Specifications

UL Standards Listing for Industrial Control Products


Topic Page Topic Page
UL 1053 1 UL 5085 9
UL 489 2 UL 1561 9
UL 943 3 UL 1778 9
UL 4248-1 4 UL 1077 9
UL 98 4 UL 1953 10
UL 508 5 UL 1059 10
UL 508A 8 UL 1283 11
UL 61010, 61010-1 8 UL 497B 11
UL 1449 11

Summary of Changes
This publication contains new and updated information as indicated in the following table.

Topic Page
Removes references to the Bulletin 900 Temperature Controllers Throughout

This document is intended to assist original equipment manufacturers (OEMs) with construction of panels, to help
ensure that they conform to the requirements of Underwriters Laboratories (UL). It is not intended to take the place of
product compliance certificates, Declarations of Conformity, user guides, instruction sheets, selection guides, or other
technical publications. Product photos in this publication are representative. Actual product appearance may differ from
what is shown. Products that are shown are not to scale.

UL 1053
UL 1053 states: “These requirements cover ground-fault current sensing devices, relaying equipment, or combinations of
ground-fault current sensing devices and relaying equipment or equivalent protection equipment for use in ordinary
UL Standards Listing for Industrial Control Products

locations that will operate to cause a disconnecting device to open all ungrounded conductors at predetermined values of
ground-fault current, in accordance with the National Electrical Code, ANSI/NFPA 70.”

Table 1 - UL 1053-Compliant Devices

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard Control No. No. Description Paragraph Photo Number

• Detects and interrupts leakage to the ground http://


Ground-fault • Helps prevent injury to exposed personnel and ab.rockwellautomation.com/
E53935 Sensing and 1492- damage to equipment
UL 1053 KDAX2 — Circuit-and-Load-Protection/
Relaying RCDA • Use with miniature circuit breakers for Circuit-Breakers/1492-Residual-
Equipment additional circuit protection from overload, Current-Devices
short circuit, and ground fault
Circuit http://
Breakers, 30.1.1 ab.rockwellautomation.com/
UL489 E197878 Molded Case, 1492- • Ground Fault Equipment Protector
DIVQ 31.1.1 Circuit-and-Load-Protection/
UL 1053 and Circuit- MCE • Range up to 50 A
66.5.4 Circuit-Breakers/1492-Thermal-
breaker Magnetic
Enclosures

UL 489
UL 489 states: “The requirements of this standard cover molded-case circuit breakers, circuit breaker and ground-fault
circuit interrupters, fused circuit breakers, high-fault protectors, and high-fault modules. These circuit breakers are
specifically intended to provide service entrance, feeder, and branch circuit protection in accordance with the National
Installation Codes in Annex B, Ref. No.1.”

Table 2 - UL 489-Compliant Devices

UL UL Category UL 508A
UL Category UL File Control No. (Edition 2013) Representative Bulletin Description Web link
Standard No. Photo Number
Control No. Description Paragraph
Circuit http://
Breakers, 30.1.1 ab.rockwellautomation.com/
UL489 E197878 Molded Case, 1492- • Ground Fault Equipment Protector
DIVQ 31.1.1 Circuit-and-Load-Protection/
UL 1053 and Circuit- MCE • Range up to 50 A
66.5.4 Circuit-Breakers/1492-Thermal-
breaker Magnetic
Enclosures
Circuit
Breakers, http://
30.1.1 ab.rockwellautomation.com/
UL 489
E197878 Molded Case, 1492- • Ground Fault Circuit Interrupter
DIVQ 31.1.1 Circuit-and-Load-Protection/
UL 943 and Circuit- MCG • Range up to 50 A Circuit-Breakers/1492-Thermal-
breaker 66.5.4
Magnetic
Enclosures

2 Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017


UL Standards Listing for Industrial Control Products

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard Control No. No. Description Paragraph Photo Number

