niversal onsultancy Services


Consulting Engineers

 
 
AlDar Al Arabiya (DAA) 
 
Plot A ‐ Emergency Lighting Calculations 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Page 1 of 1

Tel. + 962.6. 55 29 476 Fax + 962. 6.55 22 476 Email: info@ucs-jo.com


Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Fire Pump Room / Emergency Scene / Summary

Height of Room: 4.700 m, Mounting Height: 3.700 m, Maintenance factor: Values in Lux, Scale 1:92
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 79 39 109 0.498
Floor 20 79 39 110 0.491
Ceiling 50 18 13 23 0.708
Walls (4) 30 57 15 253 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 21 21
Grid: 64 x 64 Points Lower Wall 22 22
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.731, Ceiling / Working Plane: 0.234.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
THORN 96630973 (STD - standard)
1 2 AQFPRO S LED4300-840 PC MB HF QC3 4300 4300 33.0
(1.000)
Total: 8600 Total: 8600 66.0

Specific connected load: 1.99 W/m² = 2.53 W/m²/100 lx (Ground area: 33.25 m²)

Page 1
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

refrigerator / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:103
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 99 25 201 0.253
Floor 20 99 25 202 0.257
Ceiling 50 19 9.45 28 0.500
Walls (4) 30 63 12 200 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 22 22
Grid: 64 x 64 Points Lower Wall 22 22
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.638, Ceiling / Working Plane: 0.191.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629745 (STD - standard) OMEGA
1 3 4000 4000 36.5
LED 4000-840 HF Q597 (1.000)
Total: 12000 Total: 12000 109.5

Specific connected load: 1.67 W/m² = 1.68 W/m²/100 lx (Ground area: 65.60 m²)

Page 2
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Weighing & Sampling Booth / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:105
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 142 44 220 0.311
Floor 20 142 45 220 0.313
Ceiling 50 29 14 51 0.476
Walls (4) 30 98 18 537 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 21 21
Grid: 64 x 64 Points Lower Wall 22 22
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.687, Ceiling / Working Plane: 0.204.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629745 (STD - standard) OMEGA
1 3 4000 4000 36.5
LED 4000-840 HF Q597 (1.000)
Total: 12000 Total: 12000 109.5

Specific connected load: 2.83 W/m² = 1.99 W/m²/100 lx (Ground area: 38.71 m²)

Page 3
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Material Entry / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:27
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 96 55 133 0.572
Floor 20 96 54 133 0.569
Ceiling 50 14 9.20 18 0.663
Walls (4) 30 49 9.51 147 /

Workplane:
Height: 0.000 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.512, Ceiling / Working Plane: 0.145.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242098 (STD - standard) CETUS
1 1 1950 1950 19.5
LED 2000 HF 840 (1.000)
Total: 1950 Total: 1950 19.5

Specific connected load: 2.78 W/m² = 2.91 W/m²/100 lx (Ground area: 7.02 m²)

Page 4
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Labeling Room / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:66
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 140 17 429 0.120
Floor 20 121 23 235 0.188
Ceiling 70 28 12 67 0.425
Walls (4) 50 66 16 347 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 19 19
Grid: 64 x 64 Points Lower Wall 18 18
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.466, Ceiling / Working Plane: 0.202.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 2 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 8400 Total: 8400 73.0

Specific connected load: 1.75 W/m² = 1.24 W/m²/100 lx (Ground area: 41.82 m²)

Page 5
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Lift Lobby / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:37
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 73 13 143 0.178
Floor 20 73 13 143 0.178
Ceiling 70 16 6.84 26 0.422
Walls (4) 50 38 7.71 115 /

Workplane:
Height: 0.000 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.518, Ceiling / Working Plane: 0.223.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242098 (STD - standard) CETUS
1 1 1950 1950 19.5
LED 2000 HF 840 (1.000)
Total: 1950 Total: 1950 19.5

Specific connected load: 1.53 W/m² = 2.10 W/m²/100 lx (Ground area: 12.76 m²)

Page 6
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Preparation Room / Emergency Scene / Summary

Height of Room: 4.700 m, Mounting Height: 3.700 m, Maintenance factor: Values in Lux, Scale 1:81
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 67 13 153 0.194
Floor 20 58 19 99 0.326
Ceiling 70 10 7.20 14 0.689
Walls (4) 50 24 6.47 196 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 13 13
Grid: 64 x 64 Points Lower Wall 14 14
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.334, Ceiling / Working Plane: 0.156.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
PHILIPS SM480C W24L134 ACC-MLO
1 1 3498 3500 35.0
LED35S/840 NO (1.000)
Total: 3498 Total: 3500 35.0

