Professional Documents
Culture Documents
Power Supply/Charger
Installation Guide
Models Include:
AL1024ULX
- Single Output.
AL1024ULXPD4 AL1024ULXPD4CB
- Four (4) Fuse Protected Outputs. - Four (4) PTC Protected Outputs.
AL1024ULXPD8 AL1024ULXPD8CB
- Eight (8) Fuse Protected Outputs. - Eight (8) PTC Protected Outputs.
AL1024ULXPD16 AL1024ULXPD16CB
- Sixteen (16) Fuse Protected Outputs. - Sixteen (16) PTC Protected Outputs.
For a red enclosure add an “R” suffix to the part #, e.g. AL1024ULXPD8R
Outputs (auto-resettable)
Protected Power-Limited
Distribution Module(s)
Number of Output(s)
Fused Outputs
Power Supply
Power Supply
per Output
UL Listings
Altronix and
Model Number Agency Listings File Numbers
Altronix Corp.
140 58th St. Brooklyn, NY
For Access Control applications, battery capacity for 10A supply current - 1 hr. for 24VDC/12AH battery,
6.5 hrs. for 24VDC/65AH battery.
See battery size calculation worksheet for other batteries (Page 7).
Fig. 1
CAUTION: De-energize unit prior to servicing. For continued protection
against risk of electric shock and fire hazard replace fuses with the same type
and rating. Do not expose to rain or moisture.
non power-limited
+ DC ---
15A 32V
15
AC DC
AC DELAY
L G N BAT FAIL NC C NO NC C NO AC FAIL
Class 1
Wire Strap
(from
Enclosure
to Door) Power
Distribution
Module(s)
1 2
INPUT
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
Wiring:
Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper
voltage level.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage
both at the battery terminal and at the board terminals marked [– BAT +] to ensure that there is no break in the
battery connection wires.
Note: Maximum charging current under discharges is 3.6A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
AL1024ULXB2 - Power Supply Board
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery is supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
PD4UL/PD4ULCB/PD8UL/PD8ULCB - Power Distribution Module
Green (AC) Power Distribution Module Status
ON Normal operating condition.
OFF No Power Output.
-4- AL1024ULX Series
Terminal Identification:
AL1024ULXB2 - Power Supply Board
Terminal Legend Function/Description
Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.
L, N
Do not use the [G] terminal.
24VDC @ 8A continuous, 10A in alarm non power-limited output.
+ DC –
10A continuous when batteries are not used
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay
AC Fail normally energized when AC power is present. Contact rating 1A @ 28VDC. AC or
NC, C, NO brownout fail is reported within 1 minute of event. To delay reporting for up to 6 hrs.,
cut “AC delay” jumper and reset power to unit.
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
Bat Fail when DC power is present. Contact rating 1A @ 28VDC. A removed battery is reported
NC, C, NO within 5 minutes. Battery reconnection is reported within 1 minute.
Low battery threshold: 24VDC output threshold set @ approximately 21VDC.
– BAT + Stand-by battery connections. Maximum charge current 3.6A.
F1 F2 F3 F4
F1 F2 F3 F4
MADE IN USA
PD4ULCB
1P, 2P, 3P, 4P = FUSED OUTPUTS
1N, 2N, 3N, 4N = COMMON OUTPUTS PD4UL POWER DISTRIBUTING UNIT
LED
1P 1N 2P 2N 3P 3N 4P 4N INPUT
1P 1N 2P 2N 3P 3N 4P 4N POWER OUTPUTS
INPUT
COMMON POWER OUTPUTS
Class 2 Rated Power-Limited From Power Supply
Non Power-Limited From Power Supply DC Output to devices Board
DC Output to devices (Factory Installed)
Fig. 3a Fig. 3b
Replace fuses with the same type and rating 3.5A, 250V.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 PD8ULCB
PD8UL P POWER DISTRIBUTING UNIT
N INPUT
N INPUT
COMMON POWER OUTPUTS
(
DC Output to devices
1P-8P Power Outputs,
)
Board
(Factory Installed) ( 1P-8P Power Outputs,
1N-8N Common Outputs ) (Factory Installed)
Note: AL1024ULX series power supply is designed to work with batteries up to 65AH.
Please note: line [I] must not exceeds 36AH.
You have to reduce either stand-by current consumption or stand-by time in order to comply with requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size
(e.g. 3.5 AH = 4.0 AH).
1.75”
(44.45mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
0.91” 0.91”
1.5” (23.114mm) (23.114mm) 1.5”
(38.1mm) (38.1mm)
2.0” 15.5”
(50.8mm) (393.7mm)
2.0”
(50.8mm)
5.0” 5.0”
(127.0mm) (127.0mm)
0.79”
1.1” (20.06mm)
1.25” (27.94mm) 1.25”
(31.75mm) (31.75mm)
1.75”
(44.45mm)