Professional Documents
Culture Documents
Ingolstadt, Date:
2
Abstract
The main objective of the thesis is to develop the simulation model of the refrigerant cycle
in full operation mode by MATLAB Simscape and validate the model with the measurement
data from the existing heat pump prototype. It starts with introducing the fundamentals
of heat pumps, including explaining the refrigerant cycle, coefficient of performance, and
performance factor. Then review the application of different types of heat pumps,
refrigerants, and heat exchangers from the literature. For modeling the heat pump, two
methods are used in the work. The compressor and the expansion valve are using the first
method which is modeled by the datasheet and the measurement data; the condenser and
the evaporator are utilizing another method for modeling which is by the MATLAB tool
parameter estimator. The thesis has explained the detailed method of modeling the heat
pump. After completing the model, it has been run and validated by the measurement
data from the prototype. The model can operate properly and the properties of the
simulation model are reasonable. But for validating the model which means compared to
the measurement data from the prototype, there are still some flaw or errors, especially
for the evaporator model. They will be discussed in the work. Overall, the thesis still
provides a promising method for developing the simulation model of a heat pump.
3
Contents
1 Introduction .................................................................................................... 6
3 Methodology ................................................................................................. 24
4 Results ......................................................................................................... 37
4
4.3.3 Results of validating the condenser ..................................................... 55
5 Discussion .................................................................................................... 56
5.1 Discussion of the results from modeling and validating the compressor .......... 56
5.2 Discussion of the results from modeling and validating the expansion valve ... 58
5.3 Discussion of the results for modeling and validating the condenser and
evaporator....................................................................................................... 62
5.4 Discussion of the results from validating the whole heat pump system........... 64
6 Conclusions................................................................................................... 67
7 References.................................................................................................... 69
5
1 Introduction
Global warming and the global energy crisis are the problems that humans are still facing
in the year 2022. It is a long-term issue, but humans need to act on solving the problems
as soon as possible to avoid further natural disasters shortly. For example, the federal
government of Germany also wants to accelerate the energy transition. The latest act is
to achieve climate neutrality by 2045 instead of 2050 (Webseite der Bundesregierung |
Startseite, 2022).
The use of heat is the largest energy source globally, accounting for 50% of total energy
consumption in 2018. It is also responsible for 40% of global carbon dioxide emissions.
Around half of the heat produced is used for industrial processes, while the other half is
used for space and water heating. (IEA, 2022). The domestic heating for building in
Germany in 2017 is mostly supplied from fossil fuels (49% by gas and 26% by oil).
According to the carbon-neutral goal in Germany (Pelda et al., 2021) Therefore, improving
the efficiency of heating has a high potential for saving energy. The heat pump is one of
the promising solutions for high-efficient heating.
In the process of developing the simulation model, the main goal is to find the optimal
specification of the heat pump e.g., the mass flow of the refrigerant, the length of the
condenser, pipe thickness, and pipe diameter. If the simulation model has better
performance than the prototype, it can be a reference for future improvement of the design.
6
The structure of the thesis work is presented below in Figure 1.
•Methodology: To explain the methods and the processes that are used in
CH3 this research
•Reference
CH7
7
The working principle of basic heat pumps is a refrigerant cycle (working fluid cycle). Heat
pumps operate the compressor by electricity to supply the necessary work for
concentrating and transporting thermal energy. Four major components are incorporated
in the refrigerant cycle of a heat pump. The schematic presentation of the theory of the
heat pump is shown in Figure 2. It includes a compressor, a condenser, an expansion
valve, and an evaporator (c.f Figure 3). There are also other minor components such as
pipes, fans, and other control units to assist the operation. Following are the processes for
the heating operation of heat pumps. (Self et al., 2013)
1. The thermal energy is extracted from the external heat source (normally the heat source
is from the environment which is air or ground) and transferred to the evaporator. Inside
the evaporator, the enthalpy of the refrigerant (working fluid) is increased because of the
heat exchange with the external heat source. In the process, the refrigerant is boiled from
a liquid/vapor state to a vapor state before entering the compressor.
2. The vapor enters a compressor which is usually driven by electricity. The compressor
compresses the refrigerant vapor and causes it to become a high-pressure, high-
temperature vapor state.