Specific connected load: 1.12 W/m² = 1.68 W/m²/100 lx (Ground area: 31.18 m²)

Page 7
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Plant In Bound / Emergency Scene / Summary

Height of Room: 4.700 m, Mounting Height: 3.700 m, Maintenance factor: Values in Lux, Scale 1:81
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 56 23 104 0.417
Floor 20 56 23 104 0.418
Ceiling 70 16 10 25 0.615
Walls (4) 50 33 11 194 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 19 19
Grid: 64 x 64 Points Lower Wall 21 21
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.588, Ceiling / Working Plane: 0.291.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
THORN 96630973 (STD - standard)
1 1 AQFPRO S LED4300-840 PC MB HF QC3 4300 4300 33.0
(1.000)
Total: 4300 Total: 4300 33.0

Specific connected load: 1.01 W/m² = 1.80 W/m²/100 lx (Ground area: 32.71 m²)

Page 8
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Plant Office In/Out Bound / Emergency Scene / Summary

Height of Room: 4.700 m, Mounting Height: 3.700 m, Maintenance factor: Values in Lux, Scale 1:37
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 117 42 178 0.357
Floor 20 90 55 117 0.603
Ceiling 70 25 16 35 0.651
Walls (4) 50 62 14 1551 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.546, Ceiling / Working Plane: 0.213.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
PHILIPS SM480C W24L134 ACC-MLO
1 1 3498 3500 35.0
LED35S/840 NO (1.000)
Total: 3498 Total: 3500 35.0

Specific connected load: 3.25 W/m² = 2.78 W/m²/100 lx (Ground area: 10.77 m²)

Page 9
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Hall / Emergency Scene / Summary

Height of Room: 4.700 m, Mounting Height: 3.700 m, Maintenance factor: Values in Lux, Scale 1:557
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 29 1.86 117 0.063
Floor 20 29 1.60 117 0.054
Ceiling 70 7.50 1.44 33 0.193
Walls (18) 50 24 1.06 510 /

Workplane:
Height: 0.000 m
Grid: 128 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.799, Ceiling / Working Plane: 0.254.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
PHILIPS SM480C W24L134 ACC-MLO
1 3 3498 3500 35.0
LED35S/840 NO (1.000)
Total: 10495 Total: 10500 105.0

Specific connected load: 1.05 W/m² = 3.57 W/m²/100 lx (Ground area: 99.99 m²)

Page 10
Plot A Basement Level
11.10.2020

Operator
Telephone
Fax
e-Mail

D.C. Warehouse / Emergency Scene / Summary

Height of Room: 11.200 m, Mounting Height: 11.200 m, Maintenance Values in Lux, Scale 1:625
factor: 0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 119 7.34 201 0.062
Floor 20 66 1.97 198 0.030
Ceiling 50 61 14 144 0.233
Walls (8) 30 52 1.53 787 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.436, Ceiling / Working Plane: 0.513.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42183547 (STD - Standard)
1 61 CRAFT L LED26000-840 PC WB LDO WH 25201 25200 174.6
(1.000)
Total: 1537276 Total: 1537200 10650.6

Specific connected load: 3.52 W/m² = 2.96 W/m²/100 lx (Ground area: 3027.88 m²)

Page 11
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Auditorium / Emergency Scene / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:105
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 61 12 220 0.196
Floor 20 56 18 128 0.322
Ceiling 70 12 7.76 28 0.641
Walls (4) 50 29 9.25 200 /

Workplane:
Height: 0.800 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.478, Ceiling / Working Plane: 0.198.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
1 5 LTS ECL 10.2030.01 (1.000) 1760 1760 22.0
Total: 8800 Total: 8800 110.0

Specific connected load: 1.04 W/m² = 1.70 W/m²/100 lx (Ground area: 105.85 m²)

Page 1
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

CORREDOR-2 / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:427
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 45 1.05 150 0.023
Floor 20 45 1.11 149 0.024
Ceiling 70 9.90 1.16 42 0.117
Walls (22) 50 25 0.94 329 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.545, Ceiling / Working Plane: 0.218.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242098 (STD - standard) CETUS
1 7 1950 1950 19.5
LED 2000 HF 840 (1.000)
Total: 13650 Total: 13650 136.5

Specific connected load: 0.78 W/m² = 1.71 W/m²/100 lx (Ground area: 175.85 m²)

