DESIGNED BY: ENGR. E. A. NYIEKAA ( responsibility for works not supervised by him
or his authorised agent.
Location
)
job title PROJECT
Project Title: Proposed Residential Development at plot No......... Drawn by: ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
Checked by:
Client: ----------------------------
scale
sheet no. NTS
dimension
08082259483, 08164521557
notes
(1) Installation is to be done according to the
ITEM DESCRIPTION RATING cables fully concealed in 20mm UPVC pipes with
appropriate accessories.
Location
client
Checked by:
Drawing title
LEGEND
scale
sheet no. NTS
dimension
01 date
MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
BL1 BL2
client
BL1
Design : ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
BL2
Drawn by: ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
Checked by:
Drawing title
BL1 LIGHTING CIRCUIT ON THE GATE HOUSE
GEN. HOUSE
TOI/BATH BL2
BL3 BL3
BL3
BL3 BL3
GATE HOUSE
scale
sheet no. NTS
Location
client
Checked by:
Drawing title
BS1
GEN. HOUSE
BS1
DB-B
TOI/BATH
BWh
GATE HOUSE
scale
BS1 BL3 sheet no. NTS
BS1 dimension
03 date
MAY, 2019
AL1 AL3
AL4
AL4 AL3 AL1
AL3
TOI/BATH
AL4 client
ANTEROOM
AL2
AL4
TOI/BATH
LIVING ROOM
Design : ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
AL4
AL4
AL2
AL1 TOI.
AL1
AL4
TERRACE
dimension
NTS
04 date
MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
Location
AS3
DINING AREA
AS2
STORE
DB-A LOBBY AS4
AS2 job title PROJECT
AP5 AWh2
TOI/BATH
AS1
AS1
client
ANTEROOM AS5
TOI/BATH
AS5 Bedroom 3
Design : ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
LIVING ROOM AP6 Drawn by: ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
AS1 TOI.
AS1
TERRACE
scale
sheet no. NTS
POWER AND FAN CIRCUITS ON THE GROUND FLOOR dimension
05 date
MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
CLOSET CL2
CLOSET
CS1
CP1
CP2 CL2
LOUNGE CL2 CL2 client
CS1
MASTER BEDEOOM
CL1 CL1 LOUNGE
CS2 Design : ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
CS2 CL2
POWER AND FAN CIRCUITS ON THE PENT HOUSE LIGHTING CIRCUITS ON THE PENT HOUSE
scale
sheet no. NTS
dimension
06 date
MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
PEAK DIVERSITY R (W) Y(W) (4) 13A socket outlets should be installed
WAY PHASE LABEL DESCRIPTION & LOCATION POINTS B(W) FUSE RATING/CABLE
LOAD (W) FACTOR between 0.25m and 0.75m from finished floor
SIZE
.level
R AL1 Security lighting circuits 13 1300 0.8 1040 5A, 1.5mm sq pvc/cu cable
(5) All switchs should be installed between
0.75m and 1.15m and 1.0m to 1.15m. for counter
1. Y AL2 Lighting circuits in the living room 12 1200 0.8 960 5A, 1.5mm sq pvc/cu cable kitchen cabinet from the finished floor level.
2. Y 13A Ring mains power SSO in the living room 1500 30A, 2.5mm sq pvc/cu cable (8) The design Engineer assumes no
AS1 5 1.0 1500
and terrace responsibility for works not supervised by him
or his authorised agent.
B AS2 13A Ring mains power SSO in the store, dining 5 1500 1.0 1,500 30A, 2.5mm sq pvc/cu cable
area and kitchen
13A Ring mains power SSO in the bedroom2 and Location
R AS3 attached bath/toi 4 1200 1.0 1200 25A, 2.5mm sq pvc/cu cable
B AS5
13A Ring mains power SSO in bedroom 3 and the 4 1200 0.6 720 25A, 2.5mm sq pvc/cu cable
attached bath/toi
R
Radial power circuit, 2.0hp standing AC unit in
AP1 1 1500 1.0 1500 30A, 4.0mm sq pvc/cu cable
the livig room
Radial power circuit, 1.5hp split AC unit in the 1 job title PROJECT
4. Y AP2 1200 1.0 1200 25A, 4.0mm sq pvc/cu cable
dining area
B
Radial power circuit, 1.5hp split AC unit in 1
AP3 1200 1.0 1200 25A, 4.0mm sq pvc/cu cable
bedroom 2
R AWh1 50ltrs water heater in the shw/wc of bedroom 2 1 1500 1.0 1500 30A, 4.0 mm sq pvc/cu cable 3x6.0mm2
cu/pvc cable
6. Y AWh2 50ltrs water heater in the shw/wc of bedroom 1 1 1500 1.0 1500 30A, 4.0 mm sq pvc/cu cable
3x4.0mm2 Design : ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
B AWh3 50ltrs water heater in the shw/wc of bedroom 3 1 1200 1.0 1500 30A, 4.0mm sq pvc/cu cable cu/pvc cable
Drawn by: ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
R S Spare Circuitry S
3x2.5mm2
cu/pvc cable Checked by:
7. ACCU Radial cooker control unit 1 2500 1.0 2500 45A, 6.0mm sq pvc/cu cable
