Professional Documents
Culture Documents
Abstract—Noise reduction has been imperative in urban and are instigated by magnetostriction effects and Maxwell forces
overall heavily populated areas, aiming to decrease the impact acting in the magnetic core, and by the Lorentz forces in the
of undesirable or unwanted sound in the human and wildlife’s windings, [4]–[6].
health and wellbeing. In addition, transformers need to be nearer
urban agglomerates, considering the current challenges in power Other parameters that may influence the perceived noise
distribution networks due to increasing power needs and as more level, at a given distance from the transformer, include the oil
energy is being produced, stored, and distributed closer to the mass loading, tank design and reflection/absorption properties
final consumer. This equipment should not impact significantly of the surrounding structures. Therefore, the analysis of radi-
people’s life, and so, lower noise levels are required, ensuring a ated noise should comprise three major steps, as schematically
quieter performance.
Radiated noise from a power transformer is mainly due to described in Fig. 1.
the induced vibrations in its active part, which are caused by
magnetostriction effects and Maxwell forces in the iron core Structural Acoustic Sound Pressure
(no-load noise), and by Lorentz forces in the windings (load Vibration Analysis Level
noise). These vibrations promote a noise spectrum composed Modal and Harmonic Radiation and dB Experimental
by even harmonics of the power frequency, typically 50 Hz or Analysis scale validation
60 Hz. The transformer’s enclosure, tank and oil also have an
important impact, positive or negative, on the irradiated noise Fig. 1: Major steps in the analysis of a power transformer
to the environment. noise radiation.
This article addresses the vibration and harmonic response
of power transformers tanks, evaluating the effect of non-
conventional geometries on the radiated power level. Additionally, The main contribution of the present study is the analysis
based on the obtained results, the contribution of several tank of the influence of tank design in its dynamic response
components is quantified, allowing the main irradiated power and radiated noise level. Through numerical simulations, the
sources to be identified. structural performance and the sensitivity of the radiated power
Index Terms—power transformer, power transformer tank, level to an assumed harmonic loading are provided for an
FEM, modal analysis, harmonic analysis; dynamic response
innovative tank design. Obtained results are compared with
those of the standard design.
I. I NTRODUCTION
A. Tank Design Optimization and Noise Level Reduction
Environmental noise exposure can affect human and
wildlife’s health in general, thus being an increasingly more Traditionally, power transformer components, including the
concerning subject worldwide, [1]. Power networks systems tank structure, used to be continuously re-designed aiming
are associated to relatively low sound level in urban areas, mass and cost reduction. Nowadays, a more structured and
when compared, for instance, with traffic noise. Power sub- complete approach is possible through a design optimization
stations - and power transformers in particular - produce a process, based on the minimization of a multi-objective func-
continuously radiated audible discrete sound, [2], which can tion which is subjected to several constraints. The commonly
cause harm through long term exposure. Different solutions used optimization objectives include the total weight, the
have been developed to mitigate the noise of power transform- active part cost, the total owning cost, the material and/or the
ers, however they often require extra elements, such as sound manufacturing cost, [7].
barriers or dampers, [3]. Nonetheless, from the reliability From the structural point of view, the power transformer
and manufacturability point of view, noise reduction obtained tank is mainly composed by stiffened panels with diverse
through adequate design of relevant components will improve geometries and configurations, having multiple restrictions,
the final solution. for example, due to positioning of other sub-systems (often
Power transformer noise is generated mainly by the active electrical components and cooling systems). A proper design
part vibration and cooling system. In the active part, vibrations and optimization of these plates and stiffeners makes possible
to increase the strength and/or stiffness of the panels with
This work is supported by the project POCI-01-0247-FEDER-024035, with same, or even less, weight, [8].
the acronym Quiet Transformer 2, co-funded by the European Regional On the other hand, the acoustic performance of power trans-
Development Fund (ERDF) through COMPETE2020 - Programa Operacional
de Competitividade e Internacionalização (POCI) under the “Portugal 2020” formers has acquired rising importance when evaluating the
Programme. overall power transformer design. From previous researches,
k,(((
,(((WK3RZHU,QVWUXPHQWDWLRQDQG0HDVXUHPHQW0HHWLQJ (3,0
tank surface velocity pattern, and its sound radiation, are the material); (ii) structural damping (at joints and interfaces)
known to be influenced by the stiffness of the panels, type and (iii) fluid damping (through fluid-structure interactions).