Page 2
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Cafeteria / Emergency Scene / Summary

Height of Room: 2.400 m, Mounting Height: 2.400 m, Maintenance factor: Values in Lux, Scale 1:164
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 84 5.58 502 0.066
Floor 20 77 7.66 251 0.100
Ceiling 70 16 4.22 43 0.262
Walls (6) 50 37 6.02 225 /

Workplane:
Height: 0.800 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.388, Ceiling / Working Plane: 0.191.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 3 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 12600 Total: 12600 109.5

Specific connected load: 0.90 W/m² = 1.07 W/m²/100 lx (Ground area: 121.24 m²)

Page 3
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Kitchen / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:92
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 70 10 361 0.150
Floor 20 60 16 179 0.260
Ceiling 50 9.35 5.06 13 0.542
Walls (4) 30 21 5.80 46 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 22 22
Grid: 64 x 64 Points Lower Wall 22 22
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.256, Ceiling / Working Plane: 0.134.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629745 (STD - standard) OMEGA
1 1 4000 4000 36.5
LED 4000-840 HF Q597 (1.000)
Total: 4000 Total: 4000 36.5

Specific connected load: 0.88 W/m² = 1.26 W/m²/100 lx (Ground area: 41.68 m²)

Page 4
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Electrical Room / Emergency Scene / Summary

Height of Room: 2.600 m, Maintenance factor: 0.80 Values in Lux, Scale 1:30

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 175 76 293 0.436
Floor 20 119 71 161 0.598
Ceiling 70 220 42 1245 0.191
Walls (4) 50 130 44 695 /

Workplane:
Height: 0.800 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.880, Ceiling / Working Plane: 1.260.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
THORN 96630973 (STD - standard)
1 1 AQFPRO S LED4300-840 PC MB HF QC3 4300 4300 33.0
(1.000)
Total: 4300 Total: 4300 33.0

Specific connected load: 3.98 W/m² = 2.27 W/m²/100 lx (Ground area: 8.30 m²)

Page 5
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

M Toilet / Emergency Scene / Summary

Height of Room: 2.400 m, Mounting Height: 2.400 m, Maintenance factor: Values in Lux, Scale 1:59
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 76 16 134 0.209
Floor 20 76 16 134 0.210
Ceiling 50 9.56 4.92 16 0.514
Walls (8) 30 31 3.96 204 /

Workplane:
Height: 0.000 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.406, Ceiling / Working Plane: 0.126.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629019 (STD - standard) CHAL 200
1 2 1370 1370 13.2
LED1400-830 HF RSB (1.000)
Total: 2740 Total: 2740 26.4

Specific connected load: 1.73 W/m² = 2.27 W/m²/100 lx (Ground area: 15.29 m²)

Page 6
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Praying Room / Emergency Scene / Summary

Height of Room: 2.400 m, Mounting Height: 2.400 m, Maintenance factor: Values in Lux, Scale 1:41
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 70 8.09 161 0.116
Floor 20 70 8.20 161 0.117
Ceiling 70 14 5.21 24 0.366
Walls (4) 50 32 5.62 103 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 22 22
Grid: 128 x 64 Points Lower Wall 21 21
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.463, Ceiling / Working Plane: 0.204.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242098 (STD - standard) CETUS
1 1 1950 1950 19.5
LED 2000 HF 840 (1.000)
Total: 1950 Total: 1950 19.5

Specific connected load: 1.29 W/m² = 1.85 W/m²/100 lx (Ground area: 15.10 m²)

Page 7
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Work Shop Meeting / Emergency Scene / Summary

Height of Room: 2.400 m, Mounting Height: 2.400 m, Maintenance factor: Values in Lux, Scale 1:59
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 161 30 513 0.185
Floor 20 134 41 260 0.309
Ceiling 70 32 18 55 0.550
Walls (4) 50 81 22 298 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 19 19
Grid: 64 x 32 Points Lower Wall 18 18
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.486, Ceiling / Working Plane: 0.200.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 2 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 8400 Total: 8400 73.0

Specific connected load: 2.01 W/m² = 1.25 W/m²/100 lx (Ground area: 36.27 m²)

Page 8
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Changing Room / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:70
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 62 8.05 126 0.131
Floor 20 62 8.47 126 0.138
Ceiling 70 12 5.14 23 0.438
Walls (6) 50 26 5.17 135 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.427, Ceiling / Working Plane: 0.190.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629019 (STD - standard) CHAL 200
1 2 1370 1370 13.2
LED1400-830 HF RSB (1.000)
Total: 2740 Total: 2740 26.4