1492- http://
MCA • Available up to 100 A ab.rockwellautomation.com/
• Several configurations of tripping curves and Circuit-and-Load-Protection/
1492- number of poles (NEMA Style) Circuit-Breakers/1492-Thermal-
MCB Magnetic
http://
• Used as main disconnect and feeder protection ab.rockwellautomation.com/
140G •• Available in a broad range up to 3000 A Circuit-and-Load-Protection/
Provides LSIG protection with option for 100% Circuit-Breakers/140G-Circuit-
rated and several types of trip units
30.1.1 Breakers
UL 489 DIVQ E197878 — 31.1.1 http://
• Fits on frame size of a manual motor controller
66.5.4 ab.rockwellautomation.com/
140U-D • Suitable to be used as main disconnect and Circuit-and-Load-Protection/
feeder protection 30 A (100% rated), saving Circuit-Breakers/140U-Circuit-
panel space Breakers
• Available up to 63 A http://
• Several configurations of tripping curves and ab.rockwellautomation.com/
1489 • number of poles Circuit-and-Load-Protection/
Alternative to fuses for feeder protection Circuit-Breakers/1489-Thermal-
• Typically the primary protector of a control Magnetic
transformer (IEC Style)
• Inverse Time Circuit Breaker (thermal-magnetic http://
Circuit 30.1.1 trip curve) in molded case circuit breaker ab.rockwellautomation.com/
Breakers,
DIVQ E197878 Inverse Time 31.1.1 140MG frames Circuit-and-Load-Protection/
66.5.4 • Available for Type C starter applications up to Motor-Protection/140MG-Circuit-
Trip Type 150 A. Breakers
http://
Circuit Breaker ab.rockwellautomation.com/
E300325 Accessories, 140G • Accessories for the whole range of 140G Circuit
DIHS 30.1.7 Circuit-and-Load-Protection/
Disconnect Breakers Circuit-Breakers/140G-Circuit-
Handles Breakers
UL 489
http://
• Disconnect Switch (no protection) in molded ab.rockwellautomation.com/
Switches, 140G • case circuit breaker frames
WJAZ E119349 Molded 31.1.2 Circuit-and-Load-Protection/
Case Available for Type A or B starter applications up Circuit-Breakers/140G-Circuit-
to 3000 A. Breakers
Circuit • Instantaneous Trip Circuit Breaker (Magnetic http://
Breakers, 30.1.1 trip curve only) in molded case circuit breaker ab.rockwellautomation.com/
DKPU2 E224135 Adjustable 140MG frames Circuit-and-Load-Protection/
Instantaneous 31.1.1 • Available for Type D starter applications up to Motor-Protection/140MG-Circuit-
Trip Type 1200 A. Breakers

UL 943
UL 943 states: “This standard applies to Class A, single- and three-phase, ground-fault circuit-interrupters that are
intended for protection of personnel, for use only in grounded neutral systems in accordance with the National Electrical
Code (NEC), ANSI/NFPA 70, the Canadian Electrical Code, Part I, and Electrical Installations (Use), NOM-001-
SEDE. These devices are intended for use on alternating current (AC) circuits of 120 V, 208Y/120 V, 120/240 V, 127 V,
or 220Y/127 V, 60 Hz circuits.”
Table 3 - UL 943-Compliant Devices
UL UL Category UL 508A
UL UL File Representative Bulletin
Standard Category No. Control No. (Edition 2013) Photo Number Description Web link
Control No. Description Paragraph

30.1.1 http://ab.rockwellautomation.com/
UL 489 1492- • Ground Fault Circuit Interrupter
DIVQ E197878 — 31.1.1 Circuit-and-Load-Protection/Circuit-
UL 943 MCG • Range up to 50 A Breakers/1492-Thermal-Magnetic
66.5.4

Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017 3


UL Standards Listing for Industrial Control Products

UL 4248-1
This standard replaces UL 512. UL 4248-1 states: “These fuseholders and devices accommodate fuses to be employed in
electrical circuits and are intended to be used in accordance with the Canadian Electrical Code, Part I (CE Code Part I),
CSA C22.1, the National Electrical Code (NEC), ANSI/NFPA 70, or the Mexican Electrical Code, NOM-001.”

