Professional Documents
Culture Documents
Grasso Mseries
Grasso Mseries
COPYRIGHT
this document may contain or for their consequen-
All Rights reserved. ces.
No part of this documentation may be copied or pub- The manufacturer reserves the right to make techni-
lished by means of printing, photocopying, microfilm cal modifications during the course of further devel-
or otherwise without prior written consent of opment of the equipment covered by these operating
• GEA Refrigeration Germany GmbH instructions.
herein after referred to as the manufacturer. This Illustrations and drawings in these operating instruc-
restriction also applies to the drawings and diagrams tions are simplified representations. As a result of the
contained in the documentation. improvements and changes, it is possible that the
illustrations do not exactly match the unit you are
LEGAL NOTICE operating. The technical data and dimensions are
subject to change. No claims can be made on the
These operating instructions are part of the technical basis of them.
documentation for the scope of delivery. They con-
The manufacturer cannot accept liability for damages
tain important instructions for ensuring safe and
proper transport, installation, start-up, economic • which occur during the warranty period as a
operation, maintenance and repair of the unit. Their result of
observance helps in avoiding dangers, reducing
– improper operating conditions and conditions
repair costs and down-times and increasing the relia-
of use,
bility and durability of the unit.
These operating instructions are intended for the – inadequate maintenance,
users of the equipment and are specifically intended – improper operation,
for the operating company and its operating and
maintenance personnel. – incorrect installation,
It is essential that the operating company and its – incorrect or improper connection of the main
operating and maintenance staff read these operat- electrical drive,
ing instructions prior to transport, installation, start- • or which result from or can be attributed to
up, use, maintenance, repair, disassembly and dis- improper modifications or failure to observe the
posal. This obligation to read also applies to person- instructions;
nel involved in activities in the life phases of the
machine. • through the use of accessories or spare parts
The operating company must supplement these which were not supplied or recommended by the
operating instructions with instructions regarding manufacturer.
health and safety at work and environmental protec-
tion on the basis of existing national regulations for
industrial safety.
In addition to these operating instructions and the
binding accident prevention regulations valid for the
respective country and area where the product is
used, the recognised technical regulations for safe
and professional work must also be observed.
These operating instructions are part of the unit. The
entire documentation comprises these operating
instructions and all additional operating instructions
supplied with the unit. It must be kept readily availa-
ble where the unit is installed. The entire documenta-
tion must also be forwarded if the unit is installed at
another location and if the unit is sold.
These operating instructions have been written in
good faith. However, GEA Refrigeration Germany
GmbH cannot be held responsible for any errors that
Warning!
Stands for a possibly dangerous situa-
tion which leads to heavy physical
injuries or to the death.
Caution!
Stands for a possibly dangerous situa-
tion which could lead to light physical
injuries or to damages to property.
Hint!
Stands for an important tip whose
attention is important for the designa-
ted use and function of the device.
LAYOUT INFORMATION
Handling instructions
Handling instructions require you to do something. Several consecutive steps result in a handling sequence that
should be run in the specified order. The handling sequence can be divided into separate steps.
Handling sequence
1. Handling sequence step 1
– step 1,
– step 2,
– step 3.
2. Handling sequence step 2
The subsequent handling sequence is the expected result:
® Result of the handling sequence.
Individual handling steps
Individual handling steps are marked thus:
– Individual work steps
TABLE OF CONTENTS
1 BASICS 11
1.1 Importance of the documentation 11
1.2 Requirements for personnel, obligation to exercise due care 11
1.3 Legal foundations (Germany) 12
1.4 Specified Use 14
1.5 Warning against foreseeable abusive use 14
1.6 CE mark 15
2 MANUFACTURER INFORMATION 16
3 CUSTOMER SERVICE 17
3.1 Technical customer service department 17
3.2 Spare parts 17
3.3 Training courses 17
3.4 Service contracts 17
4 SAFETY 18
4.1 General information for safety 18
4.2 Behaviour in the case of emergency 18
4.3 Possible residual hazards 18
4.4 Installation in explosive atmospheres, installation zones 1 and 2 19
5 TRANSPORT, STORAGE 21
5.1 General instructions 21
5.2 Delivery 21
5.3 Transport (crane transport) 21
5.4 Bearings 23
5.5 Storage (several years) 24
6 INSTALLATION 26
6.1 Basic information for installation 26
6.2 Rigid installation 26
6.3 Anti-vibration mounting 26
6.4 Electrical connection 26
6.4.1 Use in explosive atmospheres, installation zones 1 und 2 27
6.5 Sound insulation, weather protection 27
6.6 Information regarding noise emissions 27
7 DESCRIPTION OF DESIGN AND FUNCTION 29
7.1 Installation in explosive atmospheres, installation zones 1 und 2 29
7.2 Product code of screw compressor packages - Grasso SP1, SP2, SPduo and M Series 30
7.3 Technical specifications 32
7.4 Location of the product identification (name plate) 33
7.5 Information and safety labels on the product 34
7.5.1 Labelling of the pressure and temperature sensors, heater 34
7.5.2 Label of the safety valve 34
7.5.3 Labels of the screwed connections with DiNova ring 34
7.5.4 Labels of the pipelines 35
7.5.5 Marking the direction of rotation of the compressor drive motor 35
7.5.6 Marking the direction of rotation of the oil pump motor 35
7.5.7 Labels of the pressure gauge 36
7.5.8 Labeling of the control / control cabinet 36
7.5.9 Designation of the earth connection 37
7.6 Process flow diagram 37
7.7 Main components 38
7.7.1 Screw compressor 39
7.7.2 Compressor drive motor 39
7.7.3 Compressor with coupling housing 40
7.7.4 Oil separator 40
7.7.5 OMC block with oil filter system 41
7.7.6 Oil cooler 41
7.7.7 Oil pump (optional) 41
7.7.8 Suction filter - check valve combination 42
7.7.9 Controller 43
7.7.10 Fittings 43
7.7.11 Safety devices 44
TABLE OF FIGURES
fig. 1 CE mark 15
fig. 2 Designation of the lifting points 21
fig. 3 Stopper with shackle 22
fig. 4 Transportation with a wire rope hoist 22
fig. 5 transportation using crossbeam 23
fig. 6 Location of the product identification (type plate) 33
fig. 7 Type plate 33
fig. 8 Safety labels of the pressure and temperature sensors, heater 34
fig. 9 Label of the safety valve 34
fig. 10 Labels of the screwed connections 34
fig. 11 Labels of the pipelines 35
fig. 12 Marking the direction of rotation of the compressor drive motor 35
fig. 13 Marking the direction of rotation of the oil pump motor 35
fig. 14 Labels of the pressure gauge 36
fig. 15 Test verification for the control system 36
fig. 16 Designation of the earth connection 37
fig. 17 Process flow diagram Grasso SP1, M-series 37
fig. 18 Main components of the GEA Grasso M-Series 38
fig. 19 GEA Grasso M-Series, arrangement of the SCP 39
fig. 20 GEA Grasso M-Series, arrangement of the compressor drive motor 39
fig. 21 GEA Grasso M-Series, arrangement of the coupling housing 40
fig. 22 GEA Grasso M-Series, arrangement of the oil separator 40
fig. 23 GEA Grasso M-Series, arrangement of the OMC block with oil filter system 41
fig. 24 GEA Grasso M-Series, arrangement of the oil cooler 41
fig. 25 GEA Grasso M-Series, arrangement of the (optional) oil pump 42
fig. 26 GEA Grasso M-Series, suction filter - check valve combination 42
fig. 27 GEA Grasso M-Series, arrangement of the controller 43
fig. 28 Corrosion resistance in presence of chlorides 51
fig. 29 Vacuum required to remove moisture from refrigerating plants 56
fig. 30 Stop valve open 57
fig. 31 Stop valve closed 57
fig. 32 Check valve 57
fig. 33 Shuttable check valve 57
fig. 34 Control valve 58
fig. 35 Shuttable check valve 58
fig. 36 Solenoid valve 58
fig. 37 Change-over valve 58
fig. 38 Oil pressure control valve 58
fig. 39 Overflow valve, safety valve 59
fig. 40 Pressure controlled check valve 59
fig. 41 Quick acting valve, spring-loaded 59
fig. 42 Charging valve, drain valve 59
fig. 43 Service valve 59
fig. 44 Oil temperature limiter 60
fig. 45 Temperature controlled control valve 60
fig. 46 Motor direction of rotation 62
fig. 47 Arrangement of MIN / MAX sight glasses 78
fig. 48 Operating position of the fine oil separation cartridges 79
1 BASICS
– applicable international and national standards,
1.1 Importance of the documentation – applicable occupational safety regulations,
These operating instructions are part of the technical – applicable accident prevention regulations,
documentation for the Grasso scope of delivery. It – applicable environmental protection regulations,
contains advice for operating the package/chiller
safely, properly and economically. The observance – the construction and functioning of the unit,
of the operating manual helps in avoiding dangers, – recognised technical regulations for safe work
reducing repair costs and down-times and increasing according to good professional practice.
the reliability and durability of the package/chiller.
