Professional Documents
Culture Documents
Authorized licensed978-1-4799-3656-4/14/$31.00
use limited to: King Mongkuts Institute of©2014 IEEE
Technology Ladkrabang provided by UniNet. Downloaded on February 14,2024 at 03:48:44 UTC from IEEE Xplore. Restrictions apply.
An operation of the CTO uses undervoltage relays (21) retransfer only when the LTO is in the auto mode. So
which monitors voltages of transmission lines whether are changing switching scheme, the LTO also have to be in
normal. In case of the monitored voltage belowing setting manual mode.
values, the CTO will open a CB (Circuit Breakers) of the
B. Inline and Open-loop Switching Scheme among
faulty line then close a bus-coupler CB to recieve electric Substations
power from another transmission line within 0.3 seconds
including operating time of CBs called a transfer step resulting In a downtown area, routing of the transmission line is
in a short outage of 0.2 seconds approximately. After that if very difficult and costly to provide two terminal-station
an automatic recloser of the faulty line at the terminal station transmission lines to each substation creating a switching
performs successfully then the voltages come back to normal scheme of inline and open-loop substations as simply shown
making the undervoltage relay resets. The CTO will make sure in Fig. 3.
by delaying 60 seconds before closing the opened line-coming
circuit breaker then opening the bus-coupler CB called
retransfer step. The CTO shall perform a transfer or retransfer
step when the CTO is in the auto mode only. Thus, during
maintaining or changing a switching scheme such as from
double-busbar to single-busbar scheme, the CTO have to be in
the manual mode for safty purposes.
2) Line throw-over: A substation which has a H-bus
scheme or uses a single-busbar arrangement will run a
function of line throw-over (LTO) for backing up a preferred
transmission line with an emergency transmission line as
shown in Fig. 2.
Authorized licensed use limited to: King Mongkuts Institute of Technology Ladkrabang provided by UniNet. Downloaded on February 14,2024 at 03:48:44 UTC from IEEE Xplore. Restrictions apply.
SCADA is no any requirement of additional hardwares. 3) ILTF by PLCs: A PLC (Programmable Logic
However, the SCADA has a response-time constraint due to Controller) are a device that can perform the ILTF logics with
the SCADA requsting (Polling & Control) is bases on a an independent aspect from existing systems. The ILTF needs
resolution of seconds especially for SBO (Select Before one PLC for each substions and all PLCs have to
Operate) will take more time duration for a transaction [1]. communicate with each other. The ILTF implementation by
So, the response time of the ILTF by SCADA is in range of 1- PLC requires a new investment of wiring, buying PLCs and
30 seconds depending on types of data communication thier peripherals,but it is very independent and guarunteed
(TCP/IP, Serial Communication), types of control (SBO, about the response time. The ILTF by PLC is also able to have
Direct Control) and how fast of requesting. Thus,the ILTF by redundant communication medias (TCP/IP and RS232)
SCADA is suitable to be an interrim ILTF. making it has high avaiability [3]. This paper by itself prefers
the ILTF by PLC for implementing.
Authorized licensed use limited to: King Mongkuts Institute of Technology Ladkrabang provided by UniNet. Downloaded on February 14,2024 at 03:48:44 UTC from IEEE Xplore. Restrictions apply.
the terminal station 2 to the inline substation . These steps are
shown as Fig. 7.
Figure 9. Transfer step for open-loop substation using double busbars and
faulty line coming from the terminal station 2
Figure 7. Transfer step for open-loop substation using a single busbar and a
faulty line coming from the terminal station 1
2) Transfer steps by zone-1 tripping: Transfer steps by
b) Open-loop substation using double busbars and a zone-1 tripping will perform when there is a fault occuring on
faulty line coming from the terminal station 1: Once an a transmission between two substations. The transfer steps by
undervoltage relay detects undervoltages occuring on the a zone-1 tripping will also perform diffently depending on a
terminal-substation of the inline substation for 0.2 seconds and type of busbar configuration of an open-loop substation
no pickup of any distance relay. Afterward the ILTF will open (Single Bus or Double Bus). The transfer steps by zone-1
the faulty incoming-line CB that connect to the terminal tripping have no any retransfer step because the duration of
station 1 then the ILTF will close the bus-coupler CB of the having two opened CB exceeding a time of a functional
open-loop substation for delivering electricity from the intrigrity. So the ILTF will change to the manual mode
terminal station 2 to the inline substation. These steps are automatically.
shown as Fig. 8. a) Open-loop substation using a single busbar: When
an undervoltage relay of a receiving substation measures that
voltages are below setting values and there is a zone-1 tripping
of a line at a supplying substation that supplys electricity to
the nearby receiving substation.These shows that a fault surely
happens on a line between the two substations. So the ILTF
will open two end CBs of the faulty line. After that the ILTF
will close a the emergency incoming-line CB of the open-loop
substation for delivering electric power from the terminal
station 2 to an outaged area. These steps are shown as Fig.10.
