Professional Documents
Culture Documents
CWR Design
CWR Design
Given Data :-
2
1 Grade of Concrete M-30 fck 30 N/mm
2
2 Grade of Steel M-500 fy 500 N/mm
2
3 Safe Bearing Capacity at 1.25 m 70 KN/m
3
4 Unit wt. of Liquid W 10 KN/m
3
5 Unit wt. of Soil gs 18 KN/m
:- Reference :-
I.S. 456 - 2000
I.S. 3370 PART-1 : 2021
I.S. 3370 PART-2 :2021
I.S. 3370 PART-4 :2021
2 2
D/2 + r 4.9^2 + 1.4^2
R = = = 9.275 m
2r 2 x 1.4
3
Unit Wt. of Concrete 25 KN/m
2
Self Load of Dome 0.15 x 1.00 x 1.00 x 25 = 3.75 KN/m
Live Load = 2 KN/m2
Finishes = 0 KN/m2
Toatl Load (Q) = 5.75 KN/m2
Qx R 5.75 x 9.275
T = = = 28.842 KN/m
1+ CosØ 1 + 0.849
2
Circumferential Force at Crown Cos Ø + CosØ -1
wR
(Ø = 0 ):- 1 + CosØ
1+ 1 -1 2
= 5.75 x 9.275 x = 26.67 N/mm
1+1
2
Area of Reinf Required :- 0.24 % x 150 x 1000 = 360 mm
Area of Reinf Provided :-
2
#8 @ 125 C/C = 402.1 mm
2
Area of Steel Reqd. for Moment = 58.5 mm
2
Area of Steel Reqd. for the Hoop = 654.52 mm
1.5 x 120 x1000/0.55 x500
Required No. of Bar = 5.79 Nos.
2
Area of Concrete Required :- Ac = 1.5*(Ft/σct)-(m-1)*Aspro. = 41293.2 mm
2 2
sct = 3.83 N/mm sst = 275 N/mm m = 9.33
2
Area of Concrete Provided :- = 90000 mm
Safe
Provide 2 legged stirrups of #8 @ 150 C/C