Specific connected load: 1.02 W/m² = 1.65 W/m²/100 lx (Ground area: 26.01 m²)

Page 9
Plot A Basement Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Engineering Head Office / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:81
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 143 20 418 0.138
Floor 20 122 27 227 0.224
Ceiling 70 30 14 58 0.462
Walls (4) 50 74 18 328 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 18 18
Grid: 64 x 64 Points Lower Wall 18 18
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.514, Ceiling / Working Plane: 0.210.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 2 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 8400 Total: 8400 73.0

Specific connected load: 1.82 W/m² = 1.27 W/m²/100 lx (Ground area: 40.00 m²)

Page 10
PLOT A Technical Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Mechanical Room 2 / Emergency Scene / Summary

Height of Room: 2.850 m, Mounting Height: 2.850 m, Maintenance factor: Values in Lux, Scale 1:376
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 39 4.12 132 0.106
Floor 20 39 4.26 132 0.109
Ceiling 50 12 2.41 661 0.198
Walls (4) 30 28 4.75 199 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.720, Ceiling / Working Plane: 0.310.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242063 (STD - standard)
1 4 4150 4150 40.5
FORCELED 4000 HF HT L840 (1.000)
Total: 16599 Total: 16600 162.0

Specific connected load: 0.67 W/m² = 1.72 W/m²/100 lx (Ground area: 242.38 m²)

Page 1
PLOT A Technical Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Lift Lobby / Emergency Scene / Summary

Height of Room: 2.850 m, Mounting Height: 2.850 m, Maintenance factor: Values in Lux, Scale 1:45
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 85 39 138 0.457
Floor 20 85 38 138 0.451
Ceiling 50 33 11 768 0.339
Walls (4) 30 57 18 177 /

Workplane:
Height: 0.000 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.676, Ceiling / Working Plane: 0.391.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242063 (STD - standard)
1 1 4150 4150 40.5
FORCELED 4000 HF HT L840 (1.000)
Total: 4150 Total: 4150 40.5

Specific connected load: 2.60 W/m² = 3.05 W/m²/100 lx (Ground area: 15.60 m²)

Page 2
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Female Toilet / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:66
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 89 1.01 234 0.011
Floor 20 63 2.69 114 0.043
Ceiling 50 7.75 1.26 14 0.162
Walls (6) 30 23 0.79 224 /

Workplane:
Height: 0.800 m
Grid: 64 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.248, Ceiling / Working Plane: 0.087.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629019 (STD - standard) CHAL 200
1 1 1370 1370 13.2
LED1400-830 HF RSB (1.000)
Total: 1370 Total: 1370 13.2

Specific connected load: 1.65 W/m² = 1.86 W/m²/100 lx (Ground area: 8.02 m²)

Page 1
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Hallway / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:66
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 65 10 161 0.161
Floor 20 65 10 161 0.157
Ceiling 70 15 5.99 52 0.395
Walls (6) 50 42 7.10 326 /

Workplane:
Height: 0.000 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.636, Ceiling / Working Plane: 0.233.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242098 (STD - standard) CETUS
1 2 1950 1950 19.5
LED 2000 HF 840 (1.000)
Total: 3900 Total: 3900 39.0

Specific connected load: 1.32 W/m² = 2.02 W/m²/100 lx (Ground area: 29.65 m²)

Page 2
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Female Primary Gowning / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:53
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 87 7.29 235 0.084
Floor 20 67 14 120 0.211
Ceiling 70 12 6.56 17 0.548
Walls (4) 50 27 6.77 107 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 16 16
Grid: 64 x 64 Points Lower Wall 16 16
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.276, Ceiling / Working Plane: 0.138.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629019 (STD - standard) CHAL 200
1 1 1370 1370 13.2
LED1400-830 HF RSB (1.000)
Total: 1370 Total: 1370 13.2

Specific connected load: 1.23 W/m² = 1.42 W/m²/100 lx (Ground area: 10.74 m²)

Page 3
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Encapsulation Machine / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:39
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 269 51 611 0.190
Floor 20 202 82 315 0.404
Ceiling 70 45 28 66 0.612
Walls (4) 50 103 29 518 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 14 14
Grid: 32 x 32 Points Lower Wall 14 14
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.370, Ceiling / Working Plane: 0.169.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 1 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 3900 Total: 3900 28.8

Specific connected load: 3.31 W/m² = 1.23 W/m²/100 lx (Ground area: 8.69 m²)