of stiffeners, tank shape, and type of insulating fluid, [4]. Given the (un-damped) natural frequency, ωn , and the damping
According to authors, load noise can be magnified by as much ratio, ξ, the resonance frequency of damped systems can be
as 8 – 10 dB if a tank resonance exists in the neighborhood estimated as: ωd = ωn 1 − ξ 2 , [10].
of the dominant frequency of load noise. Novosel et al., [9], The eigenvalue analysis, also referred as modal analysis, is
performed eigenfrequency and harmonic response analyses of the procedure through which the vibration characteristics of a
a transformer tank. The obtained results allowed the identi- structure are determined, in terms of natural frequencies ωi and
fication of “weak point” with higher deformations. Based on (mass normalized) modes shapes {Φi }, solving the governing
that information, by improving the tank stiffness, the sound equation of the un-damped free (harmonic) vibration:
pressure (at 100 Hz, 200 Hz and 300 Hz) was reduced up to
8 dB(A). −ω 2 [M ] + [K] {Φi } = {0} (5)
B. Structural Harmonic Response which can be derived replacing F1 = F2 = ξ = 0 in (4).
The motion of a dynamic system can be typically described 2) Response Analysis based on Mode-Superposition: In
by the following general matrix equation: order to more easily solve the governing equation (1), a set of
[M ] {ü} + [C] {u̇} + [K] {u} = {F } (1) modal coordinates is defined adopting the modal matrix [Φ] as
the transformation matrix between generalized {u} and modal
where [M ], [C] and [K] are the mass, damping and stiffness {y} coordinates:
matrices; {ü}, {u̇} and {u} are the nodal acceleration, velocity
n
and displacement vectors; {F } is the applied load vector. {u} = [Φ] {y} = {Φi } yi (6)
For linear structures undergoing steady-state vibration, si- i=1
nusoidal variation at a given frequency ω, but not necessarily In a first step, pre-multiplying (1) by the transpose modal
in phase, is assumed for all loads and displacements: T
matrix [Φ] and applying coordinate transformation (6), and,
{F } = ({F1 } + i {F2 }) eiωt in a second step, considering the orthonormality conditions:
(2)
[Φ] [K] [Φ] = Ω2
T T
{F } = ({Fmax cos ψ} + i {Fmax sin ψ}) eiωt [Φ] [M ] [Φ] = I, (7)
(R0 ) and the surface vibration velocity (v), as shown in (10), 30 mm as global element size. For the standard and curved
[13], [14]. design models, this mesh configuration created, respectively,
46165 and 48358 elements, which correspond to 138667 and
2 2
W = R0 × |v| = (ρ0 c0 SW σ) × |v| (10) 144642 nodes. All parts in contact are assumed to be bonded
in the common surfaces. Regarding boundary condition, the
In this equation, ρ0 is the density of the medium, c0 is the tank base is considered simply supported.
speed of sound in the medium, SW is the irradiating
surface Therefore, initially, a static analysis provided the pre-stress
2
area, σ is the radiation efficiency and |v| is the space state to the modal analysis, through which the frequency and
average of the time-averaged square vibration velocity, which modes shapes were obtained. Hydrostatic pressure of the oil
can be defined as, [13]: (ρ0 = 880 kg/m3 ) was considered as loading condition.
Δt Then applying the mode-superposition method, the frequency
2 1 1
|v| = vn2 dt dSW (11) response to uniform harmonic pressure loading was calculated;
SW Sw Δt 0 post processing of those results allows to predict the variation
in radiated power level (LW ) per unitary variation (1 Pa) of the
where Δt defines the considered time interval and vn is
referred excitation, given in function of the pressure loading
vibration velocity normal to the surface.
frequency.
