Signal List
Control System

Client Drawn 2019 11 20 HZX File BMG-204-01-001_R00 FOR SUBMITTAL.XLSX


Plant Checked T 2019 11 20 HJR SaveDate 2019 11 27
Project Nº Checked P 2019 11 20 LYN Similar
Contract Nº Approved 2019 11 20 ZCN Replace
Internal N° =
+
Drawing N° Index Sheet 1
BMG-204-01-001 00 of 1 A4
BMG Unit 1( LCU1) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Voltage Scale Buzzer(Y/N) Rev Remarks
/Alarm(A
1 bi LCU Panel =01CJA10GH001 +01CJA01 S82 <Unit 01> Emergency Push Button ON I DI2110 AA21 1 11 0 60 30 24VDC T
2 bi LCU Panel =01CJA10GH001 +01CJA01 <Unit 01> Master Trip relay active (SUM) I DI2110 AA21 1 11 1 60 30 24VDC A
3 bi LCU Panel =01CJA10GH001 +01CJA02 S02 <Unit 01> Synchronization Automatic I DI2110 AA21 1 11 2 60 30 24VDC
4 bi LCU Panel =01CJA10GH001 +01CJA02 S02 <Unit 01> Synchronization Manual I DI2110 AA21 1 11 3 60 30 24VDC
5 bi LCU Panel =01CJA10GH001 +01CJA02 A01 <Unit 01> SYN3000 Fault I DI2110 AA21 1 11 4 60 30 24VDC A
6 bi LCU Panel =01CJA10GH001 +01CJA01 S01 <Unit 01> Control Mode Remote I DI2110 AA21 1 11 5 60 30 24VDC
7 bi LCU Panel =01CJA10GH001 +01CJA01 S01 <Unit 01> Control Mode Local I DI2110 AA21 1 11 6 60 30 24VDC
8 bi LCU Panel =01CJA10GH001 +01CJA01 S01 <Unit 01> Control Mode Revision I DI2110 AA21 1 11 7 60 30 24VDC
9 bi LCU Panel =01CJA10GH001 +01CJA01 <Unit 01> LCU 220VDC Supply 1 MCB summary fault I DI2110 AA21 1 11 8 60 30 24VDC A
10 bi LCU Panel =01CJA10GH001 +01CJA01 <Unit 01> LCU 220VDC Supply 2 MCB summary fault I DI2110 AA21 1 11 9 60 30 24VDC A
11 bi LCU Panel =01CJA10GH001 +01CJA01 <Unit 01> LCU 24VDC MCB summary fault I DI2110 AA21 1 11 10 60 30 24VDC A
12 bi <Unit 01> Spare I DI2110 AA21 1 11 11 60 30 24VDC T
13 bi <Unit 01> Spare I DI2110 AA21 1 11 12 60 30 24VDC
14 bi <Unit 01> Spare I DI2110 AA21 1 11 13 60 30 24VDC
15 bi <Unit 01> Spare I DI2110 AA21 1 11 14 60 30 24VDC A
16 bi <Unit 01> Local trip reset operated I DI2110 AA21 1 11 15 60 30 24VDC
17 bi temperature indicator =01CJA10GH001 +01CJA02 -P12 <Unit 01> Turbine bearing metal temperature 1 T I DI2110 AA21 1 11 16 60 30 24VDC A
18 bi temperature indicator =01CJA10GH001 +01CJA02 -P12 <Unit 01> Turbine bearing metal temperature 2 T I DI2110 AA21 1 11 17 60 30 24VDC
19 bi temperature indicator =01CJA10GH001 +01CJA02 -P13 <Unit 01> Main Thrust Bearing Pad Temperature High (CT001) T I DI2110 AA21 1 11 18 60 30 24VDC A
20 bi temperature indicator =01CJA10GH001 +01CJA02 -P13 <Unit 01> Main Thrust Bearing Pad Temperature High (CT002) T I DI2110 AA21 1 11 19 60 30 24VDC T
21 bi temperature indicator =01CJA10GH001 +01CJA02 -P14 <Unit 01> Counter Thrust Bearing Pad Temperature High (CT001) T I DI2110 AA21 1 11 20 60 30 24VDC A
22 bi temperature indicator =01CJA10GH001 +01CJA02 -P14 <Unit 01> Counter Thrust Bearing Pad Temperature High (CT002) T I DI2110 AA21 1 11 21 60 30 24VDC T
23 bi temperature indicator =01CJA10GH001 +01CJA02 -P15 <Unit 01> Generator Guide Bearing Shell Temperature High (CT001) T I DI2110 AA21 1 11 22 60 30 24VDC A
24 bi temperature indicator =01CJA10GH001 +01CJA02 -P15 <Unit 01> Generator Guide Bearing Shell Temperature High (CT002) T I DI2110 AA21 1 11 23 60 30 24VDC T
differential pressure
25 bi =01MKA80 +CP301 -S01 <Unit 01> Differential Pressure Switch for Cooling Fan 1 OK I DI2110 AA21 1 11 24 60 30 24VDC
switch
differential pressure
26 bi =01MKA80 +CP302 -S01 <Unit 01> Differential Pressure Switch for Cooling Fan 2 OK I DI2110 AA21 1 11 25 60 30 24VDC
switch
differential pressure
27 bi =01MKA80 +CP303 -S01 <Unit 01> Differential Pressure Switch for Cooling Fan 3 OK I DI2110 AA21 1 11 26 60 30 24VDC
switch
differential pressure
28 bi =01MKA80 +CP304 -S01 <Unit 01> Differential Pressure Switch for Cooling Fan 4 OK I DI2110 AA21 1 11 27 60 30 24VDC
switch
29 bi <Unit 01> Spare I DI2110 AA21 1 11 28 60 30 24VDC
30 bi <Unit 01> Spare I DI2110 AA21 1 11 29 60 30 24VDC
31 bi <Unit 01> Spare I DI2110 AA21 1 11 30 60 30 24VDC
32 bi <Unit 01> Spare I DI2110 AA21 1 11 31 60 30 24VDC
33 bi limit switch =01MKA05 +CG301 -S01 <Unit 01> Limit Switch for Rotor Locking Bolt UNLOCKED I DI2110 AA21 1 11 32 60 30 24VDC STT BLOCK
34 bi limit switch =01MKA05 +CL301 -S01 <Unit 01> Water Level in Bulb high T I DI2110 AA21 1 11 33 60 30 24VDC T
differential pressure
35 bi =01MKD31 +CF301 -S01 <Unit 01> Oil Flow Main Thrust Bearing Low I DI2110 AA21 1 11 34 60 30 24VDC A
switch

36 bi flow indicator =01MKD32 +CF301 -S01 <Unit 01> Oil Flow Generator Guide Bearing Low I DI2110 AA21 1 11 35 60 30 24VDC A

37 bi flow indicator =01MKD33 +CF301 -S01 <Unit 01> Oil Flow Counter Thrust Bearing Low I DI2110 AA21 1 11 36 60 30 24VDC A

38 bi flow indicator =01MED34 +CF301 -S01 <Unit 01> Oil Flow Turbine Guide Bearing Low I DI2110 AA21 1 11 37 60 30 24VDC A

39 bi flow indicator =01MKD34 +CG001 -S01 <Unit 01> Bearing Oil Valve State I DI2110 AA21 1 11 38 60 31 24VDC
40 bi limit switch =01MKD34 +CG001 -S02 <Unit 01> Bearing Oil Valve State I DI2110 AA21 1 11 38 60 31 24VDC
41 bi <Unit 01> Spare I DI2110 AA21 1 11 40 60 30 24VDC
42 bi <Unit 01> Spare
43 bi <Unit 01> Spare I DI2110 AA21 1 11 42 60 30 24VDC
44 bi <Unit 01> Spare I DI2110 AA21 1 11 43 60 30 24VDC
45 bi <Unit 01> Spare I DI2110 AA21 1 11 44 60 30 24VDC

46 bi pressure switch =01MEV10 +CP301 -S01 <Unit 01> Bearing oil pump pressure low I DI2110 AA21 1 11 45 60 30 24VDC A
differential pressure
47 bi =01MEV10 +CP331 -S01 <Unit 01> Main thrust bearing high pressure Oil Filter A I DI2110 AA21 1 11 46 60 30 24VDC A STT BLK
switch
differential pressure
48 bi =01MEV10 +CP332 -S01 <Unit 01> Generator guide bearing high pressure Oil Filter A I DI2110 AA21 1 11 47 60 30 24VDC A STT BLK
switch
differential pressure
49 bi =01MEV10 +CP333 -S01 <Unit 01> Turbine guide bearing high pressure Oil Filter A I DI2110 AA21 1 11 48 60 30 24VDC A STT BLK
switch
50 bi pressure switch =01MEV10 +CP334 -S01 <Unit 01> Generator Guide Bearing High Oil Pressure ok I DI2110 AA21 1 11 49 60 30 24VDC A

51 bi pressure switch =01MEV10 +CP335 -S01 <Unit 01> Turbine Guide Bearing High Oil Pressure ok I DI2110 AA21 1 11 50 60 30 24VDC A
differential pressure
52 bi =01MEV20 +CP341 -S01 <Unit 01> Differential pressure switch Oil filter I DI2110 AA21 1 11 51 60 30 24VDC A
switch
53 bi <Unit 01> Spare I DI2110 AA21 1 11 52 60 30 24VDC
54 bi <Unit 01> Spare I DI2110 AA21 1 11 53 60 30 24VDC

2/38 2019/11/27
BMG Unit 1( LCU1) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Voltage Scale Buzzer(Y/N) Rev Remarks
/Alarm(A
55 bi <Unit 01> Spare I DI2110 AA21 1 11 54 60 30 24VDC
56 bi <Unit 01> Spare I DI2110 AA21 1 11 55 60 30 24VDC
57 bi <Unit 01> Spare I DI2110 AA21 1 11 56 60 30 24VDC A STT BLK
58 bi pressure switch =01PCB31 +CP002 -S01 <Unit 01> Pressure after cooling water pumps Low A I DI2110 AA21 1 11 57 60 30 24VDC A
59 bi pressure switch =01PCB31 +CP001 -S01 <Unit 01> Pressure in Cooling System Low A I DI2110 AA21 1 11 58 60 30 24VDC A
60 bi flow indicator =01PCB20 +CF301 -S01 <Unit 01> Cooling Water Flow Oil Cooler Low I DI2110 AA21 1 11 59 60 30 24VDC T
61 bi flow indicator =01PCB32 +CF301 -S01 <Unit 01> Cooling Water Flow Generator Low I DI2110 AA21 1 11 60 60 30 24VDC T
62 bi <Unit 01> Spare I DI2110 AA21 1 11 61 60 30 24VDC
63 bi <Unit 01> Spare I DI2110 AA21 1 11 62 60 30 24VDC
64 bi <Unit 01> Spare I DI2110 AA21 1 11 63 60 30 24VDC

65 bi pressure switch =01MKA91 +CP301 -S01 <Unit 01> Brake Plant Pressure Low I DI2110 AA25 1 11 0 61 30 24VDC
66 bi limit switch =01MKA90 +CG311 -S01 <Unit 01> Brake Calliper 1 OFF I DI2110 AA25 1 11 1 61 30 24VDC
67 bi limit switch =01MKA90 +CG321 -S01 <Unit 01> Brake Calliper 2 OFF I DI2110 AA25 1 11 2 61 30 24VDC
68 bi limit switch =01MKA90 +CG312 -S01 <Unit 01> Brake Lining Abrasion 1 A I DI2110 AA25 1 11 3 61 30 24VDC A
69 bi limit switch =01MKA90 +CG322 -S01 <Unit 01> Brake Lining Abrasion 2 A I DI2110 AA25 1 11 4 61 30 24VDC A
70 bi <Unit 01> Spare I DI2110 AA25 1 11 5 61 30 24VDC
71 bi =01MEA20 +CG111 -S01 XG01 <Unit 01> guide vane full closed I DI2110 AA25 1 11 6 61 30 24VDC
72 bi =01MEA20 +CG112 -S01 XG01 <Unit 01> guide vane no load position I DI2110 AA25 1 11 7 61 30 24VDC
73 bi <Unit 01> Spare I DI2110 AA25 1 11 8 61 30 24VDC
74 bi =01MEA20 +CG001 -S01 <Unit 01> GV Servomotor Lock NOT active I DI2110 AA25 1 11 9 61 30 24VDC
75 bi =01MEW10 +CF101 -S01 <Unit 01> turbine sealing water flushing flow measuring flow low A I DI2110 AA25 1 11 10 61 30 24VDC
76 bi =01MEW10 +CF102 -S01 <Unit 01> turbine sealing water processing flow measuring flow high A I DI2110 AA25 1 11 11 61 30 24VDC
77 bi =01MEW10 +CF103 -S01 <Unit 01> turbine sealing water leakage flow measuring flow high A I DI2110 AA25 1 11 12 61 30 24VDC
78 bi =01MEW45 +CP101 -S01 XG51 <Unit 01> Standstill Sealing Pressure Low (Seal NOT applied) I DI2110 AA25 1 11 13 61 30 24VDC
79 bi =01MEW45 +CP101 -S01 XG51 <Unit 01> Standstill Sealing Pressure High (Seal applied) I DI2110 AA25 1 11 14 61 30 24VDC
80 bi <Unit 01> Spare I DI2110 AA25 1 11 15 61 30 24VDC
81 bi <Unit 01> Spare I DI2110 AA25 1 11 16 61 30 24VDC
82 bi =MEW30 +CG001 <Unit 01> Shaft sealing fault I DI2110 AA25 1 11 17 61 30 24VDC
83 bi =MEW30 +CG001 <Unit 01> Shaft sealing fault I DI2110 AA25 1 11 18 61 30 24VDC
84 bi =MEW30 +CG001 <Unit 01> Shaft sealing fault I DI2110 AA25 1 11 19 61 30 24VDC
85 bi =MEW30 +CG002 <Unit 01> Shaft sealing fault I DI2110 AA25 1 11 20 61 30 24VDC
86 bi =MEW30 +CG002 <Unit 01> Shaft sealing fault I DI2110 AA25 1 11 21 61 30 24VDC
87 bi =MEW30 +CG002 <Unit 01> Shaft sealing fault I DI2110 AA25 1 11 22 61 30 24VDC
88 bi MEA60 CG301 <Unit 01> Man hole fault I DI2110 AA25 1 11 23 61 30 24VDC
89 bi <Unit 01> Spare I DI2110 AA25 1 11 24 61 30 24VDC
90 bi <Unit 01> Spare I DI2110 AA25 1 11 25 61 30 24VDC
91 bi level switch MEX16 CL311 S01 <Unit 01> Piston accumulator oil level too low T I DI2110 AA25 1 11 26 61 30 24VDC
92 bi pressure switch MEX16 CP302 S01 <Unit 01> Actuator tank pressure too low T I DI2110 AA25 1 11 27 61 30 24VDC
93 bi level switch =01MEX10 CL302 S01 <Unit 01> Governor sump tank water in oil I DI2110 AA25 1 11 28 61 30 24VDC
94 bi level switch =01MEX10 CL301 S01 <Unit 01> Governor sump tank oil level too low T I DI2110 AA25 1 11 29 61 30 24VDC A
95 bi differencial switch =01MEX10 CP301 S01 <Unit 01> Return oil filter 1 clogged I DI2110 AA25 1 11 30 61 30 24VDC A
96 bi differencial switch =01MEX10 CP302 S01 <Unit 01> Return oil filter 2 clogged I DI2110 AA25 1 11 31 61 30 24VDC A
97 bi differencial switch MEX14 CP102 S01 <Unit 01> Oil circulting filter clogged I DI2110 AA25 1 11 32 61 30 24VDC A
98 bi differencial switch MEX20 CP302 S01 <Unit 01> Pilot oil filter clogged I DI2110 AA25 1 11 33 61 30 24VDC A
99 bi level switch =01MEX20 CP301 S01 <Unit 01> Hydr.gov.Pilot pressure available I DI2110 AA25 1 11 34 61 30 24VDC A
100 bi level switch MEX70 CP301 S01 <Unit 01> ESD energized (no shutdown) I DI2110 AA25 1 11 35 61 30 24VDC
101 bi position switch MEA70 CS001 S01 <Unit 01> Hydraulic overspeed valve activated T I DI2110 AA25 1 11 36 61 30 24VDC T
102 bi level switch =01MEX18 CL301 S01 <Unit 01> Governor Leakage oil tank oil level too low I DI2110 AA25 1 11 37 61 30 24VDC A
103 bi level switch =01MEX18 CL302 S01 <Unit 01> Governor Leakage oil tank water detected I DI2110 AA25 1 11 38 61 30 24VDC
104 bi Water alarm unit MEX20 CP301 S01 <Unit 01> Stop valve activated I DI2110 AA25 1 11 39 61 30 24VDC A
105 bi Level Switch =01MEA30 CL101 (XG01) S01 <Unit 01> Runner water high tank level too high I DI2110 AA25 1 11 40 61 30 24VDC A
106 bi Level Switch =01MEA30 CL101 (XG04) S01 <Unit 01> Runner water high tank level low I DI2110 AA25 1 11 41 61 30 24VDC A
107 bi Level Switch =01MEA30 CL102 (XG03) S01 <Unit 01> Runner water high tank level high I DI2110 AA25 1 11 42 61 30 24VDC A
108 bi Level Switch =01MEA30 CL102 (XG02) S01 <Unit 01> Runner water high tank level too low I DI2110 AA25 1 11 43 61 30 24VDC A
109 bi <Unit 01> Hydraulic Overspeed Valve Reset Position I DI2110 AA25 1 11 44 61 30 24VDC
110 bi MEX14 CF301 -S01 XG02 <Unit 01> Governor oil bypass filtration cooling water flow too low I DI2110 AA25 1 11 45 61 30 24VDC
111 bi MEX14 CF302 -S01 XG06 <Unit 01> Governor oil bypass filtration cooling water flow low I DI2110 AA25 1 11 46 61 30 24VDC
112 bi MEX20 CF301 -S01 XG01 <Unit 01> governor accumulator isolating valve open I DI2110 AA25 1 11 47 61 30 24VDC
113 bi MEX30 CP301 -S01 XG01 <Unit 01> governor oil head lubrication valve I DI2110 AA25 1 11 48 61 30 24VDC
114 bi <Unit 01> Spare I DI2110 AA25 1 11 49 61 30 24VDC
115 bi <Unit 01> Spare I DI2110 AA25 1 11 50 61 30 24VDC
116 bi I DI2110 AA25 1 11 51 61 30 24VDC
117 bi <Unit 01> Spare I DI2110 AA25 1 11 52 61 30 24VDC
118 bi <Unit 01> Spare I DI2110 AA25 1 11 53 61 30 24VDC
119 bi <Unit 01> Spare I DI2110 AA25 1 11 54 61 30 24VDC
120 bi <Unit 01> Spare I DI2110 AA25 1 11 55 61 30 24VDC

3/38 2019/11/27
BMG Unit 1( LCU1) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Voltage Scale Buzzer(Y/N) Rev Remarks
/Alarm(A
121 bi <Unit 01> Spare I DI2110 AA25 1 11 56 61 30 24VDC
122 bi <Unit 01> Spare I DI2110 AA25 1 11 57 61 30 24VDC
123 bi <Unit 01> Speed>115% from D521 I DI2110 AA25 1 11 58 61 30 24VDC
124 bi <Unit 01> Speed<10% from D521 I DI2110 AA25 1 11 59 61 30 24VDC
125 bi <Unit 01> Spare I DI2110 AA25 1 11 60 61 30 24VDC
126 bi <Unit 01> Spare I DI2110 AA25 1 11 61 61 30 24VDC
127 bi <Unit 01> Spare I DI2110 AA25 1 11 62 61 30 24VDC
128 bi <Unit 01> Spare I DI2110 AA25 1 11 63 61 30 24VDC

129 bi <Unit 01> Spare I DI2110 AA29 1 11 0 62 30 24VDC


130 bi <Unit 01> Spare I DI2110 AA29 1 11 1 62 30 24VDC
131 bi =01BAA20GD001 +01BAA20 Q11 <Unit 01> 6.3kV GCB Q01 State Opened I DI2110 AA29 1 11 2 62 31 24VDC
132 bi =01BAA20GD001 +01BAA20 Q11 <Unit 01> 6.3kV GCB Q01 State Closed I DI2110 AA29 1 11 2 62 31 24VDC
133 bi BAA20 GS100 XB08 <Unit 01> 6.3kV GCB truck Position isolated position I DI2110 AA29 1 11 4 62 31 24VDC A
134 bi BAA20 GS100 XB08 <Unit 01> 6.3kV GCB truck Position service position I DI2110 AA29 1 11 4 62 31 24VDC
135 bi BAA20 GS100 XM01 <Unit 01> 6.3kV GCB Q01 gas pressure low I DI2110 AA29 1 11 6 62 30 24VDC A
136 bi BAA20 GS100 XM02 <Unit 01> 6.3kV GCB Q01 gas pressure insufficient I DI2110 AA29 1 11 7 62 30 24VDC A
137 bi BAA20 GS100 XB07 <Unit 01> 6.3kV GCB Q01 spring charged I DI2110 AA29 1 11 8 62 30 24VDC A
138 bi BAA20 GS100 XB22 <Unit 01> 6.3kV GCB control switch Remote I DI2110 AA29 1 11 9 62 30 24VDC
139 bi =01BAA10GD001 +01BAA10 Q13 <Unit 01> 6.3kV Gen. side earthing switch opened I DI2110 AA29 1 11 10 62 31 24VDC
140 bi =01BAA10GD001 +01BAA10 Q13 <Unit 01> 6.3kV Gen. side earthing switch closed I DI2110 AA29 1 11 11 62 31 24VDC
141 bi =01BAA20GD001 +01BAA20 Q12 <Unit 01> 6.3kV MT side earthing switch opened I DI2110 AA29 1 11 12 62 31 24VDC
142 bi =01BAA20GD001 +01BAA20 Q12 <Unit 01> 6.3kV MT side earthing switch closed I DI2110 AA29 1 11 13 62 31 24VDC
143 bi <Unit 01> Spare I DI2110 AA29 1 11 14 62 30 24VDC
144 bi BAA10 GH001 XB57 <Unit 01> 6.3kV BAA10/20 MCB summary fault I DI2110 AA29 1 11 15 62 30 24VDC A
145 bi =01BAA10GD001 +01BAA10 <Unit 01> EXT fuses blown I DI2110 AA29 1 11 16 62 30 24VDC
146 bi =01BAA20GD001 +01BAA20 <Unit 01> GCB cubicle syn. PT MCB status I DI2110 AA29 1 11 17 62 30 24VDC
147 bi <Unit 01> Spare I DI2110 AA29 1 11 18 62 30 24VDC
148 bi <Unit 01> Spare I DI2110 AA29 1 11 19 62 30 24VDC
149 bi <Unit 01> Spare I DI2110 AA29 1 11 20 62 30 24VDC
150 bi <Unit 01> Spare I DI2110 AA29 1 11 21 62 30 24VDC
151 bi <Unit 01> Spare I DI2110 AA29 1 11 22 62 30 24VDC
152 bi <Unit 01> Spare I DI2110 AA29 1 11 23 62 30 24VDC
153 bi <Unit 01> Spare I DI2110 AA29 1 11 24 62 30 24VDC
154 bi <Unit 01> Spare I DI2110 AA29 1 11 25 62 30 24VDC
155 bi <Unit 01> Spare I DI2110 AA29 1 11 26 62 30 24VDC
156 bi =01MKC10DE001 <Unit 01> Excitation Ready for Start I DI2110 AA29 1 11 27 62 30 24VDC
157 bi =01MKC10DE001 <Unit 01> Excitation Alarm I DI2110 AA29 1 11 28 62 30 24VDC A
158 bi =01MKC10DE001 <Unit 01> Excitation Trip I DI2110 AA29 1 11 29 62 30 24VDC T
159 bi =01MKC10DE001 <Unit 01> Spare I DI2110 AA29 1 11 30 62 30 24VDC A
160 bi =01MKC10DE001 <Unit 01> Spare I DI2110 AA29 1 11 31 62 30 24VDC A
161 bi =01MKC10DE001 <Unit 01> Excitation regulator fault I DI2110 AA29 1 11 32 62 30 24VDC A
162 bi =01MKC10DE001 <Unit 01> Excitation Automatic I DI2110 AA29 1 11 33 62 30 24VDC
163 bi =01MKC10DE001 <Unit 01> Excitation FCB ON I DI2110 AA29 1 11 34 62 31 24VDC
164 bi =01MKC10DE001 <Unit 01> Excitation FCB OFF I DI2110 AA29 1 11 34 62 31 24VDC
165 bi =01MKC10DE001 <Unit 01> Excitation Remote I DI2110 AA29 1 11 36 62 30 24VDC
166 bi <Unit 01> Excitation Local I DI2110 AA29 1 11 37 62 30 24VDC
167 bi <Unit 01> Excitation Manual I DI2110 AA29 1 11 38 62 30 24VDC
168 bi <Unit 01> Excitation MVAr Control ON I DI2110 AA29 1 11 39 62 30 24VDC
169 bi <Unit 01> Excitation AVR Upper Limit Active I DI2110 AA29 1 11 40 62 30 24VDC
170 bi <Unit 01> Excitation AVR Lower Limit Active I DI2110 AA29 1 11 41 62 30 24VDC
171 bi <Unit 01> Excitation ON I DI2110 AA29 1 11 42 62 30 24VDC
172 bi <Unit 01> Excitation OFF I DI2110 AA29 1 11 43 62 30 24VDC
173 bi <Unit 01> Spare I DI2110 AA29 1 11 44 62 30 24VDC
174 bi <Unit 01> Spare I DI2110 AA29 1 11 45 62 30 24VDC
175 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer AC power supply failure I DI2110 AA29 1 11 46 62 30 24VDC
176 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan all stop failure 20min I DI2110 AA29 1 11 47 62 30 24VDC
177 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan all stop failure 60min I DI2110 AA29 1 11 48 62 30 24VDC
178 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan all local I DI2110 AA29 1 11 49 62 30 24VDC
179 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan all remote I DI2110 AA29 1 11 50 62 30 24VDC
180 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan group 1 auto I DI2110 AA29 1 11 51 62 30 24VDC
181 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan group 1 manual I DI2110 AA29 1 11 52 62 30 24VDC
182 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan group 2 auto I DI2110 AA29 1 11 53 62 30 24VDC
183 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan group 2 manual I DI2110 AA29 1 11 54 62 30 24VDC
184 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan group 1 running/stop I DI2110 AA29 1 11 55 62 30 24VDC
185 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan group 2 running/stop I DI2110 AA29 1 11 56 62 30 24VDC
186 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan group 1 failure I DI2110 AA29 1 11 57 62 30 24VDC