Page 4
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Production Corridor / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:195
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 116 7.92 315 0.068
Floor 20 116 7.92 315 0.068
Ceiling 70 26 8.23 60 0.322
Walls (6) 50 61 6.42 323 /

Workplane:
Height: 0.000 m
Grid: 64 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.520, Ceiling / Working Plane: 0.220.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 2 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 7800 Total: 7800 57.6

Specific connected load: 1.75 W/m² = 1.50 W/m²/100 lx (Ground area: 32.91 m²)

Page 5
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Central Staging / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:65
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 189 33 572 0.175
Floor 20 155 53 285 0.346
Ceiling 70 27 17 34 0.642
Walls (4) 50 54 18 152 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 14 14
Grid: 64 x 64 Points Lower Wall 16 15
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.244, Ceiling / Working Plane: 0.141.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 1 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 3900 Total: 3900 28.8

Specific connected load: 1.92 W/m² = 1.02 W/m²/100 lx (Ground area: 14.99 m²)

Page 6
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Blister Machine / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:76
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 133 22 285 0.166
Floor 20 133 22 285 0.164
Ceiling 70 24 11 34 0.482
Walls (4) 50 47 12 153 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 14 14
Grid: 32 x 64 Points Lower Wall 16 15
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.357, Ceiling / Working Plane: 0.177.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 1 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 3900 Total: 3900 28.8

Specific connected load: 1.63 W/m² = 1.22 W/m²/100 lx (Ground area: 17.70 m²)

Page 7
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Finished Product Corridor-2 / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:44
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 146 16 320 0.108
Floor 20 146 16 319 0.108
Ceiling 70 33 9.28 63 0.282
Walls (4) 50 76 9.71 342 /

Workplane:
Height: 0.000 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.523, Ceiling / Working Plane: 0.225.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 1 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 3900 Total: 3900 28.8

Specific connected load: 2.42 W/m² = 1.66 W/m²/100 lx (Ground area: 11.91 m²)

Page 8
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Meeting Room / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:43
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 212 27 435 0.125
Floor 20 156 34 241 0.221
Ceiling 70 43 13 67 0.306
Walls (6) 50 90 14 332 /

Workplane:
Height: 0.800 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.436, Ceiling / Working Plane: 0.202.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 1 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 4200 Total: 4200 36.5

Specific connected load: 3.41 W/m² = 1.61 W/m²/100 lx (Ground area: 10.71 m²)

Page 9
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Pantry / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:26
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 305 139 471 0.455
Floor 20 206 128 261 0.624
Ceiling 70 94 48 159 0.512
Walls (4) 50 190 60 922 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.720, Ceiling / Working Plane: 0.308.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629745 (STD - standard) OMEGA
1 1 4000 4000 36.5
LED 4000-840 HF Q597 (1.000)
Total: 4000 Total: 4000 36.5

Specific connected load: 7.30 W/m² = 2.40 W/m²/100 lx (Ground area: 5.00 m²)

Page 10
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Event - With Public Office / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:64
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 178 16 458 0.089
Floor 20 143 23 246 0.159
Ceiling 70 33 9.13 136 0.275
Walls (8) 40 94 6.64 989 /

Workplane:
Height: 0.800 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.573, Ceiling / Working Plane: 0.186.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 2 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 8400 Total: 8400 73.0

Specific connected load: 2.87 W/m² = 1.61 W/m²/100 lx (Ground area: 25.46 m²)

Page 11
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Staircase 4 / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:73
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 48 6.21 138 0.130
Floor 20 48 6.25 138 0.131
Ceiling 70 10 4.19 22 0.409
Walls (4) 50 23 4.80 146 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.000 m Left Wall 22 22
Grid: 128 x 128 Points Lower Wall 22 22
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.478, Ceiling / Working Plane: 0.215.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242098 (STD - standard) CETUS
1 1 1950 1950 19.5
LED 2000 HF 840 (1.000)
Total: 1950 Total: 1950 19.5

Specific connected load: 0.83 W/m² = 1.74 W/m²/100 lx (Ground area: 23.53 m²)

Page 12
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Hall / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:470
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 40 2.12 146 0.053
Floor 20 40 2.46 146 0.062
Ceiling 70 8.57 1.83 38 0.213
Walls (12) 50 21 2.32 362 /

Workplane:
Height: 0.000 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.541, Ceiling / Working Plane: 0.215.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242098 (STD - standard) CETUS
1 4 1950 1950 19.5
LED 2000 HF 840 (1.000)
Total: 7800 Total: 7800 78.0

