Professional Documents
Culture Documents
COPYRIGHT
All Rights reserved.
No part of this publication may be copied or pub-
lished by means of printing, photocopying, microfilm
or otherwise without prior written consent of
• GEA Refrigeration Germany GmbH
herein after called manufacturer. This restriction
also applies to the corresponding drawings and dia-
grams.
LEGAL NOTICE
This documentation has been written in all con-
science. However, the manufacturer cannot be held
responsible, neither for any errors occurring in this
documentation nor for their consequences.
Warning!
Stands for a possibly dangerous situa-
tion which leads to heavy physical
injuries or to the death.
Caution!
Stands for a possibly dangerous situa-
tion which could lead to light physical
injuries or to damages to property.
Hint!
Stands for an important tip whose
attention is important for the designa-
ted use and function of the device.
TABLE OF CONTENTS
1 MAIN MODULES 9
1.1 General description 9
1.1.1 Operating areas and advantages of FX GC PP 9
1.1.2 Technical description FX GC 9
1.1.3 Chiller with reciprocating compressors - series FX GC and MX GC 10
1.1.4 Description of main components 13
1.1.4.1 Reciprocating compressor 13
1.1.4.2 Compressor drive motor 13
1.1.4.3 Evaporator + liquid separator 14
1.1.4.4 Condenser 15
1.1.4.5 Injection control 16
1.1.4.6 Oil return system 16
1.1.4.7 Fittings 16
1.1.4.8 Switching cabinet / control 17
2 MAIN DATA 19
2.1 Technical Data 19
2.1.1 Grasso FX GC PP 260 NH3 to Grasso FX GC PP 1250 NH3 19
2.1.2 Grasso FX GC PP 520 NH3 to Grasso FX GC PP 900 NH3 21
2.1.3 Grasso FX GC PP 1050 duo NH3 to Grasso FX GC PP 1800 duo NH3 23
2.1.4 Operation limits 24
2.1.5 Acoustic values 25
2.2 P+I diagrams 26
2.2.1 P+I diagram FX GC PP 26
2.2.2 Designation for main components and fixtures - Liquid chiller Grasso FX GC PP NH3 27
2.2.3 P+I diagram FX GC PP duo 29
2.2.4 Designation for main components and fixtures - Liquid chiller Grasso FX GC PP NH3 30
2.3 Main dimensions 32
2.3.1 FX GC PP 260 to FX GC PP 1250 32
2.3.2 FX GC PP 520 duo to FX GC PP 1800 duo 34
2.4 Capacity calculation 36
2.5 Pressure losses 36
3 INSTALLATION 37
3.1 Installation 37
3.1.1 Delivery 37
3.1.2 Basic information for installation 37
3.1.2.1 Information regarding installation in machinery room 37
3.1.2.2 Rigid installation 37
3.1.2.3 Installation of the Screw Compressor for Insulation against Structure-borne
Sound 37
3.1.2.4 Electrical connection 37
3.1.2.5 Sound insulation, weather protection 38
3.1.2.6 Air-cooled condenser and evaporation condenser for GG LP and GC VP ser-
ies 38
3.1.3 Cooling agent system 38
3.1.4 Heating agent system 38
3.1.5 Water pipes 38
3.1.6 Refrigerant lines 38
3.1.7 Electrical installation 39
3.1.8 Installation information 40
3.1.8.1 Foundation plan 40
3.2 COOLING AGENT SYSTEMS ON RECIPROCATING CHILLERS 41
3.2.1 Single chiller, single pump systems 41
3.2.2 Single chiller, double-pump systems 43
3.2.3 Multi chiller, double-pump systems 44
3.3 Transport (crane transport) 46
4 MAINTENANCE INSTRUCTIONS 49
4.1 Maintenance schedule for liquid chiller 49
4.2 Regular maintenance 49
4.3 Machine room information 49
TABLE OF FIGURES
fig. 1 Position of the reciprocating compressor 13
fig. 2 Position of the compressor drive motors 13
fig. 3 Arrangement of the evaporator 14
fig. 4 Position of the liquid separator 14
fig. 5 Position of the condenser 15
fig. 6 Heat recovery 15
fig. 7 Injection control 16
fig. 8 Position of the oil return 16
fig. 9 Position of the switching cabinet 17
fig. 10 P+I diagram FX GC PP 26
fig. 11 P+I diagram FX GC PP duo 29
fig. 12 Set drawing FX GC PP 32
fig. 13 Set drawing FX GC PP duo 34
fig. 14 Foundation plan 40
fig. 15 Single chiller, single pump systems 41
fig. 16 Compressor switching frequency 42
fig. 17 Single chiller, double-pump systems 43
fig. 18 Multi chiller, double-pump systems 44
fig. 19 Designation of the lifting points 46
fig. 20 Transport 47
fig. 21 Shackles 47
1 MAIN MODULES
