Chapter 6

Table 6.10.2.4(b) Secondary Conductor Rating Factors

Time in Seconds Ampacity of Wire in


On Off Percent of Full-Load
Secondary Current
5 75 35
10 70 45
15 75 55
15 45 65
15 30 75
15 15 85
Continuous Duty 110

Table 6.10.2.4(D) Contact Conductor Supports

Distance Between End Strain Size of Wire


Insulation or Clamp Type (mm2)
Intermediate Supports (m)
Less than 9 14
9 – 18 22
Over 18 30

Table 6.10.2.4(e) Demand Factors

Number of Cranes or Hoists Demand Factor


2 0.95
3 0.91
4 0.87
5 0.84
6 0.81
7 0.78

Table 6.20.2.4 Feeder Demand Factors for Elevators

Number of Elevators on a Demand Factor


Single Feeder
1 1.00
2 0.95
3 0.90
4 0.85
5 0.82
6 0.79
7 0.77
8 0.75
9 0.73

Hershey B. Samonte
10 or more 0.72
Table 6.25.5.2(d)(1) Minimum Ventilation Required in
Cubic Metres per Minute(m3/min) for Each of the Total
Number of Electric Vehicles that Can Be Charged at One Time

Branch- Circuit
Ampere Branch-Circuit Voltage
Rating
Single Phase Three Phase
115 V 230 V or 230 V or 460 V or
115/230 V 230Y/133 V 460Y/266 V
15 1.004 2.008 — —
20 1.338 2.677 4.636 9.273
30 2.008 4.015 6.954 13.909
40 2.677 5.354 9.273 18.545
50 3.346 6.692 11.591 23.181
60 4.015 8.030 13.909 27.818
100 6.692 13.284 23.181 46.363
150 — — 34.772 69.544
200 — — 46.363 92.725
250 — — 57.953 115.907
300 — — 69.544 139.088
350 — — 81.135 162.270
400 — — 92.725 185.451

Table 6.25.5.2(d)(2) Minimum Ventilation Required in


Cubic Feet per Minute (cfm) for Each of the Total
Number of Electric Vehicles that Can Be Charged at One Time

Branch- Circuit
Ampere Rating Branch-Circuit Voltage
Single Phase Three Phase
115 V 230 V or 230 V or 460 V or
115/230 V 230Y/133 V 460Y/266 V
15 35.421 70.842 — —
20 47.228 94.456 163.602 327.205
30 70.842 141.684 245.404 490.807
40 94.456 188.912 327.205 654.409
50 118.070 236.140 409.006 818.012
60 141.684 283.368 490.807 981.614
100 236.140 472.279 818.012 1636.023
150 — — 1227.018 2454.035
200 — — 1636.023 3272.047
250 — — 2045.029 4090.058
300 — — 69.544 139.088
350 — — 81.135 162.270

Hershey B. Samonte
400 — — 92.725 185.451

Table 6.30.2.1(a) Duty Cycle Multiplication


Factors for Arc Welders

Duty Cycle Multiplier for Arc Welders


Nonmotor Generator Motor Generator
100 1.00 1.00
90 0.95 0.96
80 0.89 0.91
70 0.84 0.86
60 0.78 0.81
50 0.71 0.75
40 0.63 0.69
30 0.55 0.62
20 or less 0.45 0.55

Table 6.30.3.1(a)(2) Duty Cycle Multiplication


Factors for Resistance Welders

Duty Cycle (percent) Multiplier


50 0.71
40 0.63
30 0.55
25 0.50
20 0.45
15 0.39
10 0.32
7.5 0.27
5 or less 0.22

Table 6.80.1.8 Overhead Conductor Clearances

Clearance Parameters Insulated Supply or All Other Supply or Service-Drop Conductors


Service Drop Cables, 0 – Voltage to Ground
750 Volts to Ground, 0 through 15 kV Over 15 through 50
Supported on and Cabled kV
Together with an
Effectively Grounded Bare
Messenger or Effectively
Grounded Neutral
Conductor
A. 6 900 mm 7 500 mm 8 000 mm
Clearance in any
direction to the
water
level, edge of water
surface, base of
Hershey B. Samonte
diving
platform, or
permanently
anchored
raft
B. 4 400 mm 5 200 mm 5 500 mm
Clearance in any
direction to the
diving
platform or tower
C. This limit shall extend to the outer edge of the structures listed in A and
Horizontal limit of B of this
clearance measured table but not to less than 3 000 mm
from inside wall of
the
pool

Table 6.80.1.10 Minimum Burial Depths

Wiring Method Minimum Burial


(mm)
Rigid metal conduit 150
Intermediate metal conduit 150
Nonmetallic raceways listed for direct 450
burial
without concrete encasement
Other approved raceways* 450
*Raceways approved for burial only where concrete encased shall require a concrete
envelope not less than 50 mm thick.

Table 6.90.2.1 Voltage Correction Factors for Crystalline and


Multi-Crystalline Silicon Modules

Correction factor for ambient


Ambient temperatures below 250C, multiply the
Temperature (0C) rated open-circuit voltage by the
appropriate correction factor shown below
25 to 10 1.06
9 to 0 1.10
– 1 to – 10 1.13
– 11 to – 20 1.17
– 21 to – 40 1.25

Table 6.90.4.1(c) Correction Factors

Ambient Temperature Rating of Conductor


Temperature

Hershey B. Samonte
(0C) 600C 750C 900C 1050C
30 1.00 1.00 1.00 1.00
31 - 35 0.91 0.94 0.96 0.97
36 - 40 0.82 0.88 0.91 0.93
41 - 45 0.71 0.82 0.87 0.89
46 – 50 0.58 0.75 0.82 0.86
51 - 55 0.41 0.67 0.76 0.82
56 - 60 — 0.58 0.71 0.77
61 - 70 — 0.33 0.58 0.68
71 - 80 — — 0.41 0.58