The technical personnel must:
This operating manual is directed at the users of the
package/chiller and is specifically intended for the – be able to assess the work assigned to them,
operating company and its operating and mainte- recognise and avoid possible dangers,
nance personnel. This operating manual must be – be authorised by those responsible for the safety
read prior to transport, installation, commissioning, of the system to carry out the requisite work and
maintenance, repair, disassembly/disposal. activities.
All work explained in this operating manual must only
be carried out by technical personnel. Caution!
This operating manual must be supplemented with No arbitrary changes may be made to
instructions based on prevailing national regulations the control or other components
regarding industrial safety, health protection and belonging to the unit. Maintenance
environmental protection. work may only be done by authorised
In addition to this operating manual and the manda- service staff.
tory accident prevention regulations applicable for
the respective place of installation, the accepted Special requirements for the electrical techni-
technical regulations for safe work according to good cians
professional practices must also be observed. Work on electrical components and modules may
The operating manual is a part of the total product. only be carried out by an electrical technician
The entire documentation, consisting of this operat- according to the rules relevant to electrical engineer-
ing manual as well as all supplied additional instruc- ing. Furthermore the operator has to take care that
tions, is to be always kept easily accessible at the the electrical systems, tools and fixtures are oper-
place of installation of the package/chiller. The com- ated according to the rules relevant to electrical engi-
plete set of documentation must also accompany the neering and applicable standards and serviced prop-
package/chiller if it is sold. erly.
– In principle it is prohibited to carry out work on
parts under voltage.
1.2 Requirements for personnel, obliga- – Fuses may only be replaced and not repaired or
tion to exercise due care bypassed.
the package/chiller must not be operated in the – Accident Prevention Regulation including
defective condition. implementation regulations (BGR 500, chapter
2.35) on refrigeration plants, heat pumps and
Minimum age cooling equipment (BGV B3) regarding noise
The minimum age for the operation of the package/
– EN 12284 Refrigerant fittings, safety related
chiller and installation is 18 years. All persons
technical definitions, testing and marking
involved in the assembly and installation of the pack-
age/chiller and the system must get themselves – DIN 2405 Pipes in refrigeration plants, marking
trained at regular intervals and/or familiarise them-
– VDMA specifications,in particular VDMA 24
selves with the current technical data of the device.
243 and 24 020
The training and instructions is to be conducted at
least once a year, unless some other interval has – VDI Guidelines
been agreed upon with the manufacturer.
– Instruction sheets for handling ammonia,
Obligation to exercise due care Instruction sheet for halogenated hydrocar-
bons containing fluorine BGI 648
The statutory regulations for meeting the obligation
to exercise due care are to be observed. – Safety data sheet for ammonia and other refrig-
Meeting the obligation to exercise due care accord- erants and refrigeration oils
ing to the current level of technology requires that The list of rules and standards has been taken from
everything that is Status Report No. 5 of the German Refrigeration and
Air Conditioning Engineering Association "Safety and
– technically possible (use of accepted technologi-
environmental protection in ammonia refrigeration
cal rules) and
plants" and also fully applies to other refrigerants.
– economically reasonable
Danger!
be done to prevent damage in a protectively safe
manner.
– Federal Pollution Control Act (BImSchG), 4th – guidelines and recognised engineering practice,
BimSchV listed in these operating instructions must be
observed at least!
– Water Resources Act (WHG), VawS
Hint!
– Hazardous Substances Ordinance (GefStoffV)
If the package/chiller is used in a
– Recycling and Waste Management Act (KrW-
country other than Germany, the rules
AbfG)
and regulations applicable at the place
– DIN EN 378, Part 1 to Part 4 Safety-related of installation must be observed and
technical requirements and environmental complied with!
requirements
The mandatory accident prevention regulations
applicable for the respective country and area where
the product is used must also be observed.
The pressure equipment described here must not be – electrical components are wrongly connected.
used for any purpose other than the purpose speci-
fied here. The units must only be installed by the Hint!
supplier/installer and not by the end user. If the pres-
Watch voltage and frequency!
sure equipment is not used according to the regula-
tions, the safe use of the equipment is not guaran-
– mechanical components are wrongly connected.
teed. The supplier/installer or the operator – and not
1.6 CE mark
Hint!
Watch pressure and temperature! By affixing the CE mark, the manufacturer confirms
the conformity of the product with the applicable EC
– the supporting, hanging and storage facilities are Directives and compliance with the principle require-
misused. ments stipulated within them.
2 MANUFACTURER INFORMATION
GEA Refrigeration Germany GmbH is a company
within GEA Refrigeration Technologies, the Refriger-
ation Technology Segment of the GEA Group and
provides its customers around the world with high-
quality components and services for refrigeration and
process technology applications.
Locations:
3 CUSTOMER SERVICE
GEA Refrigeration Germany GmbH supplies prod- In most cases, you will receive your spare parts
ucts of high quality and reliability. In addition, the within 24 hours after placing the order.
manufacturer ensures continuous operation of the You can contact us using the following hotlines:
refrigeration and process technology system and
provides exceptional service for the components • Wireless, out of hours
supplied. +49 (0) 172 30 14 579
• Landline, weekdays from 8 to 17 hour
+49 (30) 43 59 27 50
3.1 Technical customer service depart-
ment • Fax
+49 (30) 43 59 27 58
Do you require support from the technical customer
service department? Specially trained, experienced • Email
service technicians are available on call for you in Grasso-parts@geagroup.com
order to provide assistance in case of technical prob-
lems and to offer support in the framework of our • Order spare parts from our G-Pos. online
after-sales service. shop
24/7 Hotline: (Grasso Parts online shop)
the hotlines can reached around the clock on every gea-refrigeration.de.spareparts@gea.com
day of the week:
• Wireless 3.3 Training courses
+49 (0) 172 39 12 050
Warning!
• Landline, weekdays from 7 to 17 hours
+49 (30) 43 59 27 61 All work on our systems must only be
carried out by technical personnel!
+49 (30) 43 59 27 62 Acquire the technical know-how
• Email: required for this in good time!
Grasso-service@geagroup.com Comprehensive training courses are held regularly
outside of Germany, Austria and Switzerland please for service technicians and mechanics, thus ensuring
contact: the safe and proper use and maintenance of our sys-
• local sales office tems.
www.gearefrigeration.de • Email
technical support for liquid chillers with reciprocating Grasso-service@geagroup.com
compressors in Germany, Austria and Switzerland
• 24/7 Hotline
3.4 Service contracts
+49 (345) 78236 20
The specialists of our Technical Customer Service It is possible to sign a long-term service agreement
department support you in installations, acceptan- (service contract). For further information regarding
ces, maintenance, operating questions, on-site the content, scope and conditions of the possible
inspections and repairs of our products. service options, please contact the Technical Cus-
tomer Service department.
• Email:
3.2 Spare parts Grasso-service@geagroup.com
GEA Refrigeration Germany GmbH has its own prac-
tical and rapidly working spare parts department to
supply the necessary spare parts worldwide. Neces-
sary spare parts are shipped as quickly as possible.
4 SAFETY
4.3 Possible residual hazards
4.1 General information for safety Warning!
The safety aspects to be observed for operating the Despite careful design of the machine
equipment are shown in the chapter on "Safety". and implementation of all the safety-
relevant regulations, further risks for
The equipment has been developed and manufac-
persons and machine during all life
tured according to the currently applicable state of
phases of the package/chiller cannot
the art and is reliable in operation. It has been tested
be fully ruled out. The additional safety
and left the factory in a technically faultless safe con-
instructions in the individual chapters
dition.
of this manual must therefore be care-
In order to maintain this condition for the operation fully observed!
time, the details of the project documentation and
certificates must be observed and complied with. Residual risks that were ascertained during the risk
When operating the equipment, at least the general assessment carried out for the product according to
safety regulations and the provisions and guidelines safety standard EN ISO 14121 - Safety of Machines
referred to in this documentation must be observed. - are:
Only compliance with all provisions and guidelines – mechanical hazards due to sharp sheet metal
will enable optimum protection of the personnel as edges and projecting parts,
well as dangers to the environment and the safe and
smooth operation of the equipment. – electrical hazards as a result of inadvertently
coming in contact with terminals and cables,
– thermal hazards as a result of inadvertently com-
4.2 Behaviour in the case of emergency ing in contact with heat exchangers and pipes,
Familiarise yourselves with the local – hazards caused by vibration due to improper
evacuation plan before beginning the installation,
work. – hazards due to working materials and other
Should an emergency situation arise despite adher- materials in case of allergies orthe like,
ing to the safety regulations, the package/chiller – neglect of ergonomic principles,
must be shut down immediately and isolated from
– combinations of various hazards,
the electrical mains.