• Its GWP (Global Warming Potential) is zero. Liquid chiller with water-cooled con-
GC PP
• Its ODP (Ozone Depletion Potential) is zero. denser and closed refrigerant circuit
X Chiller series
Y Condenser version
Z Evaporator version
X1 Chiller type
X2 Refrigerant
X Chiller type
FX GC flooded evaporation
Y Condenser version
L Air cooled condenser (not in the scope of delivery for GEA Refrigeration Germany)
V Vapour condenser (not in the scope of deliver for GEA Refrigeration Germany)
Z Evaporator version
9 Nominal chiller capacity at 1500 min-1 (V300 ... V600) / 1200 min-1 / (V700 ... V1800) in kW related to cold
water operation 12 °C / 6 °C
with 1 compressors
V300 260
V450 400
V600 525
V700 600
V1100 900
V1400 1250
V1800 1500
2x V300 520
2x V450 800
2x V600 1050
2x V700 1200
2x V1100 1800
2x V1400 2500
2x V1800 3000
X2 refrigerant
NH3 Ammonia
Naming example
1.1.4.4 Condenser
Hint!
All instructions for the controls refer
to the GSC TP (hereinafter referred to
as the GSC).
Hint!
It is not permitted to add an external
controller between the GSC and the
power panel; this would extend the
safety chain to be achieved. All control
signals between the GSC and the
power panel must be processed
directly and must not flow indirectly
via an external controller. The manu-
facturer cannot otherwise guarantee
the safe operation of the system.
2 MAIN DATA
Power consumption
kW 48.1 71.2 94.3 103.4 153.3 203.6
Compressor 1) Peff
Oil charging quantity VOIL l 11.5 13.5 18.5 21.5 28.5 41.5
Electrical data of compressor motor -1500 min –-1, 400 V / 3 Ph / 50 Hz3), IP 23, air cooled
Switching cabinet for power supply 3 PEN / 400 V, internal control voltage: 230 V / 50 Hz / 24 VDC
Hint!
Variation in cooling agent and heating agent temperatures can lead to changes in the heat
exchanger and motor classification and therefore to different technical data.
Power consumption
kW 96.2 119.3 142.4 165.5
Compressor 1) Peff
Electrical data of compressor motor -1500 min –-1, 400 V / 3 Ph / 50 Hz3), IP 23, air cooled
Switching cabinet for power supply 3 PEN / 400 V, internal control voltage: 230 V / 50 Hz / 24 VDC
Hint!
Variation in cooling agent and heating agent temperatures can lead to changes in the heat
exchanger and motor classification and therefore to different technical data.
Power consumption
kW 188.6 206.8 256.7 407.2
Compressor 1) Peff
Electrical data of compressor motor -1500 min –-1, 400 V / 3 Ph / 50 Hz3), IP 23, air cooled
Switching cabinet for power supply 3 PEN / 400 V, internal control voltage: 230 V / 50 Hz / 24 VDC
Hint!
Variation in cooling agent and heating agent temperatures can lead to changes in the heat
exchanger and motor classification and therefore to different technical data.
The ammonia chillers (flooded evaporation) can be During operation of the chiller, the
operated under the most varied operation conditions increase of the cooling agent inlet tem-
within the given limits of application according to the perature must be limited to max. 3 K
requirements involved. The limits of application listed within 2 minutes.
below are based on the operational principle of the If the specified limits are exceeded for a specific
reciprocating compressor, thermodynamic relations, application, the manufacturer must be consulted.
used vessels and safety devices and practical oper-
ating conditions. The appropriate Compressor model In addition to the operating limits stated in the tables,
design should be selected for the particular operating the operating conditions of the respective compres-
conditions. sor type to be complied with must also be taken into
account (e.g. start-up regime, oil pressure, quantity
Caution! of oil, type of oil, etc.).
When considering a specific applica- The data entered pertain to the operating conditions
tion, all the conditions specified in the for a chiller or air conditioner. During shut-down or
table must be taken into account and during start-up, the limits may temporarily be excee-
adhered to. ded or not be met (never permanently).