4/38 2019/11/27
BMG Unit 1( LCU1) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Voltage Scale Buzzer(Y/N) Rev Remarks
/Alarm(A
187 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer cooling fan group 2 failure I DI2110 AA29 1 11 58 62 30 24VDC A
188 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer tap position +5% I DI2110 AA29 1 11 59 62 30 24VDC T
189 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer tap position +2.5% I DI2110 AA29 1 11 60 62 30 24VDC A
190 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer tap position rated I DI2110 AA29 1 11 61 62 30 24VDC T
191 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer tap position -2.5% I DI2110 AA29 1 11 62 62 30 24VDC
192 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer tap position -5% I DI2110 AA29 1 11 63 62 30 24VDC

193 bi <Unit 01> DEVICE READY I DI2110 AA33 1 11 0 63 30 24VDC A


194 bi <Unit 01> DEVICE FAULT I DI2110 AA33 1 11 1 63 30 24VDC
195 bi <Unit 01> VOLTAGE SUPPLY FUSE OFF I DI2110 AA33 1 11 2 63 30 24VDC A
196 bi <Unit 01> GCB TRIP CIRCUIT FAILURE I DI2110 AA33 1 11 3 63 30 24VDC A
197 bi <Unit 01> FCB TRIP CIRCUIT FAILURE I DI2110 AA33 1 11 4 63 30 24VDC A
198 bi <Unit 01> MTR CB TRIP CIRCUIT FAILURE I DI2110 AA33 1 11 5 63 30 24VDC A
199 bi <Unit 01> CONTRAL VOLTAGE FAILURE I DI2110 AA33 1 11 6 63 30 24VDC T
200 bi <Unit 01> Spare I DI2110 AA33 1 11 7 63 30 24VDC A
201 bi <Unit 01> Spare I DI2110 AA33 1 11 8 63 30 24VDC
202 bi <Unit 01> Spare I DI2110 AA33 1 11 9 63 30 24VDC
203 bi <Unit 01> Unit aux.board AC automatic change over AUTO I DI2110 AA33 1 11 10 63 30 24VDC
204 bi <Unit 01> Spare I DI2110 AA33 1 11 11 63 30 24VDC
205 bi <Unit 01> Spare I DI2110 AA33 1 11 12 63 30 24VDC
206 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer buchholz relay alarm I DI2110 AA33 1 11 13 63 30 24VDC
207 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer buchholz relay trip 1 I DI2110 AA33 1 11 14 63 30 24VDC
208 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer buchholz relay trip 2 I DI2110 AA33 1 11 15 63 30 24VDC
209 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer pressure relief trip I DI2110 AA33 1 11 16 63 30 24VDC
210 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer oil level low alarm I DI2110 AA33 1 11 17 63 30 24VDC
211 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer oil level high alarm I DI2110 AA33 1 11 18 63 30 24VDC
212 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer winding temperature alarm 105℃ I DI2110 AA33 1 11 19 63 30 24VDC
213 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer winding temperature trip 120℃ I DI2110 AA33 1 11 20 63 30 24VDC
214 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer oil temperature 1 alarm 85℃ I DI2110 AA33 1 11 21 63 30 24VDC
215 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer oil temperature 1 trip 100℃ I DI2110 AA33 1 11 22 63 30 24VDC
216 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer oil temperature 2 alarm 85℃ I DI2110 AA33 1 11 23 63 30 24VDC
217 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer oil temperature 2 trip 100℃ I DI2110 AA33 1 11 24 63 30 24VDC
218 bi =01BAT10GH001 +01BAT10 <Unit 01> main transformer OLTC trip CB I DI2110 AA33 1 11 25 63 30 24VDC
219 bi <Unit 01> Spare I DI2110 AA33 1 11 26 63 30 24VDC
220 bi <Unit 01> Spare I DI2110 AA33 1 11 27 63 30 24VDC
221 bi =01BAB10GD001 +01BAB10 <Unit 01> Gen. neutral grounding cubicle power supply MCB closed I DI2110 AA33 1 11 28 63 30 24VDC
222 bi =01BAB10GD001 +01BAB10 <Unit 01> Gen. neutral grounding cubicle MCB trip I DI2110 AA33 1 11 29 63 30 24VDC
223 bi =01BAB10GD001 +01BAB10 <Unit 01> Gen. neutral grounding cubicle control power testing I DI2110 AA33 1 11 30 63 30 24VDC
224 bi <Unit 01> Spare I DI2110 AA33 1 11 31 63 30 24VDC
225 bi <Unit 01> Spare I DI2110 AA33 1 11 32 63 30 24VDC
226 bi <Unit 01> Spare I DI2110 AA33 1 11 33 63 30 24VDC
227 bi <Unit 01> Spare I DI2110 AA33 1 11 34 63 30 24VDC
228 bi <Unit 01> Spare I DI2110 AA33 1 11 35 63 30 24VDC A
229 bi <Unit 01> Spare I DI2110 AA33 1 11 36 63 30 24VDC A
230 bi <Unit 01> Spare I DI2110 AA33 1 11 37 63 30 24VDC A
231 bi <Unit 01> Spare I DI2110 AA33 1 11 38 63 30 24VDC
232 bi <Unit 01> Spare I DI2110 AA33 1 11 39 63 30 24VDC
233 bi <Unit 01> Spare I DI2110 AA33 1 11 40 63 30 24VDC
234 bi <Unit 01> Spare I DI2110 AA33 1 11 41 63 30 24VDC
235 bi <Unit 01> Spare I DI2110 AA33 1 11 42 63 30 24VDC
236 bi <Unit 01> Spare I DI2110 AA33 1 11 43 63 30 24VDC
237 bi <Unit 01> Spare I DI2110 AA33 1 11 44 63 30 24VDC
238 bi <Unit 01> Spare I DI2110 AA33 1 11 45 63 30 24VDC
239 bi <Unit 01> Spare I DI2110 AA33 1 11 46 63 30 24VDC
240 bi <Unit 01> Spare I DI2110 AA33 1 11 47 63 30 24VDC
241 bi <Unit 01> Spare I DI2110 AA33 1 11 48 63 30 24VDC
242 bi <Unit 01> Spare I DI2110 AA33 1 11 49 63 30 24VDC
243 bi <Unit 01> Spare I DI2110 AA33 1 11 50 63 30 24VDC
244 bi <Unit 01> Spare I DI2110 AA33 1 11 51 63 30 24VDC
245 bi <Unit 01> Spare I DI2110 AA33 1 11 52 63 30 24VDC
246 bi <Unit 01> Spare I DI2110 AA33 1 11 53 63 30 24VDC
247 bi <Unit 01> Spare I DI2110 AA33 1 11 54 63 30 24VDC
248 bi <Unit 01> Spare I DI2110 AA33 1 11 55 63 30 24VDC
249 bi <Unit 01> Spare I DI2110 AA33 1 11 56 63 30 24VDC
250 bi <Unit 01> Spare I DI2110 AA33 1 11 57 63 30 24VDC
251 bi <Unit 01> Spare I DI2110 AA33 1 11 58 63 30 24VDC
252 bi <Unit 01> Spare I DI2110 AA33 1 11 59 63 30 24VDC

5/38 2019/11/27
BMG Unit 1( LCU1) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Voltage Scale Buzzer(Y/N) Rev Remarks
/Alarm(A
253 bi <Unit 01> Spare I DI2110 AA33 1 11 60 63 30 24VDC
254 bi <Unit 01> Spare I DI2110 AA33 1 11 61 63 30 24VDC
255 bi <Unit 01> Spare I DI2110 AA33 1 11 62 63 30 24VDC
256 bi <Unit 01> Spare I DI2110 AA33 1 11 63 63 30 24VDC

257 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Water Pump 1 ON I DI2110 AA45 1 11 0 64 30 24VDC
258 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Water Pump 2 ON I DI2110 AA45 1 11 1 64 30 24VDC
259 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> High Pressure Oil Pump 1 (AC) ON I DI2110 AA45 1 11 2 64 30 24VDC
260 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> High Pressure Oil Pump 2 (AC) ON I DI2110 AA45 1 11 3 64 30 24VDC
261 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Bearing Oil Pump 1 ON I DI2110 AA45 1 11 4 64 30 24VDC
262 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Bearing Oil Pump 2 ON I DI2110 AA45 1 11 5 64 30 24VDC
263 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Fans1~2 ON I DI2110 AA45 1 11 6 64 30 24VDC
264 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Fans3~4 ON I DI2110 AA45 1 11 7 64 30 24VDC
265 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Fan for Oil Vapour Exhaust ON I DI2110 AA45 1 11 8 64 30 24VDC
266 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor Oil pump 1 ON I DI2110 AA45 1 11 9 64 30 24VDC
267 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor Oil pump 2 ON I DI2110 AA45 1 11 10 64 30 24VDC
268 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor oil Leakage oil pump 1 ON I DI2110 AA45 1 11 11 64 30 24VDC
269 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor oil Leakage oil pump 2 ON I DI2110 AA45 1 11 12 64 30 24VDC
270 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor oil Circulation pump ON I DI2110 AA45 1 11 13 64 30 24VDC
271 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Fan for carbon dust exhaust ON I DI2110 AA45 1 11 14 64 30 24VDC
272 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Spare I DI2110 AA45 1 11 15 64 30 24VDC
273 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Mist Separator for Oil Head ON I DI2110 AA45 1 11 16 64 30 24VDC
274 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Oil heating motor 1 in bearing oil sump tank ON I DI2110 AA45 1 11 17 64 30 24VDC
275 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Oil heating motor 2 in bearing oil sump tank ON I DI2110 AA45 1 11 18 64 30 24VDC
276 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Oil heating motor 3 in bearing oil sump tank ON I DI2110 AA45 1 11 19 64 30 24VDC
277 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Oil heating motor 4 in bearing oil sump tank ON I DI2110 AA45 1 11 20 64 30 24VDC
278 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Oil heating motor 1 in bearing oil high tank ON I DI2110 AA45 1 11 21 64 30 24VDC
279 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Oil heating motor 2 in bearing oil high tank ON I DI2110 AA45 1 11 22 64 30 24VDC
280 bi <Unit 01> Spare I DI2110 AA45 1 11 23 64 30 24VDC
281 bi <Unit 01> Spare I DI2110 AA45 1 11 24 64 30 24VDC
282 bi <Unit 01> Spare I DI2110 AA45 1 11 25 64 30 24VDC
283 bi <Unit 01> Spare I DI2110 AA45 1 11 26 64 30 24VDC
284 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Water Pump 1 Fault I DI2110 AA45 1 11 27 64 30 24VDC A
285 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Water Pump 2 Fault I DI2110 AA45 1 11 28 64 30 24VDC A
286 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Bearing High Pressure Oil Pump 1 Fault I DI2110 AA45 1 11 29 64 30 24VDC A
287 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Bearing High Pressure Oil Pump 2 Fault I DI2110 AA45 1 11 30 64 30 24VDC A
288 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Bearing Oil Pump 1 Fault I DI2110 AA45 1 11 31 64 30 24VDC A
289 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Bearing Oil Pump 2 Fault I DI2110 AA45 1 11 32 64 30 24VDC A
290 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Fans1~2 Fault I DI2110 AA45 1 11 33 64 30 24VDC A
291 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Fans3~4 Fault I DI2110 AA45 1 11 34 64 30 24VDC A
292 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Bearing oil tank Oil dust exhaust Fault I DI2110 AA45 1 11 35 64 30 24VDC A
293 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor Oil pump 1 Fault I DI2110 AA45 1 11 36 64 30 24VDC A
294 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor Oil pump 2 Fault I DI2110 AA45 1 11 37 64 30 24VDC A
295 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor oil Leakage oil pump 1 Fault I DI2110 AA45 1 11 38 64 30 24VDC A
296 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor oil Leakage oil pump 2 Fault I DI2110 AA45 1 11 39 64 30 24VDC A
297 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Governor oil Circulation pump Fault I DI2110 AA45 1 11 40 64 30 24VDC A
298 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Fan for carbon dust exhaust Fault I DI2110 AA45 1 11 41 64 30 24VDC A
299 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Spare I DI2110 AA45 1 11 42 64 30 24VDC A
300 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Mist Separator for Oil Head Fault I DI2110 AA45 1 11 43 64 30 24VDC A
<Unit 01> Oil heating motor 1-4 in bearing oil sump tank Fault
301 bi auxiliary cubicle =01ASU10GH001 +01ASU01 I DI2110 AA45 1 11 44 64 30 24VDC A
(Summary)
<Unit 01> Oil heating motor 1/2 in bearing oil high tank Fault
302 bi auxiliary cubicle =01ASU10GH001 +01ASU01 I DI2110 AA45 1 11 45 64 30 24VDC A
(Summary)
303 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Auxiliary Cubicle AC Voltage Failure I DI2110 AA45 1 11 46 64 30 24VDC A
304 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Auxiliary Cubicle DC Voltage Failure I DI2110 AA45 1 11 47 64 30 24VDC A
305 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Aux.board Multifunction Meter Supply Failure I DI2110 AA45 1 11 48 64 30 24VDC A
306 bi auxiliary cubicle =01ASU10GH001 +01ASU01 <Unit 01> Auxiliary Cubicle Control Switches Auto Position I DI2110 AA45 1 11 49 64 30 24VDC
307 bi <Unit 01> Spare I DI2110 AA45 1 11 50 64 30 24VDC
308 bi <Unit 01> Spare I DI2110 AA45 1 11 51 64 30 24VDC
309 bi <Unit 01> 220/24V Converter 1/2 OK (SUM) I DI2110 AA45 1 11 52 64 30 24VDC
310 bi <Unit 01> Unit control board Light/Heat Supply Fault I DI2110 AA45 1 11 53 64 30 24VDC
311 bi <Unit 01> 220/24V Converter 3/4 OK (SUM) I DI2110 AA45 1 11 54 64 30 24VDC
312 bi <Unit 01> 220/24V Converter 5/6 OK (SUM) I DI2110 AA45 1 11 55 64 30 24VDC
313 bi <Unit 01> Standstill Heater Power Fault I DI2110 AA45 1 11 56 64 30 24VDC A
314 bi <Unit 01> Bearing Oil Valve Power Fault I DI2110 AA45 1 11 57 64 30 24VDC A
315 bi <Unit 01> Auxiliary 400VAC 1 Voltage Ok I DI2110 AA45 1 11 58 64 30 24VDC
316 bi <Unit 01> Auxiliary 400VAC 2 Voltage Ok I DI2110 AA45 1 11 59 64 30 24VDC
317 bi <Unit 01> Spare I DI2110 AA45 1 11 60 64 30 24VDC
318 bi <Unit 01> Spare I DI2110 AA45 1 11 61 64 30 24VDC

6/38 2019/11/27
BMG Unit 1( LCU1) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Voltage Scale Buzzer(Y/N) Rev Remarks
/Alarm(A
319 bi <Unit 01> Spare I DI2110 AA45 1 11 62 64 30 24VDC
320 bi <Unit 01> Spare I DI2110 AA45 1 11 63 64 30 24VDC

7/38 2019/11/27
BMG Unit 1( LCU1) / Digital Outputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Remarks
Unit 1 auxiliary "On" precondition
1 bo =01ASU10GH001 +01ASU01 =01PCB31 AP001 <Unit 01> Generator Cooling Water Pump 1 OFF (DO Output ) O DO2201 AA45 1 11 0 65 30 30 24VDC
before start "Off" after
cubicle
Unit 1 auxiliary 10 min follow up
2 bo =01ASU10GH001 +01ASU01 =01PCB31 AP001 <Unit 01> Generator Cooling Water Pump 1 ON (DO Output ) O DO2201 AA45 1 11 1 65 30 30 24VDC
cubicle operation if n=0
Unit 1 auxiliary "On" precondition
3 bo =01ASU10GH001 +01ASU01 =01PCB31 AP002 <Unit 01> Generator Cooling Water Pump 2 OFF (DO Output ) O DO2201 AA45 1 11 2 65 30 30 24VDC
before start "Off" after
cubicle
Unit 1 auxiliary 10 min follow up
4 bo =01ASU10GH001 +01ASU01 =01PCB31 AP002 <Unit 01> Generator Cooling Water Pump 2 ON (DO Output ) O DO2201 AA45 1 11 3 65 30 30 24VDC
cubicle operation if n=1
Unit 1 auxiliary
5 bo =01ASU10GH001 +01ASU01 =01MEV10 AP031 <Unit 01> Bearing High Pressure Oil Pump OFF (DO Output ) O DO2201 AA45 1 11 4 65 30 30 24VDC
cubicle
Unit 1 auxiliary
6 bo =01ASU10GH001 +01ASU01 =01MEV10 AP031 <Unit 01> Bearing High Pressure Oil Pump ON (DO Output ) O DO2201 AA45 1 11 5 65 30 30 24VDC “On“ precondition before, start, up to 90%
cubicle
speed, “On” at 90 % speed during, shut
Unit 1 auxiliary
7 bo =01ASU10GH001 +01ASU01 <Unit 01> Spare (DO Output ) O DO2201 AA45 1 11 6 65 30 30 24VDC down till n=0
cubicle
Unit 1 auxiliary
8 bo =01ASU10GH001 +01ASU01 =01MEV10 AP032 <Unit 01> Bearing High Pressure Oil Pump 2 Leading (DO Output ) O DO2201 AA45 1 11 7 65 30 30 24VDC
cubicle
Unit 1 auxiliary
9 bo =01ASU10GH001 +01ASU01 =01MEV10 AP001 <Unit 01> Bearing Oil Pump 1 OFF (DO Output ) O DO2201 AA45 1 11 8 65 30 30 24VDC
cubicle
Unit 1 auxiliary
10 bo =01ASU10GH001 +01ASU01 =01MEV10 AP001 <Unit 01> Bearing Oil Pump 1 ON (DO Output ) O DO2201 AA45 1 11 9 65 30 30 24VDC
On“ precondition, before start, “Off“ after
cubicle
Unit 1 auxiliary shut down (n=0)
11 bo =01ASU10GH001 +01ASU01 =01MEV10 AP002 <Unit 01> Bearing Oil Pump 2 OFF (DO Output ) O DO2201 AA45 1 11 10 65 30 30 24VDC
cubicle
Unit 1 auxiliary
12 bo =01ASU10GH001 +01ASU01 =01MEV10 AP002 <Unit 01> Bearing Oil Pump 2 ON (DO Output ) O DO2201 AA45 1 11 11 65 30 30 24VDC
cubicle
“On” precondition, before start
Unit 1 auxiliary =01MKA80 AN011, Operation controlled by =MKJ10
13 bo =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Fans1~2 OFF (DO Output ) O DO2201 AA45 1 11 12 65 30 30 24VDC
cubicle =01MKA80 AN021 CP001-S01, 10 min follow up
operation if n =0
“On” precondition, before start
Unit 1 auxiliary =01MKA80 AN011, Operation controlled by =MKJ10
14 bo =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Fans1~2 ON (DO Output ) O DO2201 AA45 1 11 13 65 30 30 24VDC
cubicle =01MKA80 AN021 CP002-S01, 10 min follow up
operation if n =0
“On” precondition, before start
Unit 1 auxiliary =01MKA80 AN031, Operation controlled by =MKJ10
15 bo =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Fans3~4 OFF (DO Output ) O DO2201 AA45 1 11 14 65 30 30 24VDC
cubicle =01MKA80 AN041 CP003-S01, 10 min follow up
operation if n =0
“On” precondition, before start
Unit 1 auxiliary =01MKA80 AN031, Operation controlled by =MKJ10
16 bo =01ASU10GH001 +01ASU01 <Unit 01> Generator Cooling Fans3~4 ON (DO Output ) O DO2201 AA45 1 11 15 65 30 30 24VDC
cubicle =01MKA80 AN041 CP004-S01, 10 min follow up
operation if n =0

17 bo <Unit 01> Spare (DO Output ) O DO2201 AA45 1 11 16 65 30 30 24VDC

18 bo <Unit 01> Spare (DO Output ) O DO2201 AA45 1 11 17 65 30 30 24VDC


Unit 1 auxiliary
19 bo =01ASU10GH001 +01ASU01 =01MEV10 AT001 <Unit 01> Generator bearing oil tank Oil Mist Extractor OFF (DO Output ) O DO2201 AA45 1 11 18 65 30 30 24VDC
cubicle
In operation if n>0
Unit 1 auxiliary
20 bo =01ASU10GH001 +01ASU01 =01MEV10 AT001 <Unit 01> Generator bearing oil tank Oil Mist Extractor ON (DO Output ) O DO2201 AA45 1 11 19 65 30 30 24VDC
cubicle
Unit 1 auxiliary “Open” precondition, before start ,
21 bo =01ASU10GH001 +01ASU01 =MKD34 AA001 <Unit 01> High tank Bearing Oil Valve OPEN (DO Output ) O DO2201 AA45 1 11 20 65 30 30 24VDC
cubicle controlled by =MKD34 CG301 S02,
Unit 1 auxiliary Closed if n=0 after, shut down, controlled
22 bo =01ASU10GH001 +01ASU01 =MKD34 AA001 <Unit 01> High tank Bearing Oil Valve CLOSE (DO Output ) O DO2201 AA45 1 11 21 65 30 30 24VDC
cubicle by =MKD34 AA301 S01
Unit 1 auxiliary
23 bo =01ASU10GH001 +01ASU01 =01MKA91AA101 <Unit 01> Mechanical Brake OFF (DO Output ) O DO2201 AA45 1 11 22 65 30 30 24VDC Activate Brake during
cubicle
shut down at n < 20%
Unit 1 auxiliary
24 bo =01ASU10GH001 +01ASU01 =01MKA91AA101 <Unit 01> Mechanical Brake ON (DO Output ) O DO2201 AA45 1 11 23 65 30 30 24VDC of rated speed
cubicle
Unit 1 auxiliary
25 bo =01ASU10GH001 +01ASU01 <Unit 01> Spare (DO Output ) O DO2201 AA45 1 11 24 65 30 30 24VDC
cubicle
Unit 1 auxiliary
26 bo cubicle =01ASU10GH001 +01ASU01 =01MEV10 AH011 <Unit 01> Bearing oil tank heating motor 1 ON (DO Output ) O DO2201 AA45 1 11 25 65 30 30 24VDC
Unit 1 auxiliary
27 bo cubicle =01ASU10GH001 +01ASU01 =01MEV10 AH012 <Unit 01> Bearing oil tank heating motor 2 ON (DO Output ) O DO2201 AA45 1 11 26 65 30 30 24VDC
Unit 1 auxiliary controlled by
28 bo cubicle =01ASU10GH001 +01ASU01 =01MEV10 AH013 <Unit 01> Bearing oil tank heating motor 3 ON (DO Output ) O DO2201 AA45 1 11 27 65 30 30 24VDC
MEV10 CT010
Unit 1 auxiliary "On" at t< 25°C
29 bo cubicle =01ASU10GH001 +01ASU01 =01MEV10 AH014 <Unit 01> Bearing oil tank heating motor 4 ON (DO Output ) O DO2201 AA45 1 11 28 65 30 30 24VDC
"Off" at t> 35°C
Unit 1 auxiliary
30 bo cubicle =01ASU10GH001 +01ASU01 =01MEV20 AH011 <Unit 01> Bearing oil high tank heating motor 1 ON (DO Output ) O DO2201 AA45 1 11 29 65 30 30 24VDC
Unit 1 auxiliary
31 bo cubicle =01ASU10GH001 +01ASU01 =01MEV20 AH012 <Unit 01> Bearing oil high tank heating motor 2 ON (DO Output ) O DO2201 AA45 1 11 30 65 30 30 24VDC

