You are on page 1of 2

General Specifications CPU Specifications Built-in RS-232/485 Port Specifications

Operating Temperature 0° to 60°C (32° to 140°F) Program Memory Type FLASH memory Port Name RS-232/RS-485 Serial Port
Storage Temperature -20° to 85°C (-4° to 185°F) User Data Memory Type Battery Backed RAM, User configurable Non-isolated serial port that can communicate via
Description* RS-232 or RS-485 (software selectable). Includes
Humidity 5 to 95% (non-condensing) RS-232, RS-485, Ethernet 10/100 BASE-T
Pluggable Option Module ESD protection and built-in surge protection.
Environmental Air No corrosive gases permitted (1Mbps throughput max), USB 2.0 Type B
Do-more Protocol (Default)
Vibration IEC60068-2-6 (Test Fc) Expansion Modules 2 expansion modules max Modbus RTU (Master & Slave)
Supported Protocols
Shock IEC60068-2-27 (Test Ea) ±2.6s per day typical at 25°C K-Sequence (Slave)
Real Time Clock Accuracy ASCII (In & Out)
Enclosure Type Open Equipment ±8s per day max at 60°C
1200, 2400, 4800, 9600, 19200, 38400, 57600, and
UL61010-2 - UL File # E185989 Canada and USA Programming Software Do-more Designer – Ver. 2.0 or higher Data Rates
Agency Approvals 115200
CE Compliant EN61131-2* Programming Cable Options BX-PGM-CBL
RS-232, 115200 bps, No Parity, 8 Data Bits, 1 Stop
Noise Immunity NEMA ICS3-304 Default Settings
Bit, Station #1
EU Directive See the “EU Directive” topic in the Help File
Terminal Block Connection Options Port Type 3-pin terminal strip 3.5mm pitch
Weight 190g (6.7 oz) Green LED is illuminated when active for TXD and
Terminal Block Kit, 90-degree screw type, Fits all BRX 10-point PLCs and Port Status LED
BX-RTB10 RXD
*Meets EMC and Safety requirements. See the D.O.C. for details. 16 point Expansion I/O Modules. Kit includes (2) 10-pin 3.8mm plugs.
Terminal Block Kit, 180-degree spring clamp type, Fits all BRX 10-point RS-485 Station Addresses 1-247
Power Supply Specifications BX-RTB10-1 PLCs and 16 point Expansion I/O Modules. Kit includes (2) 10-pin 3.8mm
plugs. Cable Recommendations
RS-232 use L19772-XXX from AutomationDirect.com
Nominal Voltage Range* 12–24 VDC RS-485 use L19827-XXX from AutomationDirect.com
Terminal Block Kit, 180-degree screw type, Fits all BRX 10-point PLCs
BX-RTB10-2 Replacement Connector ADC Part # BX-RTB03S
Input Voltage Range (Tolerance)* 10–36 VDC and 16 point Expansion I/O Modules. Kit includes (2) 10-pin 3.8mm plugs.

Maximum Input Voltage Ripple <+/- 10% ZIPLink PLC I/O cable, 20-position terminal block to 24-pin connector,
ZL-BX-CBL20 Pinout RS232 RS485
24AWG, cable length 0.5meter (1.6ft).