4. The warm temperature liquid passes through an expansion valve. It causes the pressure
of the refrigerant to drop and decreases the temperature of the refrigerant. The working
fluid state is from the high pressure, high-temperature liquid to low pressure, cool
temperature gas, and liquid.
5. Finally back to the evaporator and repeat the cycle. The scheme and pressure-enthalpy
diagram of a heat pump cycle is presented in Figure 3 and Figure 4. (Hughes et al., 1982)
8
High Temperature
Low Temperature
Expansion valve
4 3
Evaporator Condenser
Compressor
9
Pressure (P)
Pc 3 2
Pe 4 1
Enthalpy (h)
h3 = h4 h1 h2
Equation 1
𝑄𝑑𝑜𝑡,ℎ
𝐶𝑂𝑃 =
𝑃𝑒𝑙,𝑡𝑜𝑡
COP = the coefficient of performance of the heat pump, Qdot, h = the high-temperature
heat flow that is used for heating, Pel, tot = total electrical power
The performance factor (PF) is another key factor to evaluate the efficiency of a heat pump.
In reality, the temperature of the heat source is not fixed, either is the temperature of the
heat sink. The heat demand and the operation time of the heat pump can change with
different seasons. The COP at the specific boundary conditions can not present the
10
efficiency of the heat pump for a longer operation. As a result, the performance factor is
a quotient of the total heating energy (Qh) and the total electrical energy (Wel, tot). It is
shown in Equation 2. The performance factor of a heat pump that operating for a year is
called the seasonal performance factor (SPF) (Yang et al., 2021)
Equation 2
∫ 𝑄𝑑𝑜𝑡,ℎ 𝑑𝑡 𝑄ℎ
𝑃𝐹 = =
∫ 𝑃𝑒𝑙,𝑡𝑜𝑡 𝑑𝑡 𝑊𝑒𝑙,𝑡𝑜𝑡
PF = Performance factor, Qh = total heating energy, Wel, tot = Total electrical energy
The novel hybrid heat pump that is developed by InES has also utilized two different heat
sources which are air and ground sources. The design of the hybrid heat pump has an
additional circuit with a separate compressor and evaporator for each heat source. By
using different control strategies, it could have higher efficiency and a lower cost compared
to a conventional ground source heat pump. Also, efficient parallel operation of both
sources is possible, since the heat sources can operate at different evaporator pressure
levels.
Some heat pumps have the design of a reversing valve such as shown in Figure 5, the
refrigerant cycle will flow another way around the circuit. This allows the indoor heat
exchanger to provide cooling instead of heating. Which means it can also be a chiller.
However, the design was originally for defrosting the outdoor finned coil (Qu et al., 2012).
11
But the application now can be widened as most air source heat pumps are already
containing this valve.
Figure 6. Illustration of different ground source heat pumps (Geothermal Heat Pumps | Building
America Solution Center, 2022)
12
2.1.4 Refrigerant selection
Refrigerant is a fluid or gas used in heat pumps or air conditioning to transfer heat. There
are different criteria to select the suitable refrigerant for the heat pump. It needs to
consider reliability, safety, performance, economic, and environmental acceptance
(Gopalnarayanan, 1998). If focusing on the engineering point of view, the main criteria
are the critical temperature and the vapor pressure of the refrigerant. The critical
temperature has to be higher than the heat sink outlet temperature. The vapor pressure
of the refrigerant at ambient temperatures also has to be higher than ambient pressure to
avoid the air getting into the refrigerant cycle during the downtime of the heat pump
system (Moisi, 2017). Overall, considering different criteria, the refrigerant R454b has
been selected in this work. Because it is similar to the R410A in pressure level, density,
and critical temperature. Moreover, it has less global warming potential (GWP) which
means it has fewer climate pollutants. More discussion will be done in the discussion
chapter.
Another common design of the heat exchanger is the plate heat exchanger. The heat
transfer principle is similar to coil heat exchangers, but instead of using the tube, it uses
the thin plates of metal to separate two fluids. With the design, it can have a high power
density by the larger specific surface area, and create more turbulence on the surface to
have better heat transfer efficiency. (Evans, 2018b).
Sometimes the heat transfer is not only through the fluids, but it can also be from air to
fluid, from air to air, or from fluid to air. Therefore, there are even more different types of
heat exchangers. For example, finned tube coil heat exchangers, duct plate heat
exchangers, and microchannel heat exchangers.
