Professional Documents
Culture Documents
FEBRUARY 2, 1999
EIU Facilities Planning & Management
CAD Standards
TABLE OF CONTENTS
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Drawing Standards . . . . . . . . . . . . . . . . . . . . . . . . 7
Delivery of Media . . . . . . . . . . . . . . . . . . . . . . . . 18
2 rev5/27/99 cadguide
EIU Facilities Planning & Management
CAD Standards
PURPOSE
In an effort to develop and maintain accurate CAD files for the campus, Facilities
Planning & Management has established this set of guidelines to be used by the EIU
Planning Groups and consulting Architects/Engineers. It is important to maintain
accurate CAD files to facilitate university wide space analysis, sharing data with vendors,
and assisting maintenance shops in maintaining equipment and systems on the campus.
The existing CAD drawings were produced several years ago and have not had a Quality
Check performed on them. All remodeling projects in the foreseeable future will include
the requirement of the A/E to provide verified base plans until such time that all existing
buildings have received a Quality Check. The following guideline will establish
conventions for naming drawings, establishing layers, and defining space. Because this
guideline is in the development stage, it is expected to receive modifications in the next
several months and a revision date has been placed in the footer to insure that the most
current information is available for the use of architects and engineers.
This document is not intended to dictate the manner in which an architect or engineer
develops construction documents. Rather, its intent is to identify the needs of FP&M for
facilities management purposes. With this knowledge the A/E will be able to structure
the files so that a smooth transition from construction documents to management
documents can be attained. The layering convention is modeled after the American
Institute of Architects (AIA) published recommendations.
Questions regarding this guideline or requests for a copy should be directed to one of the
following people at Eastern Illinois University, Facilities Planning & Management, 600
Lincoln Avenue, Charleston, Illinois 61920.
cadguide rev5/27/99 3
EIU Facilities Planning & Management
CAD Standards
The EIU building ID, assigned by Facilities Planning & Management, is normally a two
digit number with an optional alpha-numeric character in the third position. The alpha-
numeric character is used to distinguish between building additions or separate structures
in the same complex. In the event that a building ID is a simple two digit number,
without an alpha-numeric character, the third position should be an under-score character.
The second half of the drawing name consists of four characters. If the drawing depicts a
floor plan then position four and five of the drawing name will indicate the floor and
positions six and seven will depict the drawing type. If the drawing diagrams the building
as a whole, the last four positions of the drawing name will indicate the type of drawing.
27_01BP
Drawing Type
Addition/Unit
Building ID
4 rev5/27/99 cadguide
EIU Facilities Planning & Management
CAD Standards
Drawing Type
The following drawing types have been established by FP&M for various building plans
that will be maintained for facilities management use. Other drawing types may be
established at later dates for inclusion in this list.
BP Base Plan: Basic building plan for planning and management use
FP Furniture Plan: Base Plan + furniture information
CL Reflected Ceiling: Base Plan + ceiling grid, lights, HVAC, & sprinkler system
PL Plumbing Plan: Base Plan + plumbing systems
ME Mechanical Plan: Base Plan + HVAC systems
EL Electrical Plan: Base Plan + electrical power & data/phone systems
Other drawing types that may be maintained for building management use are the
following:
SITE Site Plan: Architectural features of site work; parking, walks, etc.
UTIL Utility Site Plan: Site utility information
ELEV Building Elevations: Building Elevations w/ doors, windows, etc.
cadguide rev5/27/99 5
EIU Facilities Planning & Management
CAD Standards
The layer guidelines are organized as a hierarchy. This structure makes the list easier to
use and accommodates future expansion. Layer names are alphanumeric and use easy-to-
remember abbreviations. The layer guidelines are defined in two formats; a long format
using 6-16 characters and a short format using 3-8 characters. FP&M is still evaluating
the two formats to determine which will best satisfy our requirements. For the present,
FP&M will accept either format while we continue to evaluate the two formats. With
either format, the layers are separated into eight major groups and FP&M has added one
additional group for specific layer names used for facilities management needs. The nine
groups are identified by the first character of the layer names:
It is not the intent of Facilities Planning & Management to dictate how an A/E produces
documents within their office. Most A/E’s that have had projects at Eastern Illinois
University recently either now use a modified version of the AIA CAD Layer Guidelines
or, at least, are familiar with the system. When the project is closed out and record CAD
files are presented to FP&M the files should be such that a minimal amount of time will
be required to modify the layers so that they can be used as management tools by FP&M.
