Attention 2. Installation 3.1 Applicable Cable and Terminal Tightening Torque
• This product is designed for use in industrial applications. 3.1.1 Terminal block (European type)
Note INSTALLATION
1) Wire size
• Manufactured by: Mitsubishi Electric Corporation PRECAUTIONS
Wiring to analog device should use 20-22 AWG wire.
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan 2) Applicable cable
• Make sure to cut off all phases of the power supply externally before attempting
• Manufactured at: Mitsubishi Electric Corporation Himeji Works installation or wiring work.
840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan Type Wire size
FX3G-1DA-BD • Authorized Representative in the European Community:
Failure to do so may cause electric shock or damage to the product.

Mitsubishi Electric Europe B.V.


Single-wire 0.3 mm2 to 0.5 mm2 (AWG22 to 20)
INSTALLATION MANUAL Gothaer Str. 8, 40880 Ratingen, Germany
Caution for EC Directive
INSTALLATION
PRECAUTIONS 2-wire 2 pieces of 0.3 mm2 (AWG22)

Manual Number JY997D33601 The analog expansion boards have been found to be compliant to the • Use the product within the generic environment specifications described in PLC 3) Termination of cable end
European standards in the aforesaid manual and directive. However, for the main unit manual (Hardware Edition). Strip the coating of strand wire and twist the cable core before connecting it,
Revision E very best performance from what are in fact delicate measuring and controlled Never use the product in areas with excessive dust, oily smoke, conductive dusts, or strip the coating of single wire before connecting it.
output device Mitsubishi Electric would like to make the following points; corrosive gas (salt air, Cl 2 , H 2 S, SO 2 , or NO 2 ), flammable gas, vibration or An alternative connection is to use a ferrule with insulating sleeve.
Date April 2013
As analog devices are sensitive by nature, their use should be considered impacts, or expose it to high temperature, condensation, or rain and wind. <Reference>
carefully. For users of proprietary cables (integral with sensors or actuators), If the product is used in such conditions, electric shock, fire, malfunctions,
This manual describes the part names, dimensions, mounting, and these users should follow those manufacturers installation requirements. deterioration or damage may occur. Manufacturer Model Caulking tool
specifications of the product. Before use, read this manual and the manuals of Mitsubishi Electric recommend that shielded cables should be used. If NO other • When drilling screw holes or wiring, make sure cutting or wire debris does not
all relevant products fully to acquire proficiency in handling and operating the EMC protection is provided, then users may experience temporary loss or enter the ventilation slits. CRIMPFOX 6*1
Phoenix Contact Co., Ltd. AI 0.5-8WH
product. Make sure to learn all the product information, safety information, and accuracy between ±10 % in very heavy industrial areas. Failure to do so may cause fire, equipment failures or malfunctions. (or CRIMPFOX 6T-F*2)
precautions. However, Mitsubishi Electric suggest that if adequate EMC precautions are
Store this manual in a safe place so that it can be taken out and read whenever • Do not touch the conductive parts of the product directly. *1 Old model name: CRIMPFOX ZA 3
followed for the users complete control system, users should expect accuracy Doing so may cause device failures or malfunctions.
necessary. Always forward it to the end user. *2 Old model name: CRIMPFOX UD 6
Registration: as specified in this manual. • Connect expansion board securely to their designated connectors.
The company and product names described in this manual are registered • Sensitive analog cable should not be laid in the same trunking or cable Loose connections may cause malfunctions.
trademarks or the trademarks of their respective companies. conduit as high voltage cabling. Where possible users should run analog - Strand wire/single wire - Stick terminal with insulating sleeve
cables separately. For the installation, refer to the following manual. Insulation sleeve Contact area
Effective April 2013
• Good cable shielding should be used. When terminating the shield at Earth → FX3S Series User's Manual - Hardware Edition (Crimp area)
Specifications are subject to change without notice. → FX3G Series User's Manual - Hardware Edition
- ensure that no earth loops are accidentally created.
© 2008 Mitsubishi Electric Corporation • When reading analog values, EMC accuracy can be improved out by
averaging the readings. This can be achieved either through functions on the 3. Wiring 9mm
(0.35")
8mm
(0.31")
Safety Precaution (Read these precautions before use.) analog expansion boards or through a users program in the PLC main unit.
WIRING
This manual classifies the safety precautions into two categories: PRECAUTIONS 2.6mm(0.1") 14mm(0.55")
1. Outline
and . The FX3G-1DA-BD board (hereinafter called 1DA-BD) is an expansion board for • Make sure to cut off all phases of the power supply externally before attempting When using a stick terminal with insulating sleeve, choose a wire with proper
adding one additional analog output point. installation or wiring work. cable sheath referring to the above outside dimensions, or otherwise, the wire
Indicates that incorrect handling may cause hazardous Failure to do so may cause electric shock or damage to the product. cannot be inserted easily.
conditions, resulting in death or severe injury.
1.1 Incorporated Items
The tightening torque must be 0.22 to 0.25 N•m. Do not tighten terminal
Product Analog output expansion board FX3G-1DA-BD WIRING screws exceeding the specified torque. Failure to do so may cause equipment
Indicates that incorrect handling may cause hazardous PRECAUTIONS failures or malfunctions.
conditions, resulting in medium or slight personal injury • M3×8 tapping screws for installation: 2 pcs.
or physical damage. Included items • Side cover • When drilling screw holes or wiring, make sure cutting or wire debris does not 4) Tool
• Installation Manual (This manual) enter the ventilation slits. For tightening the terminal, use a
With
Failure to do so may cause fire, equipment failures or malfunctions. commercially available small
Depending on the circumstances, procedures indicated by may straight tip
1.2 External Dimensions, Part Names • Make sure to observe the following precautions in order to prevent any damage to screwdriver having a straight form that is
also cause severe injury. not widened toward the end as shown
the machinery or accidents due to abnormal data written to the PLC under the
It is important to follow all precautions for personal safety. right. 0.4mm 2.5mm
Unit: mm (inches) influence of noise:
[4] Caution: (0.02") (0.1")
1) Do not bundle the power line or shield of the analog input/output cable together
Associated Manuals with or lay it close to the main circuit, high-voltage line, or load line. If the diameter of screwdriver grip is too
[5] Connector cover is Otherwise, noise disturbance and/or surge induction are likely to take place. As small, tightening torque will not be able
51.2 (2.02")