13
Figure 7. Coil heat exchanger Figure 8. The plate heat exchanger (Miao et al., 2017)
(Bahrehmand & Abbassi, 2016)
14
Compressor
The compressor in the heat pump system is the pressure source that drives the working
fluid. The compressor is ideally working isentropically, which means that entropy at the
compressor inlet is equal to the entropy at the compressor outlet. In Simscape the block
for presenting the compressor is a ‘controlled mass flow rate source (2P)’ It’s a two-phase
block that can provide mass flow at an adjustable-rate with the physical signal M (Figure
9). The controlled mass flow rate source is considered an ideal block. It neglects the friction
losses and the heat losses with the environment. Therefore, it’s an adiabatic and isentropic
compressing process.
Condenser
The condenser at the heat pump system is acting as a heat exchanger. It condenses the
high-pressure superheated vapor to two-phase liquid from the compressor. It transfers
the condensation heat to warm up a water cycle for heating the house or building. The
block which is used in Simscape is ‘pipe (2P)’. (Figure 10) The block models the flow
dynamics of a two-phase fluid. It has the convective heat transfer within the pipe wall and
the friction losses with the physical signal H. The block has also the ideal assumptions,
which are the negligible gravitational force, and heat transfer at constant pressure.
15
Expansion valve
Figure 11. The expansion valve block in Figure 12. Principle of the variable local restriction
Simscape block (capture from the Simulink library)
The Expansion valve reduces the pressure level of the refrigerant from the condenser
outlet to the evaporator inlet. It is considered an isenthalpic process, which means the
enthalpy at the expansion valve inlet is equal to the enthalpy at the expansion valve outlet.
The ‘Variable Local Restriction (2P)’ block is used in Simscape (Figure 11). Because the
principle of reducing the pressure in the expansion valve is similar to the nozzle (Figure
12). Port AR is the time-varying restriction area. It is specified as a physical signal. The
control of the evaporator superheat will be influenced by an expansion valve that
modulates the refrigerant flow. It has a sensor to compare the evaporation temperature
and the temperature at the compressor inlet. This will influence the control of the opening
area to insure the refrigerant inlet of the compressor is gas. (Fallahsohi et al., 2010). The
model is based on the following assumptions: isenthalpic expansion, negligible friction
losses, without heat transfer with the environment.
Evaporator
The Evaporator in the heat pump system is similar to the condenser. It is also a heat
exchanger. Therefore, the ‘pipe (2P)’ block is used in Simscape as well (Figure 13). The
heat transfers via the physical signal H to the pipe. The refrigerant flows in the evaporator
in two-phase and flows out in the form of superheated vapor. The model is considered in
the following assumption: negligible gravity force and the heat transfer without pressure
change.
16
Refrigerant
The refrigerant R454b is used in the present work. The block ‘Two-Phase Fluid Properties
(2P)’ is used for defining the properties of the working fluid in the refrigerant cycle (Figure
14). It has several parameters that can be adjusted to present different characteristics of
refrigerants. The properties are derived from Refprop (source).
Solver configuration
The solver configuration block is the block that is used to specify simulation options for
the physical system (Figure 15). For example, the sample time for the simulation, the type
of solver to use, and other initialization options. Therefore, it is a block that is necessary
for all the Simscape models.
Figure 16. Water or brine pipe block Figure 17. Thermal liquid properties block
It is the thermal liquid block that presents the pipe of the water cycle of the condenser or
the brine cycle of the evaporator. It is the place where the refrigerant heat transfer (Figure
16). To distinguish if it is water or brine, it is determined by the thermal liquid properties
block (Figure 17).
17
Other blocks
There are several other blocks in the system. For example, the constant block defines the
mass flow rate of the mass flow source (compressor); the Simulink PS converter is a crucial
block that connects the Simscape signal and the Simulink operation signal; The thermal
mass block presents the pipe wall which is the internal energy storage in a thermal network;
sensor blocks can measure the properties of the refrigerant cycle; Mathematical
operational blocks are used for controlling the expansion valve or the compressor. All the
blocks are necessary for running the whole heat pump system on Simscape.