Y
2x1.5mm2
B S Spare Circuitry cu/pvc cable Drawing title
LOAD DISTRIBUTION FOR THE GROUND
FLOOR
R S Spare Circuitry
5A 5A 5A 5A 30A 30A 25A 25A 25A 30A 25A 25A 25A 25A 25A 30A 30A 30A S 45A S S S S
8. Y S Spare Circuitry R Y B R Y B R Y B R Y B R Y B R Y B R Y B R Y B
S 1 2 3 4 5 6 7 8
B Spare Circuitry
Total Current per phase (A) 39.55 POWER DISTRIBUTION FOR DB-A
scale
sheet no. NTS
dimension
07 date
MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
2x1.5mm2
3. Y S Spare circuitry cu/pvc cable client
B S Spare circuitry
5A 5A 5A 25A 30A S S S S S S S
R S Spare circuitry
R Y B R Y B R Y B R Y B Design : ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
4. Y S Spare circuitry
1 2 3 4 Drawn by: ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
Estimated load per phase (W) 2,000 2,000 1,040 Drawing title
LOAD DISTRIBUTION FOR THE GATE HOUSE
Total Allowed Load (W) 5,040 POWER DISTRIBUTION FOR DB-B
Total Current per phase (A) 8.76
scale
sheet no. NTS
dimension
08 date
MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
B CS1 13A Ring mains SSO in the master bedroom 3 900 1.0 900 25A, 2.5mm sq pvc/cu cable Spares Location
R CS2 13A Ring mains SSO in the lounge 3 900 1.0 900 25A, 2.5mm sq pvc/cu cable
3x4.0mm2
cu/pvc cable
2. Y CS3 13A Ring mains SSO in the lounge, closet and toi 3 900 1.0 900 25A, 4.0mm sq pvc/cu cable
B 15A Radial circuit, 1.5hp split AC unit in the 1200 25A, 4.0mm sq pvc/cu cable
CP1 1 1.0 1200 3x2.5mm2
master bedroom
cu/pvc cable job title PROJECT
15A Radial circuit, 2.0hp split AC unit in the 1.0
R CP2 lounge 1 1500 1500 30A, 4.0mm sq pvc/cu cable
B S Spare circuitry
scale
sheet no. NTS
dimension
09 date
MAY, 2019
08082259483, 08164521557
notes
client
terminal
armoured cu cable Drawing title
45KVA, 3-phase POWER SCHEMATIC DIAGRAM
M 3-Phase meter
From PHCN scale
sheet no. NTS
dimension
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
Location
35mm cu tape
client
Checked by:
Drawing title
LIGHTING ARRESTER SYSTEM
KEY
0.9m
Earth material(0.6mx0.6m)
1.2m
B
1.5m
2m
A&B tape filled with charcoal sheet no.
scale
NTS
and industrial salt
dimension
LIGHTNING ARRESTER SYSTEM. 11 date
LIGHTNING ARRESTER SYSTEM SHALL BE INSTALLED TO ENGINEER SPECIFICATION MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
BEDROOM 1 Location
CLOSET
STORE LOBBY
CAM 7
job title PROJECT
TOI/BATH
CAM 2 MASTER LOUNGE
BEDROOM
CAM 4
ANTEROOM
CAM 5 DISPLAY
TOI/BATH
Bedroom 3 client
LIVING ROOM
CAM 6
Design : ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
TOI.
Drawn by: ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
Checked by:
TERRACE
POSITION OF CCTV MONITOR IN THE MASTER BEDROOM
CAM 1
Drawing title
CCTV CIRCUITS
scale
sheet no. NTS
dimension
12 date
MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
Location
CAM 6 CCTV MONITOR
CAM 7
CAM 8
LOAD DISTRIBUTION FOR -8- CHANNEL DIGITAL VIDEO RECORDER - (DVR)
= CCTV CAMERA
CAM 1 Dome camera installed at front view
Checked by:
CAM 4 Dome camera installed at right view
8 - CHANNEL DVR
scale
sheet no. NTS
dimension
SCHEMATIC DIAGRAM OF 8 - CHANNEL DVR WITH CCTV 13 date
MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
SD F
SD F ZONE 3
F LOUNGE
CLOSET
STORE ZONE 1
LOBBY job title PROJECT
ZONE 2
SD F
TOI/BATH
ANTEROOM
SD F
SD F
TOI/BATH SD F client
SD F MASTER
BEDROOM
SD F
LIVING ROOM Design : ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
Bedroom 3
Drawn by: ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
TOI.
Checked by:
FIRE ALARM CIRCUITS ON THE GROUND FLOOR FIRE ALARM CIRCUITS ON THE PENT HOUSE
scale
sheet no. NTS
dimension
14 date
MAY, 2019
08082259483, 08164521557
notes
(1) Installation is to be done according to the
design and conformity to the rules in the latest
edition of the IEE wiring regulations.
ZONE 3 Location
SPARE
ZONE 4
2.5MM SQR.SINGLE CORE PVC COPPER
INSULATED CABLE.
job title PROJECT
client
Drawn by:
CHARGER FIRE ALARM SWITCH BREAK GLASS TYPE (GENY OR CARTRE). ENGR. E. A NYIEKAA (mnse, mnieee, mnim)
F
FIRE ALARM INDICATOR CONTROL PANEL 4-ZONE
13ASS0
A/C SUPPLY
scale
sheet no. NTS
dimension
15 date
MAY, 2019
08082259483, 08164521557