32 bo <Unit 01> Spare (DO Output ) O DO2201 AA45 1 11 31 65 30 30 24VDC

33 bo <Unit 01> Spare (DO Output ) O DO2201 AA45 1 11 32 65 30 30 24VDC

34 bo =01MEW45 + AA010 -Y02 <Unit 01> control valve standstill sealing OFF O DO2201 AA45 1 11 33 65 30 30 24VDC

35 bo =01MEW45 + AA010 -Y01 <Unit 01> control valve standstill sealing ON O DO2201 AA45 1 11 34 65 30 30 24VDC
Turbine terminal
36 bo box =01CJA10GH001 +01CJA01 MEA30 <Unit 01> Mist Separator for Oil Head OFF (DO Output ) O DO2201 AA45 1 11 35 65 30 30 24VDC
activate <31bar
stop>32.5bar

8/38 2019/11/27
BMG Unit 1( LCU1) / Digital Outputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Remarks
Turbine terminal activate <31bar
37 bo box =01CJA10GH001 +01CJA01 MEA30 <Unit 01> Mist Separator for Oil Head ON (DO Output ) O DO2201 AA45 1 11 36 65 30 30 24VDC stop>32.5bar

38 bo <Unit 01> Spare (DO Output ) O DO2201 AA45 1 11 37 65 30 30 24VDC in operation if n>0

39 bo <Unit 01> LCU Fast task Watchdog Pulse Output 1 (DO Output ) O DO2201 AA45 1 11 38 65 30 30 24VDC

40 bo LCU Panel =01CJA10GH001 +01CJA03 <Unit 01> LCU Watchdog Pulse Output 1 (DO Output ) O DO2201 AA45 1 11 39 65 30 30 24VDC

41 bo MKA60 AN001 -M01 <Unit 01> Fan for carbon dust exhaust OFF (DO Output ) O DO2201 AA49 1 11 0 66 30 30 24VDC

42 bo MKA60 AN001 -M01 <Unit 01> Fan for carbon dust exhaust ON (DO Output ) O DO2201 AA49 1 11 1 66 30 30 24VDC

43 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 2


66
30 30 24VDC

44 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 3


66
30 30 24VDC
Unit 1 auxiliary
45 bo =01BAT10GH001 +01BAT10 -X2 <Unit 01> Main transformer cooling fan group 1 start/stop O DO2201 AA49 1 11 4
66
30 30 24VDC
cubicle
Unit 1 auxiliary
46 bo =01BAT10GH001 +01BAT10 -X2 <Unit 01> Main transformer cooling fan group 2 start/stop O DO2201 AA49 1 11 5
66
30 30 24VDC
cubicle

47 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 6 66 30 30 24VDC

48 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 7 66 30 30 24VDC

49 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 8 66 30 30 24VDC

50 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 9 66 30 30 24VDC

51 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 10 66 30 30 24VDC

52 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 11 66 30 30 24VDC

53 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 12 66 30 30 24VDC

54 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 13 66 30 30 24VDC

55 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 14 66 30 30 24VDC

56 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 15 66 30 30 24VDC

57 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 16 66 30 30 24VDC

58 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 17 66 30 30 24VDC

59 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 18 66 30 30 24VDC

60 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 19 66 30 30 24VDC

61 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 20 66 30 30 24VDC

62 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 21 66 30 30 24VDC

63 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 22 66 30 30 24VDC

64 bo =01MEX20 + AA101 <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 23 66 30 30 24VDC

65 bo =01MEX20 + AA101 <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 24 66 30 30 24VDC

66 bo solenoid valve MEX70 AA101 Y01 <Unit 01> ESD valve 1 energize (open) (DO Output ) O DO2201 AA49 1 11 25 66 30 30 24VDC

67 bo solenoid valve MEX70 AA102 Y01 <Unit 01> ESD valve 2 energize (open) (DO Output ) O DO2201 AA49 1 11 26 66 30 30 24VDC

68 bo solenoid valve =01MEX16 +AA102 Y01 <Unit 01> governor oil piston accumulator isolating valve OFF (DO Output ) O DO2201 AA49 1 11 27 66 30 30 24VDC

69 bo solenoid valve =01MEX16 +AA102 Y01 <Unit 01> governor oil piston accumulator isolating valve ON (DO Output ) O DO2201 AA49 1 11 28 66 30 30 24VDC

70 bo solenoid valve =01MEX11 +AA101 Y01 <Unit 01> governor oil pump 1 loading valve ON O DO2201 AA49 1 11 29 66 30 30 24VDC

71 bo solenoid valve =01MEX12 +AA101 Y01 <Unit 01> governor oil pump 2 loading valve ON O DO2201 AA49 1 11 30 66 30 30 24VDC
Unit 1 auxiliary
72 bo =01ASU10GH001 +01ASU01 =01MEX11AP001-M01 <Unit 01> Governor oil pump 1 Stop (DO Output ) O DO2201 AA49 1 11 31
66
30 30 24VDC
cubicle
Unit 1 auxiliary
73 bo =01ASU10GH001 +01ASU01 =01MEX11AP001-M01 <Unit 01> Governor oil pump 1 Start (DO Output ) O DO2201 AA49 1 11 32
66
30 30 24VDC
cubicle
Unit 1 auxiliary
74 bo =01ASU10GH001 +01ASU01 =01MEX12AP001-M01 <Unit 01> Governor oil pump 2 Stop (DO Output ) O DO2201 AA49 1 11 33
66
30 30 24VDC
cubicle
Unit 1 auxiliary
75 bo =01ASU10GH001 +01ASU01 =01MEX12AP001-M01 <Unit 01> Governor oil pump 2 Start (DO Output ) O DO2201 AA49 1 11 34
66
30 30 24VDC
cubicle
Solenoid
76 bo =MEX30 +AA102 Y01 =01MEX30AA102-Y01 <Unit 01> Governor oil head lubrication valve (CLOSE) (DO Output ) O DO2201 AA49 1 11 35
66
30 30 24VDC
Valve
Solenoid
77 bo =MEX30 +AA102 Y01 =01MEX30AA102-Y01 <Unit 01> Governor oil head lubrication valve (OPEN) (DO Output ) O DO2201 AA49 1 11 36
66
30 30 24VDC
Valve

9/38 2019/11/27
BMG Unit 1( LCU1) / Digital Outputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Remarks
Unit 1 auxiliary
78 bo =01ASU10GH001 +01ASU01 =01MEX18AP002-M01 <Unit 01> Turbine leakage oil tank oil level high (DO Output ) O DO2201 AA49 1 11 37
66
30 30 24VDC
cubicle
Unit 1 auxiliary
79 bo =01ASU10GH001 +01ASU01 =01MEX18AP002-M01 <Unit 01> Turbine leakage oil tank oil level too high (DO Output ) O DO2201 AA49 1 11 38
66
30 30 24VDC
cubicle

80 bo <Unit 01> Spare (DO Output ) O DO2201 AA49 1 11 39 66 30 30 24VDC

Unit 1 auxiliary
81 bo =01ASU10GH001 +01ASU01 =01MEX14AP001-M01 <Unit 01> Governor oil bypass filtration cooling pump stop (DO Output ) O DO2201 AA53 1 11 0 67 30 30 24VDC
cubicle
Unit 1 auxiliary
82 bo =01ASU10GH001 +01ASU01 =01MEX14AP001-M01 <Unit 01> Governor oil bypass filtration cooling pump start (DO Output ) O DO2201 AA53 1 11 1 67 30 30 24VDC
cubicle

83 bo =01ASU10GH001 +01ASU01 MEX14 AA105 -Y01 YB01 <Unit 01> Governor oil bypass filtration cooling valve ON (DO Output ) O DO2201 AA53 1 11 2 67 30 30 24VDC

84 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 3 67 30 30 24VDC

85 bo generator CB BAA20 GS100 YB02 <Unit 01> 13.8kV GCB Q01 OPEN (DO Output ) O DO2201 AA53 1 11 4 67 30 30 24VDC

86 bo LCU Panel =01CJA10GH001 +01CJA02 A01 <Unit 01> 13.8kV GCB Q01 Synchronization start (DO Output ) O DO2201 AA53 1 11 5 67 30 30 24VDC

87 bo LCU Panel =01CJA10GH001 +01CJA02 A01 <Unit 01> 13.8kV GCB Q01 Close No Voltage (DO Output ) O DO2201 AA53 1 11 6 67 30 30 24VDC

88 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 7 67 30 30 24VDC

89 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 8 67 30 30 24VDC

90 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 9 67 30 30 24VDC

91 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 10 67 30 30 24VDC

92 bo <Unit 01> Speed Lower (DO Output ) O DO2201 AA53 1 11 11 67 30 30 24VDC

93 bo <Unit 01> Speed Raise (DO Output ) O DO2201 AA53 1 11 12 67 30 30 24VDC

94 bo =01MKC10DE001 <Unit 01> Voltage Lower (DO Output ) O DO2201 AA53 1 11 13 67 30 30 24VDC

95 bo =01MKC10DE001 <Unit 01> Voltage Raise (DO Output ) O DO2201 AA53 1 11 14 67 30 30 24VDC

96 bo =01MKC10DE001 <Unit 01> Excitaion OFF (DO Output ) O DO2201 AA53 1 11 15 67 30 30 24VDC

97 bo =01MKC10DE001 <Unit 01> Excitaion ON (DO Output ) O DO2201 AA53 1 11 16 67 30 30 24VDC

98 bo =01MKC10DE001 <Unit 01> Excitation Load setvalue (DO Output ) O DO2201 AA53 1 11 17 67 30 30 24VDC

99 bo =01MKC10DE001 <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 18 67 30 30 24VDC

100 bo =01MKC10DE001 <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 19 67 30 30 24VDC

101 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 20 67 30 30 24VDC

102 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 21 67 30 30 24VDC

103 bo <Unit 01> EQSD Electical Quick Shut Down Trip (DO Output ) O DO2201 AA53 1 11 22 67 30 30 24VDC

104 bo <Unit 01> EQSD Electical Quick Shut Down Reset (DO Output ) O DO2201 AA53 1 11 23 67 30 30 24VDC

105 bo <Unit 01> ESD Emergency Shut Down Trip (DO Output ) O DO2201 AA53 1 11 24 67 30 30 24VDC

106 bo <Unit 01> ESD Emergency Shut Down Trip Reset (DO Output ) O DO2201 AA53 1 11 25 67 30 30 24VDC

107 bo <Unit 01> MQSD Mechanical Quick shutdown Trip (DO Output ) O DO2201 AA53 1 11 26 67 30 30 24VDC

108 bo <Unit 01> MQSD Mechanical Quick Shut Down Trip Reset (DO Output ) O DO2201 AA53 1 11 27 67 30 30 24VDC

109 bo <Unit 01> Alarm Indicate (DO Output ) O DO2201 AA53 1 11 28 67 30 30 24VDC

110 bo <Unit 01> Trip reset release (DO Output ) O DO2201 AA53 1 11 29 67 30 30 24VDC

111 bo <Unit 01> Alarm/Trip Horn (DO Output ) O DO2201 AA53 1 11 30 67 30 30 24VDC

112 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 31 67 30 30 24VDC

113 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 32 67 30 30 24VDC

114 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 33 67 30 30 24VDC

115 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 34 67 30 30 24VDC

116 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 35 67 30 30 24VDC

117 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 36 67 30 30 24VDC

118 bo <Unit 01> Spare (DO Output ) O DO2201 AA53 1 11 37 67 30 30 24VDC

10/38 2019/11/27
BMG Unit 1( LCU1) / Digital Outputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Remarks

119 bo <Unit 01> LCU Fast task Watchdog Pulse Output 2 (DO Output ) O DO2201 AA53 1 11 38 67 30 30 24VDC

120 bo LCU Panel =01CJA10GH001 +01CJA03 <Unit 01> LCU Watchdog Pulse Output 2 (DO Output ) O DO2201 AA53 1 11 39 67 30 30 24VDC

11/38 2019/11/27
BMG Unit1 ( LCU1) / Analog Inputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Unit Range Rev Remarks

1 ai flow indicator =01PCB20 +CF301 -S01 <Unit 01> Cooling Water Flow Generator I AI2300 AA65 1 11 0 68 36

2 ai flow indicator =01PCB20 +CF301 -S01 <Unit 01> Cooling Water Flow for Oil Cooler I AI2300 AA65 1 11 1 68 36

3 ai level indicator =01MEV10 +CL001 -B01 <Unit 01> Bearing oil plant sump tank - oil level I AI2300 AA65 1 11 2 68 36 ???-???mm STT BLK

4 ai level indicator =01MEV20 +CL001 -B01 <Unit 01> Bearing Oil High tank - oil level I AI2300 AA65 1 11 3 68 36 ???-???mm STT BLK

5 ai Turbine terminal box <Unit 01> Spare I AI2300 AA65 1 11 4 68 36


6 ai <Unit 01> Spare I AI2300 AA65 1 11 5 68 36
7 ai <Unit 01> Spare I AI2300 AA65 1 11 6 68 36
8 ai Turbine terminal box =01MEA10 +CP001 -B01 <Unit 01> Diff. Pressure measuring for turbine flow I AI2300 AA65 1 11 7 68 36 0-1bar
9 ai Turbine terminal box =01MEX20 +CP001 -U01 <Unit 01> Pressure measuring for hydraulic link (spare) I AI2300 AA65 1 11 8 68 36 0-10bar
10 ai =01MEX20 +CT001 <Unit 01> Generator GDB high oil pressure I AI2300 AA65 1 11 9 68 36 0-1bar
11 ai Turbine terminal box =01MEX20 +GG001 <Unit 01> Turbine GDB high oil pessure AA65 1 11 10 68 36
12 ai pressure transmitter MEX16 CP001 U01 <Unit 01> governor oil piston accumulator pressure I AI2300 AA65 1 11 11 68 36 0~250 bar
13 ai level transmitter MEX16 CL311 B01 <Unit 01> governor oil piston accumulator level I AI2300 AA65 1 11 12 68 36
14 ai temp. sensor (with contact) =01MEX18 +CU001 -B01 <Unit 01> Governor leakage oil tank temperature I AI2300 AA65 1 11 13 68 36
15 ai Level. sensor (with contact) =01MEX18 +CU001 -B01 <Unit 01> Governor leakage oil tank level I AI2300 AA65 1 11 14 68 36
Pressure
16 ai switch MEX30 CP301 S01 <Unit 01> Runner servomotor lubrication oil supply status I AI2300 AA65 1 11 15 68 36 0~250 bar
IOM0-0 ao <Unit 01> Spare O AI2300 AA65 1 11 16 68 36
IOM0-1 ao <Unit 01> Spare O AI2300 AA65 1 11 17 68 36
IOM1-0 ao =01MKC10 +DE001 <Unit 01> Setting Value Reactive Power O AI2300 AA65 1 11 18 68 36
IOM1-1 ao <Unit 01> Spare O AI2300 AA65 1 11 19 68 36

17 ai temp. sensor (with contact) =01MEX10 +CU001 -B01 <Unit 01> Hydraulic governor oil temprature I AI2300 AA69 1 11 0 69 36 0~100%
18 ai Level. sensor (with contact) =01MEX10 +CU001 -B01 <Unit 01> Hydraulic governor oil sump tank level I AI2300 AA69 1 11 1 69 36 0~100%
19 ai <Unit 01> Spare I AI2300 AA69 1 11 2 69 36 0~200%
20 ai <Unit 01> Spare I AI2300 AA69 1 11 3 69 36
21 ai <Unit 01> Spare I AI2300 AA69 1 11 4 69 36
22 ai <Unit 01> Spare I AI2300 AA69 1 11 5 69 36
23 ai =01MKC10 +DE001 <Unit 01> Spare I AI2300 AA69 1 11 6 69 36
24 ai <Unit 01> Excitation Voltage I AI2300 AA69 1 11 7 69 36
25 ai <Unit 01> Spare I AI2300 AA69 1 11 8 69 36
26 ai <Unit 01> Spare I AI2300 AA69 1 11 9 69 36
27 ai =01BAT10GH001 +01BAT10 -X3 <Unit 01> Main transformer winding temperature I AI2300 AA69 1 11 10 69 36
28 ai =01BAT10GH001 +01BAT10 -X3 <Unit 01> Main transformer oil temperature 1 I AI2300 AA69 1 11 11 69 36
29 ai =01BAT10GH001 +01BAT10 -X3 <Unit 01> Main transformer oil temperature 2 I AI2300 AA69 1 11 12 69 36
30 ai =01BAT10GH001 +01BAT10 -X3 <Unit 01> Main transformer oil temperature 1 I AI2300 AA69 1 11 13 69 36
31 ai =01BAT10GH001 +01BAT10 -X3 <Unit 01> Main transformer oil temperature 2 I AI2300 AA69 1 11 14 69 36
32 ai =01MEW10 +CP001 -B01 <Unit 01> Turbine sealing common water pressure measuring I AI2300 AA69 1 11 15 69 36
IOM0-0 ao <Unit 01> Wicket Gate Openning (indication) O AI2300 AA69 1 11 16 69 36
IOM0-1 ao <Unit 01> Runner Blade Openning (indication) O AI2300 AA69 1 11 17 69 36
IOM1-0 ao <Unit 01> Active Power (indication) O AI2300 AA69 1 11 18 69 36
IOM1-1 ao <Unit 01> Speed (indication) O AI2300 AA69 1 11 19 69 36

33 ai =01MKD31 +CF301 -S01 <Unit 01> Oil Flow Main Thrust Bearing I AI2300 AA73 1 11 0 70 36 ???~??? l/min
34 ai =01MKD32 +CF301 -S01 <Unit 01> Oil Flow Generator Guide Bearing I AI2300 AA73 1 11 1 70 36 ???~??? l/min
35 ai =01MKD33 +CF301 -S01 <Unit 01> Oil Flow Counter Thrust Bearing I AI2300 AA73 1 11 2 70 36 ???~??? l/min
36 ai =01MKD34 +CF301 -S01 <Unit 01> Oil Flow Turbine Guide Bearing I AI2300 AA73 1 11 3 70 36 ???~??? l/min
37 ai =MEW41 +CF001 -U01 <Unit 01> Turbineshaft seal water supply 1 flow I AI2300 AA73 1 11 4 70 36
38 ai =MEW42 +CF001 -U01 <Unit 01> Turbineshaft seal water supply 2 flow I AI2300 AA73 1 11 5 70 36
39 ai =MEW43 +CF001 -U01 <Unit 01> Turbineshaft seal water supply 3 flow I AI2300 AA73 1 11 6 70 36
40 ai =MEW44 +CF001 -U01 <Unit 01> Turbineshaft seal water supply 4 flow I AI2300 AA73 1 11 7 70 36
41 ai =01CJA10GH001 +01CJA02 <Unit 01> Temperature Turbine guide bearing 1 (MED30 CT001) I AI2300 AA73 1 11 8 70 36
42 ai =01CJA10GH001 +01CJA02 <Unit 01> Temperature Turbine guide bearing 2 (MED30 CT101) I AI2300 AA73 1 11 9 70 36
43 ai =01CJA10GH001 +01CJA02 <Unit 01> Temperature main thrust bearing pad (MKD31-CT001) I AI2300 AA73 1 11 10 70 36 STT BLK
44 ai =01CJA10GH001 +01CJA02 <Unit 01> Temperature main thrust bearing pad (MKD31-CT002) I AI2300 AA73 1 11 11 70 36 STT BLK
45 ai =01CJA10GH001 +01CJA02 <Unit 01> Temperature counter thrust bearing pad (MKD33-CT001) I AI2300 AA73 1 11 12 70 36 STT BLK
46 ai =01CJA10GH001 +01CJA02 <Unit 01> Temperature counter thrust bearing pad (MKD33-CT001) I AI2300 AA73 1 11 13 70 36 STT BLK
47 ai =01CJA10GH001 +01CJA02 <Unit 01> Temperature Generator guide bearing shell (MKD32-CT001) I AI2300 AA73 1 11 14 70 36 STT BLK
48 ai =01CJA10GH001 +01CJA02 <Unit 01> Temperature Generator guide bearing shell (MKD32-CT001) I AI2300 AA73 1 11 15 70 36 STT BLK