Expansion valve
Evaporator
Condenser
Compressor
18
Heat exchange of condenser or evaporator
The refrigerant cycle has heat exchange with the water cycle at the condenser, and with
the brine cycle at the evaporator. The thermal liquid properties block can be set as water
or brine (Ethylene glycol). Both refrigerant cycle and water cycle have reservoirs at 2 ports.
It is considered an unlimited liquid source and sink. Moreover, each cycle has the flow rate
sources to drive the liquid. The detailed design of the heat exchanger can be found below
in Figure 19.
Evaporator Condenser
or
Zoom in
Refrigerant cycle
Water/Brine cycle
19
Cross-section area
Simscape blocks are considered physical connections. As a result, the cross-section area
is one of the crucial parameters for designing the heat pump. It is the area where the
refrigerant passes through the pipes, compressor, evaporator, expansion valve, and
evaporator. To calculate the cross-section area can be seen in Equation 3. The default
hydraulic diameter is 0.01m. The cross-section area of the pipe is calculated as 0.0000785
m 2.
Equation 3
𝜋𝐷 2
𝐴=
4
A = cross section area (m2), D = Diameter of the pipe (m)
The thermal mass of the pipe wall is one of the important factors to influence the efficiency
of the heat exchange. It is the ability of a material to absorb, store and release heat. The
pipe walls are built of copper. To calculate the thermal mass of the pipe walls, the mass
of the pipe wall and specific heat of the material are required. The mass of the pipe wall
can be calculated by Equation 4, and the specific heat of copper is around 380 J/kg/k.
multiplying the mass and specific the thermal mass of the pipe wall can be gained.
Equation 4
𝑀 =𝜋∗𝐷∗𝐿∗𝑑∗𝜌
M=mass of pipe wall (kg), D=diameter of pipe (m), L=length of pipe (m), d=pipe
thickness, ρ=density of copper
The expansion valve reduces the pressure of the refrigerant and ensures there is no liquid
flow into the compressor. During the operation of the heat pump, the control of the
opening area of the expansion valve is required. Firstly, the overheated temperature has
to be defined. It is the buffer for the operation. In this case, 4 degrees Celsius of overheat
is defined.
20
The logic of controlling the expansion valve:
If the current compressor inlet temperature – the saturation temperature > 4°C, then
open the valve.
If the current compressor inlet temperature – the saturation temperature < 4°C, then
close the valve.
At the moment, the question is if the valve should be opened, how large is the opening
area that should be? The opening area which allows the refrigerant to pass through
depends on the saturation properties sensor (for measuring the saturation temperature)
and the thermodynamic properties sensor (for measuring the current temperature) after
the evaporator. The saturation properties sensor is the ideal sensor that measures the
saturated liquid temperature at a specific pressure. The principle of it is based on
measuring the pressure and then calculating the saturated temperature of a specific
refrigerant. The thermodynamic properties sensor measures the current compressor inlet
temperature of the refrigerant. By calculating the difference between the current
compressor inlet temperature and the saturated temperature, the opening area of the
valve is controlled. To determine the size of the opening area, in this work there are two
solutions, the first one is coming from the reference of the MATLAB example of the chiller.
The second solution is to develop a PID control of the expansion valve. The second solution
is the improving solution from the first solution which will be discussed more in the
discussion chapter. Here only the first solution is described, the reason for applying the
PID control will be explained later. The first solution is to add the gain block. The function
of the gain block is “(max opening area - min opening area) / (max throat temperature –
min throat temperature)” It means the opening ratio depends on the temperature of the
refrigerant. The maximum opening area and the minimum opening area are known. The
maximum opening area depends on the orifice of the expansion valve. The minimum
opening area supposes to be set as 0 which means the valve is completely closed. But
according to the logic of the block and prevent the singularities, it cannot be set as 0.
Therefore, the minimal opening area is set as 1e-20 which is nearly close to 0. The maximal
throat temperature is the temperature point when the valve is fully opened, and the
minimum throat temperature is the temperature point when the valve is completely closed.
These parameters are unsure because the desired set temperature can vary, it cannot be
simply said at one specific temperature the valve will fully open or close. This design is
based on the chiller refrigerant example “ssc_refrigeration” from Matlab. The reference
maximum throat temperature is 270K and the minimum throat temperature is 250K.
However, it is not the optimized solution model for controlling the expansion valve. But it
21
provides a simplified solution for controlling the area of the expansion valve. In the
discussion section, a better model will be provided.
