure that liquids drain
away from equipment and do not pool.
Drainage Trenches
Do not install open drainage trenches in areas where liquid hydrocarbon spills can
occur. Hydrocarbon liquid can enter the trench and spread from one area of a plant
to another. Burning liquid can also spread through the plant in trenches, increasing
the magnitude of a fire.
• Onplot main headers of both oily and clean water systems may enter other
main drain lines without gas seals if gas-sealed catch basins or gas-sealed
manholes are used at upstream junctions.
• Main lines leaving a plot limit must be gas-sealed at the first offplot manhole.
Typical onplot drainage layouts and design calculations are given in Section 500 of
the Civil and Structural Manual.
For fire protection purposes, drainage systems that may contain flammable vapors
should be sealed both onplot and offplot. Otherwise, toxic and flammable gases
may be released in an area well away from where the release occurred. Seal oil-
water separators from both the inlet and outlet drainage lines. Unless drainage lines
are sealed, fire and explosions could propagate through the system from offplot
back to the separators.
1427 Vents
Vent manholes (usually with 2-inch pipe) at an elevation 18 inches above the
highest line or equipment within a 10-foot radius. The vent should be at least 12
feet above grade or above any walkway or work platform within the 10-foot radius.
The vent should be at least 50 horizontal feet from furnaces. The vent opening
should point straight up.
Flame arrestors are generally not warranted in sewer system vents, and the system
pressure is not adequate to pass a water seal type. Catch basins in process plants
have only 3 to 4 inches of water seal. The water seal is designed to prevent vapor
releases and thus eliminate the need for flame arrestors.
See NFPA 30 and the Tank Manual for drainage and impounding requirements.
Fire Stops
Install a solid transverse barrier as a fire stop at 300- to 500-foot intervals in main
below-grade pipeways. This prevents a spill from a leaking line from spreading to
the entire pipeway. If the spill ignites, the barrier prevents the spread of fire to other
sections of the pipeway. Provide a drain inlet in each section of the pipeway to
carry away the flow of leaks and fire water if a fire should occur.
Daylighting of Piping
Check pipeways frequently and clear any piping that is contacting the soil to
prevent external corrosion and allow good drainage flow.
1450 References
1. Seelye, Elwyn E., Data Book for Civil Engineers—Design, Volume One.
2. Handbook of Concrete Culvert Pipe Hydraulics, Portland Cement Association.
3. Design Data, American Concrete Pipe Association.
4. Water Control Federation Manual of Practice No. 9 or ASCE Manual of Engi-
neering Practice No. 37, Design and Construction of Sanitary and Storm
Sewers.
Chevron References
Civil and Structural Manual, Section 500
Tank Manual