Table 4 - UL 4248-1-Compliant Product


UL UL Category UL 508A
UL UL File Representative Bulletin
Standard Category No. Control No. (Edition 2013) Photo Number Description Web link
Control No. Description Paragraph

• Accepts a large variety of North American http://


140F • fuses up to 600 A ab.rockwellautomation.com/
Typically used both for feeder overcurrent Circuit-and-Load-Protection/
UL 4248-1 protection and IEC-style Type A motor starters 140F-Fuse-Holders
Fuseholders, 31.1.5
(replaces IZLT E 34648 Cartridge Fuse 40.1.4
UL 512) • Accepts a large variety of North American http://
fuses up to 600 A ab.rockwellautomation.com/
1491 • Typically used both for Feeder overcurrent Circuit-and-Load-Protection/
protection and NEMA-style Type A motor Disconnect-Switches/Visible-
starters Blade/1491-Fuse-Blocks

UL 98
UL 98 states: “These requirements cover individually enclosed air switches, rated 4000 A or less at 600 V or less, having
all current-carrying parts enclosed, manually operable by means of external handles, and intended to be employed in
accordance with the national installation codes listed in Annex a, Ref. No. 1.”

Table 5 - UL 98-Compliant Devices

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard No. Photo Number
Control No. Description Paragraph
• Fused and non-fused Rotary Disconnect http://ab.rockwellautomation.com/
Switches up to 1200 A Circuit-and-Load-Protection/
194R • Typically used for disconnect and overcurrent Disconnect-Switches/Non-Visible-
protection of Feeder and IEC-style Type A Blade/194R-Fused-Non-Fused-
motor starters Disconnect-Switches
Open Type 30.1.4
UL 98 WHTY E47426 • Fused and not fused Flange- or Cable-
Switch 30.1.7
operated handle Manual Disconnect http://ab.rockwellautomation.com/
1494 • Switches up to 600 A Circuit-and-Load-Protection/
Typically used for disconnect and overcurrent Disconnect-Switches/Visible-Blade
protection of Feeder and NEMA-style Type A
motor starters

4 Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017


UL Standards Listing for Industrial Control Products

UL 508
UL 508 states: “These requirements cover industrial control devices and accessories, for starting, stopping, regulating,
controlling, or protecting electric motors. These requirements also cover industrial control devices or systems that store
or process information and are provided with an output motor control function(s). This equipment is for use in ordinary
locations in accordance with the National Electrical Code, NFPA 70.”

Table 6 - UL 508-Compliant Devices


UL UL Category UL 508A
UL Category UL File Control No. (Edition 2013) Representative Bulletin Description Web link
Standard No. Photo Number
Control No. Description Paragraph

• Self-protected combination motor http://ab.rockwellautomation.com/


controllers
E205542 140M • Provide disconnect, overcurrent protection, circuit-and-load-protection/motor-
control and overload protection for Type E protection/140m-circuit-
and F motor starters up to 45 A breakers#selection
31.1.5
Combination 31.1.4
NKJH Motor 33.1.1
Controller • Pre-configured 2- and 3-component DOL
34.1.1 103 and reversing starters
107 http://ab.rockwellautomation.com/
E125316 • Provide disconnect, short-circuit protection, Motor-Control/LV-Starters/IEC-Open
190 control and overload protection for Type
191 B,C,D, E, and F motor starters

http://ab.rockwellautomation.com/
140M circuit-and-load-protection/motor-
140A • Manual Motor Controllers protection/140m-circuit-
• Typically used as at motor disconnect at the breakers#selection
26.2.4(c) load side of last overcurrent protection
30.1.5 • For safe disconnection of the motor up to
NLRV E54612 Manual Motor
Controller 31.4.3 100 A.
33.1.1 http://ab.rockwellautomation.com/
194E
34.1.1 Motor-Control/194E-Load-Switches

UL 508
http://ab.rockwellautomation.com/
194L •• Manual Motor Controllers Motor-Control/194L-Control-and-
Typically used as control switches Load-Switches

• Full Contactor line up to 1200 A http://ab.rockwellautomation.com/


100, • Controls motor at any type of motor starters Motor-Control/IEC-Contactors/IEC-
104
(IEC Style) Standard-Contactors

31.1.7 500 • Full Contactor line up to 1600 A


31.4.1(c) 505 • Controls motor at any type of motor starters http://ab.rockwellautomation.com/
Motor-Control/Contactors/NEMA
33.1.1 509 (NEMA Style)
Magnetic 33.1.3
NLDX E3125 Motor 33.7.1 700-HA
Controller 34.1.1 700-HB
42.3.1 700-HG
45.1.1(a) 700-HL • Even though some of these relays and timers
90.4.1 700-HK are tested to pilot loads in Hp, these products
700-HP are clearly identified to be used in control http://ab.rockwellautomation.com/
Relays-and-Timers
circuits
700-HD • Not for use in power circuits
700-HF
700-HH
700-HJ

Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017 5


UL Standards Listing for Industrial Control Products

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard Control No. No. Description Paragraph Photo Number

• Even though some of these relays and timers


31.1.7 are tested to pilot loads in Hp, these products http://ab.rockwellautomation.com/
700-HT
31.4.1(c) are clearly identified to be used in control
700-HV Relays-and-Timers
33.1.1 circuits
33.1.3 • Not for use in power circuits
Magnetic
NLDX E3125 Motor 33.7.1
Controller 34.1.1
42.3.1 http://ab.rockwellautomation.com/
• Definite purpose contactors for special
45.1.1(a) 400 Motor-Control/NEMA-Contactors/
applications
90.4.1 Bulletin-400

Relay Sockets • Sockets and different type of accessories to


SWIV2 E96409 and 45.1.1(a) 700
Assemblies complete relays and timers

700-HC •• General Purpose Miniature Control relay


Two 10 A and four 5 A contacts
http://ab.rockwellautomation.com/
Relays-and-Timers
Switches, • Solid state control relay based on Zero Cross
NRNT2 E14843 Industrial 45.1.1(a) 700-SH technology
Control • Range up to 100 A

UL 508 700-HN • Multifunction and multi-range


700-HR • Traditional or digital timer control
700-HX

• For bimetallic or electronic overload http://ab.rockwellautomation.com/


protection Circuit-and-Load-Protection/LV-
193 • Available for any application of IEC-style Motor-Protectors/Electronic-
Type A to F motor starters Overload-Relays

• For eutectic or electronic overload protection http://ab.rockwellautomation.com/


Circuit-and-Load-Protection/LV-
592 • Available for any application of NEMA-style Motor-Protectors/592-Overload-
See Section 34 Type A to F motor starters Relay

NKCR E14840 Auxiliary • Offers supplementary protective functions


Devices
• Allows selective addition of motor protective
809S functions for the following protection types: http://ab.rockwellautomation.com/
813S – supplemental voltage Circuit-and-Load-Protection/
814S – current Supplementary-Motor-Protectors/
817S – thermistor Monitoring-Relays
– power
– power factor
26.2.4(c)
34.1.1 • 16, 22, 30 mm mounting hole http://ab.rockwellautomation.com/
42.3.1 800 • Traditional mechanical or piezo action Push-Buttons-and-Signaling-
45.1.1(a) • NEMA or IEC style Devices
46.1.1(a)

6 Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017


UL Standards Listing for Industrial Control Products

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard Control No. No. Description Paragraph Photo Number

• Full basket of signaling devices, from stack


lights to beacons http://ab.rockwellautomation.com/
854 • Panel or internal mounting Push-Buttons-and-Signaling-
855 • Available with illumination, sound, or Devices
combination system

700-FE •• Multifunction and multi-range http://ab.rockwellautomation.com/


26.2.4(c) Economy and high performance Relays-and-Timers/General-
700-FS • Traditional timer relay
34.1.1 Purpose-Timing-Relays
NKCR E14840 Auxiliary 42.3.1
Devices
45.1.1(a)
46.1.1(a) http://ab.rockwellautomation.com/
700-CF • IEC-style control relay Relays-and-Timers/IEC-Industrial-
700-K Relays

http://ab.rockwellautomation.com/
700N • NEMA-style control relay
700P Relays-and-Timers/NEMA-
Industrial-Relays

http://ab.rockwellautomation.com/
NISD E338755 — — 800T • Emergency Stop Push-Buttons/30-mm/800T-800H

• Smart Motor Controllers provide solid-state


motor starting http://ab.rockwellautomation.com/
UL 508 150 • Thermal protection up to 1250 A (1600 A in Motor-Control/LV-Soft-Starters
inside-the-delta configuration)
NMFT
Motor 33.1.1
Controllers, 34.1.1 http://ab.rockwellautomation.com/
E96956 Mechanically 42.3.1 156 • Solid-state contactor with range up to 90 A Motor-Control/Contactors/Solid-
Operated and 90.4.2 State
Solid-State