This is the principle of controlling the expansion valve (Figure 20). In this work, only the
100% operation mode is measured, which means the compressor is operating constantly
at full power. Therefore, the temperature of the refrigerant after the evaporator will not
change. The opening area of the expansion valve will also be fixed. Thus, the control of
the expansion valve is not required in the work.
Before explaining the details of the design, the default setup of each block must be
declared. The default setup is based on MATLAB Simscape example ‘ssc_refrigeration’ (see
Table 1, Table 2, Table 3, Table 4).
22
Table 1. Parameter setup of the compressor
Description Value
Power added Isentropic
Cross-section area at port A/B 0.0000785 m2
Mass flow rate 0.0040 kg/s
Description Value
Pipe length 30 m
Cross-section area at port A/B 0.0000785 m2
Hydraulic diameter 0.01 m
Copper specific heat 390 J/kg/K
Copper density 8960 kg/m3
Description Value
Pipe length 30 m
Cross-section area at port A/B 0.0000785 m2
Hydraulic diameter 0.01 m
Mass flow 0.0040 kg/s
Description Value
Minimal throat area 0 (1e-20)
Maximal throat area 1.5 mm2
Cross-section area at port A/B 0.0000785 m2
23
3 Methodology
To evaluate the heat pump model that has been built, it has to be validated. In the
beginning, the model parameter has been set as the default value. One of the main goals
of the thesis is to validate and optimize the heat pump model in Simscape. To reach the
goal each main component of the model has been modeled first. After getting the optimal
parameters of each component, the whole system has been set with the optimal parameter
and validated once more against another measurement data set. To check if the whole
system performs comparably better than the prototype that has been built in the InES.
To validate the model, it has to compare with the data from the prototype. There are 3
different measurement datasets from different experiments on the heat pump prototype.
The period of the three experiment data is around 8 hours. Among the three measurement
datasets, 100 rows of data (approximately 15 minutes of data), which operate steadily
have been picked up separately as samples of measurement data. They are called
measurement data 1, measurement data 2, and measurement data 3 in this work.
There are different methods to model and validate different components. Developing the
compressor and expansion valve is using the first method, which is directly modeling the
components with the datasheets and the measurement data. But modeling the condenser
and evaporator is using another method, which is called the inverse modeling by the
Matlab tool parameter estimator. With this method, modeling the condenser and
evaporator with precise parameters is not essential. Therefore, it is also called
parameterless modeling. Only the major effect of the model is required. The parameter
estimator can directly optimize the parameters from the parameterless model according
to measurement data. The parameter estimator is suitable for estimating and optimizing
the parameter of a complex system. The principle of the parameter estimator is the
iteration process. It finds the error between measurement data (output) and simulation
data. When the error converges, or the error is not changed, the iteration process will stop.
It means it finds the optimized parameters for the model. Before estimation, the
parameters of the condenser and the evaporator models are the default ones. It can be
any parameter because it is the parameterless modeling approach. Therefore, it will not
affect the results of the estimation.
Figure 21 describes the principle of the parameter estimator. Each step of the iteration
process does five to seven times of simulations adjusting the parameters of the model and
comparing the results with the measurement data.
24
Amplitude
Measurement data
Simulation data
Time
For modeling the condenser and evaporator, it is directly developed by Simscape and uses
the default parameters which have been mentioned in the previous chapter. Because of
the parameter estimator tool, it’s not necessary to precisely model the condenser and the
evaporator. Modeling the physical connection is enough to optimize the parameters and
develop the models.
25
Figure 22. Specified the mass flow rate of the compressor
Empirical compressor maps are a reliable and simple approach for heating or cooling
system designers to estimate compressor refrigerant input power, capacity, current, and
mass flow rate. The maps are built by the manufacturer with extensive test matrices
(Cheung & Bach, 2015). The complete table is given in Appendix B – Datasheet of
KTN110D42UFZ_Brinecompressor. The engineers from the manufacturers have chosen ten
points as the reference and generalized a ten coefficient polynomial to estimate the
parameter of the compressor. The refrigerant that is used for testing the compressor is
R410a. The ten coefficients equation is given in Equation 5. The variable x presents the
evaporating temperature of the refrigerant, and the variable y presents the condensing
temperature of the refrigerant. The point 1 to point 10 are given in Table 5, and this is
also called the empirical map.