BX-DM1E-10ER3-D
TX
Maximum Input Power 14W GND

Cold Start Inrush Current 5A, 2ms ZIPLink PLC I/O cable, 20-position terminal block to 24-pin connector, RX RX/D-
1 GND GND
ZL-BX-CBL20-1
24AWG, cable length 1meter (3.3ft).
Maximum Inrush Current (Hot Start) 5A, 2ms TX/D+ 2 RX D-
Internal Input Protection
Reverse Polarity Protection and ZL-BX-CBL20-2
ZIPLink PLC I/O cable, 20-position terminal block to 24-pin connector,
24AWG, cable length 2meter (6.6ft).
RS232/RS485
3 TX D+ BRX MPU with Do-more! DM1 technology
Undervoltage
Removable connector included. 24 VDC required, serial port, Ethernet port, microSD slot,
Heat Dissipation 8.7W Max ZL-BX-CBL20-1P
ZIPLink PLC I/O cable, 20-position terminal block to pigtail connection, Discrete Input: 6-point, sink / source, Analog Input: 1-channel,
24AWG, cable length 1meter (3.3ft). * NOTE: When using RS-485, a terminator resistor is built-in and software selectable.
1500VAC Power Inputs to Ground current / voltage, Discrete Output: 4-point, relay, Analog Output:
Voltage Withstand (dielectric)
applied for 1 minute
ZL-BX-CBL20-2P
ZIPLink PLC I/O cable, 20-position terminal block to pigtail connection, CPU Mode Switch Functions 1-channel, current / voltage.
*Class 2 or LPS Power Supply required. 24AWG, cable length 2meter (6.6ft).
RUN position CPU is forced into RUN Mode if no errors are encountered. I/O Terminal Blocks sold separately.
ZL-RTB20 ZIPLink Two Level Feedthrough Module, 20-pole, 35mm, DIN mount.
RUN, PROGRAM and DEBUG modes are available. In this (See Terminal Block Connection Options table).
ZL-RTB20-1 ZIPLink Three Level Feedthrough Module, 20-pole, 35mm, DIN mount. TERM position position, the mode of operation can be changed through the
Do-more Designer Software. Document Name Edition/Revision Date
BX-DM1E-10ER3-D 1st Ed. RevD 1/18/2022
STOP position CPU is forced into STOP Mode.
Copyright 2021–2022, AutomationDirect.com Incorporated/All Rights Reserved Worldwide.

Dimensional Information 2.41


Terminal Block Connector Specifications Built-in Ethernet Specifications WARNING: To minimize the risk of potential safety problems, you
[61.2]
Part Number BX-RTB03S BX-RTB10 BX-RTB10-1 BX-RTB10-2 Port Name ETHERNET should follow all applicable local and national codes that regulate the
3.59″ 1.25″
Spring Clamp Screw Type- installation and operation of your equipment. These codes vary from
[91.1mm] [31.9mm]
Connector Type Screw Type-90° Screw Type-90° Description Standard transformer isolated Ethernet port with built-in
Type-180° 180° surge protection.
area to area and it is your responsibility to determine which codes
Wire Exit 180° 180° 180° 180° should be followed, and to verify that the equipment, installation, and
Transfer Rate 10Mbps (Yellow LED) and 100Mbps (Green LED)
Pitch 3.5mm 3.81mm 3.81mm 3.81mm
operation are in compliance with the latest revision of these codes.
LED is solid when network LINK is established. LED Equipment damage or serious injury to personnel can result from
Screw Size M2 M2 N/A M2
Port Status LED flashes when port is active (ACT). the failure to follow all applicable codes and standards. We do not
4.25″
4.41″ [107.9mm] Recommended <1.77 lb·in <1.77 lb·in <1.77 lb·in Do-more! Protocol guarantee the products described in this publication are suitable for
[112.1mm] N/A
Screw torque (0.2 N·m) (0.2 N·m) (0.2 N·m) Ethernet Remote I/O your particular application, nor do we assume any responsibility for
Screwdriver Blade Modbus TCP/IP (Client & Server)
2.5mm 2.5mm 2.5mm 2.5mm your product design, installation, or operation.
Width EtherNet/IP (Explicit Messaging)
Wire Gauge
Supported Protocols HOST ECOM (DirectLogic), HTTP If you have any questions concerning the installation or operation
(Single Wire)
28-16 AWG 28-16 AWG 28-18 AWG 30-16 AWG
SMTP (Email), SNTP (Time Server) of this equipment, or if you need additional information, please call
30-20 AWG TCP/IP, UDP/IP (Raw packet) Technical Support at 770-844-4200.
#8 Thru all (3 Places)
Wire Gauge (Dual (Dual Wire MQTT This publication is based on information that was available at the
Mounting Restrictions Wire)
28-16 AWG 28-16 AWG
Ferrule
30-18 AWG
C5E-STxxx-xx from AutomationDirect.com time it was printed. At AutomationDirect.com® we constantly strive to
Required)
Cable Recommendation
improve our products and services, so we reserve the right to make
Port Type RJ45, Category 5, 10/100 BASE-T, Auto Crossover
OK Wire Strip Length 0.24in (6mm) 0.24in (6mm) 0.35in (9mm) 0.26in (6.5mm) changes to the products and/or publications at any time without notice
Equiv. Dinkle part # EC350V-03P-BK EC381V-10P-BK ESC381V-10-BK EC381F-10P-BK Ethernet Port Numbers: and without any obligation. This publication may also discuss features
MODBUS TCP/IP 502, TCP that may not be available in certain revisions of the product.
EtherNet/IP (Explicit Messaging) 44818, TCP
CPU Status Indicators
HOST ECOM 28784, UDP
Indicator Status Description
Do-more Protocol 28784, UDP
OFF Base Power OFF
2″ (50mm) 2″ (50mm)
Minimum from Minimum PWR Green Base Power ON
AIRFLOW Enclosure from Wire Duct
Yellow
OFF
Low Battery
CPU is in STOP Mode
Do-more BRX Manual available at IMPORTANT!
2″ (50mm) Minimum
from Enclosure or
Wire Duct
2″ (50mm) Minimum
from Enclosure or
Wire Duct
RUN Green CPU is in RUN Mode http://www.automationdirect.com/pn/ Hot-Swapping Information
Yellow Forces are Active doc/manual/BX-DM1E-10ER3-D Note: This device cannot be Hot Swapped.
OFF No ROM Activity, No SD Card
Yellow ROM Activity (Flash or SD Card)
MEM
Green SD Card Installed and Mounted
2″ (50mm) 2″ (50mm) Red SD Card Installed and Not Mounted
Minimum from Minimum
Enclosure from Wire Duct OFF CPU is functioning normally
ERR
Red CPU Fatal Hardware Error or Software Watchdog Error