The mains cable must be blocked in such a way it is – unexpected start-up, unexpected rotation in case
not possible to restart the unit accidentally and of incorrect electrical connections or defects,
marked as such. – shut-down, emergency stop when defects are
The operator of the complete system has to take detected,
care that an isolation device, e.g. a mains switch with
– changes to the rotational speed,
appropriate contact rating and an integrated indica-
tor, is pre-installed in the mains cabling on site. – power failure,
A separate mains cable/feed cable must be laid for – failure of the control circuit or control loop,
the operation of the package/chiller.
– incorrect assembly,
The mains cable/feed cable is to be specially protec-
ted and provided with an emergency stop switch. – fracture during operation,
– operating media or objects getting thrown out,
– loss of stability and
– personnel slipping, tripping or falling.
5 TRANSPORT, STORAGE
5.2 Delivery
5.1 General instructions Shipment is made in the type of packing stipulated in
the order. The screw compressor package is gener-
Caution! ally supplied without packing.
Adequate lighting must be ensured The screw compressor package has an inert gas
during loading and unloading as well filler in the refrigerant circuit.
as for storage in order to avoid injuries
Warning!
and damage to property.
There is a danger of impacts and The compressor(s) of the screw com-
stumbling due to protruding parts on pressor package is/are not filled with
the equipment (e.g. valve caps). There oil. The screw compressor package
is also the danger of being cut on must not be started, therefore, before
sharp edges and surfaces. There is a proper assembly and start-up.
danger of crushing parts of the body
during the transport work. Personal
protective equipment (work clothing, 5.3 Transport (crane transport)
work books, gloves) must be worn
during all activities on the equipment. Warning!
Caution!
It is forbidden to attach SCPs to fit-
tings or pipes or at the eyebolts / lift-
ing rings of the compressor, the elec-
tric motor, the tank or the switching
cabinet.
5.4 Bearings
When the screw compressor packages are deliv-
ered, check for possible transport damage and report
any damage to the manufacturer in writing.
The storage area of screw compressor units shall be
roofed, plain and paved and secured against access
of unauthorized persons. Place the screw compres-
sor package onto timber planks and have it protected
from jerks or impacts.
Warning!
Screw compressor packages must be
adequately protected from external
influences (humidity, frost, extreme
heat) during storage. This usually con-
cerns lengthy standing times outdoors
before installation and start-up of the
refrigeration plant. The manufacturer
recommends the use of plastic sheet-
ing to cover the whole product.
The venting slits of the electric motors
must always be covered!
Regular ventilation of the screw com- If the screw compressor package is intended to be
pressor package packaging (if stored, the following preparatory measures must be
present) must be ensured in order to carried out ex-works (especially protection against
prevent condensation on the surfaces internal and external corrosion):
of the machine. • All process connections on the screw compres-
sor package are sealed tight.
Long-term storage
• The screw compressor package is charged with
With a standstill of the compressor of more than 16
dry gas to 1 bar.
weeks prior to start-up, there is a danger that the
shaft seal may stick on the shaft and therefore be • A suction pressure gauge has been installed.
damaged on start-up. Because of this, removal and • The facing sides of the mounted coupling hubs
cleaning of the shaft seal is mandatory in order to have been greased. (Does not apply to sliding
ensure that it functions correctly. bearing compressor drive motors)
1. Use two pressure screws to remove the cover of
Hint!
the shaft seal, including the stationary gasket
inserted in it. In case of the use of high-voltage
motors: the operating manual of the
2. Removal of the seal package arranged on the
manufacturer is to be followed, espe-
shaft with the associated slide ring by hand or, if
cially regarding any anti-condensation
tightly seated, extraction by means of an appli-
heater required.
ance. If the seating is loose, the seal package
may adhere to the stationary seal and will be • Free-standing motor and main flow shafts have
pulled out when removing the cover. been conserved.
3. Clean the shaft seat with a lint-free cloth. Grease • The space on the screw compressor for the shaft
it lightly and push the sealing package back onto seal has been greased.
the shaft again.
• The connections on the oil cooler water side
4. After pushing onto the shaft, the seal package have been sealed.
must be manually compressed against the spring
pressure which acts on it. At the same time, it The following maintenance work must be carried out
must be checked whether the gasket springs out at the storage location during storage:
again. 1. Visual inspection of the general condition of the
5. Then re-fit the cover of the shaft seal. screw compressor package.
2. Cyclical rotation of the screw compressor shaft
Warning!
(about 10 revolutions per month and the com-
Danger of cuts and crushing injuries. pressor drive motor (see operating manual).
5.5 Storage (several years) 3. Check the transport fill pressure with a pressure
gauge at the connection of item 405 (see P+I
Hint! flow chart). If this value < 1 bar, replenish dried
gas via the valve of item 85 (see P+I flow chat).
The instructions in the "Transport, All valves are already opened at the factory for a
storage" chapter must be heeded. common pressure range.
The following storage conditions must be maintained
when storing screw compressor packages that are
equipped with a control.
1. Storage temperature > 10°C
Caution!
After completion of the storage period
and prior to re-delivery, a general
review in the factory or a general
examination at the storage location,
performed by the technical customer
service technician of GEA Refrigera-
tion Germany GmbH, is recommended.
Please pay attention to the information
in the "Start-up" chapter.
The general check includes changing
the O-ring on the compressor shaft
seal as well as replacing the shaft seal
of the oil pump.
6 INSTALLATION
misalignment ≤ 0.25 mm) at the coupling is attained
again. Then tighten the foundation bolts.
6.1 Basic information for installation
Caution!
6.3 Anti-vibration mounting
During the installation, make sure that
substances escaping from leaks do The frame of the screw compressor unit must be
not reach into the soil, groundwater or aligned with the levelling bolts until the coarse align-
surface water. The applicable legal ment (radial and angular misalignment (radial and
regulations must be heeded at the angle offset ≤ 0.25 mm) at the coupling is attained
place of installation (e.g.for Germany: again.
German Federal Water Act WHG). Before tightening the foundation bolts of the isola-
tors, check that the isolators over the spring (pre-
All foundation calculations, the selection of materials dominantly made of rubber) are free and do not lie
and the soil analysis are the designer's or owner’s on the foundation.
responsibility.
A plan must be produced for proper and professional
assembly prior to the installation. The electrical and 6.4 Electrical connection
operating media connections must be established. It
must be borne in mind that, in addition to the installa- Danger!
tion area of the screw compressor package, there
Contact with live components is pro-
must be sufficient space available for the pipes as
hibited.
well as for operating during maintenance activities.
Produce the earth connection accord-
Install the screw compressor package on a level sur-
ing to the designation in the general
face. The difference from the horizontal must not be
assembly drawing. See chapter "Des-
more than 0.3 %. Provide enough space for mainte-
ignation of the earth connection".
nance work.
Under normal conditions, the screw compressor Before starting work, make sure that all parts to be
package stands solidly on the installation surface connected are de-energised, e.g. by removing the
due to its own dead weight. We recommend that you main fuse in all phases or installing a jumper wire.
provide ribbed rubber plates for shock absorption The insulation resistance of the electrical tools and
between the support surface and screw compressor fixtures and wiring is to be checked. The connection
package feet or machine base frame. may only be undertaken if this value lies in the allow-
If greater damping is required (installation on a floor able range.
ceiling or on the roof), vibration dampers must be All electrical connections must be established and all
provided. The appropriate type of vibration damper electrical consumers/sensors must be connected
must be determined and realised for this case. Also according to the circuit diagram.
decouple the secondary refrigerant lines using com-
pensators when vibration absorbers are used.
The welding seams must be inspected in accordance
with the Pressure Equipment Directive after welding
work by the customer or operator on pipe line con-
nections and flanges.
6.4.1 Use in explosive atmospheres, The manufacturer will not accept liability for damage
installation zones 1 und 2 due to incorrect outdoor installation.
Danger!
The same regulations apply to the 6.6 Information regarding noise emis-
operating instructions for screw com- sions
pressor packages in potentially explo-
sive atmospheres as described in the The noise information provides approximate parame-
respective applicable operating man- ters and apply to the installation without any secon-
ual. dary noise protection measures.
In addition to this, the following exten- The information has a tolerance of ±3 dB.
sions apply: The precise data depend closely on the emission
values for the motors, which are manufacturer
1. The relevant electrical engineering
dependent.
regulations for installations in
potentially explosive atmos- Should local conditions require adherence to noise
pheres , especially EN 60079-10, levels, a calculation should be made using the spe-
apply to the installation and con- cific motor data in individual cases.
nection of electrical components. Sound insulation measures, such as motor encapsu-
Relevant prescribed cabling mate- lation or complete package encapsulation can ach-
rial must be used. ieve a significant reduction in sound level.
2. The whole screw compressor Wearing hearing protection with sufficient noise
package must be earthed by the reduction is recommended in rooms with running
owner operator. screw compressor packages.
Caution!
According to EU Directive 2003/10/EC,
6.5 Sound insulation, weather protec- the allowable exposure limit value
tion regarding the daily noise exposure
level is 80 db(A). In the event of noise
If the screw compressor package is intended for out- levels above this limit value the sys-
door installation, it must be provided with a suitable tem operator must provide the opera-
housing for sound insulation and weather protection tor with information on exposure to
by the customer. The weather protection must pro- noise and personal hearing protection
vide the machine with adequate protection against and ensure that this is also worn
the climatic conditions at the installation location. (2003/10/EC Article 6).