Manual name Manual No. Description removed to be achieved. Use the following recommended screwdriver or an
[3] a guideline, lay the control line at least 100mm (3.94") or more away from the
FX 3S /FX 3G /FX 3GC /FX 3U / main circuit, high-voltage line or load line. appropriate replacement (grip diameter: approximately 25 mm (0.98")).
JY997D16701 Describes specifications for
[7] <Reference>
FX3UC Series analog control and programming 2) Ground the shield of the analog input/output cable at one point on the signal
MODEL CODE:
User's Manual method for FX3S/FX3G/FX3GC/ receiving side. However, do not use common grounding with heavy electrical Manufacturer Model
09R619 FX3U/FX3UC Series PLC.
- Analog Control Edition [2] systems.
[1] • Make sure to properly wire to the terminal block (European type) in accordance Phoenix Contact Co., Ltd. SZS 0.4×2.5
FX3S Series JY997D48601 E x p l a i n s F X 3 S S e r i e s P L C MASS (Weight): 20 g (0.05 lbs)
with the following precautions.
User’s Manual MODEL CODE: specifications for I/O, wiring,
35 (1.38") 15.1 14.1 Failure to do so may cause electric shock, equipment failures, a short-circuit, wire
- Hardware Edition 09R535 installation, and maintenance.
(0.6") (0.56") breakage, malfunctions, or damage to the product.
FX3G Series JY997D31301 E x p l a i n s F X 3 G S e r i e s P L C - The disposal size of the cable end should follow the dimensions described in
User’s Manual MODEL CODE: specifications for I/O, wiring, [6] the manual.
installation, and maintenance. Terminal Layout
- Hardware Edition 09R521 - Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
How to obtain manuals
VI-
V+
I+

For product manuals or documents, consult with the Mitsubishi Electric dealer - Do not solder-plate the electric wire ends.
from who you purchased your product. - Do not connect more than the specified number of wires or electric wires of
unspecified size.
5 poles - Affix the electric wires so that neither the terminal block nor the connected
Applicable standards [1]Terminal block mounting screws parts are directly stressed.
FX3G-1DA-BD units made in November, 2008 or later comply with the EC [2]POW LED: Lit while power is properly supplied from main unit
• Make sure to properly wire to the terminal blocks in accordance with the following
Directive (EMC Directive). Further information can be found in the following [3]Mounting holes (2-φ3.2)
precautions.
manual. [4]Connector cover
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire
→ FX3S Series Hardware Manual (Manual No. JY997D48301) [5]Main unit connector
breakage, malfunctions, or damage to the product.
→ FX3G Series Hardware Manual (Manual No. JY997D46001) [6]Terminal block to connect analog output
[7]Memory cassette/Display module connector - The disposal size of the cable end should follow the dimensions described in
the manual.
- Tightening torque should follow the specifications in the manual.

3.2 Wiring of Analog Output 4.2 General Specifications 4.4 List of Special Devices
→ For the terminal configuration, refer to Section 1.2 The general specifications are equivalent to the PLC main unit. R: Read W: Write
For general specifications, refer to the following manuals.
Using voltage Device number
output Terminal 1DA-BD → FX3S Series User's Manual - Hardware Edition
block → FX3G Series User's Manual - Hardware Edition FX3G Description R/W
V+ 4.3 Performance Specifications FX3S
Board A Board B
I+
Specifications Switches the output mode
Grounding VI- Item M8260 M8260 M8270 R/W
Voltage output Current output OFF: Voltage output ON: Current output

0 to 10 V DC 4 to 20 mA DC Special Output Holding Function Cancellation


Analog output Setting
(External load resistance: (External load resistance: auxiliary
Using current range OFF: Holds the analog data output just
1DA-BD 2 kΩ to 1 MΩ) 500 Ω or less) relay M8264 M8264 M8274 R/W
output Terminal before stop of the PLC.
block Digital input 12 bits, binary 11 bits, binary ON: Output the offset data at stop of
V+ Resolution 2.5 mV (10 V/4000) 8 μA (16 mA/2000) the PLC.
I+
• ±0.5 % (±50 mV) for full D8260 D8260 D8270 Output setting data R/W
Grounding VI-
scale of 10 V(when ambient Error status
temperature is 25 °C±5 °C) b0: Output data setting error
• ±1.0 % (±100 mV) for full Special b1: Unused
*1 Use 2-core shielded twisted pair cable for the analog output lines, and scale of 10 V data D8268 D8268 D8278 b2: Unused R/W
separate the analog output lines from other power lines or inductive lines. (when ambient temperature • ±0.5 % (±80 μA) for full scale register b3: Unused
is 0 °C to 55 °C) of 16 mA (when ambient b4: EEPROM error
*2 The grounding resistance should be 100 Ω or less. Shipment adjustment is carried b15 to b5: Unused
temperature is 25 °C±5 °C)
Total accuracy out by external load resistance
3.3 Grounding • ±1.0 % (±160 μA) for full D8269 D8269 D8279 Model code = 4 R
2 kΩ.
Grounding should be performed as stated below. scale of 16 mA
I f e x t e r n a l l o a d r e s i s ta n c e As for the details of the special devices, refer to the following manual.
(when ambient temperature
• The grounding resistance should be 100 Ω or less. becomes larger than 2 kΩ, the → FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual - Analog Control Edition
is 0 °C to 55 °C)
• Independent grounding should be performed for best results. output voltage will increase
When independent grounding is not performed, perform "shared grounding" of slightly.
the following figure. When the load is 1 MΩ, the
For details, refer to the following manual. output voltage becomes about
→ FX3S Series User's Manual - Hardware Edition 2 % higher than the correct
→ FX3G Series User's Manual - Hardware Edition value.
Other Other Other D/A
PLC PLC PLC 60 μs
equipment equipment equipment conversion
(The data will be updated at every scan time of the PLC.)
time