Equation 5
𝑧 = 𝑝1 + 𝑝2 ∗ 𝑥 + 𝑝3 ∗ 𝑦 + 𝑝4 ∗ 𝑥 2 + 𝑝5 ∗ 𝑥 ∗ 𝑦 + 𝑃6 ∗ 𝑦 2 + 𝑝7 ∗ 𝑥 3 + 𝑝8 ∗ 𝑥 2 ∗ 𝑦 + 𝑃9 ∗ 𝑥 ∗ 𝑦 2 + 𝑃10 ∗ 𝑦 3
26
Finally, apply them to the ten coefficients equation. The capacity, input power, flow rate,
and current of the compressor can be found. In this work, only the flow rate is required.
Do the same method for measurement data 1 (Appendix C) and measurement data 2
(Appendix D), and the optimal flow rate of the compressor can be determined. Input the
parameter of the flow rate in the 2-phase compressor block which has been mentioned
earlier. The compressor model can be developed
At the manufacturing testing condition, R410a has been used. But in the prototype and
the simulation experiment, the refrigerant R454b has been used. R454b is a better
alternative to R410a. There would have some minor errors, which will be discussed in the
discussion section. Another error is the frequency from the given datasheet is 60 Hz but
the experiment environment was 50Hz. It is another factor that will influence the result.
Figure 23. Specified the opening area of the expansion valve during full operation mode
The only thing that has to be done is to look up the orifice from the datasheet of the
expansion valve (Appendix E) and select the model that has been used in the prototype.
After knowing the orifice of the valve, the maximum opening area can be calculated. In
the measurement data, the opening percentage of the valve has been assumed from the
PWM signal (Pulse-width modulation in Appendix F). Thus, the maximum opening area
multiplies the opening percentage equal to the opening area of the expansion valve in a
specific time. After inputting the parameter of the opening area of the expansion valve in
the Simscape block, the model can be developed.
27
3.1.3 Modeling the condenser
The first step for modeling the condenser is to build the Simscape model blocks. In this
work, the simple tube-in-tube heat exchanger has been used in the simulation model. The
condenser heat exchanger Simscape model can be found in Figure 24. The reservoirs (2P)
act as the refrigerant sink and source, and reservoirs (TL) act as the water sink and source.
The controlled mass flow rate sources (2P) provide the specific mass flow rate of the
refrigerant circuit. The controlled volume flow rate source (TL) provides the specific volume
for the water circuit.
After developing the Simscape blocks the next step will be to estimate and optimize the
parameters of the models with the measurement data. The parameter estimator tool is
used for optimizing the parameters of the condenser and evaporator model in the work.
Before estimation, the parameters of the condenser and evaporator model are the random
default ones. It will not affect the results of the parameter estimation, the only matter for
28
the parameter estimation tool is the correct physical connection. That has already been
developed in Figure 24.
Now the condition parameters, target parameters, and output have to be specified.
The condition parameters are the parameters that describe the experiment condition. They
are based on the measurement data. In this case, the temperature of the refrigerant
inlet/outlet, and the pressure of the refrigerant. They can be seen as the input of the
model (Table 6 and Table 7). The target parameters are the parameters that are decided
to be estimated and optimized. In this case are the condenser length, pipe diameter, and
pipe thickness. The output presents the output of the system. The temperature of the
water is the output, it measures from two measurement data. The value of the output is
given in Appendix G and Appendix H in columns T_water out1 & T_water out2. The
following paragraph will explain the details of determining those parameters.
In this work, there are two measurement data. Therefore, the parameters of the condenser
will be optimized twice. The mean of the estimation results will be the optimal parameter
that will be used for the system.
As mentioned before, it’s important to define the output of the system and the target
parameters that need to be optimized. The output of the system defines how the system
has been evaluated or the result of the system. In this case, the main goal of the condenser
is to transfer the heat from the refrigerant circuit to the water circuit. Therefore, the
temperature outlet of the water circuit that is heated up by the refrigerant circuit is the
output of the system. The target parameters are the key factors that will influence the
29
output of the system. According to the principle of the heat exchangers, that would be
multiple factors that will affect the efficiency of the heat transfer. Such as the condenser
length, pipe diameter, pipe thickness, the surface of the pipe, material of the pipe,
turbulence, and more. In this work, only the condenser length, pipe diameter, and pipe
thickness are selected as the target parameters to be optimized. Because these factors
are more apparent and also easy to change physically from the design point of view.