See “Delivery of Media” later in these guidelines.
FP&M will require certain features be on separate layers so that modification of layer
name, color, etc. can be made quickly.
The following layer structure will be used by FP&M for facilities management use. The
layer structure for the first eight groups are not repeated in this guideline since they are
well documented in the AIA CAD Layer Guidelines. The listed layers are those included
in the ninth group created specifically for university needs. Layers for hatching, details,
6 rev5/27/99 cadguide
EIU Facilities Planning & Management
CAD Standards
notes, etc. required for construction drawings will be turned off or deleted for building
management use.
cadguide rev5/27/99 7
EIU Facilities Planning & Management
CAD Standards
DRAWING STANDARDS
TYPICAL DRAWING SETTINGS
The following settings have been established and included in the FP&M prototype
drawings. These settings will be used in all facilities management drawings used by
FP&M. If files are not received from A/E’s in the following format, final close out of the
project will be delayed until FP&M has made the modifications to the files.
MENU Acad
VIEWRES 500
BLIPS Off
UCSICON Off
COORDINATES On
GRID Off
SNAP Off
COLOR By Layer
LINETYPE By Layer
UNITS
<ARCHITECTURAL>
<270> Direction for angle 0.00 (12 o’clock)
<Y> Angles measured clockwise
FONTS
All text in submitted CAD documentation should use the font ROMANS. Plotted size of
text for room names, dimensions, and notes should be 1/8” height. Plot size of text for
plan and detail titles should be 1/4” height. The intent is to provide legible text when
documents are reduced 50%.
BLOCKS
Coloring of entities in blocks should be set to BYLAYER. A block and its entities should
all be on the same layer. All attributes for blocks must be documented.
It is the preference of FP&M to not use xrefs. If xrefs are included in submitted CAD
files complete documentation, including path established in the original drawing must be
provided. If necessary, the A/E will provide a technician, on site, to de-bug any xref
8 rev5/27/99 cadguide
EIU Facilities Planning & Management
CAD Standards
insertions that may occur during the initial loading files at FP&M. FP&M will continue
to monitor and evaluate the use of xrefs as a facilities management tool.
Scale of drawings must be as indicated on the plans. The use of scale factors to increase
or decrease the size of drawing elements is not acceptable. Plans must be directly
scaleable without requiring a scale factor to be applied. If plans are blocked into files
with different scales then the original file must be available along with documentation.
TOLERANCES
Tolerances for acceptable CAD documentation are as defined in the Audit and Quality
Assurance section of this document with regard to completeness of recording features,
accuracy of measurements, and compliance with these standards.
cadguide rev5/27/99 9
EIU Facilities Planning & Management
CAD Standards
FCXX
room numbers 00 - 99
corridor numbers 0 - 9
Room numbers need not be consecutive. Even numbered rooms should appear on the
North and East side of corridors and odd numbered rooms should appear on the South
and West side of corridors. Room numbers should agree vertically, i.e., room 1145
should be beneath room 2145 regardless of the organizational differences between the
two floors. This will allow the addition of numbers between existing rooms as
remodeling occurs over the life of the building. In no case shall a letter suffix be used.
10 rev5/27/99 cadguide
EIU Facilities Planning & Management
CAD Standards
1. Gross Area
A. Definition
The sum of all areas on all floors of a building included within the outside
faces of its exterior walls, including floor penetration areas, however
insignificant, for circulation and shaft areas that connect one floor to
another.
C. Description
cadguide rev5/27/99 11
EIU Facilities Planning & Management
CAD Standards
D. Limitations
Exclude open areas such as parking lots, playing fields, courts, and light
wells, or portions of upper floors eliminated by rooms or lobbies that rise
above single-floor ceiling height.
E. Exception
A. Definition
The sum of all areas on all floors of a building assigned to, or available for
assignment to, an occupant or specific use.
C. Description
D. Limitations
3. Nonassignable Area
12 rev5/27/99 cadguide
EIU Facilities Planning & Management
CAD Standards
A. Definition
The sum of all areas on all floors of a building not available for
assignment to an occupant or for specific use, but necessary for the general
operation of a building.
C. Description
D. Limitations
A. Definition
The sum of all areas on all floors of a building used for custodial supplies,
sink rooms, janitorial closets, and for public rest rooms. Building Service
Area does not include assignable areas.