Independent grounding Shared grounding Common grounding 0 to 4000 are adjusted to 0 to 0 to 2000 are adjusted to 4 to
Best condition Good condition Not allowed 10 V when the external load 20 mA when the external load
resistance is 2 kΩ. resistance is 250 Ω.
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm2).
• The grounding point should be close to the PLC, and all grounding wire should
be as short as possible. 10V 20mA
Analog output

Analog output

4. Specifications
output
STARTUP AND characteristics 4mA
MAINTENANCE
0 4000 4080 0 2000 2040
PRECAUTIONS Digital input Digital input
• Do not disassemble or modify the PLC. Caution:
Doing so may cause fire, equipment failures, or malfunctions. An area of dead band is located
* For repair, contact your local Mitsubishi Electric representative. in the region of 0 V.
• Do not drop the product or exert strong impact to it. Therefore the output analog
Doing so may cause damage. value may not represent the
digital value accurately.
DISPOSAL Insulation
No insulation between the PLC.
PRECAUTIONS method

• Please contact a certified electronic waste disposal company for the Occupied 0 point (This number is not related to the maximum number of
environmentally safe recycling and disposal of your device. points input/output points of the PLC.)
This manual confers no industrial property rights or any rights of any other kind,
TRANSPORTATION AND nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
STORAGE PRECAUTIONS held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
• The product is a precision instrument. During transportation, avoid any
impacts. Warranty
Failure to do so may cause failures in the product. After transportation, verify Mitsubishi will not be held liable for damage caused by factors found not to be
the operations of the product. the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
4.1 Applicable PLC caused by special factors unpredictable by Mitsubishi; damages to products
Model name Applicability other than Mitsubishi products; and to other duties.

FX3S Series PLC Ver. 1.00 or later (from first production)


For safe use
FX3G Series PLC Ver. 1.10 or later
• This product has been manufactured as a general-purpose part for general
The version number can be checked by monitoring D8001/D8101 as the last three industries, and has not been designed or manufactured to be incorporated in
digits indicate it. a device or system used in purposes related to human life.
• The number of connectable expansion boards varies depending on the main • Before using the product for special purposes such as nuclear power, electric
unit as follows: power, aerospace, medicine or passenger movement vehicles, consult with
FX3S, FX3G-14M…, FX3G-24M… Main units: 1 unit Mitsubishi Electric.
FX3G-40M…, FX3G-60M… Main units: 2 units • This product has been manufactured under strict quality control. However
Never stack up two or more expansion boards. when installing the product where major accidents or losses could occur if the
For details on the system configuration, refer to the following manual. product fails, install appropriate backup or failsafe functions in the system.
→ FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual
- Analog Control Edition

HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
Side JY997D33601E
B Side
A JAPANESE
Side
B ENGLISH
Attention 2. Installation 3.1 Applicable Cable and Terminal Tightening Torque
• This product is designed for use in industrial applications. 3.1.1 Terminal block (European type)
Note INSTALLATION
1) Wire size
• Manufactured by: Mitsubishi Electric Corporation PRECAUTIONS
Wiring to analog device should use 20-22 AWG wire.
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan 2) Applicable cable
• Make sure to cut off all phases of the power supply externally before attempting
• Manufactured at: Mitsubishi Electric Corporation Himeji Works installation or wiring work.
840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan Type Wire size
FX3G-1DA-BD • Authorized Representative in the European Community:
Failure to do so may cause electric shock or damage to the product.

Mitsubishi Electric Europe B.V.


Single-wire 0.3 mm2 to 0.5 mm2 (AWG22 to 20)
INSTALLATION MANUAL Gothaer Str. 8, 40880 Ratingen, Germany
Caution for EC Directive
INSTALLATION
PRECAUTIONS 2-wire 2 pieces of 0.3 mm2 (AWG22)