Hint!
The screw compressor package is not
intended for unprotected outdoor
installation. Protection against exter-
nal influences, especially dirt, dust
and moisture (wetness), is essential.
Max 111
315
Min 103
7.2 Product code of screw compressor packages - Grasso SP1, SP2, SPduo and M Ser-
ies
A Oil cooling
Code letter Theoretical volume flow Code letter Theoretical volume flow
at 2940 min-1 in m³/h at 2940 min-1 in m³/h
C 231 T 1460
D 265 V 1740
E 321 W 1940
G 372 Y 2390
H 471 Z 2748
Code letter Theoretical volume flow Code letter Theoretical volume flow
at 2940 min-1 in m³/h at 2940 min-1 in m³/h
L 544 XA 3250
P 805 XD 5800
R 1040 XE 7170
S 1290 XF 8560
* Grasso M Series
Y Screw compressor package version
6 Booster Vi = fixed
8 -- --
A Oil cooling
C Refrigerant injection
Examples of designation
XA B - 6 A Singe stage screw compressor package Grasso SP1 with screw compressor 3250 m³/h
(XA), refrigerant NH3 and vertically installed oil separator (B), booster with fixed internal vol-
ume ratio (6)with oil fine separation and water-cooled oil cooler (A)
TA-2A Singe stage screw compressor package Grasso SP1 or SSP1 with screw compressor 1460
m³/h (T), refrigerant NH3 and horizontally installed oil separator (A), fixed internal volume
ratio Vi = 3.6 (2) with oil fine separation and water-cooled oil cooler (A)
NA-3B Screw compressor package Grasso M with screw compressor 873 m³/h (N), refrigerant NH3
and horizontally installed oil separator (A), fixed internal volume ratio Vi = 4.8 (3)with oil fine
separation and refrigerant-cooled oil cooler (A)
LD - 2 A Screw compressor package Grasso SPduo with 2 of screw compressors 544 m³/h (L),
refrigerant NH3 and DuoPack version or multiple configuration (D), fixed internal volume
ratio Vi = 3.6 (2) with oil fine separation and water-cooled oil cooler (A)
W E - 6 A (L) Two-stage screw compressor package with LP screw compressor 1940 m³/h (W), refriger-
ant NH3 two-stage package (E), LP-compressor as booster (6), with oil fine separation and
water-cooled oil cooler (A), HP-compressor 544 m³/h (L)
– list of parameters,
7.3 Technical specifications – general assembly drawing,
Packages / chillers are designed and manufactured – P+I diagram.
for special fields of application. For technical specifi-
cations see the following.
– order specification,
7.5 Information and safety labels on the 7.5.2 Label of the safety valve
product
(safety labels)
Danger!
The safety-related labels on the pack-
age/chiller must be followed!
7.5.7 Labels of the pressure gauge 7.5.8 Labeling of the control / control
cabinet
(information plate)
(information plate)
• Label on the rear side of the control unit of the
control system (visible after opening the switch-
ing cabinet):
– Project name
– Make number of the package/chiller
– MPI address
• Label on the inside of the switching cabinet:
– Test verification for the control system
7.5.9 Designation of the earth connec- See general assembly drawing for the position of the
tion earth connections.
1 Suction side
2 Compressor
3 Oil separator
4 Pressure side
Hint!
The documentation of
the main components is
part of the product docu-
mentation (see product
description or operating
manuals of the supplier,
e.g. for the compressor
drive motor).
25 OMC block (possible as separate oil filter for greater amounts of oil) See component documentation
40 * Oil pump (possible as an external oil pump for booster) See component documentation
Hint!
The documentation of the screw com-
pressor (installation instructions, part
lists, drawings) is an integral product
documentation.
The oil cooler is used for cooling the oil heated in the
compressor in order to ensure sufficient oil viscosity
for supplying to the compressor.
Hint!
The documentation of the oil cooler
fig.23: GEA Grasso M-Series, arrangement of the OMC block (operating manual, acceptance certifi-
with oil filter system cate) is an integral part of the product
documentation.
The OMC block contains the oil distributor system in
the oil circuit. Necessary control and shutoff fittings
are integrated in the OMC-block. Connections for
7.7.7 Oil pump (optional)
temperature and pressure sensors as well as service
ports are present. The OMC block is combined with Special design for minor pressure differences
a standardised filter system and oil pump unit and (booster)
forms the central control and regulation unit within
the oil circuit.
Optionally, the OMC-block can be equipped with a 3-
way valve element (for ensuring a minimum oil tem-
perature when starting the compressor).
Hint!
The documentation for the OMC block
(operating manual, acceptance certifi-
cate) is an integral part of the product
documentation.
Hint!
The documentation of suction filter -
check valve combination is an integral
part of the compressor documenta-
tion.
Hint!
The documentation of the controller
(operating manual, circuit diagram,
parameter list, communication guide-
line) forms part of the product docu-
mentation.
7.7.10 Fittings
The term fitting generally designates a control ele-
fig.27: GEA Grasso M-Series, arrangement of the controller ment of the machine. Among other things, the term
fitting is also used for valves if these are used for the
The screw compressor package is equipped with a control and regulation of fluid flows in the piping.
GEA Omni™-type controller. Furthermore, all kinds of installations in piping, such
The GEA Omni consists of the control unit with oper- as sight glasses, measurement apertures, filters and
ator keypad and display unit, indicator lights for similar are also designated as fittings. Therefore, fit-
"Running", "Warning" and "Alarm", the emergency tings also include all kinds of valves, such as:
stop button, the output relays and the casing. – Stop valves
The GEA Omni is mounted directly on the package
– Check valves
as standard. As an option, the GEA Omni can be
installed in a control centre. – Safety valves
The GEA Omni performs the following functions – Throttle valves
as standard: Each fitting has its own field of use, according to the
• Display of all important physical and technical pressure or temperature in the pipe, the size of the
parameters, e.g. Pressure, temperature, motor pipe, the sealing requirements for the fitting, the
current, capacity, number of operating hours, reduction and direction of the flow of liquid as well as
operating mode and status signals the medium itself.
The safety fittings are used to limit the pressure in
• Automatic start up and shut down of the screw
systems which are under pressure.
compressor package and capacity control
dependent on the suction pressure or an exter- Each fitting is designed for the specific application.
nal temperature, The fittings can be operated manually or by motor,by
gear motors, or pneumatic or hydraulic cylinders, for
• Monitoring of all operating parameters example. In reset fittings, the flow of fluid in the pipe
• Compressor capacity limitation, in case the causes automatic closing of the valve.
measured discharge pressure, suction pressure, Depending on the model, different closing elements
secondary refrigerant temperature or motor cur- (e.g.valve discs, flaps, pushers) close the pipe con-
rent indicate overload nected to the fitting.
• Fault memory with date and time Hint!
• Wire failure detection for all analogue input sig- The documentation of the fittings
nals (acceptance certificates) forms part of
• Password protection for preventing unauthorised the product documentation.
access to important parameters
The safety valve is designed in accordance with DIN – Oil pressure after oil filter - optional -
EN 13136 "Refrigerating systems and heat pumps -
pressure relief devices and associated piping - meth- – Differential pressure of oil pressure after oil filter
ods for calculation". and discharge pressure (oil filter monitoring) -
optional -
Safety pressure limiter (350)
Safety pressure limiter with two separate trigger con-
tacts, one of which can only be reset using a tool. 7.7.13 Components installed by the cli-
The safety pressure limiter switches off the compres- ent
sor drive motor if the discharge pressure rises above
the set point. Warning!
Switching off pressure 1 = see parameter list The components and parts the cus-
Switching off pressure 2 = see parameter list tomer installs in particular the secon-
If it cannot be ruled out that the liquid refrigerant dary refrigerant and cooling medium
might attain more than 90% of the oil separator’s vol- circuits as well as the oil circuit need
ume, then the customer must install an additional to made from materials suitable for the
safety valve to prevent expansion of the liquid in the fluids flowing through them. Further-
oil separator (design in accordance with DIN EN more, in the event of modifications to
13136, arranged according to EN 378-2 Annex F). the product by the customer, the
effects on the safety devices are to be
checked.
7.7.12 Monitoring devices GEA Refrigeration Germany GmbH
does not assume any liability for dam-
The following operating values will be continually age arising and the violation of the
monitored in a standard screw compressor package: safety regulations which result from
– Suction pressure the use of unsuitable materials or
through modification to the product
– Discharge pressure which is not considered in the original
– Oil pressure oil circuit monitoring safety concept.
– Suction temperature
– Discharge temperature
7.8 General functional description
– Oil temperature
Screw compressor packages are refrigeration sys-
– absolute primary slide position tem components and serve to compress refrigerants
– Motor current such as ammonia (or other operating media on
request).
– Suction pressure saturation temperature
Operation as a heat pump is also possible.