www.do-moreplcs.com Tech Support 770-844-4200 Sales 800-633-0405 Your Automation Foundation!™


Terminal and Front Panel Layout Analog Current Sinking Input Circuits Analog Output Wiring
Current Source Output
– *Fuse WY0
WX0 .032A
CPU Mode 2-Wire 4-20 mA 0.032A mA Load *Fuse 1C
RUN
GND PWR
TERM
Switch
h Battery Replacement Transmitter WX
Coin Battery CR2032 1C
PWR IN- STOP
RUN
PWR IN+ ADC Part # D0-MC-BAT. + + -
Micro SD Power Voltage Output
2-Wire Transmitter

7
1C MEM
Card Slot Replacement batteries do not come Supply

6
5
10- WX0 with tape. To assist with future battery WY0

4
ERR .032A

3
PIN
WY0 SD
removal, reuse tape from the original VDC

2
Load *Fuse 1C

1
Serial Port
RS-232/485
1C
battery or add new tape.

0
HSI
X0 TX GND *Fuse
RX/D- + WX0
HSI X1 0.032A Load
RX TX/D+
HSI X2 Ethernet
E et WX Power Supply
10/100 3-Wire Current + 1C
BASE-T Port
P Transmitter
NOTE: DIP switches - +

ETHERNET
LNK

+
Analog Voltage Input Circuits
2C
HSI ACT located in this compartment –
X3 PPluggable
able are used for debug and
HSI 24VDC User
HSI
X4 OOption recovery functions only. CR2 3-Wire Transmitter Supplied Power WX0
X5 MModule 032 .032A
1C ((POM) Slot Please refer to the BRX 4-Wire Voltage *Fuse
Y0 User Manual for full Transmitter 1C
Y1 instructions on using these NOTE: Do not *Fuse
switches. + WX0 Optional Transmitter
10- 2C
remove tape from battery. 0.032A AC or DC
PIN 4-Wire 4-20 mA Power Supply
Y2
1C WX
Y3 POM Modules Transmitter – 4-Wire Transmitter
BX-DM1E-10ER3-D BX-P-SER2-TERM –
+
3-Pin Serial RS-232 *Fuse WX0
AC or DC .032A
BX-P-SER2-RJ12 User Supplied Transmitter Power
RJ12 Serial RS-232
4-Wire Transmitter 3-Wire Voltage + 1C
BX-P-SER4-TERM Transmitter - +
3-Pin Serial RS-485
BX-P-USB-B *NOTE: An Edison S500-32-R 0.032A fast-acting fuse is recommended
I/O Terminal Blocks sold separately. USB Type B for all analog voltage inputs, analog outputs, and current loops.
24 VDC User
(See Terminal Block Connection Options table). BX-P-ECOMLT
3-Wire Transmitter Supplied Power
Ethernet 10/100 BASE-T
NOTE: Only POM modules
can be hot-swapped.

