You are on page 1of 1

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20

GENERAL NOTE:
A A

Spacing of Sensor Head:


System: Automatic Fire Alarm with Addressable Detection System Maximum Coverage Area: 900 ft² (83.65 m²)
B
Standard: NFPA 72, National Fire Alarm and Signaling Code, 2013 (Considering 70% Coverage Area of Device )
01. For Flat Plate/Slab: 23.67 ft (7.22m) Max.
Occupancy Classification: G-2 (Garments Industry) Starting from Spacing/2 from Wall/Partition.
C
Hazard Group: Moderate Hazard Class-II 02. For Patch Roof/Shed Roof: 23.67 ft (7.22m) Max. C

Starting from Spacing/2 from Wall/Partition.


Product Brand: Hochiki (UL Listed), Origin: UK/USA/Japan 03. For Room: 1 Detector Per Room upto
Room Area 560 sft (52.07 sqm),
D
Control Panel: 04. For Beam-Column Slab: 1 Detector Per Bay
D

01-Loop Analog Addressable Control Panel upto Bay Area 560 sft (52.07 sqm)
with Trouble Alarm Notification Spacing Reduction Factor will be appiled when Floor
E Model: Fire NET-1127 Plus, Certification Number: UOJZ.S6468 Height is more than 12'-0" (3.66 m) E

Photoelectric Smoke Sensor (Detector): NUMBER OF CABLE RISER:02


Model: ALN-V (Hochiki), Certification Number: UROX.S1383 Circuit Type: Class-A For Sensors & Devices and
F F

Class-B For Notification Application Circuit (NAC)


Rate of Rise Heat Sensor (Detector): Number of Circuit :
Model: ATJ-EA (Hochiki), Certification Number: UQGS.S2966 Cable Riser- 01: 06 ( Class-A: 04, Class-B: 02 )
G Cable Riser- 02: 03 ( Class-A: 02, Class-B: 01 ) G

Sensor (Detector) Base:


Model: YBN-NSA-4 (Hochiki), Certification Number: UROX.S1383 Cable:
Product Brand: TIANJIE
Series Addressable Manual Pull Station (Call Point):
H H

Type: FPLR Power Limited Fire Alarm Cable


Model: DCP-AMS-LP (Hochiki), Certification Number: UNIU.S6512 Certification No.: E464899 (UL)
01. For Sensor (Detectors): 2CX1.5 mm² (Solid) Shield FPLR
I Wall Mounted Horn Strobe: 02. For Fire Alarm (NAC): 2CX2.5 mm² (Solid) Shield FPLR I

Model: HEC3-24WR (Hochiki), Certification Number: ULSZ.S1529


Required Battery:
Dual Relay Output Moudule : Fire Alarm Control Panel-01: 2X12 V, 11.2 AH Suggest: 26.00 AH
J J

Model : DCP-R2ML/DCP-R2ML-I (Hochiki), NAC-01 for Fire Alarm Control Panel : 01


Certification Number: UOXX.S5694 NAC-01 : Supply Voltage (VDC): 24 V, Last Device Voltage: 19.94 V
NAC-02 for Fire Alarm Control Panel : 01
K Short Circuit Isolator Module: NAC-02 : Supply Voltage (VDC): 24 V, Last Device Voltage: 20.39 V K

Model: DCP-SCI (Hochiki),


Certification Number: UOXX.S5694 Emergency Power:
L
Emergency Power Shall be Provided for Automatic Fire Alarm L

Conduit: with Addressable Detection System.


Rigid; Standard PVC (Poly Vinyl Chloride) Check the light source and air source before installation of sensors.

M M

PROJECT NAME SHEEL-TECH ENGINEERING & ENERGY DRAWING TITLE DRAWING NAME GENERAL NOTES
INDUSTRIAL CONSULTANT SHEEL-TECH ENGINEERING & ENERGY.
IS PRODUCE THE ALL DRAWING & DESIGN. ARCHITECTURE, STRUCTURAL, ELECTRICAL &
PLUMBING DEPARTMENT COOPERATIVELY PRODUCE & CHECK THE DRAWING. IF ANY INQUIRY
CONSULTANT

OR OBLIGATION INFORM TO SHEEL-TECH. AS PER CLIENT REQUIREMENT & SHEEL-TECH


CHECKED BY
DESIGNED BY
CLIENT NAME

Corporate Address: House No-JA/70 - (1st Floor),


B.Sc ENGINEER (ME)

TECHNICAL TEAM IT CAN BE CHANGE OR MODIFY. UNDER THE NOTE IS VALID FOR DRAWINGS
Bhuiyan Manson, Gulshan-Badda Link Road, PAGE NO 01
DRAWN BY

Cell: 01622-211284

RELATED TO THIS PROJECT:


Middle Badda, Dhaka-1212. FIRE SAFETY DESIGN A. PLEASE DO NOT SCALE FROM THIS DRAWING.
LOCATION
JAKIR AHMED

DATE 29.02.2024 B. CONTRACTORS AND SUB-CONTRACTORS ARE TO VERIFY ALL DIMENSIONS AT THE SITE.
Hot Line: +8801622-211284, ADDRESSABLE FIRE ALARM WITH C.THE CONTRACTOR IS TO NOTIFY THE CONSULTANT ABOUT ANY ISCREPANCIES/DIFFERENCES

NOTES
N E-mail:sheeltech.dhaka@gmail.com JAKIR AHMED NUR SHAHIDUL ALAM FORMAT A-2
CONTAINED IN THE DRAWING (IN RELATION TO OTHER DRAWINGS) BEFORE BEGINNING WORK. N

Architectural/Structural/Fire/ B.Sc ENGINEER (ME) B.Sc ENGINEER (CIVIL) RUET


DETECTION SYSTEM THIS DRAWING IS THE PROPERTY OF SHEEL-TECH & SHOULD NOT BE COPIED, REPRODUCED
COURSED FOR ANY OTHER PURPOSE THEN SPECIFIED WITHOUT THE PRIOR PERMISSION OF
Electrical/Intrior/Exterior/Environment. MIEB: M-31811 SCALE N/A THE ARCHITECT / ENGINEERS IN WRITING

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20

You might also like