Table 6.25.5.2(d)(1) Minimum Ventilation Required in
Cubic Metres per Minute(m3/min) for Each of the Total
Number of Electric Vehicles that Can Be Charged at One Time
Branch- Circuit
Ampere Branch-Circuit Voltage
Rating
Single Phase Three Phase
115 V 230 V or 230 V or 460 V or
115/230 V 230Y/133 V 460Y/266 V
15 1.004 2.008 — —
20 1.338 2.677 4.636 9.273
30 2.008 4.015 6.954 13.909
40 2.677 5.354 9.273 18.545
50 3.346 6.692 11.591 23.181
60 4.015 8.030 13.909 27.818
100 6.692 13.284 23.181 46.363
150 — — 34.772 69.544
200 — — 46.363 92.725
250 — — 57.953 115.907
300 — — 69.544 139.088
350 — — 81.135 162.270
400 — — 92.725 185.451
Branch- Circuit
Ampere Rating Branch-Circuit Voltage
Single Phase Three Phase
115 V 230 V or 230 V or 460 V or
115/230 V 230Y/133 V 460Y/266 V
15 35.421 70.842 — —
20 47.228 94.456 163.602 327.205
30 70.842 141.684 245.404 490.807
40 94.456 188.912 327.205 654.409
50 118.070 236.140 409.006 818.012
60 141.684 283.368 490.807 981.614
100 236.140 472.279 818.012 1636.023
150 — — 1227.018 2454.035
200 — — 1636.023 3272.047
250 — — 2045.029 4090.058
300 — — 69.544 139.088
350 — — 81.135 162.270
Hershey B. Samonte
400 — — 92.725 185.451
Hershey B. Samonte
(0C) 600C 750C 900C 1050C
30 1.00 1.00 1.00 1.00
31 - 35 0.91 0.94 0.96 0.97
36 - 40 0.82 0.88 0.91 0.93
41 - 45 0.71 0.82 0.87 0.89
46 – 50 0.58 0.75 0.82 0.86
51 - 55 0.41 0.67 0.76 0.82
56 - 60 — 0.58 0.71 0.77
61 - 70 — 0.33 0.58 0.68
71 - 80 — — 0.41 0.58