– Saturation temperature
of condensing pressure
– Number of running hours 7.9 Refrigerant circuit
– Difference between oil and discharge pressures The screw compressor draws in refrigerant vapour
(oil circuit monitoring) via the suction check valve and suction filter and
then discharges the compressed vapour into the
– Set point of controled value in °C plant via the oil separator and discharge check valve.
– Real point of controled value in °C The suction-side check valve prevents a sudden
– Internal volume ratio pressure equalisation with the low pressure side of
the chiller, while also preventing reverse rotation of
– Used refrigerant the screw compressor.
– Controled value The pressure side check valve prevents refrigerant
from re-condensing in the oil separator.
– Used options
Hint! Caution!
For specific operations the selection To avoid "zero flow" in the compres-
and evaluation will take place within sor, which can damage the compres-
the manufacturer's compressor selec- sor, the minimum control slide posi-
tion programme. tion in the manufacturer's compressor
selection programme must be adhered
to.
"Minimal control slide position <value>
% accepted start."
If the value entered is "> 0", then a lim-
itation of the control slide path must
be put in place in coordination with the
manufacturer. The path limitation can
be set created mechanically with a
stop sleeve or by installing virtual con-
trols (virtual stop sleeve) on the com-
pressor.
≤28 bar
Maximum permitted pressure p bar g. max. or
≤52 bar
M/N *) M/N *)
Compressor frame size H L
28 bar 52 bar
*) For type M/N, the compressor drive shaft ends are different for 28 bar and 52 bar versions.
**) When running the compressor, the maximum torque falls by 25% as opposed to electrical drives.
Hint!
Water quality requirements, parameters
If you fail to adhere to the limiting val-
ues stated in VDI 3803, the manufac- Criterion Value Unit
turer cannot provide any warranty for
water carrying parts within its supplied Active biological
components. KBE < 10,000 per ml
components
Clarification as to whether or not it is
possible to adhere to these limiting Thickness factor EZ 2-4
values with the respective water condi-
tions should be agreed on with a spe- The use of carbon steel and cast iron is required in
cialist company during the planning the most of applications water conditioning with cor-
and design phase. rosion inhibitors.
The limiting values as per VDI 3803, as required for The use of stainless steel requires very special moni-
the use of carbon steel components in non corrosive toring of water in apply to Chloride contents (risk of
water systems, are listed below. stress crack and pitting corrosion).
Hint!
Water quality requirements, parameters
Recommend when using plate heat
Criterion Value Unit exchangers in the refrigerant circuit
< 100 ppm Cl while using steel 1.4301
Appearance clear, with- and
out sedi- maximum 40°C wall temperature in the
ment plate heat exchanger
< 200 ppm Cl while using steel 1.4401
Colour colourless and
maximum 100 °C wall temperature in
Odour none the plate heat exchanger
Electrical conductiv-
LF < 220 mS/m
ity
Ca2+,
Soil alkali < 0.5 mol/m³
Mg2+
General hardness,
GH < 20 °d
for stabilization
Carbonate hard-
ness without hard- KH <4 °d
ness stabilizer
fig.28: Corrosion resistance in presence of chlorides
Hint!
Manufacturer's recommendation: Use
uncontaminated secondary refriger-
ants and cooling media, in particular in
chillers and when using of plate heat
exchangers.
The media quality must be assured by
means of an appropriate filter on the
inlet to the heat exchanger. The mesh
for such a filter must be ≤ 0.9 mm!
Should the chiller be required to
remain in operation during filter clean-
ing, double filters must be used. Pres-
sure loss through the filter must be
taken into consideration on the build-
ing side when configuring the pump.
8 START-UP
The following points must be observed before
commencing with the start-up:
8.1 Important information for start-up
– Check of the external condition of the screw
Warning! compressor package (check of insulation, trans-
port damage... ).
Contact with live components is pro-
hibited. – The area around the machine in which the start-
up is carried out must be marked and secured
Hint! against the access of unauthorised persons. Suf-
The Customer Service department of ficient lighting of the working area must be
GEA Refrigeration Germany GmbH ensured to prevent personal injury and material
offer comprehensive support for start- damage.
ing up the screw compressor package. – Personal protection gear (work clothing, work
For contact details, please refer to the boots, gloves) must be worn during all work on
chapter entitled "Technical customer the screw compressor package. There is a dan-
service". ger of impact and stumblingfrom protruding parts
on the screw compressor package (e.g. valve
Warning! caps). There is also the danger of cut wounds on
The screw compressor package must sharp edges and rough surfaces. All activities
only be operated by suitably skilled must therefore be carried out with particular
personnel who are familiar with the attention.
contents of the operating manual for – Suitable hearing protection must be worn in
screw compressor packages. order to protect against damage to hearing or
The safety regulations for refrigeration deafness.
plants must always be observed in
– Thermal hazards resulting in injuries due to
order to prevent damage to the screw
compressor package and injury to the burns or freezing may occur on contact with
operating staff. parts of the system which are at a very high or
very low temperature. Personal protective equip-
The screw compressor packages are tested and ment must be worn.
accepted at the works. By the time these screw – Suitable tools or special tools must be used.
compressor packages are delivered to the cus-
tomer, the following work will have been carried – Check that all electrical work has been carried
out: out in accordance with the standards (e.g.protec-
tive earth, insulation, shielding, covers). If neces-
• Complete installation of the cooling system and sary, an earth connection must be provided.
in particular:
– Pipes and pipe sections must be secured to
– cleaning and drying the refrigerant and oil ensure sufficient mechanical strength. The pipes
circuits and equipment of the screw compressor pack-
– Leak test with air age must not be entered.
– Evacuation of the refrigerant circuit and filling – Operating media (nitrogen, oil, refrigerant) can
with protective gas (nitrogen) to a pressure escape. Preventive measures must be taken to
of 0.3 to 0.5 bar (above atmospheric) collect and dispose of them in an environmen-
tally responsible manner (e.g.using an oil pan).
• Electrical wiring and testing of the wiring
Personal breathing protection must be kept
• Factory setting for the parameters on the control ready in the event of a refrigerant leak. The
safety data sheets of the oil and refrigerant used
• Factory setting of the safety and monitoring devi-
must be read prior to commencing start-up work.
ces
Familiarise yourself with the evacuation plan of
• Works trial runs (at the request of the client) the installation location.
The screw compressor package has been designed 8.5 Start-up procedure
for plug-in and reliable automatic operation.
All connections must be carried out according to the The following procedures should be completed in the
current installation regulations. sequence in which they are described:
Connections to the screw compressor package must
be flexible and free of loads.
8.5.1 Checking the electrical connec-
Hint! tion
Dimensioning of the inlet pipe cross-
Danger!
sections must be according to DIN
VDE 100 Part 520. Contact with live components is pro-
hibited.
Before starting work, make sure that all parts to be
connected are de-energised, e.g. by removing the Check that all electrical work has been carried out in
main fuse in all phases or installing a jumper wire. accordance with the standards (e.g.protective earth,
The insulation resistance of the electrical tools and insulation, shielding, covers). If necessary, an earth
fixtures and wiring is to be checked. The connection connection must be provided.
may only be undertaken if this value lies in the allow-
able range.
Connections and almost all external connections are 8.5.2 Leak test
pre-wired at the factory.
Hint!
Warning!
See type plate for permissible operat-
Produce the earth connection accord- ing pressure.
ing to the designation in the general
assembly drawing. See chapter "Des- The necessary safety precautions should be taken
ignation of the earth connection". before performing the leak test.
An approx. 3-hour pressure drop test with dry nitro-
The electrical consumers and sensor must be con- gen is used for the test. Test pressure: 7 bar
nected according to the circuit diagram. All electrical
A pressure drop of 2% is allowed during the 3 hours.
connections must be made according to the circuit
Fluctuations in the ambient temperature must be
diagram, e.g.
taken into account.
– Compressor drive motor
Caution!
Checking devices which could be
damaged by the specified test pres-
sure must be removed or blocked
before the leak test is performed.
Caution!
The valves must be in operating position prior to the start-up of the package / chiller. Trouble-
free operation is only possible in this manner!
Caution!
An oil pressure being set too high or too low may result in serious compressor damage or
even the total breakdown of the compressor after just a short period of operation!
controlled self-sufficient
– ½” connections
– with cap
– Connection Rp ¼”
– For pressure gauge and pressure transmitter
When charging with oil for the first time, oil must be
charged via the service valve (135) too. To this end,
8.5.5 Oil charge the stop valve (065) must then be closed.
Caution! While operating the package, the oil level must be
regularly checked (see chapter "Oil level check").
Check the oil grade to be charged! See
contract/project or recommendation of Caution!
GEA Refrigeration Germany GmbH. A
Due to the use of selected compo-
comprehensive overview of the allowa-
nents, the refrigerating machine oils
ble oil types is provided in "Technical
tend to absorb more moisture. There-
information on lubricating oils". This
fore, when charging a compressor the
technical information is part of the
oil should be allowed to come into
product documentation.
contact with air for a short time only.