Manual Number JY997D33601 The analog expansion boards have been found to be compliant to the • Use the product within the generic environment specifications described in PLC 3) Termination of cable end
European standards in the aforesaid manual and directive. However, for the main unit manual (Hardware Edition). Strip the coating of strand wire and twist the cable core before connecting it,
Revision E very best performance from what are in fact delicate measuring and controlled Never use the product in areas with excessive dust, oily smoke, conductive dusts, or strip the coating of single wire before connecting it.
output device Mitsubishi Electric would like to make the following points; corrosive gas (salt air, Cl 2 , H 2 S, SO 2 , or NO 2 ), flammable gas, vibration or An alternative connection is to use a ferrule with insulating sleeve.
Date April 2013
As analog devices are sensitive by nature, their use should be considered impacts, or expose it to high temperature, condensation, or rain and wind. <Reference>
carefully. For users of proprietary cables (integral with sensors or actuators), If the product is used in such conditions, electric shock, fire, malfunctions,
This manual describes the part names, dimensions, mounting, and these users should follow those manufacturers installation requirements. deterioration or damage may occur. Manufacturer Model Caulking tool
specifications of the product. Before use, read this manual and the manuals of Mitsubishi Electric recommend that shielded cables should be used. If NO other • When drilling screw holes or wiring, make sure cutting or wire debris does not
all relevant products fully to acquire proficiency in handling and operating the EMC protection is provided, then users may experience temporary loss or enter the ventilation slits. CRIMPFOX 6*1
Phoenix Contact Co., Ltd. AI 0.5-8WH
product. Make sure to learn all the product information, safety information, and accuracy between ±10 % in very heavy industrial areas. Failure to do so may cause fire, equipment failures or malfunctions. (or CRIMPFOX 6T-F*2)
precautions. However, Mitsubishi Electric suggest that if adequate EMC precautions are
Store this manual in a safe place so that it can be taken out and read whenever • Do not touch the conductive parts of the product directly. *1 Old model name: CRIMPFOX ZA 3
followed for the users complete control system, users should expect accuracy Doing so may cause device failures or malfunctions.
necessary. Always forward it to the end user. *2 Old model name: CRIMPFOX UD 6
Registration: as specified in this manual. • Connect expansion board securely to their designated connectors.
The company and product names described in this manual are registered • Sensitive analog cable should not be laid in the same trunking or cable Loose connections may cause malfunctions.
trademarks or the trademarks of their respective companies. conduit as high voltage cabling. Where possible users should run analog - Strand wire/single wire - Stick terminal with insulating sleeve
cables separately. For the installation, refer to the following manual. Insulation sleeve Contact area
Effective April 2013
• Good cable shielding should be used. When terminating the shield at Earth → FX3S Series User's Manual - Hardware Edition (Crimp area)
Specifications are subject to change without notice. → FX3G Series User's Manual - Hardware Edition
- ensure that no earth loops are accidentally created.
© 2008 Mitsubishi Electric Corporation • When reading analog values, EMC accuracy can be improved out by
averaging the readings. This can be achieved either through functions on the 3. Wiring 9mm
(0.35")
8mm
(0.31")
Safety Precaution (Read these precautions before use.) analog expansion boards or through a users program in the PLC main unit.
WIRING
This manual classifies the safety precautions into two categories: PRECAUTIONS 2.6mm(0.1") 14mm(0.55")
1. Outline
and . The FX3G-1DA-BD board (hereinafter called 1DA-BD) is an expansion board for • Make sure to cut off all phases of the power supply externally before attempting When using a stick terminal with insulating sleeve, choose a wire with proper
adding one additional analog output point. installation or wiring work. cable sheath referring to the above outside dimensions, or otherwise, the wire
Indicates that incorrect handling may cause hazardous Failure to do so may cause electric shock or damage to the product. cannot be inserted easily.
conditions, resulting in death or severe injury.
1.1 Incorporated Items
The tightening torque must be 0.22 to 0.25 N•m. Do not tighten terminal
Product Analog output expansion board FX3G-1DA-BD WIRING screws exceeding the specified torque. Failure to do so may cause equipment
Indicates that incorrect handling may cause hazardous PRECAUTIONS failures or malfunctions.
conditions, resulting in medium or slight personal injury • M3×8 tapping screws for installation: 2 pcs.
or physical damage. Included items • Side cover • When drilling screw holes or wiring, make sure cutting or wire debris does not 4) Tool
• Installation Manual (This manual) enter the ventilation slits. For tightening the terminal, use a
With
Failure to do so may cause fire, equipment failures or malfunctions. commercially available small
Depending on the circumstances, procedures indicated by may straight tip
1.2 External Dimensions, Part Names • Make sure to observe the following precautions in order to prevent any damage to screwdriver having a straight form that is
also cause severe injury. not widened toward the end as shown
the machinery or accidents due to abnormal data written to the PLC under the
It is important to follow all precautions for personal safety. right. 0.4mm 2.5mm
Unit: mm (inches) influence of noise:
[4] Caution: (0.02") (0.1")
1) Do not bundle the power line or shield of the analog input/output cable together
Associated Manuals with or lay it close to the main circuit, high-voltage line, or load line. If the diameter of screwdriver grip is too
[5] Connector cover is Otherwise, noise disturbance and/or surge induction are likely to take place. As small, tightening torque will not be able
51.2 (2.02")

Manual name Manual No. Description removed to be achieved. Use the following recommended screwdriver or an
[3] a guideline, lay the control line at least 100mm (3.94") or more away from the
FX 3S /FX 3G /FX 3GC /FX 3U / main circuit, high-voltage line or load line. appropriate replacement (grip diameter: approximately 25 mm (0.98")).
JY997D16701 Describes specifications for
[7] <Reference>
FX3UC Series analog control and programming 2) Ground the shield of the analog input/output cable at one point on the signal
MODEL CODE:
User's Manual method for FX3S/FX3G/FX3GC/ receiving side. However, do not use common grounding with heavy electrical Manufacturer Model
09R619 FX3U/FX3UC Series PLC.
- Analog Control Edition [2] systems.
[1] • Make sure to properly wire to the terminal block (European type) in accordance Phoenix Contact Co., Ltd. SZS 0.4×2.5
FX3S Series JY997D48601 E x p l a i n s F X 3 S S e r i e s P L C MASS (Weight): 20 g (0.05 lbs)
with the following precautions.
User’s Manual MODEL CODE: specifications for I/O, wiring,
35 (1.38") 15.1 14.1 Failure to do so may cause electric shock, equipment failures, a short-circuit, wire
- Hardware Edition 09R535 installation, and maintenance.
(0.6") (0.56") breakage, malfunctions, or damage to the product.
FX3G Series JY997D31301 E x p l a i n s F X 3 G S e r i e s P L C - The disposal size of the cable end should follow the dimensions described in
User’s Manual MODEL CODE: specifications for I/O, wiring, [6] the manual.
installation, and maintenance. Terminal Layout
- Hardware Edition 09R521 - Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
How to obtain manuals
VI-
V+
I+