Outlet tempera-
ture with frost- min -10
tKA °C
resistant cool- max +15
ing agents
Condensing min 10
pc bar (a)
pressure max 23
[dB(A)]
63 125 250 500 1000 2000 4000 8000
260 75 90 81 89 92 90 87 85 83 77
400 78 92 91 89 85 92 91 87 85 79
525 80 96 83 95 94 97 93 84 83 82
Size GC P duo
520 79 93 84 92 95 93 90 88 86 80
650 81 94 84 92 93 94 92 89 87 81
800 81 95 84 92 88 95 94 90 88 82
900 84 97 85 96 95 98 95 89 87 84
1050 86 99 86 98 97 100 96 87 86 85
1) Measuring point distance 1m; coolant and heating pump range tolerances up to +3 dB
1 Customer
2 GEA Refrigeration Germany GmbH
3 Temperature probe, delivered separately
4 Flow controller, delivered separately
5 Temperature probe, delivered separately/for installation in line 2 m after evaporator
6 Cooling agent
7 Heating agents
8 Connection made on the liquid separator
Item Name
1 Customer
2 GEA Refrigeration Germany GmbH
3 Temperature probe, delivered separately
4 Flow controller, delivered separately
5 Temperature probe, delivered separately/for installation in line 2 m after evaporator
6 Cooling agent
7 Heating agents
8 Connection made on the liquid separator
250 Pressure stop valve Compressor 1 2320 Stop valve, oil return
Item Name
FX GC PP L1 L2 B H
mm
FX GC PP duo L1 L2 B H
mm
3 INSTALLATION
The insulation resistance of the electrical tools and ing in the supply documentation for the dimensions
fixtures and wiring is to be checked. The connection and position of the water connections to the evapora-
may only be undertaken if this value lies in the allow- tor.
able range.
• The evaporator should be installed on the pres-
All electrical connections must be established and all sure side of the pump.
electrical consumers/sensors must be connected
according to the circuit diagram. • Arrange a dirt collector immediately upstream of
the evaporator (recommended mesh size 0.5
3.1.2.5 Sound insulation, weather pro- mm).
tection • The volume of cooling agent should be kept at a
If the chiller is intended for outside installation, it constant level.
must be equipped with a suitable casing for sound 3.1.4 Heating agent system
and weather protection by the customer. The
weather protection must provide sufficient protection After the chiller has been aligned, it can be connec-
for the machine with regard to the climatic conditions ted on the heating agent side. The piping for the
at the installation location. heating agent connections must be installed on site
by the plant engineer.
Hint!
If the chiller is mounted on vibration isolators, the
The chiller is not intended for unpro- water lines must be connected to the evaporator
tected outside installation. Protection using flexible connections. The size and position of
against outside influences, especially the water connections for the condenser are indica-
dirt, dust and moisture (wetness) is ted in the drawing contained in the order documenta-
essential. tion.
GEA Refrigeration Germany GmbH will not accept • Install the condenser on the pressure side of the
liability for damage due to incorrect outdoor installa- pump.
tion.
• Arrange a dirt trap immediately upstream of the
3.1.2.6 Air-cooled condenser and condenser (recommended mesh size 0.5 mm).
evaporation condenser for GG • Check the water quality.
LP and GC VP series
3.1.5 Water pipes
If an air-cooled condenser or evaporation condenser
is used, certain points must be observed: • All pipes must be installed with flexible connec-
tions, separate from the chiller unit. No additional
The condenser is not integrated in the liquid chiller; it static or dynamic loads must be applied to the
is installed separately. It is usually installed on the chiller connections.
roof of the building.
The connection between the liquid chiller and the • Make sure that vibrations cannot be transmitted.
condenser must be made on site and the necessary • Charging and draining must be possible.
fittings also mounted on site.
• The pipes must be flushed before connecting.
Take summer and winter operating conditions with This is carried out to remove soiling, foreign par-
respect to refrigerant displacements into considera- ticles and welding residue from the system.
tion in line with local circumstances.
Provide for the installation of a refrigerant collector. 3.1.6 Refrigerant lines
3.1.3 Cooling agent system • FX GC PP
Chillers of the FX GC PP series are delivered
After the chiller has been aligned, it can be connec- with complete refrigerant piping, tested and filled
ted on the cooling agent side. The piping system for with nitrogen on the refrigerant side.
the cooling agent connections must be installed on
The blow-off lines for the safety valves are to be
site by the plant engineer.
installed and connected on site (by the client)
If the chiller is mounted on vibration isolators, the
water lines must be connected to the evaporator
using flexible connections. Please refer to the draw-
Danger!
Contact with live components is pro-
hibited.