For severely hygroscopic oils, the oil The contents of an opened drum have
container must be placed under a pro- to be used up within one working day,
tective atmosphere. provided the drum is properly closed
between charging.
The vacuum present in the screw compressor pack-
age before pressure compensation may be utilised
for charging the package with oil. A separate oil
charging pump is required after the pressure com- 8.5.5.1 Pressure compensation with
pensation and for refilling with oil. the cooling system
The connection of the oil draining or oil charging stop
valve (090) must be connected with the oil charging Re-establish the vacuum. Carry out pressure com-
container. pensation via the service stop valve (285).
The direction of the arrow given for the oil pump 8. Check the excitation of the solenoid valves of the
must correspond to the direction of rotation of the oil adjusting device for capacity control in the Mini-
pump motor. mum direction.
Caution! 9. Simulate the minimum end position of the control
Since the slide ring shaft seal of the oil slide and check the switching function of main
pump is dependent on the direction of switch and star-delta contactor (for motors with
rotation and can be damaged when star-delta starting).
this direction is wrong, checking must 10. Checking the switching function of the solenoid
be reduced to a very short running valve by forcing the digital outputs.
period (less than 2 seconds).
11. Check the "Oil circuit monitoringfailure". only for
The adjusted differential pressure between the oil external oil pumpAfter 6s, the of the compres-
pump pressure side and the unit final pressure is sor drive motor must be shut off. To do so, the
checked with the oil pump rotating in the correct valve (70) must be throttled in such a manner
direction. It must not fall below the prescribed set that the alarm value for oil difference pressure as
value in the P+I diagram. stated on the parameter list is ot reached.
While the compressor is not running and the oil has 12. Set the motor current limitation acc. to nominal
not yet reached the operating temperature, the differ- motor data. See parameter list!
ential pressure can be slightly higher than the indica-
ted value.
The differential pressure can be changed by rotating 8.5.7 Checking of the safety pressure
the spindle on the oil pressure control valve. (The dif- limiter
ferential pressure is increased by turning it inwards
and vice versa). 1. Setting of the shut-off values as per the panel
data report
2. Switch on the compressor package
8.5.6 Checking the fault monitoring
3. Initiation of the shut-off value
1. Disconnect the incoming feeder of the compres-
4. Check the reaction:
sor drive motor from the mains supply when
checking the safety device (e.g. remove LV/HBC – Compressor must shut off immediately
fuse links).
– Fault report on the display of the control unit
2. Apply voltage to the control device.
3. Check the built-in pressure transducer and
resistance thermometer for correct wiring.
8.5.8 Checking of the emergency-OFF
button.
To do so, loosen the relevant contacts. The mes-
sage "Broken wire <sensor XXX>" appears on Hint!
the display of the control. Check that the display
is correct after the contact has been re-estab- Upon actuation, the emergency-Off
lished. button must immediately shut off the
compressor.
Further information can be found in the con-
troller manual. 1. Actuation of the emergency-OFF button.
4. Check limit values. 2. Check the reaction:
Limit value = see parameter list
– Compressor must shut off immediately
5. Switch on the screw compressor package/chiller
– Fault report in the display of the control
from the controller.
3. Resetting of the emergency-OFF actuation to
6. "Oil circuit monitoring failure” must be indicated
end the test.
after a starting delay time of 20 sec.
7. Reconnect the oil pump motor to the mains sup-
ply.
For units with the control GEA Omni, digital output B Motor
must be forced for this.
The set value of the oil differential pressure should – The compressor drive motor is started directly
be taken from the P+I flow chart of the specific and then switched off again by forcing the digital
project. outputs.
Oil differential pressure = oil pressure item (110)
Hint!
- discharge pressure item (105)
The differential pressure can be changed by rotating Prior to the start-up of the compressor
the spindle on the oil pressure regulating valve (the drive motor, the manufacturer's infor-
differential pressure is increased by turning it mation, e.g. on the lubrication of the
inwards and vice versa). To do so, the seal on the oil motor, must be followed at all costs.
pressure control valve (075) must be removed. – If the direction of rotation of the motor is incor-
In comparison to normal operation conditions, the oil rect, it should be corrected while the electric
differential pressure can be slightly higher if only the switchgear is secured to prevent the motor from
oil pump is operated or if the operating temperature being switched on accidentally. Then the motor
is not reached yet (with the valve open to the same must work for at least 1 hour, unencumbered
degree). and free from errors. This is important in order to
In this case, the oil differential pressure should be dry out residual moisture in the motor (caused
readjusted (according to the value in the P+I flow during transport or storage).
chart) after start of the unit and reaching of the oper- – The coupling protection must be in place during
ation temperature. this start-up period as required by the labour
safety regulations.
8.5.10 Checking the direction of rotation – After checking the direction of rotation of the
drive motor, the coupling may be connected with
of the drive motor
the motor.
Warning!
The coupling must not yet connect the
8.5.11 Mounting the coupling
motor and compressor!
1. The electric switchgear is secured to prevent it
– Secure the electric switchgear so as to prevent from being switched on accidentally.
the compressor drive motor from being switched
on accidentally. 2. Mount the coupling while observing the instruc-
tions of the separate documentation.
– With the control slide in the MIN or MAX position,
it should be possible to rotate the compressor 3. The values for radial and angular deviations
shaft easily and smoothly by hand. When check- given in the coupling documentation must be
ing the direction of rotation of the compressor checked and corrected if necessary. The axis
driving motor pay attention to the conditions for distance between the compressor drive motor
switching the compressor on. and the compressor must be checked.
4. The real values have to record at data sheet of 4. The minimum end position (0%) must be
coupling documentation. Please send back a reached and signalled when the "Decrease
copy of the filled data sheet to: power" button is pressed.
GEA Refrigeration Germany GmbH 5. Vent the adjusting device by moving the control
Holzhauser Straße 165 slide backwards and forwards about ten times.
13509 Berlin
Fax: +49 (0)30 - 43 592 759
8.5.15 Checking the control slide adjust-
Caution! ment times
Observe the maintenance instruction!
Caution!
Regrease the coupling at the prescri-
bed intervals if scheduled in the main- Only adjustment times between 30 and
tenance instruction for the coupling! 60 seconds are permissible.
Hint!
The oil heater in the oil separator can
be switched on while the screw com-
pressor package is not running. It is
then automatically switched off when
the screw compressor package is star-
ted and switched on when it is shut
down. If the ambient temperature is
below 5°C, the oil heater must be
switched on at least one hour before
the screw compressor package is star-
ted.
2 Manual + Auto Manual Start/Stop via TP and full automatic local Manual Auto
capacity control
3 Auto + Auto Full automatic start/stop and local capacity control Auto Auto
4 Remote Start/stop and capacity demand via digital contacts External External
+ HW (cont) (hardware) from a remote master controller. The GSC continuous
TP derives from the continuous +/- signals the pulses
for capacity (indirect).
5 Remote Start/stop and capacity demand via digital contacts External External
+ HW (pulse) (hardware) from a remote master controller. The mas- pulses
ter also generates the +/- signals as pulses for control-
ling the slide capacity directly.
6 Remote Start/Stop from a remote master controller via digital External Local
+ HW (loc. contacts (hardware). The GSC TP controls the output + setpoint Setpoint
SW) depending on a local setpoint (TP) and from this set- deviation
point also automatically switches the product ON/OFF.
7 Remote Start/Stop from a remote master controller via digital External Remote
+ HW (ext. contacts (hardware). The GSC TP controls the output + setpoint Setpoint
SW) depending on an external setpoint (analog input) and deviation
from this setpoint also automatically switches the
product ON/OFF.
8 Remote Start/stop and capacity demand via network from a Network Network
+ Net (cont) remote master controller. The GSC TP derives from continuous
the continuous +/- signals the pulses for controlling the
capacity (indirect).
9 Remote Start/stop and capacity demand via network from a Network Network
+ Net (pulse) remote master controller. The master also generates pulses
the +/- signals as pulses for controlling the capacity
directly.
10 Remote Start/stop from a central master controller via a bus Network Local
+ Bus (loc. signal. The GSC TP controls the output depending on + setpoint Setpoint
SW) a local setpoint (TP) and from this setpoint also auto- deviation
matically switches the product ON/OFF.
11 Remote Start/stop from a central master controller via a bus Network Network
+ Bus (net. signal. The GSC TP controls the output depending on + setpoint Setpoint
SW) an external setpoint sent externally via the network deviation
and from this setpoint also automatically switches the
product ON/OFF.
9.3.2 Setting of setpoint and limiting GEA Omni performs the following functions as
values as well as safety devices standard:
Table of malfunctions
The suction pressure is too low, Slow loss of refrigerant through Check the entire system for leaks.
performance is reduced and the leaks in the refrigerant circuit. Eliminate leakage, replenish refrig-
system overheats. erant if necessary.
The suction pressure increases, the The compressor/s are sucking in Check the filling of the system,
compressor(s) frost up to impermis- wet steam or liquid when started drain any refrigerant, repair safety
sibly high level or make noises that up. The safety device to prevent a device. Check for superheating.
suggests fluid (refrigerant) in the too-high liquid level is not respond-
compressor. ing.