For product manuals or documents, consult with the Mitsubishi Electric dealer - Do not solder-plate the electric wire ends.
from who you purchased your product. - Do not connect more than the specified number of wires or electric wires of
unspecified size.
5 poles - Affix the electric wires so that neither the terminal block nor the connected
Applicable standards [1]Terminal block mounting screws parts are directly stressed.
FX3G-1DA-BD units made in November, 2008 or later comply with the EC [2]POW LED: Lit while power is properly supplied from main unit
• Make sure to properly wire to the terminal blocks in accordance with the following
Directive (EMC Directive). Further information can be found in the following [3]Mounting holes (2-φ3.2)
precautions.
manual. [4]Connector cover
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire
→ FX3S Series Hardware Manual (Manual No. JY997D48301) [5]Main unit connector
breakage, malfunctions, or damage to the product.
→ FX3G Series Hardware Manual (Manual No. JY997D46001) [6]Terminal block to connect analog output
[7]Memory cassette/Display module connector - The disposal size of the cable end should follow the dimensions described in
the manual.
- Tightening torque should follow the specifications in the manual.

3.2 Wiring of Analog Output 4.2 General Specifications 4.4 List of Special Devices
→ For the terminal configuration, refer to Section 1.2 The general specifications are equivalent to the PLC main unit. R: Read W: Write
For general specifications, refer to the following manuals.
Using voltage Device number
output Terminal 1DA-BD → FX3S Series User's Manual - Hardware Edition
block → FX3G Series User's Manual - Hardware Edition FX3G Description R/W
V+ 4.3 Performance Specifications FX3S
Board A Board B
I+
Specifications Switches the output mode
Grounding VI- Item M8260 M8260 M8270 R/W
Voltage output Current output OFF: Voltage output ON: Current output

0 to 10 V DC 4 to 20 mA DC Special Output Holding Function Cancellation


Analog output Setting
(External load resistance: (External load resistance: auxiliary
Using current range OFF: Holds the analog data output just
1DA-BD 2 kΩ to 1 MΩ) 500 Ω or less) relay M8264 M8264 M8274 R/W
output Terminal before stop of the PLC.
block Digital input 12 bits, binary 11 bits, binary ON: Output the offset data at stop of
V+ Resolution 2.5 mV (10 V/4000) 8 μA (16 mA/2000) the PLC.
I+
• ±0.5 % (±50 mV) for full D8260 D8260 D8270 Output setting data R/W
Grounding VI-
scale of 10 V(when ambient Error status
temperature is 25 °C±5 °C) b0: Output data setting error
• ±1.0 % (±100 mV) for full Special b1: Unused
*1 Use 2-core shielded twisted pair cable for the analog output lines, and scale of 10 V data D8268 D8268 D8278 b2: Unused R/W
separate the analog output lines from other power lines or inductive lines. (when ambient temperature • ±0.5 % (±80 μA) for full scale register b3: Unused
is 0 °C to 55 °C) of 16 mA (when ambient b4: EEPROM error
*2 The grounding resistance should be 100 Ω or less. Shipment adjustment is carried b15 to b5: Unused
temperature is 25 °C±5 °C)
Total accuracy out by external load resistance
3.3 Grounding • ±1.0 % (±160 μA) for full D8269 D8269 D8279 Model code = 4 R
2 kΩ.
Grounding should be performed as stated below. scale of 16 mA
I f e x t e r n a l l o a d r e s i s ta n c e As for the details of the special devices, refer to the following manual.
(when ambient temperature
• The grounding resistance should be 100 Ω or less. becomes larger than 2 kΩ, the → FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual - Analog Control Edition
is 0 °C to 55 °C)
• Independent grounding should be performed for best results. output voltage will increase
When independent grounding is not performed, perform "shared grounding" of slightly.
the following figure. When the load is 1 MΩ, the
For details, refer to the following manual. output voltage becomes about
→ FX3S Series User's Manual - Hardware Edition 2 % higher than the correct
→ FX3G Series User's Manual - Hardware Edition value.
Other Other Other D/A
PLC PLC PLC 60 μs
equipment equipment equipment conversion
(The data will be updated at every scan time of the PLC.)
time

Independent grounding Shared grounding Common grounding 0 to 4000 are adjusted to 0 to 0 to 2000 are adjusted to 4 to
Best condition Good condition Not allowed 10 V when the external load 20 mA when the external load
resistance is 2 kΩ. resistance is 250 Ω.
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm2).
• The grounding point should be close to the PLC, and all grounding wire should
be as short as possible. 10V 20mA
Analog output

Analog output

4. Specifications
output
STARTUP AND characteristics 4mA
MAINTENANCE
0 4000 4080 0 2000 2040
PRECAUTIONS Digital input Digital input
• Do not disassemble or modify the PLC. Caution:
Doing so may cause fire, equipment failures, or malfunctions. An area of dead band is located
* For repair, contact your local Mitsubishi Electric representative. in the region of 0 V.
• Do not drop the product or exert strong impact to it. Therefore the output analog
Doing so may cause damage. value may not represent the
digital value accurately.
DISPOSAL Insulation
No insulation between the PLC.
PRECAUTIONS method

• Please contact a certified electronic waste disposal company for the Occupied 0 point (This number is not related to the maximum number of
environmentally safe recycling and disposal of your device. points input/output points of the PLC.)
This manual confers no industrial property rights or any rights of any other kind,
TRANSPORTATION AND nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
STORAGE PRECAUTIONS held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
• The product is a precision instrument. During transportation, avoid any
impacts. Warranty
Failure to do so may cause failures in the product. After transportation, verify Mitsubishi will not be held liable for damage caused by factors found not to be
the operations of the product. the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
4.1 Applicable PLC caused by special factors unpredictable by Mitsubishi; damages to products
Model name Applicability other than Mitsubishi products; and to other duties.