1 Consuming devices
2 Mixing/buffer tank
3 incorrect
4 better
5 best
R Return
S Supply
The construction of the buffer tank should ensure optimum mixing of the entering cooled cooling agent with the
existing cooling agent in order to achieve appropriate cooling and warming in the same time frame.
Qomin ·150
Vbuffer req. = ----------------------------------- (m³)
pcooling agent · Cρ cooling agent · Δt
1 Temperature
2 Time
3 restart (after 10 minutes)
4 Temperature setpoint
5 Switching state of the compressor
6 Δ tcontrol
7 Δ tcontrol
8 OUT
9 IN
10 Buffer
11 Heating
12 Cooling
Hint!
Ensure that the chiller pump flow is always (at least 20 %) greater than the total pump flow of
the consumer system.
1 Chiller group
2 Equalising / Connecting Tank
3 < 5°C switch-off of the chiller group by the controller
4 > 7°C switch-on of the chiller group by the controller
5 Consuming devices
6 Controller
7 Mixing/buffer tank
R Return
S Supply
1 Main PLC
2 Under PLC
3 Unit n
4 Unit 2
5 Unit 1
6 Equalising / Connecting Tank
7 < 5°C switch-off of the chiller group by the controller
8 > 7°C switch-on of the chiller group by the controller
9 Consuming devices
10 Controller
11 Mixing/buffer tank
R Return
S Supply
Hint!
Ensure that the chiller pump flow is always (at least 20 %) greater than the total pump flow of
the consumer system.
Unlike the mixing tank, the equalising tank should guarantee laminary flow to obtain stratification of the warm
and cold cooling agent. The inlets should be executed in such a manner that no impulse will be introduced and
the cooling agent velocity in the tank should be less than:
2300 x J (m²/s)
d Tank (m)
Ammonia liquid chillers are high-quality products which must be handled with extreme care during transport. Pro-
tect the equipment from impacts and put it down carefully.
Danger!
Make certain there is no one under the suspended load during transport with the crane!
When transported by crane, the chiller must have the same position (frame downwards) as in operation.
Caution!
It is prohibited to strap liquid chillers to any fittings or pipes or to the eyebolts/lugs on the
compressor, electric motor, heat exchanger or switching cabinet.
Use the four carrier eyes on the base frame as lifting points for crane transport. Only use the lifting points provi-
ded.
The lifting points are marked!
Take special care not to attach the ropes near to small nominal diameter pipes or to insulation and not to dam-
age them. To prevent damage, attach cross-arms to the ropes.
fig.20: Transport
1 Cross-arm
Make suitable arrangements (timber or Armaflex support) to avoid damage to the surface. Shackles must be
used.
fig.21: Shackles
Warning!
Chillers must be adequately protected from external influences during transport.
Position the chiller on the transport vehicle in such a way that it is prevented from sliding, tilting or falling down.
Load securing is preferably carried out by lashing to the specified points. The pipes and equipment parts of the
chiller must not be stepped on. Components must be secured against vibrations. The competent staff member or
the company is responsible for ensuring transport safety.
4 MAINTENANCE INSTRUCTIONS
4.1 Maintenance schedule for liquid • There should be no danger that the equipment
can be damaged by in-plant transport and han-
chiller
dling operations.
The maintenance schedule listed below indicates the • Sufficient space must be available for visual
operating hours at which maintenance activities inspection and maintenance work on the equip-
should be carried out. For most of the maintenance ment.
work, the chiller unit must be disconnected. To avoid
shutting down the system at inconvenient times, • The floor on which the equipment is set up must
such maintenance work should be carried out during be such that ammonia and oil cannot seep in the
regular shut-downs as far as possible. ground.
To reduce maintenance costs, we have set up the The accident prevention directive "Refrigerating sys-
schedule so that various kinds of work can be carried tems, heat pumps and chillers" BGVD4, (see Art. 16)
out at the same time. stipulates additional requirements for the installation
It is advisable to service the chiller unit once a year, of ammonia chillers in order to guarantee that such
irrespective of the number of operating hours. equipment is operated safely.
Chiller unit maintenance must be carried out by the You will find more information on the machine room
plant engineer/client in accordance with the enclosed situation in our brochure "Installing liquid chillers in
schedule. the member states of the European Union - EN 378
requirements".