The condensation pressure is too There is air or other non-condensa- Vent the refrigerant circuit.
high. ble gases in the refrigerant circuit.
The compressor(s) will not start-up The electrical circuit is interrupted Turn on the power, check safety
after switching on or it shuts down by a unit in the safety chain. devices and replace or correctly
immediately after starting again. adjust if necessary.
The compressors do not adapt to The capacity control device is mal- Check the oil circuit. The compres-
the required capacity. functioning due to disturbances in sors should only be repaired by
the oil circuit or mechanical influen- experts. Check the position detec-
ces. tor of the compressor control slide.
The compressors are shut off very The condensation pressure is too See above.
often by the maximum pressure high.
governor.
The maximum pressure governor is Remove the maximum pressure
defective or set wrongly. governor, repair it, set it correctly or
replace it.
The compressors are shut off very The suction pressure is too low. Open all valves on the suction side
often by the minimum pressure of the compressors.
governor.
Table of malfunctions
The heat transfer capacity of the Check the evaporator for elevated
evaporator decreases. oil concentration, drain oil if neces-
sary.
When operting, the package/chiller The compressor(s) or the drive Inform the GEA Refrigeration Ger-
is louder than permitted. motor(s) is/are defective. many GmbH customer service
1. In addition, for the persons responsible for main- There is an increased danger of slip-
taining the SCP, the legal safety regulations con- ping due to contact of operating media
cerning the installation of the SCP in potentially with the floor!
explosive atmospheres with respect to the main-
The screw compressor package must be serviced by
tenance of the individual components or sub-
appropriately trained operating staff only. For all
assemblies or their complete replacement apply.
maintenance work, the maintenance instructions
2. The maintenance may only be carried out in must be complied with.
agreement / with the knowledge and release of A maintenance checklist is part of the product docu-
the operator. mentation. The maintenance certificates in the main-
3. The maintenance and replacement regulations tenance checklist are completed and signed as part
resulting from the operating manual for the com- of the inspection and maintenance by authorised fit-
ponents are to be complied with. ters as evidence of the work done.
During the guarantee period, these confirmed main-
4. Appropriate special tools approved for the poten-
tenance certificates are a prerequisite for any claims
tially explosive atmosphere must be used.
under the guarantee.
5. Only original spare parts may be used. Other- The responsible certified specialist company must be
wise, any claim of warranty is void or, in case of informed if any repairs are required.
damage, the operator is liable for this.
All maintenance and service tasks have to be carried
6. Each maintenance inspection (see maintenance out with care to preserve the functionality of the
book) must also include the checking of the screw compressor package. Guarantee claims will
secure fit of the threaded connections for the not be valid if the customer failed to follow the main-
coupling safety hood. tenance instructions.
10.2 Important information for service 10.3 Cleaning the heat exchanger
personnel
The following chapter is primarily aimed at the main-
tenance and service personnel of the screw com-
pressor package.
Contact with live components is pro- – ensuring sufficient ventilation and venting,
hibited. – performance of all welding work with the use of
Maintenance work on the running forming gas.
screw compressor package is not per- If gas filled pipes are opened for maintenance work,
mitted. these pipes must be in a gas-free condition.
Work involving intervention in the refrigerant circuit
must only be carried out by qualified engineers in
accordance with the guarantee conditions.
The screw compressor package must always be
switched off before being dismantled. Before begin-
ning the work, it must be ensured that all parts sub-
ject to maintenance/servicing are de-energised(e.g.
by removing the main fuse or installing a shorting
bridge).
The refrigerant must be removed from the applicable
parts of the system parts. This work must be carried
out with great care, taking into account the safety
regulations, so that the maintenance personnel are
not injured by the refrigerant or by the refrigeration
unit oil present in the system.
Parts of the system under pressure must be com-
pletely vented before opening. While carrying out the
repair, it is must always be ensured that a complete
pressure balance of the affected pressure chambers
with the environment is preserved.
10.4.2 Repair work New inspection and approval is required after pres-
sure vessels that are subject to approval have been
Modifications and repair work may only be carried
repaired or changed. Welding may only be carried
out by qualified persons or persons with suitable
out by approved welders with a valid welder’s card.
training with the manufacturer's consent and must
strictly comply with the rules set out in the mainte-
nance instruction for the components concerned.
10.4.3 Maintenance intervals
Hint!
Caution!
The following maintenance notes must
be observed: The maintenance intervals in accord-
ance with the maintenance schedule
Only spare parts made by the original component must be observed.
manufacturer may be used for repairs and for replac-
ing wearing parts. These are available from the The maintenance schedule is an integral part of the
spare parts department. product documentation. The maintenance schedule
contains all the maintenance instructions and certifi-
cations for the first 15 years of performance of the
10.4.2.1 Repair information screw compressor package. The maintenance certifi-
cates are completed and signed as well as acknowl-
Important features of the technology and production edged on the display of the control as part of the
process must be taken into account when repairing inspection and maintenance by authorised fitters as
the plant: evidence of the work done.
– complete sealing of all devices and pipes. During the warranty period, these validated mainte-
nance certificates also serve as a precondition for
– Dryness and cleanliness of the entire plant. any warranty claim put to GEA Refrigeration Ger-
– Use of welding methods causing only a minimum many GmbH.
amount of dirt to collect in the plant.
– Pipes bent on a pipe-bending machine only
10.4.4 Maintenance work
using refrigerating oil.
– If repairing the piping system from your own Hint!
stocks, we recommend that you use a pipe with The documentation for the main com-
NBK surface quality (annealed and descaled, ponents is a part of the product docu-
mechanically or chemically descaled after mentation. This contains important
annealing). information to be considered before
– When carrying out repairs to piping systems, beginning the maintenance work.
care should be taken to maintain the original pip-
ing routes.
– Only pipes of sufficient material quality, which 10.4.4.1 Maintenance of the screw
are certified according to DIN 10216-2 should be compressor
used.
Maintenance works are to be periodically carried out
on the screw compressor (see maintenance sched-
ule). These include:
10.4.2.2 Repairs of pressure vessels
subject to approval inspection – Measure axial play of bearings,
– Check shaft seal,
Hint!
– Check primary slide movement,
The responsible monitoring body
(e.g.TÜV) must be notified in advance. – Check the adjustment of the position sensor.
10. Reopen valves in accordance with item 3. The 10.4.4.4.2 Cleaning the filter element
valve (80) must be returned to its initial position. The metal-gauze element used in the filter can be
11. After the pressure has been compensated, vent cleaned and reused several times before it has to be
the oil filter via the vent valve. changed.
Manual cleaning
10.4.4.4 Maintenance of the suction fil- Immerse the soiled metal-gauze element in a clean,
grease-dissolving liquid, then blow it through with
ter
compressed air from the outside inwards. Here it is
important to place a cylindrical part – possibly wrap-
ped in corrugated cardboard – inside the element to
10.4.4.4.1 Changing the filter element catch the dirt particles.
6. Allow the element to drain off into a suitable con- – when the operating time of the oil charge has
tainer. reached the technically specified oil change
interval,
Caution!
Warning!
When carrying out maintenance,
always inspect the sealing ring (O- Oil change intervals
ring) of the cover for mechanical dam- Oil change with ammonia as the refrig-
age and replace it if necessary. erant after every 5,000operating hours
or after 1 year at the latest.
7. Reassemble all parts with the new or cleaned fil- Oil change with freon as the refrig-
ter element following the same procedure in erant after 10,000operating hours or
reverse order. after 2 years at the latest.
– if the oil becomes unacceptably contaminated- sure between the screw compressor package/
due to a major accident (e.g. water penetration chiller and suction line. If screw compressor
into the refrigerant circuit). packages operated in parallel or other separate
The degree to which oil in refrigeration plants has chillers are present, the refrigerant should pref-
aged must be checked by analysis and in compari- erably be drawn off at a pressure which is
son of the data with those of fresh oil. Oil ageing can approx. 1 to3 bar above atmospheric pressure.
also be judged from the darkening of the oil colour Then re-close the stop valves bypass and the
and the deposits found in the oil filters. If the degree suction-side stop valve. Otherwise the pressure
of ageing cannot be assessed reliably by laboratory can be reduced by opening the vent valve on the
analysis and the results of visual examination, it is suction filter and then disposing of the refrigerant
advisable to change the oil at the following intervals as specified by law.
(see maintenance checklist). 4. Then drain the used oil through the oil
The assessment of the condition of the refrigerating draining/oil charging valves and dispose of it
machine oil by means of a general visual inspection (Caution! hazardous waste!). Once this has
(contamination) or laboratory analysis must be car- been done, re-close the valve and if possible
ried out: continue to draw off the refrigerant with a com-
pressor connected in parallel or a disposal
– after 5000 operating hours:
device until atmospheric pressure is almost
or reached.