12/38 2019/11/27
BMG Unit1 ( LCU1) / Pt100 Inputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 signal Name (Lastest) I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Unit Range Type Rev Remarks
1 te temp. sensor =01MKA20 +CT001 -B01 <Unit 01> Temperature Stator winding - phase U1 I AI6310 A103 1 11 0 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
2 te temp. sensor =01MKA20 +CT002 -B01 <Unit 01> Temperature Stator winding - phase V1 I AI6310 A103 1 11 1 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
3 te temp. sensor =01MKA20 +CT003 -B01 <Unit 01> Temperature Stator winding - phase W1 I AI6310 A103 1 11 2 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
4 te temp. sensor =01MKA20 +CT004 -B01 <Unit 01> Temperature Stator winding - phase U2 I AI6310 A103 1 11 3 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
5 te temp. sensor =01MKA20 +CT005 -B01 <Unit 01> Temperature Stator winding - phase V2 I AI6310 A104 1 11 4 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
6 te temp. sensor =01MKA20 +CT006 -B01 <Unit 01> Temperature Stator winding - phase W2 I AI6310 A104 1 11 5 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
7 te temp. sensor <Unit 01> Spare I AI6310 A104 1 11 6 71 36 36
8 te temp. sensor <Unit 01> Spare I AI6310 A104 1 11 7 71 36 36
9 te temp. sensor <Unit 01> Spare I AI6310 A105 1 11 8 71 36 36
10 te temp. sensor =01MKA30 +CT001 -B01 <Unit 01> Temperature Center Stator core 01 I AI6310 A105 1 11 9 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
11 te temp. sensor =01MKA30 +CT002 -B01 <Unit 01> Temperature Center Stator core 02 I AI6310 A105 1 11 10 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
12 te temp. sensor =01MKA30 +CT003 -B01 <Unit 01> Temperature Center Stator core 03 I AI6310 A105 1 11 11 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
13 te temp. sensor <Unit 01> Spare I AI6310 A106 1 11 12 71 36 36
14 te temp. sensor <Unit 01> Spare I AI6310 A106 1 11 13 71 36 36
15 te temp. sensor <Unit 01> Spare I AI6310 A106 1 11 14 71 36 36
16 te temp. sensor =01MKA81 +CT001 -B01 <Unit 01> Temperature Generator hot air (CT001) I AI6310 A105 1 11 15 71 36 36 A(???℃) 4 - wire
17 te temp. sensor =01MKA81 +CT002 -B01 <Unit 01> Temperature Generator hot air (CT002) I AI6310 A107 1 11 16 71 36 36 A(???℃) 4 - wire
18 te temp. sensor =01MKA82 +CT001 -B01 <Unit 01> Temperature Generator cold air (CT001) I AI6310 A107 1 11 17 71 36 36 A(???℃) 4 - wire
19 te temp. sensor =01MKA82 +CT002 -B01 <Unit 01> Temperature Generator cold air (CT002) I AI6310 A107 1 11 18 71 36 36 A(???℃) 4 - wire
20 te temp. sensor <Unit 01> Spare I AI6310 A107 1 11 19 71 36 36
21 te temp. sensor <Unit 01> Spare I AI6310 A108 1 11 20 71 36 36
22 te temp. sensor =01MKD31 +CT003 -B01 <Unit 01> Temperature main thrust bearing pad (CT003) I AI6310 A108 1 11 21 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
23 te temp. sensor =01MKD31 +CT004 -B01 <Unit 01> Temperature main thrust bearing pad (CT004) I AI6310 A108 1 11 22 71 36 36 T(???℃) / A(???℃) 4 - wire STT BLK
24 te temp. sensor <Unit 01> Spare I AI6310 A108 1 11 23 71 36 36
25 te temp. sensor <Unit 01> Spare I AI6310 A109 1 11 24 71 36 36
26 te temp. sensor =01MEV10 +CT001 -B01 <Unit 01> Temperature Oil in Bearing oil sump tank I AI6310 A109 1 11 25 71 36 36 4 - wire Activate oil heater at < 25 degree
27 te temp. sensor =01MEV20 +CT001 -B01 <Unit 01> Temperature Oil in Bearing oil upper tank I AI6310 A109 1 11 26 71 36 36 4 - wire Activate oil heater at < 25 degree
28 te temp. sensor =01PCB20 +CT001 -B01 <Unit 01> Temperature cooling water before oil - water cooler I AI6310 A109 1 11 27 71 36 36 4 - wire
29 te temp. sensor =01PCB20 +CT002 -B01 <Unit 01> Temperature cooling water after oil - water cooler I AI6310 A110 1 11 28 71 36 36 4 - wire
30 te temp. sensor =01PCB31 +CT001 -B01 <Unit 01> Temperature cooling water after Water/water heat exchanger I AI6310 A110 1 11 29 71 36 36 4 - wire
31 te temp. sensor =01PCB32 +CT001 -B01 <Unit 01> Temperature cooling water before air-water cooler I AI6310 A110 1 11 30 71 36 36 4 - wire
32 te temp. sensor =01PCB32 +CT002 -B01 <Unit 01> Temperature cooling water after air-water cooler I AI6310 A110 1 11 31 71 36 36 4 - wire

33 te temp. sensor =01MKA60 +CT001 -B01 <Unit 01> Temperature Slip rings I AI6310 A213 1 11 0 72 36 36
34 te temp. sensor =01PCB30 +CT001 -B01 <Unit 01> River water temperature I AI6310 A213 1 11 1 72 36 36
35 te temp. sensor =01MEA30 +CT001 -B1 <Unit 01> Turbine oil head temperature I AI6310 A213 1 11 2 72 36 36 alarm >60℃,trip >80℃
36 te temp. sensor <Unit 01> Spare I AI6310 A213 1 11 3 72 36 36

37 te temp. sensor <Unit 01> Spare I AI6310 A214 1 11 4 72 36 36

38 te temp. sensor <Unit 01> Spare I AI6310 A214 1 11 5 72 36 36

39 te temp. sensor <Unit 01> Spare I AI6310 A214 1 11 6 72 36 36


40 te temp. sensor <Unit 01> Spare I AI6310 A214 1 11 7 72 36 36
41 te temp. sensor <Unit 01> Spare I AI6310 A215 1 11 8 72 36 36
42 te temp. sensor <Unit 01> Spare I AI6310 A215 1 11 9 72 36 36
43 te temp. sensor <Unit 01> Spare I AI6310 A215 1 11 10 72 36 36
44 te temp. sensor <Unit 01> Spare I AI6310 A215 1 11 11 72 36 36
45 te <Unit 01> Spare I AI6310 A216 1 11 12 72 36 36
46 te <Unit 01> Spare I AI6310 A216 1 11 13 72 36 36
47 te <Unit 01> Spare I AI6310 A216 1 11 14 72 36 36
48 te <Unit 01> Spare I AI6310 A216 1 11 15 72 36 36
49 te <Unit 01> Spare I AI6310 A217 1 11 16 72 36 36
50 te <Unit 01> Spare I AI6310 A217 1 11 17 72 36 36
51 te <Unit 01> Spare I AI6310 A217 1 11 18 72 36 36
52 te <Unit 01> Spare I AI6310 A217 1 11 19 72 36 36
53 te <Unit 01> Spare I AI6310 A218 1 11 20 72 36 36
54 te <Unit 01> Spare I AI6310 A218 1 11 21 72 36 36
55 te <Unit 01> Spare I AI6310 A218 1 11 22 72 36 36
56 te <Unit 01> Spare I AI6310 A218 1 11 23 72 36 36
57 te <Unit 01> Spare I AI6310 A219 1 11 24 72 36 36
58 te <Unit 01> Spare I AI6310 A219 1 11 25 72 36 36
59 te <Unit 01> Spare I AI6310 A219 1 11 26 72 36 36
60 te <Unit 01> Spare I AI6310 A219 1 11 27 72 36 36
61 te <Unit 01> Spare I AI6310 A220 1 11 28 72 36 36
62 te <Unit 01> Spare I AI6310 A220 1 11 29 72 36 36
63 te <Unit 01> Spare I AI6310 A220 1 11 30 72 36 36
64 te <Unit 01> Spare I AI6310 A220 1 11 31 72 36 36

13/38 2019/11/27
BMG Unit1 ( LCU1) / Speed Inputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Unit Rev I/O Remarks
1 ao MEX20 AA001 Y01 <Unit 01> GV proportional valve set value O AO6380 A413 1 11 0 74 36 36
2 ao MEX30 AA001 Y01 <Unit 01> RU proportional valve set value O AO6380 A413 1 11 1 74 36 36
3 ao Spare O AO6380 A413 1 11 2 74 36 36
4 ao Spare O AO6380 A413 1 11 3 74 36 36
5 ai LPE20 CP001 -B01 <Unit 01> Pressure measuring of upstream side I AI6300 A414 1 11 4 74 36 36 0~5Bar
6 ai LQA10 CP001 -B01 <Unit 01> Pressure measuring of downstream side I AI6300 A414 1 11 5 74 36 36 0~5Bar
7 ai MEX20 AA001 -B01 XQ01 <Unit 01> guide vane control valve postion I AI6300 A414 1 11 6 74 36 36
8 ai <Unit 01> Active Power Feedback I AI6300 A414 1 11 7 74 36 36
9 ai MEA20 CG001 -B01 XQ01 <Unit 01> Wicket Gate Position I AI6300 A415 1 11 8 74 36 36
10 ai MEA30 CG001 -B01 XQ01 <Unit 01> Runner Blade Position I AI6300 A415 1 11 9 74 36 36
11 ai MEX30 AA001 -B01 XQ01 <Unit 01> runner control valve postion I AI6300 A415 1 11 10 74 36 36
12 ai =01CJA10GH001 +01CJA02 U01 <Unit 01> Unit 1 Pickup 2 from D521 I AI6300 A415 1 11 11 74 36 36
13 im <Unit 01> Unit 1 PT Speed Signal I TE6420 A416 1 11 12 74 36 36
14 im pick up sensor =01'MEA20 +CS001 -B1 XQ1 <Unit 01> Unit 1 Pickup 1 I TE6420 A416 1 11 13 74 36 36
15 im Spare I TE6420 A416 1 11 14 74 36 36
16 im Spare I TE6420 A416 1 11 15 74 36 36
17 im pick up sensor =01CJA10GH001 +01CJA02 U01 <Unit 01> Unit 1 Pickup 2 from D521 I TE6420 A417 1 11 16 74 36 36
18 im Spare I TE6420 A417 1 11 17 74 36 36
19 im Spare I TE6420 A417 1 11 18 74 36 36
20 im Spare I TE6420 A417 1 11 19 74 36 36
21 bi LCU Panel =01CJA10GH001 +01CJA02 S43 <Unit 01> Governor Remote Auto I DI6100 A418 1 11 20 74 30 36
22 bi LCU Panel =01CJA10GH001 +01CJA02 S43 <Unit 01> Governor Local Auto I DI6100 A418 1 11 21 74 30 36
23 bi LCU Panel =01CJA10GH001 +01CJA02 S43 <Unit 01> Governor Local Manual I DI6100 A418 1 11 22 74 30 36
24 bi LCU Panel =01CJA10GH001 +01CJA02 S41 <Unit 01> Wicket Gate Decrease Local I DI6100 A418 1 11 23 74 30 36
25 bi LCU Panel =01CJA10GH001 +01CJA02 S41 <Unit 01> Wicket Gate Increase Local I DI6100 A418 1 11 24 74 30 36
26 bi LCU Panel =01CJA10GH001 +01CJA02 S42 <Unit 01> Runner Blade Decrease Local I DI6100 A418 1 11 25 74 30 36
27 bi LCU Panel =01CJA10GH001 +01CJA02 S42 <Unit 01> Runner Blade Increase Local I DI6100 A418 1 11 26 74 30 36
28 bi LCU Panel =01CJA10GH001 +01CJA02 A01 <Unit 01> Decrease Speed from SYN3000 I DI6100 A418 1 11 27 74 30 36
29 bi LCU Panel =01CJA10GH001 +01CJA02 A01 <Unit 01> Increase Speed from SYN3000 I DI6100 A418 1 11 28 74 30 36

Turbine terminal box =01MEA20 +CG101~108 -S01 XG51 <Unit 01> guide vane safety link #1~#8 broken
30 bi I DI6100 A418 1 11 29 74 30 36
31 bi Spare I DI6100 A418 1 11 30 74 30 36
32 bi Spare I DI6100 A418 1 11 31 74 30 36
33 bi BAA20 GS100 XB01 <Unit 01> 6.3kV GCB Q01 State Open I DI6100 A418 1 11 32 74 30 36
34 bi BAA20 GS100 XB01 <Unit 01> 6.3kV GCB Q01 State Closed I DI6100 A418 1 11 33 74 30 36
35 bi Spare I DI6100 A418 1 11 34 74 30 36
36 bi Spare I DI6100 A418 1 11 35 74 30 36
37 bi Spare I DI6100 A419 1 11 36 74 30 36
38 bi Spare I DI6100 A419 1 11 37 74 30 36
39 bi Spare I DI6100 A419 1 11 38 74 30 36
40 bi Spare I DI6100 A419 1 11 39 74 30 36
41 bi Spare I DI6100 A419 1 11 40 74 30 36
42 bi Spare I DI6100 A419 1 11 41 74 30 36
43 bi Spare I DI6100 A419 1 11 42 74 30 36
44 bi Spare I DI6100 A419 1 11 43 74 30 36
45 bi Spare I DI6100 A419 1 11 44 74 30 36
46 bi Spare I DI6100 A419 1 11 45 74 30 36
47 bi Spare I DI6100 A419 1 11 46 74 30 36
48 bi Spare I DI6100 A419 1 11 47 74 30 36
49 bi Spare I DI6100 A419 1 11 48 74 30 36
50 bi Spare I DI6100 A419 1 11 49 74 30 36
51 bi Spare I DI6100 A419 1 11 50 74 30 36
52 bi Spare I DI6100 A419 1 11 51 74 30 36
53 bo <Unit 01> Speed<1% (DO Output ) O DO6200 A420 1 11 52 74 30 36
54 bo <Unit 01> Speed<20% (DO Output ) O DO6200 A420 1 11 53 74 30 36
55 bo <Unit 01> Speed<90% (DO Output ) O DO6200 A420 1 11 54 74 30 36
56 bo <Unit 01> Speed>90% (DO Output ) O DO6200 A420 1 11 55 74 30 36
57 bo <Unit 01> Speed>115% (DO Output ) O DO6200 A420 1 11 56 74 30 36
58 bo <Unit 01> Speed>160% (DO Output ) O DO6200 A420 1 11 57 74 30 36
59 bo <Unit 01> Electronic turbine governor fault (DO Output ) O DO6200 A420 1 11 58 74 30 36
60 bo <Unit 01> Speed detection OK (no failure) (DO Output ) O DO6200 A420 1 11 59 74 30 36
61 bo <Unit 01> Wicket Gate Full Closed (DO Output ) O DO6200 A420 1 11 60 74 30 36
62 bo <Unit 01> Wicket Gate Under No Load Position (DO Output ) O DO6200 A420 1 11 61 74 30 36
63 bo Spare O DO6200 A420 1 11 62 74 30 36
64 bo Spare O DO6200 A420 1 11 63 74 30 36
65 bo Spare O DO6200 A420 1 11 64 74 30 36
66 bo Spare O DO6200 A420 1 11 65 74 30 36
67 bo Spare O DO6200 A420 1 11 66 74 30 36
68 bo Spare O DO6200 A420 1 11 67 74 30 36

14/38 2019/11/27
BMG Unit1 ( LCU1) / PT/CT input from Modbus Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Unit Range Remarks
1 ai Unit 1 13.8kV generator current I1 C MODBUS 1 11 0 74 36 36
2 ai Unit 1 13.8kV generator current I2 C MODBUS 1 11 1 74 36 36
3 ai Unit 1 13.8kV generator current I3 C MODBUS 1 11 2 74 36 36
4 ai Unit 1 13.8kV generator current IN C MODBUS 1 11 3 74 36 36
5 ai Unit 1 13.8kV generator voltage U1 C MODBUS 1 11 4 74 36 36
6 ai Unit 1 13.8kV generator voltage U2 C MODBUS 1 11 5 74 36 36
7 ai Unit 1 13.8kV generator voltage U3 C MODBUS 1 11 6 74 36 36
8 ai Unit 1 13.8kV generator voltage UN C MODBUS 1 11 7 74 36 36
9 ai Unit 1 13.8kV generator frequency f C MODBUS 1 11 8 74 36 36
10 ai Unit 1 13.8kV generator power factor cos C MODBUS 1 11 9 74 36 36
11 ai Unit 1 13.8kV generator active power P C MODBUS 1 11 10 74 36 36
12 ai Unit 1 13.8kV generator reactive power Q C MODBUS 1 11 11 74 36 36
13 ai Unit 1 13.8kV generator active energy kWh C MODBUS 1 11 12 74 36 36
14 ai Unit 1 13.8kV generator reactive energy kVarh C MODBUS 1 11 13 74 36 36
15 ai Spare C MODBUS 1 11 14 74 36 36
16 ai Spare C MODBUS 1 11 15 74 36 36

15/38 2019/11/27
BMG Unit1 ( LCU1) / Protection IEC104 Communication Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Unit Range Remarks
1 bi Unit 1 Generator Minimum Impedance Protection (21G) Trip C IEC104 1 11 0 1 30 30
2 bi Unit 1 Generator Reverse Power Protection (32) Trip C IEC104 1 11 1 1 30 30
3 bi Unit 1 Generator Shaft Current Protection (38) Trip C IEC104 1 11 2 1 30 30
4 bi Unit 1 Generator Loss Of Excitation Protection (40) Trip C IEC104 1 11 3 1 30 30
Unit 1 Generator Negative Phase Sequence Current
5 bi C IEC104 1 11 4 1 30 30
Protection (46) Trip
6 bi Unit 1 Generator Overload Protection (49) Trip C IEC104 1 11 5 1 30 30
Unit 1 Generator Phase Instantaneous/Time Delay Over
7 bi C IEC104 1 11 6 1 30 30
Current Protection (50/51) Trip
Unit 1 Generator Circuit Breaker Failure Protection
8 bi C IEC104 1 11 7 1 30 30
(GCB_50BF) Trip
9 bi Unit 1 Generator Rotor Earth Fault Protection (64R) Trip C IEC104 1 11 8 1 30 30
10 bi Unit 1 Generator Out Of Step Protection (78) Trip C IEC104 1 11 9 1 30 30
11 bi Unit 1 Generator Differential Protection (87G) Trip C IEC104 1 11 10 1 30 30
12 bi Unit 1 Generator Under Voltage Protection (27) Trip C IEC104 1 11 11 1 30 30
13 bi Unit 1 Generator Over Voltage Protection (59) Trip C IEC104 1 11 12 1 30 30
Unit 1 Generator 95% Stator Earth Fault Protection (59NS)
14 bi C IEC104 1 11 13 1 30 30
Trip
Unit 1 Generator 100% Stator Earth Fault Protection (64S)
15 bi C IEC104 1 11 14 1 30 30
Trip
16 bi Unit 1 Generator Under/Over Frequency Protection (81) Trip C IEC104 1 11 15 1 30 30
Unit 1 Transformer-Generator Block Differential Protection
17 bi C IEC104 1 11 16 1 30 30
(87GT) Trip
18 bi Unit 1 Main Transformer Over-Fluxing Protection (24T) Trip C IEC104 1 11 17 1 30 30
Unit 1 Main Transformer Instantanous/Time Delay Earth
19 bi C IEC104 1 11 18 1 30 30
Fault Over Current Protection (50/51NT) Trip
Unit 1 10.5kV Busbar Earthing Detection Protection (59N)
20 bi C IEC104 1 11 19 1 30 30
Alarm
21 bi Unit 1 Main Transformer Differential Protection (87T) Trip C IEC104 1 11 20 1 30 30
22 bi Unit 1 Main Transformer Over-Fluxing Protection (24T) Trip C IEC104 1 11 21 1 30 30
23 bi Unit 1 Main Transformer Overload Protection (49T) Trip C IEC104 1 11 22 1 30 30
Unit 1 Main Transformer Phase Instantaneous/Time Delay
24 bi C IEC104 1 11 23 1 30 30
Over Current Protection (50/51T) Trip
Unit 1 Main Transformer Circuit Breaker Failure Protection
25 bi C IEC104 1 11 24 1 30 30
(TCB_50BF) Trip
Unit 1 Main Transformer Internal Earth-Fault Protection
26 bi C IEC104 1 11 25 1 30 30
(Ground Differential Protection) (87TN) Trip

16/38 2019/11/27
BMG Common( LCU10) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)
1 bi LCU10 Control Mode Remote I DI2110 AA21 1 51 0 60 30 30 24VDC
2 bi LCU10 Control Mode Local I DI2110 AA21 1 51 1 60 30 30 24VDC
3 bi LCU10 Control Mode Revision I DI2110 AA21 1 51 2 60 30 30 24VDC
4 bi LCU10 220VDC Power 1 Supply Failure I DI2110 AA21 1 51 3 60 30 30 24VDC A
5 bi LCU10 220VDC Power 2 Supply Failure I DI2110 AA21 1 51 4 60 30 30 24VDC A
6 bi LCU10 24VDC Power Supply Failure I DI2110 AA21 1 51 5 60 30 30 24VDC A
7 bi LCU10 Power Converter 1 OK I DI2110 AA21 1 51 6 60 30 30 24VDC
8 bi LCU10 Light Power Fault I DI2110 AA21 1 51 7 60 30 30 24VDC A
9 bi Spare I DI2110 AA21 1 51 8 60 30 30 24VDC
10 bi CB -Q01~06 common remote mode I DI2110 AA21 1 51 9 60 30 30 24VDC
11 bi =20BFA10GH001 +20BFA01 -Q01 SST1 incoming CB -Q01 opened I DI2110 AA21 1 51 10 60 31 31 24VDC
12 bi =20BFA10GH001 +20BFA01 -Q01 SST1 incoming CB -Q01 closed I DI2110 AA21 1 51 11 60 31 31 24VDC
13 bi =20BFA10GH001 +20BFA01 -Q01 SST1 incoming CB -Q01 ready to close I DI2110 AA21 1 51 12 60 30 30 24VDC A
14 bi =20BFA10GH001 +20BFA01 -Q01 SST1 incoming CB -Q01 tripped I DI2110 AA21 1 51 13 60 30 30 24VDC
15 bi =20BFB10GH001 +20BFB01 -Q02 SST2 incoming CB -Q02 opened I DI2110 AA21 1 51 14 60 31 31 24VDC
16 bi =20BFB10GH001 +20BFB01 -Q02 SST2 incoming CB -Q02 closed I DI2110 AA21 1 51 15 60 31 31 24VDC A
17 bi =20BFB10GH001 +20BFB01 -Q02 SST2 incoming CB -Q02 ready to close I DI2110 AA21 1 51 16 60 30 30 24VDC
18 bi =20BFB10GH001 +20BFB01 -Q02 SST2 incoming CB -Q02 tripped I DI2110 AA21 1 51 17 60 30 30 24VDC
19 bi =20BFC10GH001 +20BFC02 -Q03 SST3 incoming CB -Q03 opened I DI2110 AA21 1 51 18 60 31 31 24VDC A
20 bi =20BFC10GH001 +20BFC02 -Q03 SST3 incoming CB -Q03 closed I DI2110 AA21 1 51 19 60 31 31 24VDC
21 bi =20BFC10GH001 +20BFC02 -Q03 SST3 incoming CB -Q03 ready to close I DI2110 AA21 1 51 20 60 30 30 24VDC
22 bi =20BFC10GH001 +20BFC02 -Q03 SST3 incoming CB -Q03 tripped I DI2110 AA21 1 51 21 60 30 30 24VDC A
23 bi =20BFC10GH001 +20BFC02 -Q04 DG incoming CB -Q04 opened I DI2110 AA21 1 51 22 60 31 31 24VDC
24 bi =20BFC10GH001 +20BFC02 -Q04 DG incoming CB -Q04 closed I DI2110 AA21 1 51 23 60 31 31 24VDC
25 bi =20BFC10GH001 +20BFC02 -Q04 DG incoming CB -Q04 ready to close I DI2110 AA21 1 51 24 60 30 30 24VDC A
26 bi =20BFC10GH001 +20BFC02 -Q04 DG incoming CB -Q04 tripped I DI2110 AA21 1 51 25 60 30 30 24VDC
27 bi =20BFC10GH001 +20BFC01 -Q05 Coupling CB with SST1 -Q05 opened I DI2110 AA21 1 51 26 60 31 31 24VDC
28 bi =20BFC10GH001 +20BFC01 -Q05 Coupling CB with SST1 -Q05 closed I DI2110 AA21 1 51 27 60 31 31 24VDC A
29 bi =20BFC10GH001 +20BFC01 -Q05 Coupling CB with SST1 -Q05 ready to close I DI2110 AA21 1 51 28 60 30 30 24VDC
30 bi =20BFC10GH001 +20BFC01 -Q05 Coupling CB with SST1 -Q05 tripped I DI2110 AA21 1 51 29 60 30 30 24VDC
31 bi =20BFC10GH001 +20BFC03 -Q06 Coupling CB with SST2 -Q06 opened I DI2110 AA21 1 51 30 60 31 31 24VDC
32 bi =20BFC10GH001 +20BFC03 -Q06 Coupling CB with SST2 -Q06 closed I DI2110 AA21 1 51 31 60 31 31 24VDC
33 bi =20BFC10GH001 +20BFC03 -Q06 Coupling CB with SST2 -Q06 ready to close I DI2110 AA21 1 51 32 60 30 30 24VDC
34 bi =20BFC10GH001 +20BFC03 -Q06 Coupling CB with SST2 -Q06 tripped I DI2110 AA21 1 51 33 60 30 30 24VDC A
35 bi Spare I DI2110 AA21 1 51 34 60 30 30 24VDC A
36 bi Spare I DI2110 AA21 1 51 35 60 30 30 24VDC A
37 bi =20BFA10GH001 +20BFA01 400V AC SST1 ok/available I DI2110 AA21 1 51 36 60 30 30 24VDC A
38 bi =20BFB10GH001 +20BFB01 400V AC SST2 ok/available I DI2110 AA21 1 51 37 60 30 30 24VDC A
39 bi =20BFC10GH001 +20BFC02 400V AC SST3 ok/available I DI2110 AA21 1 51 38 60 30 30 24VDC A
40 bi =20BFC10GH001 +20BFC02 400V AC DG ok/available I DI2110 AA21 1 51 39 60 30 30 24VDC A
41 bi =20BFA10GH001 +20BFA02 400V AC bus 1 (SST1) ok/available I DI2110 AA21 1 51 40 60 30 30 24VDC A
42 bi =20BFB10GH001 +20BFB02 400V AC bus 2 (SST2) ok/available I DI2110 AA21 1 51 41 60 30 30 24VDC T
43 bi =20BFC10GH001 +20BFC03 400V AC common bus ok/available I DI2110 AA21 1 51 42 60 30 30 24VDC A
44 bi Spare I DI2110 AA21 1 51 43 60 30 30 24VDC A
45 bi Spare I DI2110 AA21 1 51 44 60 30 30 24VDC T
46 bi =01BBT10GH001 +01BBT10 SST1 doors closed I DI2110 AA21 1 51 45 60 30 30 24VDC
47 bi =01BBT10GH001 +01BBT10 SST1 over temperature alarm I DI2110 AA21 1 51 46 60 30 30 24VDC
48 bi =01BBT10GH001 +01BBT10 SST1 temperature supervision device fault I DI2110 AA21 1 51 47 60 30 30 24VDC
49 bi =01BBT10GH001 +01BBT10 SST1 over temperature trip I DI2110 AA21 1 51 48 60 30 30 24VDC
50 bi =02BBT10GH001 +02BBT10 SST2 doors closed I DI2110 AA21 1 51 49 60 30 30 24VDC
51 bi =02BBT10GH001 +02BBT10 SST2 over temperature alarm I DI2110 AA21 1 51 50 60 30 30 24VDC
52 bi =02BBT10GH001 +02BBT10 SST2 temperature supervision device fault I DI2110 AA21 1 51 51 60 30 30 24VDC
53 bi =02BBT10GH001 +02BBT10 SST2 over temperature trip I DI2110 AA21 1 51 52 60 30 30 24VDC
54 bi Spare I DI2110 AA21 1 51 53 60 30 30 24VDC
55 bi Spare I DI2110 AA21 1 51 54 60 30 30 24VDC
56 bi =20XKA10GH001 +20XKA01 -X2 DG fault I DI2110 AA21 1 51 55 60 30 30 24VDC
57 bi =20XKA10GH001 +20XKA01 -X2 DG parameter OK I DI2110 AA21 1 51 56 60 30 30 24VDC
58 bi =20XKA10GH001 +20XKA01 -X2 DG MCB trip I DI2110 AA21 1 51 57 60 30 30 24VDC
59 bi =20XKA10GH001 +20XKA01 -X2 DG CB opened I DI2110 AA21 1 51 58 60 30 30 24VDC
60 bi =20XKA10GH001 +20XKA01 -X2 DG CB closed I DI2110 AA21 1 51 59 60 30 30 24VDC
61 bi Spare I DI2110 AA21 1 51 60 60 30 30 24VDC
62 bi Spare I DI2110 AA21 1 51 61 60 30 30 24VDC
63 bi Spare I DI2110 AA21 1 51 62 60 30 30 24VDC
64 bi Spare I DI2110 AA21 1 51 63 60 30 30 24VDC