Specific connected load: 0.70 W/m² = 1.76 W/m²/100 lx (Ground area: 111.38 m²)

Page 13
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Employee Office / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:66
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 153 20 439 0.133
Floor 20 121 26 235 0.213
Ceiling 70 34 15 80 0.433
Walls (4) 50 77 15 565 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 16 16
Grid: 32 x 32 Points Lower Wall 17 17
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.524, Ceiling / Working Plane: 0.221.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 1 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 4200 Total: 4200 36.5

Specific connected load: 2.30 W/m² = 1.50 W/m²/100 lx (Ground area: 15.88 m²)

Page 14
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Coating Utilities Room / Emergency Scene / Summary

Height of Room: 3.000 m, Mounting Height: 3.000 m, Maintenance factor: Values in Lux, Scale 1:73
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 136 23 416 0.166
Floor 20 113 33 237 0.290
Ceiling 70 27 16 51 0.595
Walls (4) 50 68 18 394 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 16 16
Grid: 128 x 64 Points Lower Wall 14 14
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.506, Ceiling / Working Plane: 0.201.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 2 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 7800 Total: 7800 57.6

Specific connected load: 1.64 W/m² = 1.21 W/m²/100 lx (Ground area: 35.03 m²)

Page 15
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Blender / Emergency Scene / Summary

Height of Room: 3.000 m, Mounting Height: 6.600 m, Maintenance factor: Values in Lux, Scale 1:106
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 58 40 67 0.687
Floor 20 52 38 58 0.731
Ceiling 70 13 11 24 0.879
Walls (4) 50 27 19 50 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.497, Ceiling / Working Plane: 0.216.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 2 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 7800 Total: 7800 57.6

Specific connected load: 1.47 W/m² = 2.52 W/m²/100 lx (Ground area: 39.21 m²)

Page 16
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Fluid Bed Dryer / Emergency Scene / Summary

Height of Room: 6.600 m, Mounting Height: 6.600 m, Maintenance factor: Values in Lux, Scale 1:159
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 57 23 75 0.400
Floor 20 53 25 65 0.474
Ceiling 70 18 8.54 47 0.484
Walls (4) 50 39 11 362 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 14 14
Grid: 64 x 64 Points Lower Wall 14 14
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.715, Ceiling / Working Plane: 0.308.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 3 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 11699 Total: 11700 86.4

Specific connected load: 0.96 W/m² = 1.68 W/m²/100 lx (Ground area: 89.90 m²)

Page 17
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

WIP Storage / Emergency Scene / Summary

Height of Room: 6.600 m, Mounting Height: 6.600 m, Maintenance factor: Values in Lux, Scale 1:99
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 72 53 81 0.734
Floor 20 64 50 70 0.778
Ceiling 70 30 17 68 0.577
Walls (4) 50 56 20 620 /

Workplane:
Height: 0.800 m
Grid: 16 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.827, Ceiling / Working Plane: 0.412.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 2 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 7800 Total: 7800 57.6

Specific connected load: 1.84 W/m² = 2.54 W/m²/100 lx (Ground area: 31.36 m²)

Page 18
Plot A Ground Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Tables Counting Line Secondary Packaging / Emergency Scene / Summary

Height of Room: 6.600 m, Mounting Height: 6.600 m, Maintenance factor: Values in Lux, Scale 1:135
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 70 27 92 0.390
Floor 20 64 31 81 0.485
Ceiling 70 17 9.28 38 0.531
Walls (4) 50 39 11 268 /

Workplane:
Height: 0.800 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.581, Ceiling / Working Plane: 0.251.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
ZUMTOBEL 42182682 (STD - Standard)
1 3 CLEAN A-MP LED4000-840 M600Q LDO 3900 3900 28.8
(1.000)
Total: 11699 Total: 11700 86.4

Specific connected load: 1.05 W/m² = 1.52 W/m²/100 lx (Ground area: 81.90 m²)

Page 19
Plot A Ground Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Mechanical Floor 1 / Emergency Scene / Summary

Height of Room: 4.200 m, Mounting Height: 3.200 m, Maintenance factor: Values in Lux, Scale 1:305
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 49 6.55 130 0.133
Floor 20 49 6.35 130 0.129
Ceiling 50 12 3.61 24 0.312
Walls (6) 30 34 3.33 243 /