– at the end of one year's operation 5. Otherwise depressurise the screw compressor
or package/chiller by opening the vent valve on the
suction filter, taking into account the safety rules
– after remedying major damage.
for refrigeration systems.
or
6. Open the drain plugs and valves on the oil
– if the oil is dark coloured or very cloudy. cooler, oil separator and OMC block to drain any
residual oil. Then re-close the drain plugs and
valves.
10.4.4.5.2 Oil change, maintenance
7. Replace the filter element of the oil filter; replace
work
and/or clean the filter element of the suction filter
Take oil samples for analysis and comparison with combination.
the fresh oil data at regular intervals. Check the col- 8. Evacuate the screw compressor package/chiller
ouration of the oil visually and assess the degree of using a vacuum pump.
contamination.
Depending on the results, the user must decide Warning!
whether to approve the postponement of filling the oil Shut off the oil pump!
until the next assessment date or whether to have
the oil changed. 9. Pressurise the screw compressor package/chiller
Inadmissibly damp oil must be removed from the with a slight overpressure via the stop valve
compressor unit/chiller immediately. bypass check valve on the pressure side.
10. Then check all components for leakages. On
successful completion, perform a complete pres-
10.4.4.5.3 Changing the oil sure compensation with the discharge line fol-
1. The screw compressor package/chiller must be lowed by a repeated leakage test of the screw
run for at least half an hour to reach its operating compressor package/chiller. The oil charge oil
temperature before the oil can be changed. and start-up of the screw compressor package/
chiller must be accomplished in accordance with
2. First shut down the screw compressor package/ the operating instructions.
chiller as described in the operating instructions.
3. Open the stop valve in the bypass line around
the check valve on the suction side and the stop
valve on the suction side to equalise the pres-
Hint!
fig.47: Arrangement of MIN / MAX sight glasses
The regular examination of all operat-
1 Sight glass - MAX (operation)
ing data, such as pressure, tempera-
2 Sight glass - MIN (standstill) ture, power consumption, degree of fil-
ter fouling, etc., helps in the early
The oil level is checked visually via the sight glasses detection of potential failure!
of the oil separator. The oil level should have a value
between 1/2 filling level of sight glass N10c (MAX -
operation) and 1/2 height of sight glass N10b (MIN -
10.4.4.7 Changing the fine oil separa-
standstill).
tion cartridges
If the oil level is too low, i.e. the oil level has a value
less than 1/2 filling level of sight glass N10b (MIN - The fine oil separation cartridges should be replaced
standstill), oil must be replenished. no later than after 25,000 run hours or 5 years.
If the oil carry over of the screw compressor package 10.4.4.8 Tightening screw fastenings
increases severely (oil recharging at unusually short
Screw fastenings of components can become loose
intervals), replacement may be necessary even ear-
due to vibration or movement. Screw fastenings
lier.
must therefore be checked regularly to ensure they
are tight and retightened if necessary.
Screw fastenings must only be tightened to the maxi-
mum tightening torques.
Unless otherwise stated by warning signs, the tight-
ening torque is dependent on the size and strength
of the screw fastening.
the leak must therefore be located and remedied if If leaks are determined, these must be sealed imme-
there is: diately. Release the test pressure before beginning
repair! Evacuate the system after repairs are com-
– Loss of the inert gas charge (delivery state),
plete and after rechecking for leaks.
– Loss of the entire refrigerant charge
or
10.4.4.12 Venting the refrigerant circuit
– underfilling.
Lower refrigerant levels in the containers are due to When air penetrates the refrigerant circuit, this
loss of refrigerant as a result of leaks. For this rea- makes itself felt in a fall-off in performance and the
son, all pipes, connections and valve glands should manometer on the discharge side of the compressor
be checked regularly, especially in the initial period indicates a higher pressure compared to the conden-
of assembly. sation temperature. Any leaks must be remedied. In
The most striking feature if there is a leak in the filled extreme cases, air in the circuit may interrupt the
refrigerant circuit is the smell of refrigerant. The flow of refrigerant and cause the oil cooling to fail.
odour threshold of ammonia in the air is approx. 5 There are several ways of venting the system. The
ppm and thus well below the permitted MAK values. air or the NH3-air mixture is vented via the vent
Methods of leak detection: valves of the condenser or the suction filter in water
filled vessels when the package is at a standstill.
– Regular visual inspections.
If air is in the mixture, the venting ammonia is absor-
– Smudges/dirt stains indicate leaking bed from water.
refrigerant/oil mixture.
Hint!
– Leak tests with nitrogen with a max. of 0.5%
ammonia by volume, an elapsed time of more Continuous venting using a Grasso
than 3 hours and application of a foaming agent purger is recommended.
to all the joints with a brush. Oil-filled compres-
sors or circuit sections must only be charged
with nitrogen – not air – to generate pressure. 10.4.4.13 Refrigerant evacuation
– Use of an NH3 leak detector.
Hint!
– Ammonia produces the following colours when
Shut the oil pump during evacuation!
leak tests are performed:
– Red litmus paper turns blue, The purpose of evacuating the system is to remove
air and moisture from the refrigerant circuit.
– Blotting paper impregnated with phenolph-
thalein turns red (moisten). Evacuation is required:
10.4.4.14 Checking the bearing noise Maintenance of the compressor drive motor includes
the following activities:
The bearings of the drive motor and the compressor
must be checked for unusual running noise, espe- – Lubrication of the motor
cially in comparison to previous maintenance. Recur- Lubrication intervals and quantities according to
rent vibration measurements are recommended. the "Motor documentation" or "Type plate".
– Cleaning of the motor (externally)
10.4.4.15 Checking the solenoid valves Select a suitable cleaning agent according to the
for capacity control "Motor documentation".
Hint!
The compressor drive motor must be
maintained in accordance with the
"Motor documentation".
Parameter to be Every 24
Weekly Monthly Remark
checked to 72hrs
10.4.4.23 Insulation
Check the insulation (if present) on components,
containers and piping for damage.
Damaged insulation must be replaced. The insula-
tion strength must be selected according to the tem-
perature and humidity at the place of installation.
Details on the insulation can be found in the P+I dia-
gram.
Caution!
No screw connections must be used
under the insulation if the piping is
insulated. The pipes must be welded.
Hint!
The tightening torques for the adjust-
ing elements should be obtained from
the data sheet. The data sheet forms
part of the product documentation.
11 DECOMMISSIONING
3. Switch off the main switch of the three-phase
electric system.
11.1 Shut-down in the event of danger-
ous situations 4. If necessary, shut off the secondary refrigerant,
heating agent or the cooling water supply.
The safety equipment of the screw compressor pack-
age complies with EN 378. 5. Ensure that the venting slots of the electric
motors are covered under all circumstances!
By means of automatic monitoring of the individual
operating parameters, the control unit detects haz- ® Shut-down has been carried out
ardous situations in good time and automatically
switches off the screw compressor package.
The cause of the fault is displayed on the control unit 11.3 Standstill for a period >48 hours
and can then be corrected.
Hint!
Among other things, the concept of the screw com-
pressor packages is based onlow maintenance The obligation to label the plant as
refrigerant circuits that are as well sealed as possi- "Plant not in operation" must be
ble. However, residual risks remain, especially due observed!
to possible leaks or escaping refrigerant or rotating
drive parts. If the screw compressor package is shut down for a
period >48 hours, the following activities must be
Hint! performed:
The EMERGENCY STOP switch in the 1. Switch off the compressor in accordance with the
switching cabinet is used to quickly operating instructions for the electrical switch-
switch off the chiller whenever neces- gear.
sary.
2. Switch off all ancillary drives.
Leaking refrigerant can be detected with a gas 3. Switch off the main switch of the three-phase
detector (not included in the scope of delivery). This electric system.
detector can be integrated in the automatic safety
4. Close the stop valve (or combined stop/check
chain.
valves) on the suction side and the pressure
Please consult the safety regulations in this docu- side.
mentation for information about what to do in the
case of leaking refrigerant. 5. Close the stop valves (or shuttable check valves)
in the suction line of the economiser.
6. Shut off the secondary refrigerant, heating agent
11.2 Standstill for a period <48 hours or cooling water.
12 DECOMMISSIONING, DISPOSAL
Preparatory measures – National regulations (e.g. EN 378-4, Appendix A)
Hint! must be observed for the reclamation and dis-
posal of operating media (oil).
The information in the chapter
"Decommissioning" must be – No unauthorised persons must be within the
observed. installation area of the plant during decommis-
sioning, as they could come into contact with
refrigerant.
Hint!
– All components of the plant which are not to be
Care must be taken during disposal re-used, as well as refrigerant and operating
and devaluation that the various mate- media, must be stored in suitable separate con-
rials are separated and taken for recy- tainers. They must be treated as waste and dis-
cling. Disposal of component remains posed of safely.
and components in the domestic ref-
uge or on refuse tips is not permitted. Hint!
The legal regulations applicable to the Re-use of operating media is not pos-
place of installation regarding the dis- sible!
posal of electrical equipment must be
taken into account.
Dismantled components must be dis-
posed of correctly and according to
legal requirements.