FX3S Series PLC Ver. 1.00 or later (from first production)


For safe use
FX3G Series PLC Ver. 1.10 or later
• This product has been manufactured as a general-purpose part for general
The version number can be checked by monitoring D8001/D8101 as the last three industries, and has not been designed or manufactured to be incorporated in
digits indicate it. a device or system used in purposes related to human life.
• The number of connectable expansion boards varies depending on the main • Before using the product for special purposes such as nuclear power, electric
unit as follows: power, aerospace, medicine or passenger movement vehicles, consult with
FX3S, FX3G-14M…, FX3G-24M… Main units: 1 unit Mitsubishi Electric.
FX3G-40M…, FX3G-60M… Main units: 2 units • This product has been manufactured under strict quality control. However
Never stack up two or more expansion boards. when installing the product where major accidents or losses could occur if the
For details on the system configuration, refer to the following manual. product fails, install appropriate backup or failsafe functions in the system.
→ FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual
- Analog Control Edition

HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
Side JY997D33601E
B Side
A JAPANESE
Side
B ENGLISH
Attention 2. Installation 3.1 Applicable Cable and Terminal Tightening Torque
• This product is designed for use in industrial applications. 3.1.1 Terminal block (European type)
Note INSTALLATION
1) Wire size
• Manufactured by: Mitsubishi Electric Corporation PRECAUTIONS
Wiring to analog device should use 20-22 AWG wire.
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan 2) Applicable cable
• Make sure to cut off all phases of the power supply externally before attempting
• Manufactured at: Mitsubishi Electric Corporation Himeji Works installation or wiring work.
840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan Type Wire size
FX3G-1DA-BD • Authorized Representative in the European Community:
Failure to do so may cause electric shock or damage to the product.

Mitsubishi Electric Europe B.V.


Single-wire 0.3 mm2 to 0.5 mm2 (AWG22 to 20)
INSTALLATION MANUAL Gothaer Str. 8, 40880 Ratingen, Germany
Caution for EC Directive
INSTALLATION
PRECAUTIONS 2-wire 2 pieces of 0.3 mm2 (AWG22)

Manual Number JY997D33601 The analog expansion boards have been found to be compliant to the • Use the product within the generic environment specifications described in PLC 3) Termination of cable end
European standards in the aforesaid manual and directive. However, for the main unit manual (Hardware Edition). Strip the coating of strand wire and twist the cable core before connecting it,
Revision E very best performance from what are in fact delicate measuring and controlled Never use the product in areas with excessive dust, oily smoke, conductive dusts, or strip the coating of single wire before connecting it.
output device Mitsubishi Electric would like to make the following points; corrosive gas (salt air, Cl 2 , H 2 S, SO 2 , or NO 2 ), flammable gas, vibration or An alternative connection is to use a ferrule with insulating sleeve.
Date April 2013
As analog devices are sensitive by nature, their use should be considered impacts, or expose it to high temperature, condensation, or rain and wind. <Reference>
carefully. For users of proprietary cables (integral with sensors or actuators), If the product is used in such conditions, electric shock, fire, malfunctions,
This manual describes the part names, dimensions, mounting, and these users should follow those manufacturers installation requirements. deterioration or damage may occur. Manufacturer Model Caulking tool
specifications of the product. Before use, read this manual and the manuals of Mitsubishi Electric recommend that shielded cables should be used. If NO other • When drilling screw holes or wiring, make sure cutting or wire debris does not
all relevant products fully to acquire proficiency in handling and operating the EMC protection is provided, then users may experience temporary loss or enter the ventilation slits. CRIMPFOX 6*1
Phoenix Contact Co., Ltd. AI 0.5-8WH
product. Make sure to learn all the product information, safety information, and accuracy between ±10 % in very heavy industrial areas. Failure to do so may cause fire, equipment failures or malfunctions. (or CRIMPFOX 6T-F*2)
precautions. However, Mitsubishi Electric suggest that if adequate EMC precautions are
Store this manual in a safe place so that it can be taken out and read whenever • Do not touch the conductive parts of the product directly. *1 Old model name: CRIMPFOX ZA 3
followed for the users complete control system, users should expect accuracy Doing so may cause device failures or malfunctions.
necessary. Always forward it to the end user. *2 Old model name: CRIMPFOX UD 6
Registration: as specified in this manual. • Connect expansion board securely to their designated connectors.
The company and product names described in this manual are registered • Sensitive analog cable should not be laid in the same trunking or cable Loose connections may cause malfunctions.
trademarks or the trademarks of their respective companies. conduit as high voltage cabling. Where possible users should run analog - Strand wire/single wire - Stick terminal with insulating sleeve
cables separately. For the installation, refer to the following manual. Insulation sleeve Contact area
Effective April 2013
• Good cable shielding should be used. When terminating the shield at Earth → FX3S Series User's Manual - Hardware Edition (Crimp area)
Specifications are subject to change without notice. → FX3G Series User's Manual - Hardware Edition
- ensure that no earth loops are accidentally created.
© 2008 Mitsubishi Electric Corporation • When reading analog values, EMC accuracy can be improved out by
averaging the readings. This can be achieved either through functions on the 3. Wiring 9mm
(0.35")
8mm
(0.31")
Safety Precaution (Read these precautions before use.) analog expansion boards or through a users program in the PLC main unit.
WIRING
This manual classifies the safety precautions into two categories: PRECAUTIONS 2.6mm(0.1") 14mm(0.55")
1. Outline
and . The FX3G-1DA-BD board (hereinafter called 1DA-BD) is an expansion board for • Make sure to cut off all phases of the power supply externally before attempting When using a stick terminal with insulating sleeve, choose a wire with proper
adding one additional analog output point. installation or wiring work. cable sheath referring to the above outside dimensions, or otherwise, the wire
Indicates that incorrect handling may cause hazardous Failure to do so may cause electric shock or damage to the product. cannot be inserted easily.
conditions, resulting in death or severe injury.
1.1 Incorporated Items
The tightening torque must be 0.22 to 0.25 N•m. Do not tighten terminal
Product Analog output expansion board FX3G-1DA-BD WIRING screws exceeding the specified torque. Failure to do so may cause equipment
Indicates that incorrect handling may cause hazardous PRECAUTIONS failures or malfunctions.
conditions, resulting in medium or slight personal injury • M3×8 tapping screws for installation: 2 pcs.
or physical damage. Included items • Side cover • When drilling screw holes or wiring, make sure cutting or wire debris does not 4) Tool
• Installation Manual (This manual) enter the ventilation slits. For tightening the terminal, use a
With
Failure to do so may cause fire, equipment failures or malfunctions. commercially available small
Depending on the circumstances, procedures indicated by may straight tip
1.2 External Dimensions, Part Names • Make sure to observe the following precautions in order to prevent any damage to screwdriver having a straight form that is
also cause severe injury. not widened toward the end as shown
the machinery or accidents due to abnormal data written to the PLC under the
It is important to follow all precautions for personal safety. right. 0.4mm 2.5mm
Unit: mm (inches) influence of noise:
[4] Caution: (0.02") (0.1")
1) Do not bundle the power line or shield of the analog input/output cable together
Associated Manuals with or lay it close to the main circuit, high-voltage line, or load line. If the diameter of screwdriver grip is too
[5] Connector cover is Otherwise, noise disturbance and/or surge induction are likely to take place. As small, tightening torque will not be able
51.2 (2.02")