17/38 2019/11/27
BMG Common( LCU10) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)

65 bi =20BTL10GH001 +20BTL01 220V DC 1# Rectifier Charger - Device Abnormity I DI2110 AA25 1 51 0 61 30 30 24VDC T
66 bi =20BTL10GH001 +20BTL01 220V DC 1# Rectifier Charger - All Alarm I DI2110 AA25 1 51 1 61 30 30 24VDC T
67 bi =20BTL10GH001 +20BTL01 220V DC 1# Rectifier Charger - Communication Alarm I DI2110 AA25 1 51 2 61 30 30 24VDC A
68 bi =20BTL10GH001 +20BTL01 220V DC 1# Rectifier Charger - Feeder Alarm I DI2110 AA25 1 51 3 61 30 30 24VDC A
69 bi =20BTL10GH001 +20BTL01 220V DC 1# Rectifier Charger - Bus Alarm I DI2110 AA25 1 51 4 61 30 30 24VDC T
70 bi =20BTL10GH001 +20BTL01 220V DC 1# Rectifier Charger - Battery Alarm I DI2110 AA25 1 51 5 61 30 30 24VDC T
71 bi =20BTL10GH001 +20BTL01 220V DC 1# Rectifier Charger - Rectifier Module Alarm I DI2110 AA25 1 51 6 61 30 30 24VDC A
72 bi =20BTL10GH001 +20BTL01 220V DC 1# Rectifier Charger - AC Power Alarm I DI2110 AA25 1 51 7 61 30 30 24VDC A
73 bi =20BTM10GH001 +20BTM01 220V DC 2# Rectifier Charger - Device Abnormity I DI2110 AA25 1 51 8 61 30 30 24VDC A
74 bi =20BTM10GH001 +20BTM01 220V DC 2# Rectifier Charger - All Alarm I DI2110 AA25 1 51 9 61 30 30 24VDC A
75 bi =20BTM10GH001 +20BTM01 220V DC 2# Rectifier Charger - Communication Alarm I DI2110 AA25 1 51 10 61 30 30 24VDC A

=20BTM10GH001 +20BTM01 220V DC 2# Rectifier Charger - Feeder Alarm


76 bi I DI2110 AA25 1 51 11 61 30 30 24VDC T
77 bi =20BTM10GH001 +20BTM01 220V DC 2# Rectifier Charger - Bus Alarm I DI2110 AA25 1 51 12 61 30 30 24VDC A
78 bi =20BTM10GH001 +20BTM01 220V DC 2# Rectifier Charger - Battery Alarm I DI2110 AA25 1 51 13 61 30 30 24VDC A
79 bi =20BTM10GH001 +20BTM01 220V DC 2# Rectifier Charger - Rectifier Module Alarm I DI2110 AA25 1 51 14 61 30 30 24VDC A
80 bi =20BTM10GH001 +20BTM01 220V DC 2# Rectifier Charger - AC Power Alarm I DI2110 AA25 1 51 15 61 30 30 24VDC A
81 bi =20BUA10GH001 +20BUA01 220V DC 1# DC Distribution - Device Failure I DI2110 AA25 1 51 16 61 30 30 24VDC T
82 bi =20BUA10GH001 +20BUA01 220V DC 1# DC Distribution - Bus Voltage Abnormal I DI2110 AA25 1 51 17 61 30 30 24VDC A
83 bi =20BUA10GH001 +20BUA01 220V DC 1# DC Distribution - Bus Insulation Abnormal I DI2110 AA25 1 51 18 61 30 30 24VDC
84 bi =20BUA10GH001 +20BUA01 220V DC 1# DC Distribution - Communication Alarm I DI2110 AA25 1 51 19 61 30 30 24VDC A
85 bi =20BUA10GH001 +20BUA01 220V DC 1# DC Distribution - Feeder Group MCB Trip I DI2110 AA25 1 51 20 61 30 30 24VDC
86 bi =20BUB10GH001 +20BUB01 220V DC 2# DC Distribution - Device Failure I DI2110 AA25 1 51 21 61 30 30 24VDC
87 bi =20BUB10GH001 +20BUB01 220V DC 2# DC Distribution - Bus Voltage Abnormal I DI2110 AA25 1 51 22 61 30 30 24VDC
88 bi =20BUB10GH001 +20BUB01 220V DC 2# DC Distribution - Bus Insulation Abnormal I DI2110 AA25 1 51 23 61 30 30 24VDC
89 bi =20BUB10GH001 +20BUB01 220V DC 2# DC Distribution - Communication Alarm I DI2110 AA25 1 51 24 61 30 30 24VDC
90 bi =20BUB10GH001 +20BUB01 220V DC 2# DC Distribution - Feeder Group MCB Trip I DI2110 AA25 1 51 25 61 30 30 24VDC
91 bi Spare I DI2110 AA25 1 51 26 61 30 30 24VDC
92 bi Spare I DI2110 AA25 1 51 27 61 30 30 24VDC
93 bi Spare I DI2110 AA25 1 51 28 61 30 30 24VDC
94 bi Spare I DI2110 AA25 1 51 29 61 30 30 24VDC
95 bi =20BRA10GH001 +20BRA01 1# Inverter Bypass Power Suppy ON I DI2110 AA25 1 51 30 61 30 30 24VDC
96 bi =20BRA10GH001 +20BRA01 1# Inverter AC Rectifier Power Suppy ON I DI2110 AA25 1 51 31 61 30 30 24VDC
97 bi =20BRA10GH001 +20BRA01 1# Inverter DC Power Supply ON I DI2110 AA25 1 51 32 61 30 30 24VDC
98 bi =20BRA10GH001 +20BRA01 1# DC Fault I DI2110 AA25 1 51 33 61 30 30 24VDC
99 bi =20BRA10GH001 +20BRA01 1# Inverter Fault I DI2110 AA25 1 51 34 61 30 30 24VDC
100 bi =20BRA10GH001 +20BRA01 1# Inverter Communication Failure I DI2110 AA25 1 51 35 61 30 30 24VDC
101 bi =20BRA10GH001 +20BRA01 1# Inverter AC Distribution - Feeder Group MCB Trip I DI2110 AA25 1 51 36 61 30 30 24VDC
102 bi =20BRB10GH001 +20BRB01 2# Inverter Bypass Power Suppy ON I DI2110 AA25 1 51 37 61 30 30 24VDC
103 bi =20BRB10GH001 +20BRB01 2# Inverter AC Rectifier Power Suppy ON I DI2110 AA25 1 51 38 61 30 30 24VDC
104 bi =20BRB10GH001 +20BRB01 2# Inverter DC Power Supply ON I DI2110 AA25 1 51 39 61 30 30 24VDC
105 bi =20BRB10GH001 +20BRB01 2# DC Fault I DI2110 AA25 1 51 40 61 30 30 24VDC
106 bi =20BRB10GH001 +20BRB01 2# Inverter Fault I DI2110 AA25 1 51 41 61 30 30 24VDC
107 bi =20BRB10GH001 +20BRB01 2# Inverter Communication Failure I DI2110 AA25 1 51 42 61 30 30 24VDC
108 bi =20BRB10GH001 +20BRB01 2# Inverter AC Distribution - Feeder Group MCB Trip I DI2110 AA25 1 51 43 61 30 30 24VDC
109 bi =20XKA10GH001 +20XKA01 -X1 DG fault I DI2110 AA25 1 51 44 61 30 30 24VDC
110 bi =20XKA10GH001 +20XKA01 -X1 DG parameter OK I DI2110 AA25 1 51 45 61 30 30 24VDC
111 bi Spare I DI2110 AA25 1 51 46 61 30 30 24VDC
112 bi Spare I DI2110 AA25 1 51 47 61 30 30 24VDC
113 bi =01BAA30GD001 +01BAA30 SST1 13.8kV load break switch disconnector Q11 control circuit fault I DI2110 AA25 1 51 48 61 30 30 24VDC
114 bi =01BAA30GD001 +01BAA30 SST1 13.8kV load break switch disconnector Q11 control switch remote I DI2110 AA25 1 51 49 61 30 30 24VDC
115 bi =01BAA30GD001 +01BAA30 SST1 13.8kV load break switch disconnector Q11 opened I DI2110 AA25 1 51 50 61 31 31 24VDC
116 bi =01BAA30GD001 +01BAA30 SST1 13.8kV load break switch disconnector Q11 closed I DI2110 AA25 1 51 51 61 31 31 24VDC
117 bi =01BAA30GD001 +01BAA30 SST1 13.8kV earthing switch opened I DI2110 AA25 1 51 52 61 31 31 24VDC
118 bi =03BAA30GD001 +03BAA30 SST1 13.8kV earthing switch closed I DI2110 AA25 1 51 53 61 31 31 24VDC
119 bi =03BAA30GD001 +03BAA30 SST2 13.8kV load break switch disconnector Q31 control circuit fault I DI2110 AA25 1 51 54 61 30 30 24VDC
120 bi =03BAA30GD001 +03BAA30 SST2 13.8kV load break switch disconnector Q31 control switch remote I DI2110 AA25 1 51 55 61 30 30 24VDC
121 bi =03BAA30GD001 +03BAA30 SST2 13.8kV load break switch disconnector Q31 opened I DI2110 AA25 1 51 56 61 31 31 24VDC
122 bi =03BAA30GD001 +03BAA30 SST2 13.8kV load break switch disconnector Q31 closed I DI2110 AA25 1 51 57 61 31 31 24VDC
123 bi =03BAA30GD001 +03BAA30 SST2 13.8kV earthing switch opened I DI2110 AA25 1 51 58 61 31 31 24VDC
124 bi =03BAA30GD001 +03BAA30 SST2 13.8kV earthing switch closed I DI2110 AA25 1 51 59 61 31 31 24VDC
125 bi Spare I DI2110 AA25 1 51 60 61 30 30 24VDC
126 bi Spare I DI2110 AA25 1 51 61 61 30 30 24VDC
127 bi Spare I DI2110 AA25 1 51 62 61 30 30 24VDC

18/38 2019/11/27
BMG Common( LCU10) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)
128 bi Spare I DI2110 AA25 1 51 63 61 30 30 24VDC

129 bi QEB01 AN001 XB02 air compressor 1# off I DI2110 AA29 1 51 0 62 31 31 24VDC
130 bi QEB01 AN001 XB01 air compressor 1# on I DI2110 AA29 1 51 1 62 31 31 24VDC
131 bi QEB01 AN001 XM01 air compressor 1# electric failure I DI2110 AA29 1 51 2 62 30 30 24VDC A
132 bi Spare I DI2110 AA29 1 51 3 62 30 30 24VDC
133 bi QEB01 AN002 XB02 air compressor 2# off I DI2110 AA29 1 51 4 62 31 31 24VDC
134 bi QEB01 AN002 XB01 air compressor 2# on I DI2110 AA29 1 51 5 62 31 31 24VDC
135 bi QEB01 AN002 XM01 air compressor 2# electric failure I DI2110 AA29 1 51 6 62 30 30 24VDC A
136 bi Spare I DI2110 AA29 1 51 7 62 30 30 24VDC
137 bi QEB01 CP001 S01 pressure switch start mian compressor - 9bar I DI2110 AA29 1 51 8 62 30 30 24VDC
138 bi QEB01 CP001 S02 pressure switch stop compressor - 10bar I DI2110 AA29 1 51 9 62 30 30 24VDC
139 bi QEB01 CP001 S01 pressure switch start spare compressor - 5bar I DI2110 AA29 1 51 10 62 30 30 24VDC
140 bi QEB01 CP001 S02 pressure switch stop compressor - 10bar I DI2110 AA29 1 51 11 62 30 30 24VDC
141 bi GMM10 AP001 XB02 drainage pump 1# off I DI2110 AA29 1 51 12 62 31 31 24VDC
142 bi GMM10 AP001 XB01 drainage pump 1# on I DI2110 AA29 1 51 13 62 31 31 24VDC
143 bi GMM10 AP001 XM01 drainage pump 1# electric failure I DI2110 AA29 1 51 14 62 30 30 24VDC A
144 bi GMM10 CF101 S01 drainage pump 1# outlet flow too low I DI2110 AA29 1 51 15 62 30 30 24VDC A
145 bi Spare I DI2110 AA29 1 51 16 62 30 30 24VDC
146 bi Spare I DI2110 AA29 1 51 17 62 30 30 24VDC
147 bi GMM10 AP002 XB02 drainage pump 2# off I DI2110 AA29 1 51 18 62 31 31 24VDC
148 bi GMM10 AP002 XB01 drainage pump 2# on I DI2110 AA29 1 51 19 62 31 31 24VDC
149 bi GMM10 AP002 XM01 drainage pump 2# electric failure I DI2110 AA29 1 51 20 62 30 30 24VDC A
150 bi GMM10 CF102 S01 drainage pump 2# outlet flow too low I DI2110 AA29 1 51 21 62 30 30 24VDC A
151 bi Spare I DI2110 AA29 1 51 22 62 30 30 24VDC
152 bi Spare I DI2110 AA29 1 51 23 62 30 30 24VDC
153 bi GMM10 CL101 G01 float switch stop drainage pump water level I DI2110 AA29 1 51 24 62 30 30 24VDC
154 bi GMM10 CL101 G02 float switch start drainage pump water level I DI2110 AA29 1 51 25 62 30 30 24VDC
155 bi GMM10 CL101 G03 float switch start second pump water level I DI2110 AA29 1 51 26 62 30 30 24VDC
156 bi GMM10 CL101 G04 float switch alarming water level I DI2110 AA29 1 51 27 62 30 30 24VDC
157 bi GMM10 AP101 XB02 dewatering pump 1# off I DI2110 AA29 1 51 28 62 31 31 24VDC
158 bi GMM10 AP101 XB01 dewatering pump 1# on I DI2110 AA29 1 51 29 62 31 31 24VDC
159 bi GMM10 AP101 XM01 dewatering pump 1# electric failure I DI2110 AA29 1 51 30 62 30 30 24VDC A
160 bi GMM10 CF201 S01 dewatering pump 1# outlet flow too low I DI2110 AA29 1 51 31 62 30 30 24VDC A
161 bi GMM10 AP102 XB02 dewatering pump 2# off I DI2110 AA29 1 51 32 62 31 31 24VDC
162 bi GMM10 AP102 XB01 dewatering pump 2# on I DI2110 AA29 1 51 33 62 31 31 24VDC
163 bi GMM10 AP102 XM01 dewatering pump 2# electric failure I DI2110 AA29 1 51 34 62 30 30 24VDC A
164 bi GMM10 CF202 S01 dewatering pump 2# outlet flow too low I DI2110 AA29 1 51 35 62 30 30 24VDC A
165 bi Spare I DI2110 AA29 1 51 36 62 30 30 24VDC
166 bi Spare I DI2110 AA29 1 51 37 62 30 30 24VDC
167 bi Spare I DI2110 AA29 1 51 38 62 30 30 24VDC
168 bi Spare I DI2110 AA29 1 51 39 62 30 30 24VDC
169 bi Spare I DI2110 AA29 1 51 40 62 30 30 24VDC A
170 bi Spare I DI2110 AA29 1 51 41 62 30 30 24VDC A
171 bi MEA60 CG301 Man hole open alarm I DI2110 AA29 1 51 42 62 30 30 24VDC
172 bi spare I DI2110 AA29 1 51 43 62 30 30 24VDC
173 bi MEW30AT011 shaft sealing water filter 1 stop I DI2110 AA29 1 51 44 62 30 30 24VDC
174 bi MEW30AT011 shaft sealing water filter 1 running I DI2110 AA29 1 51 45 62 30 30 24VDC
175 bi MEW30AT011 shaft sealing water filter 1 fault I DI2110 AA29 1 51 46 62 30 30 24VDC
176 bi MEW30AT021 shaft sealing water filter 2 stop I DI2110 AA29 1 51 47 62 30 30 24VDC
177 bi MEW30AT021 shaft sealing water filter 2 running I DI2110 AA29 1 51 48 62 30 30 24VDC
178 bi MEW30AT021 shaft sealing water filter 2 fault I DI2110 AA29 1 51 49 62 30 30 24VDC
179 bi MEW30AP001-M01 shaft sealing water pump 1 OFF I DI2110 AA29 1 51 50 62 30 30 24VDC
180 bi MEW30AP001-M01 shaft sealing water pump 1 ON I DI2110 AA29 1 51 51 62 30 30 24VDC
181 bi MEW30AP002-M01 shaft sealing water pump 2 OFF I DI2110 AA29 1 51 52 62 30 30 24VDC
182 bi MEW30AP002-M01 shaft sealing water pump 2 ON I DI2110 AA29 1 51 53 62 30 30 24VDC
183 bi filter 4 running I DI2110 AA29 1 51 54 62 30 30 24VDC
184 bi filter 4 fault I DI2110 AA29 1 51 55 62 30 30 24VDC
185 bi Network Gateway 1 Inverter supply MCB summary fault I DI2110 AA29 1 51 56 62 30 30 24VDC
186 bi Network Gateway 1 220V DC MCB summary fault I DI2110 AA29 1 51 57 62 30 30 24VDC
187 bi Network Gateway 1 24V DC MCB summary fault I DI2110 AA29 1 51 58 62 30 30 24VDC
188 bi Network Gateway 1 Light/heat MCB fault I DI2110 AA29 1 51 59 62 30 30 24VDC
189 bi Network Gateway 2 Inverter supply MCB summary fault I DI2110 AA29 1 51 60 62 30 30 24VDC
190 bi Network Gateway 2 220V DC MCB summary fault I DI2110 AA29 1 51 61 62 30 30 24VDC
191 bi Network Gateway 2 24V DC MCB summary fault I DI2110 AA29 1 51 62 62 30 30 24VDC
192 bi Spare I DI2110 AA29 1 51 63 62 30 30 24VDC

19/38 2019/11/27
BMG Common( LCU10) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)

193 bi =20BLB10GH001 +20BLB10 Indoor Lighting Panel 1 Power Incoming Supply Failure I DI2110 AA29 1 51 0 63 31 31 24VDC
194 bi =20BLB10GH001 +20BLB10 Indoor Lighting Panel 1 Power Feeders Supply Failure I DI2110 AA29 1 51 1 63 31 31 24VDC
195 bi =20BLB20GH001 +20BLB20 Indoor Lighting Panel 2 Power Incoming Supply Failure I DI2110 AA29 1 51 2 63 30 30 24VDC A
196 bi =20BLB20GH001 +20BLB20 Indoor Lighting Panel 2 Power Feeders Supply Failure I DI2110 AA29 1 51 3 63 30 30 24VDC
197 bi =20BLB30GH001 +20BLB30 Indoor Lighting Panel 3 Power Incoming Supply Failure I DI2110 AA29 1 51 4 63 31 31 24VDC
198 bi =20BLB30GH001 +20BLB30 Indoor Lighting Panel 3 Power Feeders Supply Failure I DI2110 AA29 1 51 5 63 31 31 24VDC
199 bi =20BLB40GH001 +20BLB40 Indoor Lighting Panel 4 Power Incoming Supply Failure I DI2110 AA29 1 51 6 63 30 30 24VDC A
200 bi =20BLB40GH001 +20BLB40 Indoor Lighting Panel 4 Power Feeders Supply Failure I DI2110 AA29 1 51 7 63 30 30 24VDC
201 bi =20BLB50GH001 +20BLB50 Indoor Lighting Panel 5 Power Incoming Supply Failure I DI2110 AA29 1 51 8 63 30 30 24VDC
202 bi =20BLB50GH001 +20BLB50 Indoor Lighting Panel 5 Power Feeders Supply Failure I DI2110 AA29 1 51 9 63 30 30 24VDC
203 bi =20BLB60GH001 +20BLB60 Indoor Lighting Panel 6 Power Incoming Supply Failure I DI2110 AA29 1 51 10 63 30 30 24VDC
204 bi =20BLB60GH001 +20BLB60 Indoor Lighting Panel 6 Power Feeders Supply Failure I DI2110 AA29 1 51 11 63 30 30 24VDC
205 bi Spare I DI2110 AA29 1 51 12 63 31 31 24VDC
206 bi Spare I DI2110 AA29 1 51 13 63 31 31 24VDC
207 bi Spare I DI2110 AA29 1 51 14 63 30 30 24VDC A
208 bi Spare I DI2110 AA29 1 51 15 63 30 30 24VDC A
209 bi Spare I DI2110 AA29 1 51 16 63 30 30 24VDC
210 bi Spare I DI2110 AA29 1 51 17 63 30 30 24VDC
211 bi Spare I DI2110 AA29 1 51 18 63 31 31 24VDC
212 bi Spare I DI2110 AA29 1 51 19 63 31 31 24VDC
213 bi Spare I DI2110 AA29 1 51 20 63 30 30 24VDC A
214 bi Spare I DI2110 AA29 1 51 21 63 30 30 24VDC A
215 bi Spare I DI2110 AA29 1 51 22 63 30 30 24VDC
216 bi Spare I DI2110 AA29 1 51 23 63 30 30 24VDC
217 bi Spare I DI2110 AA29 1 51 24 63 30 30 24VDC
218 bi Spare I DI2110 AA29 1 51 25 63 30 30 24VDC
219 bi Spare I DI2110 AA29 1 51 26 63 30 30 24VDC
220 bi Spare I DI2110 AA29 1 51 27 63 30 30 24VDC
221 bi Spare I DI2110 AA29 1 51 28 63 31 31 24VDC
222 bi Spare I DI2110 AA29 1 51 29 63 31 31 24VDC
223 bi Spare I DI2110 AA29 1 51 30 63 30 30 24VDC A
224 bi Spare I DI2110 AA29 1 51 31 63 30 30 24VDC A
225 bi Spare I DI2110 AA29 1 51 32 63 31 31 24VDC
226 bi Spare I DI2110 AA29 1 51 33 63 31 31 24VDC
227 bi Spare I DI2110 AA29 1 51 34 63 30 30 24VDC A
228 bi Spare I DI2110 AA29 1 51 35 63 30 30 24VDC A
229 bi Spare I DI2110 AA29 1 51 36 63 30 30 24VDC
230 bi Spare I DI2110 AA29 1 51 37 63 30 30 24VDC
231 bi Spare I DI2110 AA29 1 51 38 63 30 30 24VDC
232 bi Spare I DI2110 AA29 1 51 39 63 30 30 24VDC
233 bi Spare I DI2110 AA29 1 51 40 63 30 30 24VDC A
234 bi Spare I DI2110 AA29 1 51 41 63 30 30 24VDC A
235 bi Spare I DI2110 AA29 1 51 42 63 30 30 24VDC
236 bi Spare I DI2110 AA29 1 51 43 63 30 30 24VDC
237 bi Spare I DI2110 AA29 1 51 44 63 30 30 24VDC
238 bi Spare I DI2110 AA29 1 51 45 63 30 30 24VDC
239 bi Spare I DI2110 AA29 1 51 46 63 30 30 24VDC
240 bi Spare I DI2110 AA29 1 51 47 63 30 30 24VDC
241 bi Spare I DI2110 AA29 1 51 48 63 30 30 24VDC
242 bi Spare I DI2110 AA29 1 51 49 63 30 30 24VDC
243 bi Spare I DI2110 AA29 1 51 50 63 30 30 24VDC
244 bi Spare I DI2110 AA29 1 51 51 63 30 30 24VDC
245 bi Spare I DI2110 AA29 1 51 52 63 30 30 24VDC
246 bi Spare I DI2110 AA29 1 51 53 63 30 30 24VDC
247 bi Spare I DI2110 AA29 1 51 54 63 30 30 24VDC
248 bi Spare I DI2110 AA29 1 51 55 63 30 30 24VDC
249 bi Spare I DI2110 AA29 1 51 56 63 30 30 24VDC
250 bi Spare I DI2110 AA29 1 51 57 63 30 30 24VDC
251 bi Spare I DI2110 AA29 1 51 58 63 30 30 24VDC
252 bi Spare I DI2110 AA29 1 51 59 63 30 30 24VDC
253 bi Spare I DI2110 AA29 1 51 60 63 30 30 24VDC
254 bi Spare I DI2110 AA29 1 51 61 63 30 30 24VDC
255 bi Spare I DI2110 AA29 1 51 62 63 30 30 24VDC