II. C ASE STUDY C. Discussion of results
A. Introduction 1) Pre-stress (static) analysis: When compared with the
Conventional power transformer tanks are designed with a standard design, the results provided by the pre-stress analysis
prismatic shape and straight reinforcements (Fig. 2a). Aiming demonstrate that the tank with curved side panels has higher
to improve the tank current design, different alternative so- strength due to its increased joint flexibility. As expected,
lutions have been explored at Efacec. The development of a the global deformation is governed by the tank stiffeners in
lighter tank with the same or higher capacity to accommodate both cases; indeed, with the innovative design, the maximum
pressure variations was demonstrated previously through an displacement (transversally to the base plate) is reduced by
innovative tank design, [8]. This new design is based on the 3.3%; however, the average value increased 6.4%, due to the
use of curved panels manufactured from shells and curved inherent higher joint flexibility (of the panels interface) in a
(planar) stiffeners, as shown in Fig. 2b, allowing to increase curved design, as demonstrated by Fig. 3.
the wall bending strength with limited impact on total weight,
ensuring that the tank withstands pressure loadings imposed
from the manufacturing stage up to the use of the equipment.
600
500
400
(a) 1st mode shape, f1 =63.1 Hz (b) 2nd mode shape, f2 =71.2 Hz
300
200
100
Standard Design
Curved Design
0
0 100 200 300 400 500 600
65
60
55
50
(c) Standard design, f = 200 Hz (d) Curved design, f = 200 Hz 45
40
0 50 100 150 200 250 300 350
65
Fig. 6: Velocity contour map of the front panels for different
60
excitation frequencies, f (same color scale for both designs).
55
50
45
40
0 50 100 150 200 250 300 350
80 Overall
All Panels
Cover
Stiffeners (b) Curved design
70
Fig. 8: Detailed analysis of the radiated power sources in the
60
side panels.
50
As a complementary analysis of the results, the comparison
40 between both designs, for each radiated power source, is
provided in Fig. 9. Given that the side panels are the dominant
30
0 50 100 150 200 250 300 350 source of radiated power, Fig. 9a allows to conclude that
the tank design with curved panels provides increased overall
(a) Standard design stiffness and strength, without a negative impact in the power
80 Overall transformer radiated power level.
All Panels
Cover
70
Stiffeners III. C ONCLUSION
The presented research provided a detailed analysis regard-
60
ing the vibration response of a curved tank design and com-
50
pared the results with those of the equivalent standard design
solution. The simulation was performed in three sequential
40 steps.
The first was a pre-stress (static) analysis, whose results
30
0 50 100 150 200 250 300 350 demonstrated that the innovative design allows to achieve
higher strength due to its increased joint flexibility. Although
(b) Curved design the maximum displacement of the stiffeners is reduced only
Fig. 7: Global analysis of the radiated power sources in the by 3.3%, the maximum and average total deformation of the
transformer tank. base plates were reduced in 20.5% and 5.6%, respectively.
The average stiffeners displacement is 6.4% higher, due
to the increased local flexibility of the panels joints. The
,(((WK3RZHU,QVWUXPHQWDWLRQDQG0HDVXUHPHQW0HHWLQJ (3,0
85
Standard Design
transformer tank. Additionally, the front panels contribution
80
Curved Design
was also observed to be significantly higher than that of the
lateral panels, except in specific small bandwidths of excitation
75
frequencies: 72 Hz - 86 Hz and 128 Hz - 150 Hz, respectively
70 for the standard and curved designs.
In addition to the side panels, secondary sources of radiated
65
power include the tank cover and the stiffeners. Indeed, the
60
cover becomes a relevant source only for excitation frequen-
cies close to 70 Hz, which corresponds, in both designs, to its
55
0 50 100 150 200 250 300 350 1st resonance. In the remaining analysed frequency range, not
only the cover but also the stiffeners contribution are small or
(a) All panels even negligible.
80
Standard Design
Curved Design Additional numerical simulations of the vibroacoustic re-
70 sponse, including for example: the oil mass loading, detailed
acoustic power excitation, as well as the inclusion of the active
60
part, may be necessary to more realistically reproduce the
operating conditions of a power transformer. Nevertheless,
50
the present research allowed to conclude that the curved
40
tank design is a better solution from several points of view;
when compared with the standard design, it provides increased
30 overall stiffness and strength, without impacting people’s life
0 50 100 150 200 250 300 350
with increased noise pollution.