Manual name Manual No. Description removed to be achieved. Use the following recommended screwdriver or an
[3] a guideline, lay the control line at least 100mm (3.94") or more away from the
FX 3S /FX 3G /FX 3GC /FX 3U / main circuit, high-voltage line or load line. appropriate replacement (grip diameter: approximately 25 mm (0.98")).
JY997D16701 Describes specifications for
[7] <Reference>
FX3UC Series analog control and programming 2) Ground the shield of the analog input/output cable at one point on the signal
MODEL CODE:
User's Manual method for FX3S/FX3G/FX3GC/ receiving side. However, do not use common grounding with heavy electrical Manufacturer Model
09R619 FX3U/FX3UC Series PLC.
- Analog Control Edition [2] systems.
[1] • Make sure to properly wire to the terminal block (European type) in accordance Phoenix Contact Co., Ltd. SZS 0.4×2.5
FX3S Series JY997D48601 E x p l a i n s F X 3 S S e r i e s P L C MASS (Weight): 20 g (0.05 lbs)
with the following precautions.
User’s Manual MODEL CODE: specifications for I/O, wiring,
35 (1.38") 15.1 14.1 Failure to do so may cause electric shock, equipment failures, a short-circuit, wire
- Hardware Edition 09R535 installation, and maintenance.
(0.6") (0.56") breakage, malfunctions, or damage to the product.
FX3G Series JY997D31301 E x p l a i n s F X 3 G S e r i e s P L C - The disposal size of the cable end should follow the dimensions described in
User’s Manual MODEL CODE: specifications for I/O, wiring, [6] the manual.
installation, and maintenance. Terminal Layout
- Hardware Edition 09R521 - Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
How to obtain manuals
VI-
V+
I+

For product manuals or documents, consult with the Mitsubishi Electric dealer - Do not solder-plate the electric wire ends.
from who you purchased your product. - Do not connect more than the specified number of wires or electric wires of
unspecified size.
5 poles - Affix the electric wires so that neither the terminal block nor the connected
Applicable standards [1]Terminal block mounting screws parts are directly stressed.
FX3G-1DA-BD units made in November, 2008 or later comply with the EC [2]POW LED: Lit while power is properly supplied from main unit
• Make sure to properly wire to the terminal blocks in accordance with the following
Directive (EMC Directive). Further information can be found in the following [3]Mounting holes (2-φ3.2)
precautions.
manual. [4]Connector cover
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire
→ FX3S Series Hardware Manual (Manual No. JY997D48301) [5]Main unit connector
breakage, malfunctions, or damage to the product.
→ FX3G Series Hardware Manual (Manual No. JY997D46001) [6]Terminal block to connect analog output
[7]Memory cassette/Display module connector - The disposal size of the cable end should follow the dimensions described in
the manual.
- Tightening torque should follow the specifications in the manual.