20/38 2019/11/27
BMG Common( LCU10) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)
256 bi Spare I DI2110 AA29 1 51 63 63 30 30 24VDC

21/38 2019/11/27
BMG Common( LCU10) / Digital Outputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Remarks
/Alarm(A)
1 bo =20BFA10GH001 +20BFA01 -Q01 SST1 incoming CB -Q01 open O DO2201 AA49 1 41 0 63 30 30
2 bo =20BFA10GH001 +20BFA01 -Q01 SST1 incoming CB -Q01 close O DO2201 AA49 1 41 1 63 30 30
3 bo =20BFB10GH001 +20BFB01 -Q02 SST2 incoming CB -Q02 open O DO2201 AA49 1 41 2 63 30 30
4 bo =20BFB10GH001 +20BFB01 -Q02 SST2 incoming CB -Q02 close O DO2201 AA49 1 41 3 63 30 30
5 bo =20BFC10GH001 +20BFC02 -Q03 SST3 incoming CB -Q03 open O DO2201 AA49 1 41 4 63 30 30
6 bo =20BFC10GH001 +20BFC02 -Q03 SST3 incoming CB -Q03 close O DO2201 AA49 1 41 5 63 30 30
7 bo =20BFC10GH001 +20BFC02 -Q04 DG incoming CB -Q04 open O DO2201 AA49 1 41 6 63 30 30
8 bo =20BFC10GH001 +20BFC02 -Q04 DG incoming CB -Q04 close O DO2201 AA49 1 41 7 63 30 30
9 bo =20BFC10GH001 +20BFC01 -Q05 Coupling CB with SST1 -Q05 open O DO2201 AA49 1 41 8 63 30 30
10 bo =20BFC10GH001 +20BFC01 -Q05 Coupling CB with SST1 -Q05 close O DO2201 AA49 1 41 9 63 30 30
11 bo =20BFC10GH001 +20BFC03 -Q06 Coupling CB with SST2 -Q06 open O DO2201 AA49 1 41 10 63 30 30
12 bo =20BFC10GH001 +20BFC03 -Q06 Coupling CB with SST2 -Q06 close O DO2201 AA49 1 41 11 63 30 30
13 bo =20XKA10GH001 +20XKA01 -X2 Diesel Generator Start O DO2201 AA49 1 41 12 63 30 30
14 bo =20XKA10GH001 +20XKA01 -X2 Diesel Generator Stop O DO2201 AA49 1 41 13 63 30 30
15 bo Spare O DO2201 AA49 1 41 14 63 30 30
16 bo Spare O DO2201 AA49 1 41 15 63 30 30
17 bo =01BAA30GD001 +01BAA30 SST1 13.8kV load break switch disconnector Q11 open O DO2201 AA49 1 41 16 63 30 30
18 bo =01BAA30GD001 +01BAA30 SST1 13.8kV load break switch disconnector Q11 close O DO2201 AA49 1 41 17 63 30 30
19 bo =03BAA30GD001 +03BAA30 SST2 13.8kV load break switch disconnector Q31 open O DO2201 AA49 1 41 18 63 30 30
20 bo =03BAA30GD001 +03BAA30 SST2 13.8kV load break switch disconnector Q31 close O DO2201 AA49 1 41 19 63 30 30
21 bo Spare O DO2201 AA49 1 41 20 63 30 30
22 bo Spare O DO2201 AA49 1 41 21 63 30 30
23 bo QEB01 AN001 YB02 air compressor 1# stop O DO2201 AA49 1 41 22 63 30 30
24 bo QEB01 AN001 YB01 air compressor 1# start O DO2201 AA49 1 41 23 63 30 30
25 bo QEB01 AN002 YB02 air compressor 2# stop O DO2201 AA49 1 41 24 63 30 30
26 bo QEB01 AN002 YB01 air compressor 2# start O DO2201 AA49 1 41 25 63 30 30
27 bo GMM10 AP001 YB02 drainage pump 1# stop O DO2201 AA49 1 41 26 63 30 30
28 bo GMM10 AP001 YB01 drainage pump 1# start O DO2201 AA49 1 41 27 63 30 30
29 bo GMM10 AP002 YB02 drainage pump 2# stop O DO2201 AA49 1 41 28 63 30 30
30 bo GMM10 AP002 YB01 drainage pump 2# start O DO2201 AA49 1 41 29 63 30 30
31 bo GMM10 AP101 YB02 dewatering pump 1# stop O DO2201 AA49 1 41 30 63 30 30
32 bo GMM10 AP101 YB01 dewatering pump 1# start O DO2201 AA49 1 41 31 63 30 30
33 bo GMM10 AP102 YB02 dewatering pump 2# stop O DO2201 AA49 1 41 32 63 30 30
34 bo GMM10 AP102 YB01 dewatering pump 2# start O DO2201 AA49 1 41 33 63 30 30
35 bo Spare O DO2201 AA49 1 41 34 63 30 30
36 bo Spare O DO2201 AA49 1 41 35 63 30 30
37 bo Spare O DO2201 AA49 1 41 36 63 30 30
38 bo Spare O DO2201 AA49 1 41 37 63 30 30
39 bo Spare O DO2201 AA49 1 41 38 63 30 30
40 bo Spare O DO2201 AA49 1 41 39 63 30 30

1 bo Spare O DO2201 AA53 1 41 0 64 30 30


2 bo Spare O DO2201 AA53 1 41 1 64 30 30
3 bo Spare O DO2201 AA53 1 41 2 64 30 30
4 bo Spare O DO2201 AA53 1 41 3 64 30 30
5 bo shaft sealing water filter 1 Stop O DO2201 AA53 1 41 4 64 30 30
6 bo shaft sealing water filter 1 Start O DO2201 AA53 1 41 5 64 30 30
7 bo shaft sealing water filter 2 Stop O DO2201 AA53 1 41 6 64 30 30
8 bo shaft sealing water filter 2 Start O DO2201 AA53 1 41 7 64 30 30
9 bo MEW30AP001-M01 shaft sealing water pump 1 STOP O DO2201 AA53 1 41 8 64 30 30
10 bo MEW30AP001-M01 shaft sealing water pump 1 START O DO2201 AA53 1 41 9 64 30 30
11 bo MEW30AP002-M01 shaft sealing water pump 2 STOP O DO2201 AA53 1 41 10 64 30 30
12 bo MEW30AP002-M01 shaft sealing water pump 2 START O DO2201 AA53 1 41 11 64 30 30
13 bo Spare O DO2201 AA53 1 41 12 64 30 30
14 bo Spare O DO2201 AA53 1 41 13 64 30 30
15 bo Spare O DO2201 AA53 1 41 14 64 30 30
16 bo Spare O DO2201 AA53 1 41 15 64 30 30
17 bo Spare O DO2201 AA53 1 41 16 64 30 30
18 bo Spare O DO2201 AA53 1 41 17 64 30 30
19 bo Spare O DO2201 AA53 1 41 18 64 30 30
20 bo Spare O DO2201 AA53 1 41 19 64 30 30
21 bo Spare O DO2201 AA53 1 41 20 64 30 30

22/38 2019/11/27
BMG Common( LCU10) / Digital Outputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Remarks
/Alarm(A)
22 bo Spare O DO2201 AA53 1 41 21 64 30 30
23 bo Spare O DO2201 AA53 1 41 22 64 30 30
24 bo Spare O DO2201 AA53 1 41 23 64 30 30
25 bo Spare O DO2201 AA53 1 41 24 64 30 30
26 bo Spare O DO2201 AA53 1 41 25 64 30 30
27 bo Spare O DO2201 AA53 1 41 26 64 30 30
28 bo Spare O DO2201 AA53 1 41 27 64 30 30
29 bo Spare O DO2201 AA53 1 41 28 64 30 30
30 bo Spare O DO2201 AA53 1 41 29 64 30 30
31 bo Spare O DO2201 AA53 1 41 30 64 30 30
32 bo Spare O DO2201 AA53 1 41 31 64 30 30
33 bo Spare O DO2201 AA53 1 41 32 64 30 30
34 bo Spare O DO2201 AA53 1 41 33 64 30 30
35 bo Spare O DO2201 AA53 1 41 34 64 30 30
36 bo Spare O DO2201 AA53 1 41 35 64 30 30
37 bo Spare O DO2201 AA53 1 41 36 64 30 30
38 bo Spare O DO2201 AA53 1 41 37 64 30 30
39 bo Spare O DO2201 AA53 1 41 38 64 30 30
40 bo Spare O DO2201 AA53 1 41 39 64 30 30

23/38 2019/11/27
BMG Common ( LCU10) / Analog Inputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name Source Terminal Box I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Unit Range Remarks
1 an =20BUA10GH001 +20BUA01 1# 220V DC bus voltage 400VAC I AI2300 AA65 1 41 0 65 30 36 V 0-450
2 an =20BUA10GH001 +20BUA01 1# 220V DC bus current 400VAC I AI2300 AA65 1 41 1 65 30 36 V 0-450
3 an =20BTL10GH001 +20BTL01 1# rectifier voltage 400VAC I AI2300 AA65 1 41 2 65 30 36 A 0-100
4 an =20BTL10GH001 +20BTL01 1# rectifier current 400VAC I AI2300 AA65 1 41 3 65 30 36 A 0-100
5 an =20BTL10GH001 +20BTL01 1# 220V battery voltage 400VAC I AI2300 AA65 1 41 4 65 30 36 V 0-300
6 an =20BTL10GH001 +20BTL01 1# 220V battery current 400VAC I AI2300 AA65 1 41 5 65 30 36 V 0-300
7 an =20BUB10GH001 +20BUB01 2# 220V DC bus voltage 220VDC I AI2300 AA65 1 41 6 65 30 36 A 0-50
8 an =20BUB10GH001 +20BUB01 2# 220V DC bus current 220VDC I AI2300 AA65 1 41 7 65 30 36 V 0-300
9 an =20BTM10GH001 +20BTM01 2# rectifier voltage I AI2300 AA65 1 41 8 65 30 36
10 an =20BTM10GH001 +20BTM01 2# rectifier current I AI2300 AA65 1 41 9 65 30 36
11 an =20BTM10GH001 +20BTM01 2# 220V battery voltage I AI2300 AA65 1 41 10 65 30 36
12 an =20BTM10GH001 +20BTM01 2# 220V battery current I AI2300 AA65 1 41 11 65 30 36
13 an =20BRA10GH001 +20BRA01 1# Inverter UPS output current I AI2300 AA65 1 41 12 65 30 36
14 an =20BRA10GH001 +20BRA01 1# Inverter UPS output voltage I AI2300 AA65 1 41 13 65 30 36
15 an =20BRB10GH001 +20BRB01 2# Inverter UPS output current I AI2300 AA65 1 41 14 65 30 36
16 an =20BRB10GH001 +20BRB01 2# Inverter UPS output voltage I AI2300 AA65 1 41 15 65 30 36

17 an QEB01 CP001 pressure sensor for air receiver 1# I AI2300 AA69 1 41 0 66 30 36 0~10bar
18 an GMM10 CL001 XQ01 level sensor for drainage pit I AI2300 AA69 1 41 1 66 30 36 0~3.5m
19 an GMM10 CP501 B01 drainage pump 1# inlet water flow I AI2300 AA69 1 41 2 66 30 36 0~10bar
20 an GMM 10 CP502 B01 drainage pump 1# outlet water flow I AI2300 AA69 1 41 3 66 30 36 0~10bar
21 an GMM10 CP001 B01 pressure transmitter for pump common inlet I AI2300 AA69 1 41 4 66 30 36 0~100%
22 an GMM10 CP503 B01 drainage pump 2# inlet water flow I AI2300 AA69 1 41 5 66 30 36 0~100%
23 an GMM 10 CP504 B01 drainage pump 2# outlet water flow I AI2300 AA69 1 41 6 66 30 36
24 an CFA10 CP001 Reservoir water level measuring I AI2300 AA69 1 41 7 66 30 36
25 an CFA10 CP201 Tail water level measuring I AI2300 AA69 1 41 8 66 30 36 0~100%
26 an CFA10 CP101 Pressure transmitter after trash rack I AI2300 AA69 1 41 9 66 30 36 0~100%
27 an I AI2300 AA69 1 41 10 66 30 36
28 an I AI2300 AA69 1 41 11 66 30 36
29 an I AI2300 AA69 1 41 12 66 30 36
30 an I AI2300 AA69 1 41 13 66 30 36
31 an I AI2300 AA69 1 41 14 66 30 36
32 an I AI2300 AA69 1 41 15 66 30 36

24/38 2019/11/27
BMG Switchyard (LCU20) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind KKS0 KKS1 KKS2 KKS3 Signal Name Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)
1 bi LCU20 Control Mode Remote AA21 1 61 0 60 30 30 24VDC
2 bi LCU20 Control Mode Local AA21 1 61 1 60 30 30 24VDC
3 bi LCU20 Control Mode Revision AA21 1 61 2 60 30 30 24VDC
4 bi LCU20 220VDC Power 1 Supply Failure AA21 1 61 3 60 30 30 24VDC
5 bi LCU20 220VDC Power 2 Supply Failure AA21 1 61 4 60 30 30 24VDC
6 bi LCU20 24VDC Power Supply Failure AA21 1 61 5 60 30 30 24VDC
7 bi LCU20 Synchronization Automatic AA21 1 61 6 60 30 30 24VDC
8 bi LCU20 Synchronization Manual AA21 1 61 7 60 30 30 24VDC
9 bi LCU20 SYN3000 Fault AA21 1 61 8 60 30 30 24VDC
10 bi LCU20 Power Converter 1 OK AA21 1 61 9 60 30 30 24VDC
11 bi LCU20 Light Power Fault AA21 1 61 10 60 30 30 24VDC
12 bi Spare AA21 1 61 11 60 30 30 24VDC
13 bi Spare AA21 1 61 12 60 30 30 24VDC
14 bi Spare AA21 1 61 13 60 30 30 24VDC
15 bi Spare AA21 1 61 14 60 30 30 24VDC
16 bi Spare AA21 1 61 15 60 30 30 24VDC
17 bi =11AEA03GS100 +11AEA03 -Q01 115kV Line 1 11AEA03GS100-Q01 Circuit Breaker Open AA21 1 61 16 60 31 31 24VDC
18 bi =11AEA03GS100 +11AEA03 -Q01 115kV Line 1 11AEA03GS100-Q01 Circuit Breaker Closed AA21 1 61 17 60 31 31 24VDC
19 bi =11AEA03GS110 +11AEA03 -Q01 115kV Line 1 11AEA03GS110-Q01 Disconnector Open AA21 1 61 18 60 31 31 24VDC
20 bi =11AEA03GS110 +11AEA03 -Q01 115kV Line 1 11AEA03GS110-Q01 Disconnector Closed AA21 1 61 19 60 31 31 24VDC
21 bi =11AEA03GS120 +11AEA03 -Q01 115kV Line 1 11AEA03GS120-Q01 Disconnector Open AA21 1 61 20 60 31 31 24VDC
22 bi =11AEA03GS120 +11AEA03 -Q01 115kV Line 1 11AEA03GS120-Q01 Disconnector Closed AA21 1 61 21 60 31 31 24VDC
23 bi Spare AA21 1 61 22 60 31 31 24VDC
24 bi Spare AA21 1 61 23 60 31 31 24VDC
25 bi =11AEA03GS191 +11AEA03 -Q01 115kV Line 1 11AEA03GS191-Q01 Earthing Switch Open AA21 1 61 24 60 31 31 24VDC
26 bi =11AEA03GS191 +11AEA03 -Q01 115kV Line 1 11AEA03GS191-Q01 Earthing Switch Closed AA21 1 61 25 60 31 31 24VDC
27 bi =11AEA03GS192 +11AEA03 -Q01 115kV Line 1 11AEA03GS192-Q01 Earthing Switch Open AA21 1 61 26 60 31 31 24VDC
28 bi =11AEA03GS192 +11AEA03 -Q01 115kV Line 1 11AEA03GS192-Q01 Earthing Switch Closed AA21 1 61 27 60 31 31 24VDC
29 bi =11AEA03GS193 +11AEA03 -Q01 115kV Line 1 11AEA03GS193-Q01 Earthing Switch Open AA21 1 61 28 60 31 31 24VDC
30 bi =11AEA03GS193 +11AEA03 -Q01 115kV Line 1 11AEA03GS193-Q01 Earthing Switch Closed AA21 1 61 29 60 31 31 24VDC
31 bi Spare AA21 1 61 30 60 31 31 24VDC
32 bi Spare AA21 1 61 31 60 31 31 24VDC
33 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay CB motor over current over time AA21 1 61 32 60 30 30 24VDC
34 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay contol MCB trip AA21 1 61 33 60 30 30 24VDC
35 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay indication&heater MCB trip AA21 1 61 34 60 30 30 24VDC
36 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay motor MCB trip AA21 1 61 35 60 30 30 24VDC
37 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay VT MCB trip AA21 1 61 36 60 30 30 24VDC
38 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay CB SF6 pressure low alarm AA21 1 61 37 60 30 30 24VDC
39 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay G1 SF6 pressure low alarm AA21 1 61 38 60 30 30 24VDC
40 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay G2 SF6 pressure low alarm AA21 1 61 39 60 30 30 24VDC
41 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay G3 SF6 pressure low alarm AA21 1 61 40 60 30 30 24VDC
42 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay G4 SF6 pressure low alarm AA21 1 61 41 60 30 30 24VDC
43 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay alarm power fault AA21 1 61 42 60 30 30 24VDC
44 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay alarm device fault AA21 1 61 43 60 30 30 24VDC
45 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay DES/FES remote position AA21 1 61 44 60 30 30 24VDC
46 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay DES/FES local position AA21 1 61 45 60 30 30 24VDC
47 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay CB remote position AA21 1 61 46 60 30 30 24VDC
48 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay CB local position AA21 1 61 47 60 30 30 24VDC
49 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay bypass signal AA21 1 61 48 60 30 30 24VDC
50 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay alarm power MCB trip AA21 1 61 49 60 30 30 24VDC
51 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay SF6 pressure low lockout AA21 1 61 50 60 30 30 24VDC
52 bi =11AEA03GH001 +11AEA03 110kV Line 1 bay CB motor running AA21 1 61 51 60 30 30 24VDC
53 bi Spare AA21 1 61 52 60 30 30 24VDC
54 bi Spare AA21 1 61 53 60 30 30 24VDC
55 bi Spare AA21 1 61 54 60 30 30 24VDC
56 bi Spare AA21 1 61 55 60 30 30 24VDC
57 bi =11AEA05GS191 +11AEA05 -Q01 115kV Bus-bar 11AEA05GS191-Q01 Earthing Switch Open AA21 1 61 56 60 31 31 24VDC
58 bi =11AEA05GS191 +11AEA05 -Q01 115kV Bus-bar 11AEA05GS191-Q01 Earthing Switch Closed AA21 1 61 57 60 31 31 24VDC
59 bi Spare AA21 1 61 58 60 30 30 24VDC
60 bi Spare AA21 1 61 59 60 30 30 24VDC
61 bi 110kV Bus bar PROTECTION MCB OFF AA21 1 61 60 60 30 30 24VDC

25/38 2019/11/27
BMG Switchyard (LCU20) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind KKS0 KKS1 KKS2 KKS3 Signal Name Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)
62 bi 110kV Bus bar FIELD PROTECTION RELAY FAULT AA21 1 61 61 60 30 30 24VDC
63 bi 110kV Bus bar CENTRAL UNIT DRS-MBB RELAY FAULT AA21 1 61 62 60 30 30 24VDC
64 bi Spare AA21 1 61 63 60 30 30 24VDC