Workplane:
Height: 0.000 m
Grid: 128 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.700, Ceiling / Working Plane: 0.235.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
THORN 96630973 (STD - standard)
1 8 AQFPRO S LED4300-840 PC MB HF QC3 4300 4300 33.0
(1.000)
Total: 34399 Total: 34400 264.0

Specific connected load: 0.71 W/m² = 1.44 W/m²/100 lx (Ground area: 372.84 m²)

Page 1
Plot A Ground Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Archive Room / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:70
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 133 30 374 0.224
Floor 20 103 38 192 0.370
Ceiling 70 19 9.83 26 0.530
Walls (4) 31 52 12 127 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 19 19
Grid: 64 x 64 Points Lower Wall 21 21
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.372, Ceiling / Working Plane: 0.139.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629745 (STD - standard) OMEGA
1 1 4000 4000 36.5
LED 4000-840 HF Q597 (1.000)
Total: 4000 Total: 4000 36.5

Specific connected load: 2.00 W/m² = 1.50 W/m²/100 lx (Ground area: 18.27 m²)

Page 2
Plot A Ground Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Meeting Room 2 / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:69
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 124 13 398 0.104
Floor 20 93 18 203 0.195
Ceiling 70 21 6.23 75 0.291
Walls (4) 32 65 6.57 589 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 19 19
Grid: 32 x 32 Points Lower Wall 21 21
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.572, Ceiling / Working Plane: 0.173.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629745 (STD - standard) OMEGA
1 1 4000 4000 36.5
LED 4000-840 HF Q597 (1.000)
Total: 4000 Total: 4000 36.5

Specific connected load: 2.30 W/m² = 1.86 W/m²/100 lx (Ground area: 15.90 m²)

Page 3
Plot A First Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Manager Office 4 / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:68
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 145 18 435 0.127
Floor 20 116 24 233 0.204
Ceiling 70 32 13 79 0.418
Walls (4) 50 73 14 525 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 16 16
Grid: 64 x 64 Points Lower Wall 17 17
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.518, Ceiling / Working Plane: 0.218.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 1 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 4200 Total: 4200 36.5

Specific connected load: 2.14 W/m² = 1.47 W/m²/100 lx (Ground area: 17.06 m²)

Page 1
Plot A First Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Work Station / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:196
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 67 2.61 423 0.039
Floor 20 60 3.65 208 0.060
Ceiling 70 9.86 2.07 304 0.210
Walls (6) 6 42 3.21 2351 /

Workplane:
Height: 0.800 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.672, Ceiling / Working Plane: 0.146.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 4 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 16800 Total: 16800 146.0

Specific connected load: 0.89 W/m² = 1.32 W/m²/100 lx (Ground area: 163.67 m²)

Page 2
Plot A First Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Female Toilet / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:53
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 85 7.97 225 0.094
Floor 20 64 18 109 0.285
Ceiling 50 6.80 4.14 9.78 0.608
Walls (6) 30 19 3.06 176 /

Workplane:
Height: 0.800 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.184, Ceiling / Working Plane: 0.080.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96629019 (STD - standard) CHAL 200
1 1 1370 1370 13.2
LED1400-830 HF RSB (1.000)
Total: 1370 Total: 1370 13.2

Specific connected load: 1.23 W/m² = 1.46 W/m²/100 lx (Ground area: 10.72 m²)

Page 3
Plot A First Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Security Room / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:52
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 167 51 234 0.308
Floor 20 167 51 236 0.307
Ceiling 70 36 14 184 0.395
Walls (6) 25 143 15 1215 /

Workplane:
Height: 0.000 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.861, Ceiling / Working Plane: 0.220.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 2 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 8400 Total: 8400 73.0

Specific connected load: 5.30 W/m² = 3.18 W/m²/100 lx (Ground area: 13.77 m²)

Page 1
Plot A First Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Open Office / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:167
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 86 2.33 422 0.027
Floor 20 76 3.30 225 0.043
Ceiling 70 14 1.85 71 0.137
Walls (7) 12 46 4.09 469 /

Workplane:
Height: 0.800 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.528, Ceiling / Working Plane: 0.157.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 4 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 16800 Total: 16800 146.0

Specific connected load: 1.06 W/m² = 1.23 W/m²/100 lx (Ground area: 137.84 m²)

Page 2
Plot A First Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Meeting Room / Emergency Scene / Summary

Height of Room: 2.800 m, Mounting Height: 2.800 m, Maintenance factor: Values in Lux, Scale 1:53
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 181 55 328 0.307
Floor 20 134 81 179 0.605
Ceiling 70 18 10 57 0.566
Walls (4) 16 97 12 800 /