The next step is to input the measurement data into this model. The measurement data
are the volume flow rate of the water circuit, temperature inlet and outlet of the water
circuit, temperature inlet and outlet of the refrigerant circuit, and the pressure of the
refrigerant. The mass flow rate of the refrigerant circuit is dependent on the result of
modeling the compressor. Among the measurement data, the temperature outlet of the
water circuit is the output of the system. To make the estimator more precise, two
experiment datasets have been added for each measurement data, that’s the reason why
there are two outputs in each parameter estimation. The process of parameter estimation
is shown in Figure 25. Measurement data 1 and measurement data 2 are given in Appendix
G and Appendix H. They are used for estimating the parameters of the condenser model.
1. Open the Simulink “APPS” and open the parameter estimator panel (Figure 30).
2. Specify the experiments for parameter estimation. Select the new experiment (exp1)
and enter the output. As mentioned in the previous section, the output is the outlet
temperature of the water circuit (the columns T_water_out 1 & T_water_out 2 in Appendix
G). According to the format requirement of the parameter estimator tool, the output should
30
be written in the timetable form. The first column indicates the time steps and the second
column is the value of the measurement data.
3. Set the initial state. It is not a necessary step for the estimation. But it can reduce the
simulation time or have fewer iteration steps. According to the measurement data, the
temperature of the water circuit outlet is around 310 K. Therefore, the initial state of the
temperature is also set as 310 K.
4. Select parameters which are going to be optimized. As mentioned in the previous section,
the condenser length, pipe diameter, and pipe thickness are chosen as the target
parameters.
5. Define the range of the parameters (Figure 31). For the default setting of the condenser,
the length is 30, the pipe diameter is 0.01m and the pipe thickness is 0.0005m. These
values can be changed during the optimizing process. However, the value needs to be
restricted. The parameter's value should be higher than 0, and the maximum value should
be less than ten times the default value. The scales are set to the same value as the
maximum value of the parameter, to present a clearer view of the resulting plot. The Y-
axis of the resulting plot will be the “scaled value”.
6. Add the new experiment (exp2) and do it again from step 2 to step 5. As mentioned in
the previous section, there are two experiments (exp1 and exp2) for each measurement
data (measurement data 1 and measurement data 2).
7. Plot the estimated model response and start the estimation. Do the same process from
step 1 to step 6 again with measurement data 2. The mean value of the optimal
parameters of measurement data 1 and measurement data 2 will be the final result. The
optimal parameters will be shown in the results chapter.
Before estimation, the initial response will be shown in the following. The estimated model
response plot for measurement data 1 is shown in Figure 26 and Figure 27. And for
measurement data 2 is shown in Figure 28 and Figure 29.
31
Figure 26. Model response before estimation Figure 27. Model response before estimation
(measurement data 1 exp1) (measurement data 1 exp2)
Figure 28.Model response before estimation Figure 29. Model response before estimation
(measurement data 2 exp1) (measurement data 2 exp2)
32
The selected area is the place to input the measurement data.
33
3.1.4 Modeling the Evaporator
Modeling the evaporator is similar to modeling the condenser. The main difference
between the condenser model and the evaporator model is the properties of the thermal
liquid circuit. For the condenser, the property of the thermal liquid circuit is water. But for
the evaporator, the property of the thermal liquid circuit has to be set as Ethylene glycol.
The design of the model can be found in Figure 32. The liquid property can be set by the
thermal liquid property block that is highlighted by the red circle.
The next step to optimize the parameters of the evaporator model is also using the
parameter estimator. The processes of operating the parameter estimation tool for the
evaporator are the same. The complete processes can be found in the last chapter. The
target parameters are evaporator length, pipe diameter, and pipe thickness. The
measurement data and condition parameters are different from the condenser (Table 8
34
and Table 9). And the output for the evaporator model is the temperature outlet of the
brine. The values can be found in Appendix I and Appendix J in the columns T_out_brine1
& T_out_brine1. Of course, the different condition parameters and different output will come
up with different optimization results. To optimize the evaporator model, there are also
two measurement data are used. The complete measurement data 1 and measurement
data 2 can be found in Appendix I and Appendix J.