65 bi =11AEA04GS100 +11AEA04 -Q01 115kV Line 2 11AEA04GS100-Q01 Circuit Breaker Open AA25 1 61 0 61 31 31 24VDC
66 bi =11AEA04GS100 +11AEA04 -Q01 115kV Line 2 11AEA04GS100-Q01 Circuit Breaker Closed AA25 1 61 1 61 31 31 24VDC
67 bi =11AEA04GS110 +11AEA04 -Q01 115kV Line 2 11AEA04GS110-Q01 Disconnector Open AA25 1 61 2 61 31 31 24VDC
68 bi =11AEA04GS110 +11AEA04 -Q01 115kV Line 2 11AEA04GS110-Q01 Disconnector Closed AA25 1 61 3 61 31 31 24VDC
69 bi =11AEA04GS120 +11AEA04 -Q01 115kV Line 2 11AEA04GS120-Q01 Disconnector Open AA25 1 61 4 61 31 31 24VDC
70 bi =11AEA04GS120 +11AEA04 -Q01 115kV Line 2 11AEA04GS120-Q01 Disconnector Closed AA25 1 61 5 61 31 31 24VDC
71 bi Spare AA25 1 61 6 61 31 31 24VDC
72 bi Spare AA25 1 61 7 61 31 31 24VDC
73 bi =11AEA04GS191 +11AEA04 -Q01 115kV Line 2 11AEA04GS191-Q01 Earthing Switch Open AA25 1 61 8 61 31 31 24VDC
74 bi =11AEA04GS191 +11AEA04 -Q01 115kV Line 2 11AEA04GS191-Q01 Earthing Switch Closed AA25 1 61 9 61 31 31 24VDC
75 bi =11AEA04GS192 +11AEA04 -Q01 115kV Line 2 11AEA04GS192-Q01 Earthing Switch Open AA25 1 61 10 61 31 31 24VDC
76 bi =11AEA04GS192 +11AEA04 -Q01 115kV Line 2 11AEA04GS192-Q01 Earthing Switch Closed AA25 1 61 11 61 31 31 24VDC
77 bi =11AEA04GS193 +11AEA04 -Q01 115kV Line 2 11AEA04GS193-Q01 Earthing Switch Open AA25 1 61 12 61 31 31 24VDC
78 bi =11AEA04GS193 +11AEA04 -Q01 115kV Line 2 11AEA04GS193-Q01 Earthing Switch Closed AA25 1 61 13 61 31 31 24VDC
79 bi Spare AA25 1 61 14 61 31 31 24VDC
80 bi Spare AA25 1 61 15 61 31 31 24VDC
81 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay DES/FES remote position AA25 1 61 16 61 30 30 24VDC
82 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay DES/FES local position AA25 1 61 17 61 30 30 24VDC
83 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay CB remote position AA25 1 61 18 61 30 30 24VDC
84 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay CB local position AA25 1 61 19 61 30 30 24VDC
85 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay bypass signal AA25 1 61 20 61 30 30 24VDC
86 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay alarm power MCB trip AA25 1 61 21 61 30 30 24VDC
87 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay SF6 pressure low lockout AA25 1 61 22 61 30 30 24VDC
88 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay CB motor running AA25 1 61 23 61 30 30 24VDC
89 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay CB motor over current over time AA25 1 61 24 61 30 30 24VDC
90 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay contol MCB trip AA25 1 61 25 61 30 30 24VDC
91 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay indication&heater MCB trip AA25 1 61 26 61 30 30 24VDC
92 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay motor MCB trip AA25 1 61 27 61 30 30 24VDC
93 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay VT MCB trip AA25 1 61 28 61 30 30 24VDC
94 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay CB SF6 pressure low alarm AA25 1 61 29 61 30 30 24VDC
95 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay G1 SF6 pressure low alarm AA25 1 61 30 61 30 30 24VDC
96 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay G2 SF6 pressure low alarm AA25 1 61 31 61 30 30 24VDC
97 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay G3 SF6 pressure low alarm AA25 1 61 32 61 30 30 24VDC
98 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay G4 SF6 pressure low alarm AA25 1 61 33 61 30 30 24VDC
99 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay alarm power fault AA25 1 61 34 61 30 30 24VDC
100 bi =11AEA04GH001 +11AEA04 110kV Line 2 bay alarm device fault AA25 1 61 35 61 30 30 24VDC
101 bi Spare AA25 1 61 36 61 30 30 24VDC
102 bi Spare AA25 1 61 37 61 30 30 24VDC
103 bi =11AEA01GS100 +11AEA01 -Q01 115kV MTR1 11AEA01GS100-Q01 Circuit Breaker Open AA25 1 61 38 61 31 31 24VDC
104 bi =11AEA01GS100 +11AEA01 -Q01 115kV MTR1 11AEA01GS100-Q01 Circuit Breaker Closed AA25 1 61 39 61 31 31 24VDC
105 bi =11AEA01GS110 +11AEA01 -Q01 115kV MTR1 11AEA01GS110-Q01 Disconnector Open AA25 1 61 40 61 31 31 24VDC
106 bi =11AEA01GS110 +11AEA01 -Q01 115kV MTR1 11AEA01GS110-Q01 Disconnector Closed AA25 1 61 41 61 31 31 24VDC
107 bi Spare AA25 1 61 42 61 31 31 24VDC
108 bi Spare AA25 1 61 43 61 31 31 24VDC
109 bi =11AEA01GS191 +11AEA01 -Q01 115kV MTR1 11AEA01GS191-Q01 Earthing Switch Open AA25 1 61 44 61 31 31 24VDC
110 bi =11AEA01GS191 +11AEA01 -Q01 115kV MTR1 11AEA01GS191-Q01 Earthing Switch Closed AA25 1 61 45 61 31 31 24VDC
111 bi =11AEA01GS192 +11AEA01 -Q01 115kV MTR1 11AEA01GS192-Q01 Earthing Switch Open AA25 1 61 46 61 31 31 24VDC
112 bi =11AEA01GS192 +11AEA01 -Q01 115kV MTR1 11AEA01GS192-Q01 Earthing Switch Closed AA25 1 61 47 61 31 31 24VDC
113 bi Spare AA25 1 61 48 61 30 30 24VDC
114 bi Spare AA25 1 61 49 61 30 30 24VDC
115 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay CB motor over current over time AA25 1 61 50 61 30 30 24VDC
116 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay contol MCB trip AA25 1 61 51 61 30 30 24VDC
117 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay indication & heater MCB trip AA25 1 61 52 61 30 30 24VDC
118 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay motor MCB trip AA25 1 61 53 61 30 30 24VDC
119 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay VT MCB trip AA25 1 61 54 61 30 30 24VDC
120 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay alarm power fault AA25 1 61 55 61 30 30 24VDC
121 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay alarm device fault AA25 1 61 56 61 30 30 24VDC
122 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay DES/FES remote position AA25 1 61 57 61 30 30 24VDC

26/38 2019/11/27
BMG Switchyard (LCU20) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind KKS0 KKS1 KKS2 KKS3 Signal Name Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)
123 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay DES/FES local position AA25 1 61 58 61 30 30 24VDC
124 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay CB remote position AA25 1 61 59 61 30 30 24VDC
125 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay CB local position AA25 1 61 60 61 30 30 24VDC
126 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay bypass signal AA25 1 61 61 61 30 30 24VDC
127 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay alarm power MCB trip AA25 1 61 62 61 30 30 24VDC
128 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay CB motor running AA25 1 61 63 61 30 30 24VDC

129 bi =11AEA02GS100 +11AEA02 -Q01 115kV MTR2 11AEA02GS100-Q01 Circuit Breaker Open AA29 1 61 0 62 31 31 24VDC
130 bi =11AEA02GS100 +11AEA02 -Q01 115kV MTR2 11AEA02GS100-Q01 Circuit Breaker Closed AA29 1 61 1 62 31 31 24VDC
131 bi =11AEA02GS110 +11AEA02 -Q01 115kV MTR2 11AEA02GS110-Q01 Disconnector Open AA29 1 61 2 62 31 31 24VDC
132 bi =11AEA02GS110 +11AEA02 -Q01 115kV MTR2 11AEA02GS110-Q01 Disconnector Closed AA29 1 61 3 62 31 31 24VDC
133 bi Spare AA29 1 61 4 62 31 31 24VDC
134 bi Spare AA29 1 61 5 62 31 31 24VDC
135 bi =11AEA02GS191 +11AEA02 -Q01 115kV MTR2 11AEA02GS191-Q01 Earthing Switch Open AA29 1 61 6 62 31 31 24VDC
136 bi =11AEA02GS191 +11AEA02 -Q01 115kV MTR2 11AEA02GS191-Q01 Earthing Switch Closed AA29 1 61 7 62 31 31 24VDC
137 bi =11AEA02GS192 +11AEA02 -Q01 115kV MTR2 11AEA02GS192-Q01 Earthing Switch Open AA29 1 61 8 62 31 31 24VDC
138 bi =11AEA02GS192 +11AEA02 -Q01 115kV MTR2 11AEA02GS192-Q01 Earthing Switch Closed AA29 1 61 9 62 31 31 24VDC
139 bi Spare AA29 1 61 10 62 31 31 24VDC
140 bi Spare AA29 1 61 11 62 31 31 24VDC
141 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay CB motor over current over time AA29 1 61 12 62 30 30 24VDC
142 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay contol MCB trip AA29 1 61 13 62 30 30 24VDC
143 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay indication &heater MCB trip AA29 1 61 14 62 30 30 24VDC
144 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay motor MCB trip AA29 1 61 15 62 30 30 24VDC
145 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay VT MCB trip AA29 1 61 16 62 30 30 24VDC
146 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay alarm power fault AA29 1 61 17 62 30 30 24VDC
147 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay alarm device fault AA29 1 61 18 62 30 30 24VDC
148 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay DES/FES remote position AA29 1 61 19 62 30 30 24VDC
149 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay DES/FES local position AA29 1 61 20 62 30 30 24VDC
150 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay CB remote position AA29 1 61 21 62 30 30 24VDC
151 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay CB local position AA29 1 61 22 62 30 30 24VDC
152 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay bypass signal AA29 1 61 23 62 30 30 24VDC
153 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay alarm power MCB trip AA29 1 61 24 62 30 30 24VDC
154 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay CB motor running AA29 1 61 25 62 30 30 24VDC
155 bi Spare AA29 1 61 26 62 30 30 24VDC
156 bi Spare AA29 1 61 27 62 30 30 24VDC
157 bi =11AEA08GH001 +11AEA08 110kV VT bay control MCB trip AA29 1 61 28 62 30 30 24VDC
158 bi =11AEA08GH001 +11AEA08 110kV VT bay indication MCB trip AA29 1 61 29 62 30 30 24VDC
159 bi =11AEA08GH001 +11AEA08 110kV VT bay motor MCB trip AA29 1 61 30 62 30 30 24VDC
160 bi =11AEA08GH001 +11AEA08 110kV VT bay heater MCB trip AA29 1 61 31 62 30 30 24VDC
161 bi =11AEA08GH001 +11AEA08 110kV VT bay VT1 MCB trip AA29 1 61 32 62 30 30 24VDC
162 bi =11AEA08GH001 +11AEA08 110kV VT bay VT2 MCB trip AA29 1 61 33 62 30 30 24VDC
163 bi =11AEA08GH001 +11AEA08 110kV VT bay G1 SF6 pressure low alarm AA29 1 61 34 62 30 30 24VDC
164 bi =11AEA08GH001 +11AEA08 110kV VT bay G2 SF6 pressure low alarm AA29 1 61 35 62 30 30 24VDC
165 bi =11AEA08GH001 +11AEA08 110kV VT bay G3 SF6 pressure low alarm AA29 1 61 36 62 30 30 24VDC
166 bi =11AEA08GH001 +11AEA08 110kV VT bay G4 SF6 pressure low alarm AA29 1 61 37 62 30 30 24VDC
167 bi =11AEA08GH001 +11AEA08 110kV VT bay alarm power fault AA29 1 61 38 62 30 30 24VDC
168 bi =11AEA08GH001 +11AEA08 110kV VT bay alarm device fault AA29 1 61 39 62 30 30 24VDC
169 bi =11AEA08GH001 +11AEA08 110kV VT bay FES mimic position AA29 1 61 40 62 30 30 24VDC
170 bi =11AEA08GH001 +11AEA08 110kV VT bay FES maintenance position AA29 1 61 41 62 30 30 24VDC
171 bi =11AEA08GH001 +11AEA08 110kV VT bay bypass signal AA29 1 61 42 62 30 30 24VDC
172 bi =11AEA08GH001 +11AEA08 110kV VT bay alarm power MCB trip AA29 1 61 43 62 30 30 24VDC
173 bi Spare AA29 1 61 44 62 30 30 24VDC
174 bi Spare AA29 1 61 45 62 30 30 24VDC
175 bi 115kV Line 1 PROTECTION MCB OFF AA29 1 61 46 62 30 30 24VDC
176 bi 115kV Line 1 FIELD PROTECTION RELAY FAULT AA29 1 61 47 62 30 30 24VDC
177 bi 115kV Line 1 DISTANCE PROTECTION ZONE1 TRIP AA29 1 61 48 62 30 30 24VDC
178 bi 115kV Line 1 DISTANCE PROTECTION ZONE2 TRIP AA29 1 61 49 62 30 30 24VDC
179 bi 115kV Line 1 DISTANCE PROTECTION ZONE3 TRIP AA29 1 61 50 62 30 30 24VDC
180 bi 115kV Line 1 DISTANCE PROTECTION ZONE4 TRIP AA29 1 61 51 62 30 30 24VDC
181 bi 115kV Line 1 SWITCH ONTO FAULT PROTECTION TRIP AA29 1 61 52 62 30 30 24VDC
182 bi 115kV Line 1 AUTO-RECLOSE CAMMAND AA29 1 61 53 62 30 30 24VDC

27/38 2019/11/27
BMG Switchyard (LCU20) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind KKS0 KKS1 KKS2 KKS3 Signal Name Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)
183 bi 115kV Line 1 TELE-COMMUNICATION ASSISTED PROTECTION TRIP AA29 1 61 54 62 30 30 24VDC
184 bi 115kV Line 1 LINE CB NOT READY TO LCU AA29 1 61 55 62 30 30 24VDC
185 bi 115kV Line 1 AR ON(AUTO-RECLOSE SWITCH ON) AA29 1 61 56 62 30 30 24VDC
186 bi 115kV Line 1 LINE OVER CURRENT PROTECTION TRIP AA29 1 61 57 62 30 30 24VDC
187 bi 115kV Line 1 LINE DIRECTIONAL EARTH FAULT PROTECTION TRIP AA29 1 61 58 62 30 30 24VDC
188 bi 115kV Line 1 LINE DIFFERENTIAL PROTECTION TRIP AA29 1 61 59 62 30 30 24VDC
189 bi 115kV Line 1 LINE DIFFERENTIAL PROTECTION CHANNEL FAIL AA29 1 61 60 62 30 30 24VDC
190 bi 115kV Line 1 LINE CB COIL1 TRIP CIRCUIT FAILURE AA29 1 61 61 62 30 30 24VDC
191 bi 115kV Line 1 LINE CB COIL2 TRIP CIRCUIT FAILURE AA29 1 61 62 62 30 30 24VDC
192 bi Spare AA29 1 61 63 62 30 30 24VDC

193 bi 115kV Line 2 PROTECTION MCB OFF AA33 1 61 0 63 30 30 24VDC


194 bi 115kV Line 2 FIELD PROTECTION RELAY FAULT AA33 1 61 1 63 30 30 24VDC
195 bi 115kV Line 2 DISTANCE PROTECTION ZONE1 TRIP AA33 1 61 2 63 30 30 24VDC
196 bi 115kV Line 2 DISTANCE PROTECTION ZONE2 TRIP AA33 1 61 3 63 30 30 24VDC
197 bi 115kV Line 2 DISTANCE PROTECTION ZONE3 TRIP AA33 1 61 4 63 30 30 24VDC
198 bi 115kV Line 2 DISTANCE PROTECTION ZONE4 TRIP AA33 1 61 5 63 30 30 24VDC
199 bi 115kV Line 2 SWITCH ONTO FAULT PROTECTION TRIP AA33 1 61 6 63 30 30 24VDC
200 bi 115kV Line 2 AUTO-RECLOSE CAMMAND AA33 1 61 7 63 30 30 24VDC
201 bi 115kV Line 2 TELE-COMMUNICATION ASSISTED PROTECTION TRIP AA33 1 61 8 63 30 30 24VDC
202 bi 115kV Line 2 LINE CB NOT READY TO LCU AA33 1 61 9 63 30 30 24VDC
203 bi 115kV Line 2 AR ON(AUTO-RECLOSE SWITCH ON) AA33 1 61 10 63 30 30 24VDC
204 bi 115kV Line 2 LINE OVER CURRENT PROTECTION TRIP AA33 1 61 11 63 30 30 24VDC
205 bi 115kV Line 2 LINE DIRECTIONAL EARTH FAULT PROTECTION TRIP AA33 1 61 12 63 30 30 24VDC
206 bi 115kV Line 2 LINE DIFFERENTIAL PROTECTION TRIP AA33 1 61 13 63 30 30 24VDC
207 bi 115kV Line 2 LINE DIFFERENTIAL PROTECTION CHANNEL FAIL AA33 1 61 14 63 30 30 24VDC
208 bi 115kV Line 2 LINE CB COIL1 TRIP CIRCUIT FAILURE AA33 1 61 15 63 30 30 24VDC
209 bi 115kV Line 2 LINE CB COIL2 TRIP CIRCUIT FAILURE AA33 1 61 16 63 30 30 24VDC
210 bi Spare AA33 1 61 17 63 30 30 24VDC
211 bi Spare AA33 1 61 18 63 30 30 24VDC
212 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay CB SF6 pressure low alarm AA33 1 61 19 63 30 30 24VDC
213 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay G1 SF6 pressure low alarm AA33 1 61 20 63 30 30 24VDC
214 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay G2 SF6 pressure low alarm AA33 1 61 21 63 30 30 24VDC
215 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay G3 SF6 pressure low alarm AA33 1 61 22 63 30 30 24VDC
216 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay G4 SF6 pressure low alarm AA33 1 61 23 63 30 30 24VDC
217 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay G5 SF6 pressure low alarm AA33 1 61 24 63 30 30 24VDC
218 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay G6 SF6 pressure low alarm AA33 1 61 25 63 30 30 24VDC
219 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay G7 SF6 pressure low alarm AA33 1 61 26 63 30 30 24VDC
220 bi =11AEA01GH001 +11AEA01 110kV MTR1 bay SF6 pressure low lockout AA33 1 61 27 63 30 30 24VDC
221 bi Spare AA33 1 61 28 63 30 30 24VDC
222 bi Spare AA33 1 61 29 63 30 30 24VDC
223 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay CB SF6 pressure low alarm AA33 1 61 30 63 30 30 24VDC
224 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay G1 SF6 pressure low alarm AA33 1 61 31 63 30 30 24VDC
225 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay G2 SF6 pressure low alarm AA33 1 61 32 63 30 30 24VDC
226 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay G3 SF6 pressure low alarm AA33 1 61 33 63 30 30 24VDC
227 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay G4 SF6 pressure low alarm AA33 1 61 34 63 30 30 24VDC
228 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay G5 SF6 pressure low alarm AA33 1 61 35 63 30 30 24VDC
229 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay G6 SF6 pressure low alarm AA33 1 61 36 63 30 30 24VDC
230 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay G7 SF6 pressure low alarm AA33 1 61 37 63 30 30 24VDC
231 bi =11AEA02GH001 +11AEA02 110kV MTR2 bay SF6 pressure low lockout AA33 1 61 38 63 30 30 24VDC
232 bi Spare AA33 1 61 39 63 30 30 24VDC
233 bi Spare AA33 1 61 40 63 30 30 24VDC
234 bi =20BLB10GH001 +20BLB10 Indoor Lighting Board 1 Power Incoming Supply Trip AA33 1 61 41 63 30 30 24VDC
235 bi =20BLB10GH001 +20BLB10 Indoor Lighting Board 1 Feeders Group Trip AA33 1 61 42 63 30 30 24VDC
236 bi =20BLB20GH001 +20BLB20 Indoor Lighting Board 2 Power Incoming Supply Trip AA33 1 61 43 63 30 30 24VDC
237 bi =20BLB20GH001 +20BLB20 Indoor Lighting Board 2 Feeders Group Trip AA33 1 61 44 63 30 30 24VDC
238 bi =20BLB30GH001 +20BLB30 Indoor Lighting Board 3 Power Incoming Supply Trip AA33 1 61 45 63 30 30 24VDC
239 bi =20BLB30GH001 +20BLB30 Indoor Lighting Board 3 Feeders Group Trip AA33 1 61 46 63 30 30 24VDC
240 bi =20BLB40GH001 +20BLB40 Indoor Lighting Board 4 Power Incoming Supply Trip AA33 1 61 47 63 30 30 24VDC
241 bi =20BLB40GH001 +20BLB40 Indoor Lighting Board 4 Feeders Group Trip AA33 1 61 48 63 30 30 24VDC
242 bi =20BLB50GH001 +20BLB50 Indoor Lighting Board 5 Power Incoming Supply Trip AA33 1 61 49 63 30 30 24VDC
243 bi =20BLB50GH001 +20BLB50 Indoor Lighting Board 5 Feeders Group Trip AA33 1 61 50 63 30 30 24VDC

28/38 2019/11/27
BMG Switchyard (LCU20) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind KKS0 KKS1 KKS2 KKS3 Signal Name Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Voltage Buzzer(Y/N) Remarks
/Alarm(A)
244 bi =20BLB60GH001 +20BLB60 Indoor Lighting Board 6 Power Incoming Supply Trip AA33 1 61 51 63 30 30 24VDC
245 bi =20BLB60GH001 +20BLB60 Indoor Lighting Board 6 Feeders Group Trip AA33 1 61 52 63 30 30 24VDC
246 bi Spare AA33 1 61 53 63 30 30 24VDC
247 bi Spare AA33 1 61 54 63 30 30 24VDC
248 bi Spare AA33 1 61 55 63 30 30 24VDC
249 bi Spare AA33 1 61 56 63 30 30 24VDC
250 bi Spare AA33 1 61 57 63 30 30 24VDC
251 bi Spare AA33 1 61 58 63 30 30 24VDC
252 bi Spare AA33 1 61 59 63 30 30 24VDC
253 bi Spare AA33 1 61 60 63 30 30 24VDC
254 bi Spare AA33 1 61 61 63 30 30 24VDC
255 bi Spare AA33 1 61 62 63 30 30 24VDC
256 bi Spare AA33 1 61 63 63 30 30 24VDC

29/38 2019/11/27
BMG Switchyard (LCU20) / Digital Outputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Remarks
/Alarm(A)
1 bo =11AEA03GS110 +11AEA03 -Q01 115kV Line 1 11AEA03GS100-Q01 Circuit Breaker Open O DO2201 AA53 1 61 0 68 30 30
2 bo =11AEA03GS110 +11AEA03 -Q01 115kV Line 1 11AEA03GS100-Q01 Circuit Breaker Close O DO2201 AA53 1 61 1 68 30 30
3 bo =11AEA03GS110 +11AEA03 -Q01 115kV Line 1 11AEA03GS110-Q01 Disconnector Open O DO2201 AA53 1 61 2 68 30 30
4 bo =11AEA03GS110 +11AEA03 -Q01 115kV Line 1 11AEA03GS110-Q01 Disconnector Close O DO2201 AA53 1 61 3 68 30 30
5 bo =11AEA03GS120 +11AEA03 -Q01 115kV Line 1 11AEA03GS120-Q01 Disconnector Open O DO2201 AA53 1 61 4 68 30 30
6 bo =11AEA03GS120 +11AEA03 -Q01 115kV Line 1 11AEA03GS120-Q01 Disconnector Close O DO2201 AA53 1 61 5 68 30 30
7 bo Spare O DO2201 AA53 1 61 6 68 30 30
8 bo Spare O DO2201 AA53 1 61 7 68 30 30
9 bo =11AEA03GS191 +11AEA03 -Q01 115kV Line 1 11AEA03GS191-Q01 Earthing Switch Open O DO2201 AA53 1 61 8 68 30 30
10 bo =11AEA03GS191 +11AEA03 -Q01 115kV Line 1 11AEA03GS191-Q01 Earthing Switch Close O DO2201 AA53 1 61 9 68 30 30
11 bo =11AEA03GS192 +11AEA03 -Q01 115kV Line 1 11AEA03GS192-Q01 Earthing Switch Open O DO2201 AA53 1 61 10 68 30 30
12 bo =11AEA03GS192 +11AEA03 -Q01 115kV Line 1 11AEA03GS192-Q01 Earthing Switch Close O DO2201 AA53 1 61 11 68 30 30
13 bo =11AEA03GS193 +11AEA03 -Q01 115kV Line 1 11AEA03GS193-Q01 Earthing Switch Open O DO2201 AA53 1 61 12 68 30 30
14 bo =11AEA03GS193 +11AEA03 -Q01 115kV Line 1 11AEA03GS193-Q01 Earthing Switch Close O DO2201 AA53 1 61 13 68 30 30
15 bo Spare O DO2201 AA53 1 61 14 68 30 30
16 bo Spare O DO2201 AA53 1 61 15 68 30 30
17 bo =11AEA04GS100 +11AEA04 -Q01 115kV Line 2 11AEA04GS100-Q01 Circuit Breaker Open O DO2201 AA53 1 61 16 68 30 30
18 bo =11AEA04GS100 +11AEA04 -Q01 115kV Line 2 11AEA04GS100-Q01 Circuit Breaker Close O DO2201 AA53 1 61 17 68 30 30
19 bo =11AEA04GS110 +11AEA04 -Q01 115kV Line 2 11AEA04GS110-Q01 Disconnector Open O DO2201 AA53 1 61 18 68 30 30
20 bo =11AEA04GS110 +11AEA04 -Q01 115kV Line 2 11AEA04GS110-Q01 Disconnector Close O DO2201 AA53 1 61 19 68 30 30
21 bo =11AEA04GS120 +11AEA04 -Q01 115kV Line 2 11AEA04GS120-Q01 Disconnector Open O DO2201 AA53 1 61 20 68 30 30
22 bo =11AEA04GS120 +11AEA04 -Q01 115kV Line 2 11AEA04GS120-Q01 Disconnector Close O DO2201 AA53 1 61 21 68 30 30
23 bo Spare O DO2201 AA53 1 61 22 68 30 30
24 bo Spare O DO2201 AA53 1 61 23 68 30 30
25 bo =11AEA04GS191 +11AEA04 -Q01 115kV Line 2 11AEA04GS191-Q01 Earthing Switch Open O DO2201 AA53 1 61 24 68 30 30
26 bo =11AEA04GS191 +11AEA04 -Q01 115kV Line 2 11AEA04GS191-Q01 Earthing Switch Close O DO2201 AA53 1 61 25 68 30 30
27 bo =11AEA04GS192 +11AEA04 -Q01 115kV Line 2 11AEA04GS192-Q01 Earthing Switch Open O DO2201 AA53 1 61 26 68 30 30
28 bo =11AEA04GS192 +11AEA04 -Q01 115kV Line 2 11AEA04GS192-Q01 Earthing Switch Close O DO2201 AA53 1 61 27 68 30 30
29 bo =11AEA04GS193 +11AEA04 -Q01 115kV Line 2 11AEA04GS193-Q01 Earthing Switch Open O DO2201 AA53 1 61 28 68 30 30
30 bo =11AEA04GS193 +11AEA04 -Q01 115kV Line 2 11AEA04GS193-Q01 Earthing Switch Close O DO2201 AA53 1 61 29 68 30 30
31 bo Spare O DO2201 AA53 1 61 30 68 30 30
32 bo Spare O DO2201 AA53 1 61 31 68 30 30
33 bo =11AEA05GS191 +11AEA05 -Q01 115kV Bus-bar A 11AEA05GS191-Q01 Earthing Switch Open O DO2201 AA53 1 61 32 68 30 30
34 bo =11AEA05GS191 +11AEA05 -Q01 115kV Bus-bar A 11AEA05GS191-Q01 Earthing Switch Close O DO2201 AA53 1 61 33 68 30 30
35 bo Spare O DO2201 AA53 1 61 34 68 30 30
36 bo Spare O DO2201 AA53 1 61 35 68 30 30
37 bo Spare O DO2201 AA53 1 61 36 68 30 30
38 bo Spare O DO2201 AA53 1 61 37 68 30 30
39 bo Spare O DO2201 AA53 1 61 38 68 30 30
40 bo Spare O DO2201 AA53 1 61 39 68 30 30