Figure 8. Transfer step for open-loop substation using double busbars and a
faulty line coming from the terminal station 1
Authorized licensed use limited to: King Mongkuts Institute of Technology Ladkrabang provided by UniNet. Downloaded on February 14,2024 at 03:48:44 UTC from IEEE Xplore. Restrictions apply.
Figure 11. Transfer step by zone-1 tripping for open-loop substation using Figure 13. Retransfer step for open-loop substation using double busbars and a
double busbars faulty line coming from the terminal station 1
3) Retransfer steps: Retransfer steps will perform when a c) Open-loop substation using double busbars and a
transfer step has done and the fault has been cleared including faulty line coming from the terminal station 2: If the fault is
the ILTF is still in the auto mode. The retransfer steps will temporaly then the tripped CB of the terminal station 2 will
make the switching scheme is ready for a next line be able to reenergize electric power to the open-loop
transferring. So the availability of these substation will recover substation by an automatic reclosure. So the undervoltage
to normal. The retransfer steps also will perform diffently relay of the tripped line will found that the voltages is normal.
depending on a type of busbar configuration of an open-loop However, the ILTF still wait for 60 seconds for sure. After
substation (Single Bus or Double Bus) and what faulty line is that the ILTF will close the tripped CB of the open-loop
substation that connects to the terminal station 2 then open the
(Terminal Station 1 or Terminal Station 2).
bus-coupler CB of the open-loop substation. These steps are
a) Open-loop substation using a single busbar and a shown as Fig. 14.
faulty line coming from the terminal station 1: Typically,the
terminal station 1 has an automatic recloser that recloses only
1 shot after 4 seconds. Thus,if a fault is temporary then the
tripped CB of the terminal station will be able to energize to
an inline substation again. So the undervoltage relay of the
inline substation will found that the voltages come back to
normal. After that the ILTF still wait for 60 seconds to ensure
no flicker again, then the ILTF will close the tripped
incoming-line CB which connect to the terminal station 1 then
open the emergency-line CB of the open-loop substation.
These steps are shown as Fig. 12.
Figure 14. Retransfer step for open-loop substation using double busbars and a
faulty line coming from the terminal station 2
IV. CONCLUSION
The proposed techniques and applications of the ILTF can
increase reliability of power distribution system and ultimately
prevent a big outage. The ILTF also can get rid of a weak
point of the inline substations. This paper presents the
solutions (SCADA, IEC61850 and PLCs) to increase
reliability of the inline substations. The ILTF is able to
Figure 12. Retransfer step for open-loop substation using a single busbar and decrease wide-area outages of load of whole in-line substation
a faulty line coming from the terminal station 1 from 5-10 minutes to 0.2-0.3 seconds
b) Open-loop substation using double busbars and a
faulty line coming from the terminal station 1: A terminal REFERENCES
station normally has automatic reclosures. Consequecely,if the [1] Wu, F.F., Mosleshi, K. and Bose, A. (2005) “Power system control
fault is temporary then the tripped CB of the terminal station centers: past, present, and future”, Proceedings of the IEEE, Vol. 93,
No. 11, November, pp.1890–1908.
1 could energize the power again to the inline substation. So
[2] Communication Delivery Time Performance Requirements for Electric
the undervoltage relay of the tripped line will detect that the Power Substation Automation, Std. 1646-2004,IEEE Power Eng. Soc.
voltages is normal. However, the ILTF still wait for 60 (Power Eng. Soc.),Feb.2005,IEEE Std.,NY,USA
seconds for sure. After that the ILTF will close the tripped CB [3] IEC, IEC TC-57. Power System Control and Associated
of an inline substation that connects to the terminal station 1 Communications—Data and Communication Security, Geneva,
Switzerland, Tech. Rep. IEC TR 62210, 2003, 1st Ed.
then open the bus-coupler CB of the open-loop substation.
These steps are shown as Fig. 13.
Authorized licensed use limited to: King Mongkuts Institute of Technology Ladkrabang provided by UniNet. Downloaded on February 14,2024 at 03:48:44 UTC from IEEE Xplore. Restrictions apply.