700-SA
700-SC • Solid-state control relay with range up to 5 A http://ab.rockwellautomation.com/
NMFT2 Relays-and-Timers/General-
700-SF
700-SK Purpose-Timing-Relays

http://ab.rockwellautomation.com/
Circuit-and-Load-Protection/1692-
1692 • Electronic protection for control circuits Electronic-Circuit-Protection-
Module

Power Circuit • Switched Mode Power supply http://ab.rockwellautomation.com/


1607 • For DC supply to control circuits up to 200 W, Power-Supplies/ArmorPower-On-
E56639 and Motor-
NMTR 42.3.1 on machine Machine#overview
mounted
Apparatus

Mode Power supply, for DC supply http://ab.rockwellautomation.com/


1606 • Switched Power-Supplies/Switched-Mode-
to control circuits up to 960 W, in panel Power-Supplies

Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017 7


UL Standards Listing for Industrial Control Products

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard Control No. No. Description Paragraph Photo Number

http://ab.rockwellautomation.com/
1420 • Power Monitor 500 and 1000 for load
E56639 Power Circuit 1408 profiling, cost allocation, or energy control Energy-Monitoring/1408-
NMTR 42.3.1 PowerMonitor-1000
and Motor-
E143184 mounted • Busbar mounting system up to 1250 A http://ab.rockwellautomation.com/
Apparatus
29.2.2 141A • Accommodates multiple configurations of Motor-Control/LV-Starters/Busbar-
NMTR2 E56639 motor starters and circuit breakers Mounting-System
42.3.1

UL 508 Wiring and connection system to quickly http://ab.rockwellautomation.com/


E113724 Programmable 42.3.1
NRAQ 1492 • I/O Connection-Devices/Bulletin-1492-
Controllers 54.1.1.(a) connect to PLC
IO-Wiring-Systems

NRAQ2
NMTR2 E113724 http://ab.rockwellautomation.com/
NRAQ E56639 • Signal Conditioners for Current, Voltage,
Various Various 931 Signal-Interface/Signal-
MRAG E10314 Thermocouple, and specialty application Conditioners
NWGD E34550
PICQ

UL 508A
UL 508A states: “These requirements cover industrial control panels intended for general industrial use, operating from
a voltage of 1000 volts or less. This equipment is intended for installation in ordinary locations, in accordance with the
National Electrical Code, ANSI/NFPA 70, where the ambient temperature does not exceed 40 °C (104 °F) maximum.”

Table 7 - UL 508A-Compliant Devices

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard Control No. No. Description Paragraph Photo Number

• Receptacles only (not the entire assembly) are covered


1492- • UNDER UL 943 (KCXS)
UL508A NITW E54866 — — Receptacle is assembled to the enclosure that is provided —
REC as part of the 1492-REC15x and 1492-REC20x products
• The complete assembly has the UL508A listing

UL 61010, 61010-1
UL 61010 applies to electrical equipment for measurement, control, and laboratory use.

UL 61010-1 states: “This part of IEC 61010 specifies general safety requirements for the following types of electrical
equipment and their accessories, wherever they are intended to be used...
a. Electrical test and measurement equipment
b. Electrical industrial process-control equipment
c. Electrical laboratory equipment”
Table 8 - UL 61010-Compliant Devices
UL UL Category UL 508A
UL UL File Representative Bulletin
Standard Category No. Control No. (Edition 2013) Photo Number Description Web link
Control No. Description Paragraph
http://
Measuring, Testing
1426 • High end power monitoring and power ab.rockwellautomation.com/
UL 61010 PICQ E345550 and Signal- — quality analysis Energy-Monitoring/1426-
generation PowerMonitor-5000

8 Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017


UL Standards Listing for Industrial Control Products

UL 5085
UL 5085 applies to low-voltage transformers.

Table 9 - UL 5085-Compliant Devices


UL UL Category UL 508A
UL Category UL File Control No. (Edition 2013) Representative Bulletin Description Web link
Standard No. Photo Number
Control No. Description Paragraph

Transformers, 35.1.1 http://ab.rockwellautomation.com/


1497 •• Machine Tool (0.5…3kVA)
UL 5085 XPTQ E52057 General Power-Supplies/Control-
42.1.1.1 Control Power Transformer (0.63…3kVA)
Purpose Transformers

UL 1561
UL 1561 applies to general purpose and power transformers.