Discrete Input Specifications Discrete Output Specifications High Speed Input (HSI) Functions I/O Wiring
Input Type Sink/Source Output Type Relay Form A (SPST) Input Inputs 10/ 18/
10E 18E
36/
36E
Discrete Input Discrete
Function Required1
Total Inputs per Module 6 High Speed – All inputs may be used as standard inputs Total Outputs per Module 4 Relay
1 Up counters Wiring Output Wiring
Commons 2 (3 points/common) Isolated Commons 2 (2 points/common) Isolated High-Speed 1 Down counters Sinking Input
Nominal Voltage Rating 12–24 VAC/DC Maximum current per common 4A Counting 2 Up/Down counters
Position Scaling
2 Pulse/Direction (Bidirectional) counters nC
Input Voltage Range 9–30 VAC/DC Nominal Voltage Ratings 12–48 VDC, 24–240 VAC Frequency Relay Output
Measurement 2 Quadrature (A and B) counters Up to (3)
Maximum Voltage 30 VAC/DC Operating Voltage Range 5–60 VDC, 5–264 VAC Xn
DC Frequency 0–250kHz - High Speed Maximum Voltage 60VDC, 264VAC
3 Quadrature (A and B with Z) counters nC
Interval 1 Single Input (Edge) timers X
Minimum Pulse Width 0.5 μs - High Speed Minimum Output Current 0.1mA @ 24VAC/DC Measurement 2 Dual Input (Dual Edge) timers Xn
47–63 Hz (60–240Hz filter must be set in software for Maximum Output Current 2A Duration
LOAD Yn Y
AC Frequency 1 Single Input (Edge) timers
AC operation)
Maximum Leakage Current 1µA (DC), 300µA (AC) due to RC snubber
Measurement Xn
Input Impedance 3kΩ @ 24VDC
Table-Driven Programmable limit switches LOAD Yn
Maximum Switching Frequency 10Hz Output(s)2 Preset tables
Input Current (typical) 6mA @ 24 VAC/DC Sourcing Input
Status Indicators Logic Side, Green 4 Input interrupts Up to (4)
Maximum Input Current 12mA @ 30 VAC/DC Interrupt(s) 0 Timer interrupts nC
Maximum OFF Current 2.0 mA 0 Match register interrupts
ON Voltage Level > 9.0 VAC/VDC 1. Standard inputs may be used with high-speed functions, but at lower response frequencies of
approximately 120Hz.
Xn
OFF Voltage Level < 2.0 VAC/VDC 2. Table Driven Output(s) are triggered by an Axis Position or a high-speed counter/timer accumu- X
Status Indicators Logic Side, Green
lator value. It requires the selection of 1 discrete output. (see HSO Note 1 below) Xn
Supply Power
High Speed Output (HSO) Functions Xn Wiring
Outputs 10/ 18/ 36/
Function2
Required1 10E 18E 36E
Analog Input Specifications Analog Output Specifications Virtual axis 4 4 4 AC Input
0
GND
Inputs per Module 1 Outputs per Module 1 2 PTO linear step/direction outputs 2 3 3
PTO rotary clockwise/counter- nC
Input Voltage Range* Software Selectable ±10V, ±5V, 0-10V, 0-5V Output Voltage Range* Software Selectable ±10V, ±5V, 0-10V, 0-5V Pulse Mode 2 2 3 3 DC
Input Current Range* Software Selectable ±20mA, 4-20 mA Minimum Voltage Load Impedance 1kΩ 2
clockwise (CW/CCW) outputs
PTO quadrature (A and B) output 2 3 3 Xn
- PWR IN –
Power
Resolution 16 bit @ ± 10V, ± 20mA Output Current Range* Software Selectable ±20mA, 4-20 mA 1 PWM pulse width modulation outputs 4 4 4
Xn
X + PWR IN +

Conversion Time 1.2 ms Maximum Current Load Impedance 500Ω Axis Profile Relative/Absolute positioning, Velocity mode, Trapezoid, S-curve, DC Power In
Electronic gearing, Camming, Following, Homing, Jogging
Input Impedance Voltage Modes 100kΩ Settling Time < 1ms 12–24VDC
1. Standard outputs may be used for high-speed functions, but at lower response frequencies of
Input Impedance Current Modes 249Ω Resolution 16 bit @ ± 10V, ± 20mA approximately 110Hz. Use of relay outputs is not recommended. Xn Class 2 or LPS User Supplied Power

2. This is the total number of functions. A combination of high-speed outputs and standard out-
*Software selectable per channel. *Software selectable per channel. puts may be used up to this total.

www.do-moreplcs.com Tech Support 770-844-4200 Sales 800-633-0405 Your Automation Foundation!™