(b) Stiffeners R EFERENCES
80
Standard Design
Curved Design
[1] L. Goines, L. Hagler et al., “Noise pollution: a modern plague,” Southern
70
Medical Journal-Birmingham Alabama, vol. 100, no. 3, pp. 287–294,
2007.
[2] E. Csanyi, “Problems with audible substation noise and what you can
60 do about it,” EEP - Electrical Engineering Portal, 2017.
[3] I. StdC57.136, Guide for Sound Level Abatement & Determination for
50 Liquid-Inmersed Power Transformers and Shunt Reactors Over 500kVA,
Institute of Electrical and Electronics Engineers Std., 2000.
[4] R. S. Girgis, M. Bernesjo, and J. Anger, “Comprehensive analysis of
40
load noise of power transformers,” in Power & Energy Society General
Meeting, 2009. PES’09. IEEE. IEEE, 2009, pp. 1–7.
30 [5] M. Ertl and H. Landes, “Vibroacoustics and sound emission character-
0 50 100 150 200 250 300 350
istics of thin-walled, oil-immersed transformer vessels,” in Proceedings
of the International Conference on Acoustics NAG/DAGA 2009, Mar.
(c) Tank cover 2009.
[6] M. Beltle and S. Tenbohlen, “Vibration analysis of power transformers,”
Fig. 9: Comparison between the standard and curved designs, in 18th International Symposium on High Voltage Engineering, ISH2013,
for each radiated power source. 2013.
[7] H. Mehta and R. M. Patel, “A review on transformer design optimization
and performance analysis using artificial intelligence techniques,” Inter-
national Journal of Science and Research, vol. 3, no. 9, pp. 726–728,
research results showed that this also has a positive impact 2014.
in the structural strength of the curved tank design. Indeed, [8] H. F. G. Mendes, C. J. P. Coutinho, S. M. O. Tavares, L. M. R. Félix,
and A. N. Martins de Matos, “Advanced modeling and experimental
the average value of the equivalent stress state was reduced in validation of an optimized power transformer tank,” in Proceedings of
4.5%, 7.6% and 6.1% in the stiffeners, base plates and overall the ASME 2018 International Mechanical Engineering Congress and
structure. Exposition, IMECE2018, Nov. 2018.
[9] J. Novosel, B. Bošnjak, F. Kelemen, K. C. Bikić, H. Pregartner, and
J. Case, “Influence of the power transformer tank design on the sound
The second step consisted in a modal analysis up to 600 Hz, level,” Procedia Engineering, vol. 202, pp. 280–287, 2017.
whose results predict similar modal density for both design [10] L. F. Braña, H. M. Campelo, and X. M. López-Fernández, “Quiet trans-
options. The innovative tank geometry has significantly less formers: Design issues,” Advanced Research Workshop on Transformers
(ARWtr), 2013.
modes of vibration under 90 Hz (only 2), when compared with [11] D. Ewins, Modal Testing: Theory, Practice and Application, 2nd ed.
the standard design (which has a total of 14). These expected Research Studies Press Ltd., 2000.
modal results, in the lower frequency range, reflect the higher [12] H. Leventhall, “Low frequency noise and annoyance,” Noise & Health,
vol. 6, no. 23, p. 59, 2004.
stiffness of the overall tank structure. [13] M. Kozupa and K. Kolber, “Radiation efficiency as a crucial parameter
in transformer noise evaluation,” in Forum Acusticum, 2014.
Lastly, the third step predicted the tank radiated power, up [14] T. A. Fiorentin, L. F. Lopes, O. M. da Silva Junior, and A. Lenzi,
to 350 Hz. Results of these response analyses showed that “Vibroacoustic models of air-core reactors,” International Journal of
the main source of radiated power are the side panels of Acoustics and Vibration, vol. 21, no. 4, pp. 453–461, 2016.