Table 10 - UL 1561-Compliant Devices

UL UL UL File UL Category Control UL 508A Representative Bulletin


Category (Edition 2013) Description Web link
Standard No. No. Description Photo Number
Control No. Paragraph
http://
Power and General- 35.1.2
1497D • General Purpose Transformer ab.rockwellautomation.com/
UL 1561 XQNX E311296 purpose Transformers,
42.1.1.1 (0.05…25kVA) Power-Supplies/General-Purpose-
Dry Type Transformer

UL 1778
UL 1778 states: “This Standard applies to UNINTERRUPTIBLE POWER SYSTEMS (UPS). The primary function
of the UPS for this Standard is to ensure continuity of an alternating power source. The UNINTERRUPTIBLE
POWER SYSTEM may also serve to improve the quality of the power source by keeping it within specified
characteristics. This Standard is applicable to movable, stationary, fixed, and built-in UPS for distribution systems up to
600 V a.c. This equipment is designed to be installed in accordance with the Canadian Electrical Code, Part I, CSA
C22.1, or the National Electrical Code, ANSI/NFPA 70, and, unless otherwise identified, the Standard for the
Protection of Electronic Computer Data-Processing Equipment, ANSI/NFPA 75.”

Table 11 - UL 1778-Compliant Devices

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard Control No. No. Description Paragraph Photo Number

• Provides continuity of AC control voltage http://ab.rockwellautomation.com/


E190749 Uninterruptible 1609 • when main grid fails
UL 1778 YEDU — Power-Supplies/Uninterruptible-
Power-supply Available for industrial (up to 1.5kVA) or Power-Supplies
commercial applications (up to 10kVA)

UL 1077
UL 1077 states: “These requirements apply to supplementary protectors intended for use as overcurrent, or over- or
under-voltage protection within an appliance or other electrical equipment where branch circuit overcurrent protection
is already provided, or is not required. Compliance with the following is acceptable for use as a component of an end
product.”

Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017 9


UL Standards Listing for Industrial Control Products

Table 12 - UL 1077-Compliant Devices

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard Control No. No. Description Paragraph Photo Number

• Available up to 63 A
• Several configurations of tripping curves and http://
1492-SPM number of poles ab.rockwellautomation.com/
• Correct alternative to fuses for control circuit Circuit-and-Load-Protection/
1492-D protection Circuit-Breakers/1492-
Protectors, • Typically the secondary of an IEC-style Supplementary-Protectors
UL 1077 QVNU2 E65138 Supplementary 40.1.3 control transformer
http://
• Available as single-pole devices ab.rockwellautomation.com/
1492-GH • Range from 0.2…15 A Circuit-and-Load-Protection/
• Push to set Circuit-Breakers/1492-High-
Density#overview

UL 1953
UL 1953 states: “These requirements cover power distribution blocks that are rated 1000 volts or less and intended to be
used on either the line side or load side of service equipment in accordance with the National Electrical Code, NFPA 70.
These blocks are used for splicing and tapping conductors in order to distribute power to separate circuits or loads.”

Table 13 - UL 1953-Compliant Devices


UL UL Category UL 508A
UL UL File Representative Bulletin
Standard Category No. Control No. (Edition 2013) Photo Number Description Web link
Control No. Description Paragraph
http://
1492-PDME • Enclosed power distribution blocks for main ab.rockwellautomation.com/
1492-PDE supply distribution up to 510 A terminal-blocks/1492-pde-
Power enclosed
UL 1953 QPQS E313475 Distribution 28.2.4 1492-PD • Open power distribution blocks for main
Blocks 1492-PDL supply distribution up to 760 A http://
ab.rockwellautomation.com/
• Open power distribution blocks for main terminal-blocks/1492-pd-
1492-PDL supply distribution up to 760 A open-style#selection
• Available for feeder applications

UL 1059
UL 1059 states: “These requirements cover assemblies of wiring terminals and supporting blocks intended to provide for
the connection of wiring. Compliance with these requirements does not assure that the terminal block is suitable for use
as a component of an end product.”