Workplane:
Height: 0.800 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.586, Ceiling / Working Plane: 0.099.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 2 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 8400 Total: 8400 73.0

Specific connected load: 3.87 W/m² = 2.14 W/m²/100 lx (Ground area: 18.87 m²)

Page 3
Plot A First Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

IT Manager / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:43
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 136 8.41 409 0.062
Floor 20 101 13 207 0.133
Ceiling 70 16 5.13 58 0.322
Walls (4) 15 62 4.13 482 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.800 m Left Wall 18 18
Grid: 32 x 32 Points Lower Wall 17 17
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.479, Ceiling / Working Plane: 0.118.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96630187 (STD - standard) OMEGA
1 1 4200 4200 36.5
PRO LED4200-840 HF E3 Q597 (1.000)
Total: 4200 Total: 4200 36.5

Specific connected load: 2.35 W/m² = 1.74 W/m²/100 lx (Ground area: 15.51 m²)

Page 4
Plot A First Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Electrical Room / Emergency Scene / Summary

Height of Room: 3.100 m, Mounting Height: 3.100 m, Maintenance factor: Values in Lux, Scale 1:26
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 255 203 298 0.796
Floor 20 170 142 189 0.833
Ceiling 70 76 53 93 0.697
Walls (4) 50 158 60 425 /

Workplane:
Height: 0.800 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.694, Ceiling / Working Plane: 0.298.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
PHILIPS SM480C W24L134 ACC-MLO
1 1 3498 3500 35.0
LED35S/840 NO (1.000)
Total: 3498 Total: 3500 35.0

Specific connected load: 7.86 W/m² = 3.08 W/m²/100 lx (Ground area: 4.45 m²)

Page 5
Plot A First Level - Mezzanine
11.10.2020

Operator
Telephone
Fax
e-Mail

Telephone Room / Emergency Scene / Summary

Height of Room: 3.100 m, Mounting Height: 3.100 m, Maintenance factor: Values in Lux, Scale 1:26
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 289 241 328 0.834
Floor 20 183 160 200 0.873
Ceiling 70 111 82 127 0.733
Walls (4) 50 209 78 513 /

Workplane:
Height: 0.800 m
Grid: 16 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.858, Ceiling / Working Plane: 0.385.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
PHILIPS SM480C W24L134 ACC-MLO
1 1 3498 3500 35.0
LED35S/840 NO (1.000)
Total: 3498 Total: 3500 35.0

Specific connected load: 11.84 W/m² = 4.10 W/m²/100 lx (Ground area: 2.96 m²)

Page 6
Plot A Roof Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Electrical Room / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:28
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 241 104 386 0.432
Floor 20 173 111 228 0.642
Ceiling 80 48 31 60 0.640
Walls (4) 50 109 37 328 /

Workplane:
Height: 0.760 m
Grid: 64 x 32 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.469, Ceiling / Working Plane: 0.198.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
PHILIPS SM480C W24L134 ACC-MLO
1 1 3498 3500 35.0
LED35S/840 NO (1.000)
Total: 3498 Total: 3500 35.0

Specific connected load: 4.60 W/m² = 1.91 W/m²/100 lx (Ground area: 7.60 m²)

Page 1
Plot A Roof Level
11.10.2020

Operator
Telephone
Fax
e-Mail

Lift Room / Emergency Scene / Summary

Height of Room: 2.600 m, Mounting Height: 2.600 m, Maintenance factor: Values in Lux, Scale 1:78
0.80

Surface U [%] Eav [lx] Emin [lx] Emax [lx] u0


Workplane / 111 13 308 0.119
Floor 20 83 17 165 0.205
Ceiling 50 31 6.75 586 0.220
Walls (4) 30 58 10 169 /

Workplane: UGR Lengthways- Across to luminaire axis


Height: 0.760 m Left Wall 21 20
Grid: 128 x 64 Points Lower Wall 24 21
Boundary Zone: 0.000 m (CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.558, Ceiling / Working Plane: 0.278.

Luminaire Parts List

No. Pieces Designation (Correction Factor) ) (Luminaire) [lm] ) (Lamps) [lm] P [W]
Thorn 96242063 (STD - standard)
1 1 4150 4150 40.5
FORCELED 4000 HF HT L840 (1.000)
Total: 4150 Total: 4150 40.5

Specific connected load: 2.33 W/m² = 2.11 W/m²/100 lx (Ground area: 17.39 m²)

Page 2