3.2 Wiring of Analog Output 4.2 General Specifications 4.4 List of Special Devices
→ For the terminal configuration, refer to Section 1.2 The general specifications are equivalent to the PLC main unit. R: Read W: Write
For general specifications, refer to the following manuals.
Using voltage Device number
output Terminal 1DA-BD → FX3S Series User's Manual - Hardware Edition
block → FX3G Series User's Manual - Hardware Edition FX3G Description R/W
V+ 4.3 Performance Specifications FX3S
Board A Board B
I+
Specifications Switches the output mode
Grounding VI- Item M8260 M8260 M8270 R/W
Voltage output Current output OFF: Voltage output ON: Current output

0 to 10 V DC 4 to 20 mA DC Special Output Holding Function Cancellation


Analog output Setting
(External load resistance: (External load resistance: auxiliary
Using current range OFF: Holds the analog data output just
1DA-BD 2 kΩ to 1 MΩ) 500 Ω or less) relay M8264 M8264 M8274 R/W
output Terminal before stop of the PLC.
block Digital input 12 bits, binary 11 bits, binary ON: Output the offset data at stop of
V+ Resolution 2.5 mV (10 V/4000) 8 μA (16 mA/2000) the PLC.
I+
• ±0.5 % (±50 mV) for full D8260 D8260 D8270 Output setting data R/W
Grounding VI-
scale of 10 V(when ambient Error status
temperature is 25 °C±5 °C) b0: Output data setting error
• ±1.0 % (±100 mV) for full Special b1: Unused
*1 Use 2-core shielded twisted pair cable for the analog output lines, and scale of 10 V data D8268 D8268 D8278 b2: Unused R/W
separate the analog output lines from other power lines or inductive lines. (when ambient temperature • ±0.5 % (±80 μA) for full scale register b3: Unused
is 0 °C to 55 °C) of 16 mA (when ambient b4: EEPROM error
*2 The grounding resistance should be 100 Ω or less. Shipment adjustment is carried b15 to b5: Unused
temperature is 25 °C±5 °C)
Total accuracy out by external load resistance
3.3 Grounding • ±1.0 % (±160 μA) for full D8269 D8269 D8279 Model code = 4 R
2 kΩ.
Grounding should be performed as stated below. scale of 16 mA
I f e x t e r n a l l o a d r e s i s ta n c e As for the details of the special devices, refer to the following manual.
(when ambient temperature
• The grounding resistance should be 100 Ω or less. becomes larger than 2 kΩ, the → FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual - Analog Control Edition
is 0 °C to 55 °C)
• Independent grounding should be performed for best results. output voltage will increase
When independent grounding is not performed, perform "shared grounding" of slightly.
the following figure. When the load is 1 MΩ, the
For details, refer to the following manual. output voltage becomes about
→ FX3S Series User's Manual - Hardware Edition 2 % higher than the correct
→ FX3G Series User's Manual - Hardware Edition value.
Other Other Other D/A
PLC PLC PLC 60 μs
equipment equipment equipment conversion
(The data will be updated at every scan time of the PLC.)
time

Independent grounding Shared grounding Common grounding 0 to 4000 are adjusted to 0 to 0 to 2000 are adjusted to 4 to
Best condition Good condition Not allowed 10 V when the external load 20 mA when the external load
resistance is 2 kΩ. resistance is 250 Ω.
• The grounding wire size should be AWG 22-20 (0.3-0.5 mm2).
• The grounding point should be close to the PLC, and all grounding wire should
be as short as possible. 10V 20mA
Analog output

Analog output

4. Specifications
output
STARTUP AND characteristics 4mA
MAINTENANCE
0 4000 4080 0 2000 2040
PRECAUTIONS Digital input Digital input
• Do not disassemble or modify the PLC. Caution:
Doing so may cause fire, equipment failures, or malfunctions. An area of dead band is located
* For repair, contact your local Mitsubishi Electric representative. in the region of 0 V.
• Do not drop the product or exert strong impact to it. Therefore the output analog
Doing so may cause damage. value may not represent the
digital value accurately.
DISPOSAL Insulation
No insulation between the PLC.
PRECAUTIONS method

• Please contact a certified electronic waste disposal company for the Occupied 0 point (This number is not related to the maximum number of
environmentally safe recycling and disposal of your device. points input/output points of the PLC.)
This manual confers no industrial property rights or any rights of any other kind,
TRANSPORTATION AND nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
STORAGE PRECAUTIONS held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
• The product is a precision instrument. During transportation, avoid any
impacts. Warranty
Failure to do so may cause failures in the product. After transportation, verify Mitsubishi will not be held liable for damage caused by factors found not to be
the operations of the product. the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
4.1 Applicable PLC caused by special factors unpredictable by Mitsubishi; damages to products
Model name Applicability other than Mitsubishi products; and to other duties.

FX3S Series PLC Ver. 1.00 or later (from first production)


For safe use
FX3G Series PLC Ver. 1.10 or later
• This product has been manufactured as a general-purpose part for general
The version number can be checked by monitoring D8001/D8101 as the last three industries, and has not been designed or manufactured to be incorporated in
digits indicate it. a device or system used in purposes related to human life.
• The number of connectable expansion boards varies depending on the main • Before using the product for special purposes such as nuclear power, electric
unit as follows: power, aerospace, medicine or passenger movement vehicles, consult with
FX3S, FX3G-14M…, FX3G-24M… Main units: 1 unit Mitsubishi Electric.
FX3G-40M…, FX3G-60M… Main units: 2 units • This product has been manufactured under strict quality control. However
Never stack up two or more expansion boards. when installing the product where major accidents or losses could occur if the
For details on the system configuration, refer to the following manual. product fails, install appropriate backup or failsafe functions in the system.
→ FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual
- Analog Control Edition