41 bo =11AEA01GS100 +11AEA01 -Q01 115kV MTR1 11AEA01GS100-Q01 Circuit Breaker Open O DO2201 AA57 1 61 0 69 30 30
42 bo =11AEA01GS100 +11AEA01 -Q01 115kV MTR1 11AEA01GS100-Q01 Circuit Breaker Close O DO2201 AA57 1 61 1 69 30 30
43 bo =11AEA01GS110 +11AEA01 -Q01 115kV MTR1 11AEA01GS110-Q01 Disconnector Open O DO2201 AA57 1 61 2 69 30 30
44 bo =11AEA01GS110 +11AEA01 -Q01 115kV MTR1 11AEA01GS110-Q01 Disconnector Close O DO2201 AA57 1 61 3 69 30 30
45 bo Spare O DO2201 AA57 1 61 4 69 30 30
46 bo Spare O DO2201 AA57 1 61 5 69 30 30
47 bo =11AEA01GS191 +11AEA01 -Q01 115kV MTR1 11AEA01GS191-Q01 Earthing Switch Open O DO2201 AA57 1 61 6 69 30 30
48 bo =11AEA01GS191 +11AEA01 -Q01 115kV MTR1 11AEA01GS191-Q01 Earthing Switch Close O DO2201 AA57 1 61 7 69 30 30
49 bo =11AEA01GS192 +11AEA01 -Q01 115kV MTR1 11AEA01GS192-Q01 Earthing Switch Open O DO2201 AA57 1 61 8 69 30 30
50 bo =11AEA01GS192 +11AEA01 -Q01 115kV MTR1 11AEA01GS192-Q01 Earthing Switch Close O DO2201 AA57 1 61 9 69 30 30
51 bo Spare O DO2201 AA57 1 61 10 69 30 30
52 bo Spare O DO2201 AA57 1 61 11 69 30 30
53 bo =11AEA02GS100 +11AEA02 -Q01 115kV MTR2 11AEA02GS100-Q01 Circuit Breaker Open O DO2201 AA57 1 61 12 69 30 30
54 bo =11AEA02GS100 +11AEA02 -Q01 115kV MTR2 11AEA02GS100-Q01 Circuit Breaker Close O DO2201 AA57 1 61 13 69 30 30
55 bo =11AEA02GS110 +11AEA02 -Q01 115kV MTR2 11AEA02GS110-Q01 Disconnector Open O DO2201 AA57 1 61 14 69 30 30
56 bo =11AEA02GS110 +11AEA02 -Q01 115kV MTR2 11AEA02GS110-Q01 Disconnector Close O DO2201 AA57 1 61 15 69 30 30

30/38 2019/11/27
BMG Switchyard (LCU20) / Digital Outputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Remarks
/Alarm(A)
57 bo Spare O DO2201 AA57 1 61 16 69 30 30
58 bo Spare O DO2201 AA57 1 61 17 69 30 30
59 bo =11AEA02GS191 +11AEA02 -Q01 115kV MTR2 11AEA02GS191-Q01 Earthing Switch Open O DO2201 AA57 1 61 18 69 30 30
60 bo =11AEA02GS191 +11AEA02 -Q01 115kV MTR2 11AEA02GS191-Q01 Earthing Switch Close O DO2201 AA57 1 61 19 69 30 30
61 bo =11AEA02GS192 +11AEA02 -Q01 115kV MTR2 11AEA02GS192-Q01 Earthing Switch Open O DO2201 AA57 1 61 20 69 30 30
62 bo =11AEA02GS192 +11AEA02 -Q01 115kV MTR2 11AEA02GS192-Q01 Earthing Switch Close O DO2201 AA57 1 61 21 69 30 30
63 bo Spare O DO2201 AA57 1 61 22 69 30 30
64 bo Spare O DO2201 AA57 1 61 23 69 30 30
65 bo SYN3000 Channel 1 Selected O DO2201 AA57 1 61 24 69 30 30
66 bo SYN3000 Channel 2 Selected O DO2201 AA57 1 61 25 69 30 30
67 bo Spare O DO2201 AA57 1 61 26 69 30 30
68 bo Spare O DO2201 AA57 1 61 27 69 30 30
69 bo Spare O DO2201 AA57 1 61 28 69 30 30
70 bo Spare O DO2201 AA57 1 61 29 69 30 30
71 bo Spare O DO2201 AA57 1 61 30 69 30 30
72 bo Spare O DO2201 AA57 1 61 31 69 30 30
73 bo Spare O DO2201 AA57 1 61 32 69 30 30
74 bo Spare O DO2201 AA57 1 61 33 69 30 30
75 bo Spare O DO2201 AA57 1 61 34 69 30 30
76 bo Spare O DO2201 AA57 1 61 35 69 30 30
77 bo Spare O DO2201 AA57 1 61 36 69 30 30
78 bo Spare O DO2201 AA57 1 61 37 69 30 30
79 bo Spare O DO2201 AA57 1 61 38 69 30 30
80 bo Spare O DO2201 AA57 1 61 39 69 30 30

31/38 2019/11/27
BMG Switchyard (LCU20) / Analog Inputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Unit Range Remarks
1 an Spare I AI2300 AA69 1 61 0 72 36 36
2 an Spare I AI2300 AA69 1 61 1 72 36 36
3 an Spare I AI2300 AA69 1 61 2 72 36 36
4 an Spare I AI2300 AA69 1 61 3 72 36 36
5 an Spare I AI2300 AA69 1 61 4 72 36 36
6 an Spare I AI2300 AA69 1 61 5 72 36 36
7 an Spare I AI2300 AA69 1 61 6 72 36 36
8 an Spare I AI2300 AA69 1 61 7 72 36 36
9 an Spare I AI2300 AA69 1 61 8 72 36 36
10 an Spare I AI2300 AA69 1 61 9 72 36 36
11 an Spare I AI2300 AA69 1 61 10 72 36 36
12 an Spare I AI2300 AA69 1 61 11 72 36 36
13 an Spare I AI2300 AA69 1 61 12 72 36 36
14 an Spare I AI2300 AA69 1 61 13 72 36 36
15 an Spare I AI2300 AA69 1 61 14 72 36 36
16 an Spare I AI2300 AA69 1 61 15 72 36 36

32/38 2019/11/27
BMG Switchyard (LCU20) / PT/CT input from Modbus Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name Source Terminal Box I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Unit Range Remarks
1 ai 115kV Line 1 current I1 Multifunction Meter C MODBUS 1 61 0 1 36 36
2 ai 115kV Line 1 current I2 Multifunction Meter C MODBUS 1 61 1 1 36 36
3 ai 115kV Line 1 current I3 Multifunction Meter C MODBUS 1 61 2 1 36 36
4 ai 115kV Line 1 current IN Multifunction Meter C MODBUS 1 61 3 1 36 36
5 ai 115kV Line 1 voltage U1 Multifunction Meter C MODBUS 1 61 4 1 36 36
6 ai 115kV Line 1 voltage U2 Multifunction Meter C MODBUS 1 61 5 1 36 36
7 ai 115kV Line 1 voltage U3 Multifunction Meter C MODBUS 1 61 6 1 36 36
8 ai 115kV Line 1 voltage UN Multifunction Meter C MODBUS 1 61 7 1 36 36
9 ai 115kV Line 1 frequency f Multifunction Meter C MODBUS 1 61 8 1 36 36
10 ai 115kV Line 1 power factor cos Multifunction Meter C MODBUS 1 61 9 1 36 36
11 ai 115kV Line 1 active power P Multifunction Meter C MODBUS 1 61 10 1 36 36
12 ai 115kV Line 1 reactive power Q Multifunction Meter C MODBUS 1 61 11 1 36 36
13 ai 115kV Line 1 active energy kWh Multifunction Meter C MODBUS 1 61 12 1 36 36
14 ai 115kV Line 1 reactive energy kVarh Multifunction Meter C MODBUS 1 61 13 1 36 36
15 ai Spare Multifunction Meter C MODBUS 1 61 14 1 36 36
16 ai Spare Multifunction Meter C MODBUS 1 61 15 1 36 36
17 ai 115kV Line 2 current I1 Multifunction Meter C MODBUS 1 61 0 2 36 36
18 ai 115kV Line 2 current I2 Multifunction Meter C MODBUS 1 61 1 2 36 36
19 ai 115kV Line 2 current I3 Multifunction Meter C MODBUS 1 61 2 2 36 36
20 ai 115kV Line 2 current IN Multifunction Meter C MODBUS 1 61 3 2 36 36
21 ai 115kV Line 2 voltage U1 Multifunction Meter C MODBUS 1 61 4 2 36 36
22 ai 115kV Line 2 voltage U2 Multifunction Meter C MODBUS 1 61 5 2 36 36
23 ai 115kV Line 2 voltage U3 Multifunction Meter C MODBUS 1 61 6 2 36 36
24 ai 115kV Line 2 voltage UN Multifunction Meter C MODBUS 1 61 7 2 36 36
25 ai 115kV Line 2 frequency f Multifunction Meter C MODBUS 1 61 8 2 36 36
26 ai 115kV Line 2 power factor cos Multifunction Meter C MODBUS 1 61 9 2 36 36
27 ai 115kV Line 2 active power P Multifunction Meter C MODBUS 1 61 10 2 36 36
28 ai 115kV Line 2 reactive power Q Multifunction Meter C MODBUS 1 61 11 2 36 36
29 ai 115kV Line 2 active energy kWh Multifunction Meter C MODBUS 1 61 12 2 36 36
30 ai 115kV Line 2 reactive energy kVarh Multifunction Meter C MODBUS 1 61 13 2 36 36
31 ai Spare Multifunction Meter C MODBUS 1 61 14 2 36 36
32 ai Spare Multifunction Meter C MODBUS 1 61 15 2 36 36
1 ai 115kV MT1# current I1 Multifunction Meter C MODBUS 1 61 0 3 36 36
2 ai 115kV MT1# current I2 Multifunction Meter C MODBUS 1 61 1 3 36 36
3 ai 115kV MT1# current I3 Multifunction Meter C MODBUS 1 61 2 3 36 36
4 ai 115kV MT1# current IN Multifunction Meter C MODBUS 1 61 3 3 36 36
5 ai 115kV MT1# voltage U1 Multifunction Meter C MODBUS 1 61 4 3 36 36
6 ai 115kV MT1# voltage U2 Multifunction Meter C MODBUS 1 61 5 3 36 36
7 ai 115kV MT1# voltage U3 Multifunction Meter C MODBUS 1 61 6 3 36 36
8 ai 115kV MT1# voltage UN Multifunction Meter C MODBUS 1 61 7 3 36 36
9 ai 115kV MT1# frequency f Multifunction Meter C MODBUS 1 61 8 3 36 36
10 ai 115kV MT1# power factor cos Multifunction Meter C MODBUS 1 61 9 3 36 36
11 ai 115kV MT1# active power P Multifunction Meter C MODBUS 1 61 10 3 36 36
12 ai 115kV MT1# reactive power Q Multifunction Meter C MODBUS 1 61 11 3 36 36
13 ai 115kV MT1# active energy kWh Multifunction Meter C MODBUS 1 61 12 3 36 36
14 ai 115kV MT1# reactive energy kVarh Multifunction Meter C MODBUS 1 61 13 3 36 36
15 ai Spare Multifunction Meter C MODBUS 1 61 14 3 36 36
16 ai Spare Multifunction Meter C MODBUS 1 61 15 3 36 36
17 ai 115kV MT2# current I1 Multifunction Meter C MODBUS 1 61 0 4 36 36
18 ai 115kV MT2# current I2 Multifunction Meter C MODBUS 1 61 1 4 36 36
19 ai 115kV MT2# current I3 Multifunction Meter C MODBUS 1 61 2 4 36 36
20 ai 115kV MT2# current IN Multifunction Meter C MODBUS 1 61 3 4 36 36
21 ai 115kV MT2# voltage U1 Multifunction Meter C MODBUS 1 61 4 4 36 36
22 ai 115kV MT2# voltage U2 Multifunction Meter C MODBUS 1 61 5 4 36 36
23 ai 115kV MT2# voltage U3 Multifunction Meter C MODBUS 1 61 6 4 36 36
24 ai 115kV MT2# voltage UN Multifunction Meter C MODBUS 1 61 7 4 36 36
25 ai 115kV MT2# frequency f Multifunction Meter C MODBUS 1 61 8 4 36 36
26 ai 115kV MT2# power factor cos Multifunction Meter C MODBUS 1 61 9 4 36 36
27 ai 115kV MT2# active power P Multifunction Meter C MODBUS 1 61 10 4 36 36
28 ai 115kV MT2# reactive power Q Multifunction Meter C MODBUS 1 61 11 4 36 36
29 ai 115kV MT2# active energy kWh Multifunction Meter C MODBUS 1 61 12 4 36 36
30 ai 115kV MT2# reactive energy kVarh Multifunction Meter C MODBUS 1 61 13 4 36 36

The signals of Unit 2 are same with Unit 1 33/38 2019/11/27


BMG Switchyard (LCU20) / PT/CT input from Modbus Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name Source Terminal Box I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Unit Range Remarks
31 ai Spare Multifunction Meter C MODBUS 1 61 14 4 36 36
32 ai Spare Multifunction Meter C MODBUS 1 61 15 4 36 36

The signals of Unit 2 are same with Unit 1 34/38 2019/11/27


BMG Intake (LCU30) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Rev Remarks
/Alarm(A)
1 bi Spillway RTU Control Mode Remote I DI6100 A105 1 71 32 60 30 30
2 bi Spillway RTU Control Mode Local I DI6100 A105 1 71 33 60 30 30
3 bi Spillway RTU Control Mode Revision I DI6100 A105 1 71 34 60 30 30
4 bi Spillway RTU 220VDC Power 1 Supply Failure I DI6100 A105 1 71 35 60 30 30
5 bi Spillway RTU 220VDC Power 2 Supply Failure I DI6100 A105 1 71 36 60 30 30
6 bi Spillway RTU 24VDC Power Supply Failure I DI6100 A105 1 71 37 60 30 30
7 bi Spillway RTU Power Converter 1 OK I DI6100 A105 1 71 38 60 30 30
8 bi Spillway RTU Light Power Fault I DI6100 A105 1 71 39 60 30 30
9 bi Spare I DI6100 A105 1 71 40 60 30 30
10 bi Spare I DI6100 A105 1 71 41 60 30 30
11 bi Spare I DI6100 A105 1 71 42 60 30 30
12 bi Spare I DI6100 A105 1 71 43 60 30 30
13 bi Spare I DI6100 A105 1 71 44 60 30 30
14 bi Spare I DI6100 A105 1 71 45 60 30 30
15 bi Spare I DI6100 A105 1 71 46 60 30 30
16 bi Spare I DI6100 A105 1 71 47 60 30 30
17 bi Spare I DI2110 A106 1 71 48 60 30 30
18 bi Spare I DI2110 A106 1 71 49 60 30 30
19 bi Spare I DI2110 A106 1 71 50 60 30 30
20 bi Spare I DI2110 A106 1 71 51 60 30 30
21 bi Spare I DI2110 A106 1 71 52 60 30 30
22 bi Spare I DI2110 A106 1 71 53 60 30 30
23 bi Spare I DI2110 A106 1 71 54 60 30 30
24 bi Spare I DI2110 A106 1 71 55 60 30 30
25 bi Spare I DI2110 A106 1 71 56 60 30 30
26 bi Spare I DI2110 A106 1 71 57 60 30 30
27 bi Spare I DI2110 A106 1 71 58 60 30 30
28 bi Spare I DI2110 A106 1 71 59 60 30 30
29 bi Spare I DI2110 A106 1 71 60 60 30 30
30 bi Spare I DI2110 A106 1 71 61 60 30 30
31 bi Spare I DI2110 A106 1 71 62 60 30 30
32 bi Spare I DI2110 A106 1 71 63 60 30 30

33 bi Spare I DI2110 A107 1 71 64 60 30 30


34 bi Spare I DI2110 A107 1 71 65 60 30 30
35 bi Spare I DI2110 A107 1 71 66 60 30 30
36 bi Spare I DI2110 A107 1 71 67 60 30 30
37 bi Spare I DI2110 A107 1 71 68 60 30 30
38 bi Spare I DI2110 A107 1 71 69 60 30 30
39 bi Spare I DI2110 A107 1 71 70 60 30 30
40 bi Spare I DI2110 A107 1 71 71 60 30 30
41 bi Spare I DI2110 A107 1 71 72 60 30 30
42 bi Spare I DI2110 A107 1 71 73 60 30 30
43 bi Spare I DI2110 A107 1 71 74 60 30 30
44 bi Spare I DI2110 A107 1 71 75 60 30 30
45 bi Spare I DI2110 A107 1 71 76 60 30 30
46 bi Spare I DI2110 A107 1 71 77 60 30 30
47 bi Spare I DI2110 A107 1 71 78 60 30 30
48 bi Spare I DI2110 A107 1 71 79 60 30 30
49 bi Spare I DI2110 A108 1 71 80 60 30 30
50 bi Spare I DI2110 A108 1 71 81 60 30 30
51 bi Spare I DI2110 A108 1 71 82 60 30 30
52 bi Spare I DI2110 A108 1 71 83 60 30 30
53 bi Spare I DI2110 A108 1 71 84 60 30 30
54 bi Spare I DI2110 A108 1 71 85 60 30 30
55 bi Spare I DI2110 A108 1 71 86 60 30 30
56 bi Spare I DI2110 A108 1 71 87 60 30 30

35/38 2019/11/27
BMG Intake (LCU30) / Digital Inputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 KKS3 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Rev Remarks
/Alarm(A)
57 bi Spare I DI2110 A108 1 71 88 60 30 30
58 bi Spare I DI2110 A108 1 71 89 60 30 30
59 bi Spare I DI2110 A108 1 71 90 60 30 30
60 bi Spare I DI2110 A108 1 71 91 60 30 30
61 bi Spare I DI2110 A108 1 71 92 60 30 30
62 bi Spare I DI2110 A108 1 71 93 60 30 30
63 bi Spare I DI2110 A108 1 71 94 60 30 30
64 bi Spare I DI2110 A108 1 71 95 60 30 30

36/38 2019/11/27
BMG Intake ( LCU30) / Digital Outputs Hardware Interface Signals

Trip(T)
ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Remarks
/Alarm(A)
1 bo Spare O DO6200 A109 1 71 96 60 30 30
2 bo Spare O DO6200 A109 1 71 97 60 30 30
3 bo Spare O DO6200 A109 1 71 98 60 30 30
4 bo Spare O DO6200 A109 1 71 99 60 30 30
5 bo Spare O DO6200 A109 1 71 100 60 30 30
6 bo Spare O DO6200 A109 1 71 101 60 30 30
7 bo Spare O DO6200 A109 1 71 102 60 30 30
8 bo Spare O DO6200 A109 1 71 103 60 30 30
9 bo Spare O DO6200 A109 1 71 104 60 30 30
10 bo Spare O DO6200 A109 1 71 105 60 30 30
11 bo Spare O DO6200 A109 1 71 106 60 30 30
12 bo Spare O DO6200 A109 1 71 107 60 30 30
13 bo Spare O DO6200 A109 1 71 108 60 30 30
14 bo Spare O DO6200 A109 1 71 109 60 30 30
15 bo Spare O DO6200 A109 1 71 110 60 30 30
16 bo Spare O DO6200 A109 1 71 111 60 30 30
17 bo Spare O DO6200 A109 1 71 112 60 30 30
18 bo Spare O DO6200 A110 1 71 113 60 30 30
19 bo Spare O DO6200 A110 1 71 114 60 30 30
20 bo Spare O DO6200 A110 1 71 115 60 30 30
21 bo Spare O DO6200 A110 1 71 116 60 30 30
22 bo Spare O DO6200 A110 1 71 117 60 30 30
23 bo Spare O DO6200 A110 1 71 118 60 30 30
24 bo Spare O DO6200 A110 1 71 119 60 30 30
25 bo Spare O DO6200 A110 1 71 120 60 30 30
26 bo Spare O DO6200 A110 1 71 121 60 30 30
27 bo Spare O DO6200 A110 1 71 122 60 30 30
28 bo Spare O DO6200 A110 1 71 123 60 30 30
29 bo Spare O DO6200 A110 1 71 124 60 30 30
30 bo Spare O DO6200 A110 1 71 125 60 30 30
31 bo Spare O DO6200 A110 1 71 126 60 30 30
32 bo Spare O DO6200 A110 1 71 127 60 30 30

37/38 2019/11/27
BMG Intake (LCU30) / Analog Inputs Hardware Interface Signals

ID_No Kind Denomination KKS0 KKS1 KKS2 Signal Name Source Terminal Box I/O Board_type Interf_no Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 TI Unit Range Remarks
1 an CFA10 CP001 Reservoir water level measuring I AI6300 A103 1 71 0 60 30 36
CFA10 CP101
CP102 CP103
2 an CP104 Pressure transmitter after trash rack I AI6300 A103 1 71 1 60 30 36
3 an Spare I AI6300 A103 1 71 2 60 30 36
4 an Spare I AI6300 A103 1 71 3 60 30 36
5 an Spare I AI6300 A104 1 71 4 60 30 36
6 an Spare I AI6300 A104 1 71 5 60 30 36
7 an Spare I AI6300 A104 1 71 6 60 30 36
8 an Spare I AI6300 A104 1 71 7 60 30 36