Table 14 - UL 1059-Compliant Devices

UL UL UL File UL Category UL 508A Representative Bulletin


Category Control No. (Edition 2013) Description Web link
Standard Control No. No. Description Paragraph Photo Number

http://ab.rockwellautomation.com/Circuit-
1492-GS •• Range from 0.2…25 A and-Load-Protection/Circuit-Breakers/
Trigger to set 1492-High-Density#overview
14.2(a)
UL 1059 XCFR2 E40735 Terminal Block
28.2.1
1492-J
1492-W •• Control terminal blocks http://ab.rockwellautomation.com/
Wire size from 30 …2/0 AWG Terminal-Blocks/IEC-Screw-Terminal-Blocks
1492-R

10 Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017


UL Standards Listing for Industrial Control Products

UL 1283
UL 1283 states: “These requirements cover electromagnetic interference (EMI) filters installed on, or connected to,
1,000 V or lower potential circuits, 50 – 60 Hz, or up to 1,500[V DC], and installed in accordance with the National
Electrical Code, NFPA 70.”

Table 15 - UL 1283-Compliant Devices


UL UL Category UL 508A
UL UL File Representative Bulletin
Standard Category No. Control No. (Edition 2013) Photo Number Description Web link
Control No. Description Paragraph

Electromagnetic 4983-DC • Combination of a filter and a surge protective http://


UL 1283 FOKY2 E316867 Interference 47.1.2 4983-PF • device ab.rockwellautomation.com/
Filters DIN rail or panel mounting Surge-Protectors-Filters

UL 497B
UL 497B states: “These requirements cover protectors for data communications and fire-alarm circuits.”

Table 16 - UL 497B-Compliant Devices


UL UL Category UL 508A
UL Category UL File Control No. (Edition 2013) Representative Bulletin Description Web link
Standard No. Photo Number
Control No. Description Paragraph
• Designed to protect industrial
Isolated Loop http://
4983-DD • communication networks
UL 497B QVGQ E317213 Circuit — ab.rockwellautomation.com/
Combination of 3-electrode gas discharge
Protectors Surge-Protectors-Filters
tubes and fast-clamping diodes

UL 1449
UL 1449 states: “These requirements cover enclosed and open-type Surge Protective Devices (SPDs) designed for
repeated limiting of transient voltage surges as specified in the standard on 50 or 60 Hz power circuits not exceeding
1000 V and for PV applications up to 1500[V DC]...”

Table 17 - UL 1449-Compliant Devices


UL UL Category UL 508A
UL UL File Representative Bulletin
Standard Category No. Control No. (Edition 2013) Photo Number Description Web link
Control No. Description Paragraph
• Combines a high-energy varistor (MOV)
Surge- 4983-DH • network with a gas discharge tube (DH) http://
UL 1449 VZCA2 E334011 protective — 4983-DS Can also be connected in parallel and used ab.rockwellautomation.com/
Devices with an MOV to clamp high-voltage surges Surge-Protectors-Filters
(4983-DS)

Rockwell Automation Publication CMPNTS-SR002B-EN-P - August 2017 11


Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.rockwellautomation.com/global/ Provides declarations of conformity, certificates, and other certification details.
certification/overview.page

You can view or download publications at http://www.rockwellautomation.com/global/literature-library/


overview.page. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.

Rockwell Automation Support


Use the following resources to access support information.

Knowledgebase Articles, How-to Videos, FAQs, Chat,


Technical Support Center www.rockwellautomation.com/knowledgebase
User Forums, and Product Notification Updates.
www.rockwellautomation.com/global/support/get-support-
Local Technical Support Phone Numbers Locate the phone number for your country.
now.page
Find the Direct Dial Code for your product. Use the www.rockwellautomation.com/global/support/direct-
Direct Dial Codes code to route your call directly to a technical support dial.page
engineer.
Installation Instructions, Manuals, Brochures, and
Literature Library www.rockwellautomation.com/literature
Technical Data.

Product Compatibility and Download Center Get help determining how products interact, check
features and capabilities, and find associated www.rockwellautomation.com/global/support/pcdc.page
(PCDC) firmware.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.

Allen-Bradley, LISTEN. THINK. SOLVE., Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Publication CMPNTS-SR002B-EN-P - August 2017


Supersedes Publication CMPNTS-SR002A-EN-P June 2017 Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like