• After 100 operating hours: Change the lubricat-
ing oil and carry out compressor maintenance 4.4 Personal protection
(see compressor manual)
The company shall provide personal safety equip-
• Replace the disposable suction gas filter on the ment against exposure to refrigerant. This equipment
compressor with the replacement filter provided shall be stored ready-for-use outside the hazardous
after a maximum of 100 hours. Check the tight- areas in an easily accessible manner.
ening torques of the coupling pins. Safety equipment for at least two persons should be
• Every 2,500 hours: Inspection and maintenance available.
of the liquid chiller unit Safety equipment for ammonia:
• Every 10,000 hours: General inspection and – Safety gloves
maintenance of the liquid chiller unit
– Safety goggles
4.2 Regular maintenance – Respiratory equipment with filter
2,500-hour (or annual) maintenance: Safety systems:
1. Inspection and maintenance of the compressor To ensure a high level of safety against leaking
ammonia
2. Check that the chiller unit is level (adjustment of
– Ammonia warning systems and
the vibration insulators if necessary)
3. Inspect water piping flanged connections for – Absorption systems
stress can be ordered.
10,000-hour maintenance:
1. Carry out the 2,500-hour maintenance
2. Carry our general inspection of the compressor
and maintain compressor as described in the
compressor manual.
5 SPECIFICATION
5.1 FX GC PP NH3
Power consumption kW
Condenser rating kW
Cooling agents
Heating agents
Condensing temperature oC
Length mm
Width mm
Height mm
Refrigerant charge kg
Shipping weight kg
Operating weight kg
5.1.2 Package
Compressor type
Wiring
Painting Protective paint system S 2.15 acc. to EN ISO 12944-5 for environmental
conditions C2 acc. to EN ISO 12944-2.
Insulation type Suction pipe and liquid separator insulated with Armaflex
Controller
Flow switch for cooling agent Mechanical flow switch, delivered separately
Design IMB 3
Number of poles
Frequency 50
Rated current A
Type of power supply Switching cabinet, protection class IP 54, completely wired internally,
main switch gear assembly, fuse disconnect, circuit breaker for drive
motor, protection for auxiliary motor including thermal overcurrent trigger
and fuses, control transformer with double control circuit fuse on primary
and secondary side, 24 V DC power supply,
Evaporator
Plate heat exchanger of modular semi-welded design; secondary refrigerant ports are complete with flanges
and counter flanges.
Condenser
Plate heat exchanger of modular semi-welded design; cooling medium ports are complete with flanges and
counter flanges.
Safety devices
Change-over valve 1
Approval for chiller Work's Certificate, Certificate of Conformity acc. to Machine Directive
98/37/EG. Calculation and manufacture acc. to AD 2000 and EN 378.
Approval pressure equipment Certificate of Conformity acc. to Pressure Equipment Directive (PED)
97/23/EG. Calculation and manufacture acc. to AD 2000 and EN 378.
Sets of documentation 2
Foundations, pipes on water side, spare parts and special tools, refriger-
Not included in scope of delivery
ant and lubricating oil, performance test and start up.
Power consumption kW
Condenser rating kW
Cooling agents
Heating agents
Condensing temperature oC
Length mm
Width mm
Height mm
Refrigerant charge kg
Shipping weight kg
Operating weight kg
5.2.2 Package
Wiring Wiring
Painting Protective paint system S 2.15 acc. to EN ISO 12944-5 for environmental
conditions C2 acc. to EN ISO 12944-2.
Insulation type Suction pipe and liquid separator insulated with Armaflex
Controller
Flow switch for cooling agent Mechanical flow switch, delivered separately
Drive motor(s)
Motor 1
Design IMB 3
Number of poles
Frequency 50
Rated current A
Motor 2
Design IMB 3
Number of poles
Frequency 50
Rated current A
Type of power supply Switching cabinet, protection class IP 54, completely wired internally,
main switch gear assembly, fuse disconnect, circuit breaker for drive
motor, protection for auxiliary motor including thermal overcurrent trigger
and fuses, control transformer with double control circuit fuse on primary
and secondary side, 24 V DC power supply,
Evaporator
Plate heat exchanger of modular semi-welded design; secondary refrigerant ports are complete with flanges
and counter flanges.
Condenser
Plate heat exchanger of modular semi-welded design; cooling medium ports are complete with flanges and
counter flanges.
Safety devices
Change-over valve 1
Approval for chiller Work's Certificate, Certificate of Conformity acc. to Machine Directive
98/37/EG. Calculation and manufacture acc. to AD 2000 and EN 378.
Approval pressure equipment Certificate of Conformity acc. to Pressure Equipment Directive (PED)
97/23/EG. Calculation and manufacture acc. to AD 2000 and EN 378.
Sets of documentation 2
Foundations, pipes on water side, spare parts and special tools, refriger-
Not included in scope of delivery
ant and lubricating oil, performance test and start up.