C. Description
cadguide rev5/27/99 13
EIU Facilities Planning & Management
CAD Standards
D. Limitations
Deductions should not be made for necessary building columns and minor
projections. Areas defined as central physical plant shop areas, or special
purpose storage or maintenance rooms, such as linen closets and
housekeeping rooms in residence halls, should not be included. Does not
include private rest rooms.
5. Circulation Area
A. Definition
The sum of all areas on all floors of a building required for physical access
to some subdivision of space, whether physically bounded by partitions or
not.
C. Description
Included should be, but is not limited to, public corridors, fire towers
elevators, elevator lobbies, tunnels, bridges, and each floor’s footprint of
elevator shafts, escalators and stairways. Receiving areas, such as loading
docks, should be treated as circulation space. Any part of a loading dock
that is not covered is to be excluded from both circulation area and the
gross building area. A loading dock which is also used for central storage
should be regarded as assignable area. Also included are corridors,
whether walled or not, provided they are within the outside facileness of
the buildings to the extent of the roof drip line.
D. Limitations
Deductions should not be made for necessary building columns and minor
projections. When determining corridor areas, only spaces required for
14 rev5/27/99 cadguide
EIU Facilities Planning & Management
CAD Standards
6. Mechanical Area
A. Definition
C. Description
D. Limitations
A. Definition
The sum of all areas on all floors of a building either assigned to, or
available for assignment to, an occupant or specific use, or necessary for
the general operation of a building.
B. Basis for Measurement
Net usable area is computed by summing the assignable area and the
nonassignable area.
cadguide rev5/27/99 15
EIU Facilities Planning & Management
CAD Standards
C. Description
D. Limitations
8. Structural Area
A. Definition
The sum of all areas on all floors of a building that cannot be occupied or
put to use because of structural building features.
C. Description
16 rev5/27/99 cadguide
EIU Facilities Planning & Management
CAD Standards
12.2.1
12.2.2
1. Two sets of 3.5” high density disks or CD ROM, properly labeled and formatted
with MS_DOS version 3.3 or later, containing CAD drawing files of the record
drawings. These files shall include all record drawings for which the architect
possesses corresponding CAD drawings and shall at least include the following
architectural record drawings: floor plans, exterior elevations, building sections,
plumbing systems, HVAC systems, electrical systems, and site plans. Files must
be in either AutoCAD Release 14 DWG format or in AutoCAD DXF format.
Any individual file on a “floppy disk” shall not exceed 1MB of data. If this is
unavoidable in isolated incidents, condensing software may be used, and all
executables of said software will be provided to the Owner. The AIA CAD Layer
cadguide rev5/27/99 17
EIU Facilities Planning & Management
CAD Standards
Guidelines as amended in the EIU Guidelines for CAD Projects shall dictate the
layer naming conventions unless otherwise stated in individual project programs.
It shall be understood that the CAD drawings themselves are not record drawings.
2. One set of mylar plots of the CAD drawings. These plots shall be regarded as
record drawings.
18 rev5/27/99 cadguide
EIU Facilities Planning & Management
CAD Standards
DELIVERY OF MEDIA
All drawing information should be submitted to EIU Facilities Planning & Maintenance
as described below. All drawing information submitted should be in accordance with the
Drawing Standards section of this document and must comprise stamped and signed
record drawings.
Electronic files shall be delivered on either a 3 1/2” disks or CD_ROM formatted using
Windows 3.3. The disks must be labeled with the following information:
EIU building number
EIU or CDB project number
Submittal date
Set label (i.e.; disk 1 of 3 )
A readme file shall be included on disk number 1 that contains the above information
along with an index of drawings that include drawing file name, drawing name, drawing
number within the set, scale, drawing date, and xref listing and their paths. A hard copy
of this readme file shall be delivered with the disks.
One Quality Control/Quality Assurance Checklist done in accordance with the Audit and
Quality Assurance section of this document.
cadguide rev5/27/99 19
EIU Facilities Planning & Management
CAD Standards
At the close of the project, FP&M’s project manager will conduct an audit that will
include comparing the CAD documents with the built project. A visual examination of
the CAD drawings will be conducted to ensure the presence, location, and approximate
dimensional accuracy of all significant features including, doors, windows, walls,
columns, stairs, ramps, and other general floor-plan layout items. Obvious errors or
omissions will be noted on a review sheet.
Depending on the results of the visual audit, the Project Manager may conduct field
verification of actual dimensions by measuring 10% - 15% of the useable rooms to
compare with the CAD drawings.
20 rev5/27/99 cadguide