Before estimating, the initial model responses have been plotted. The estimated model
response plot for measurement data 1 is shown in Figure 33 and Figure 34. And for
measurement data 2 is shown in Figure 35 and Figure 36.
35
Figure 33. Model response before estimation Figure 34. Model response before estimation
(measurement data 1 exp1) (measurement data 1 exp2)
Figure 35. Model response before estimation Figure 36. Model response before estimation
(measurement data 2 exp1) (measurement data 2 exp2)
36
4 Results
This chapter is presenting the results of modeling the compressor, expansion valve,
condenser, and evaporator. After obtaining the optimized parameters of each component,
the final validation of the whole system will be done, and the result of validating the whole
system will be shown in this chapter as well.
For modeling the condenser and evaporator, the parameter estimator is used in the work.
The chapter is focused on the results of the target parameters which are optimized by the
parameter estimator. They are condenser and evaporator length, pipe thickness, and pipe
diameter. Those are based on two measurement data. The final results of the target
parameters will be the mean value of the results from these two measurement data.
Table 10. Measurement of the pressure of refrigerant for measurement data 1&2
37
Table 11. Inquiry of pressure-temperature table for measurement data 1&2
After inputting the condensing temperature and evaporating temperature, the results of
the mass flow rate can be determined by the ten coefficients equation and the empirical
maps. Finally, compared with the rated condition data. The reason for doing this is to
check if the value is reasonable. Then transfer the mass flow rate unit from kg/h to kg/s
which is the SI unit that is used in the Simscape model (Table 12 & Table 13).
𝑧 = 𝑝1 + 𝑝2 ∗ 𝑥 + 𝑝3 ∗ 𝑦 + 𝑝4 ∗ 𝑥 2 + 𝑝5 ∗ 𝑥 ∗ 𝑦 + 𝑃6 ∗ 𝑦 2 + 𝑝7 ∗ 𝑥 3 + 𝑝8 ∗ 𝑥 2 ∗ 𝑦 + 𝑃9 ∗ 𝑥 ∗ 𝑦 2 + 𝑃10 ∗ 𝑦 3
The rated condition data is the experiment results from the manufacturer. There are
different than the result of our model because the experiment environments are different.
For example, the electricity frequency in Germany is 50Hz instead of 60Hz; and the
refrigerant which is used in the thesis is R454B instead of R410A. They could cause an
error to compare the result with the datasheet from the manufacturer.
Table 12. Results of the compressor modeling for measurement data 1&2
38
After gaining the mass flow rate results from measurement data 1 and measurement data
2, the mean value has been taken as the final result of the compressor modeling. Because
the two values are closed and they are in the error margin, considering there is the
refrigerant and frequency difference.
39
4.1.3 Results of modeling the condenser
The result of modeling the condenser is the result of the parameter estimation. The target
parameters are condenser length, pipe diameter, and pipe thickness. As mentioned in the
previous chapter, in the process of parameter estimation, there are two measurement
data. Each measurement data has two experiments (outputs). The final result of the
parameter of the condenser will be the mean value of the result of the two measurement
data.
Measurement data 1
After the estimation, the simulation model response which is the comparison between the
measurement data and the simulated data will be shown in Figure 38 and Figure 39. They
are slightly different than the initial model responses which are shown in Figure 26 and
Figure 27. The iteration process of the parameter estimation of measurement data 1 is
given in Figure 40. Y-axis is the scaled value, and X-axis is the iteration. This estimation
has four iteration processes to optimize the target parameters. The results of the target
parameters of measurement data 1 are given in Table 14.
Figure 38. Real model response after estimation Figure 39. Real model response after estimation
(measurement data 1 exp1) (measurement data 1 exp2)
40
Figure 40. Iteration process of the parameter estimation of measurement data 1
Table 14. The results of the target parameters after estimation (measurement data 1)
Measurement data 2
The estimation results of measurement data 2 of the condenser are presented in Table 15.
Same as measurement data 1. Firstly, compared the real model responses with the
estimated model responses which are shown in Figure 28 and Figure 29. The real model
responses of measurement data 2 after the estimation are presented in Figure 41 and
Figure 42. The iteration process of the parameter estimation of measurement data 2 is
given in Figure 43.
41
Figure 41. Real model response after estimation Figure 42. Real model response after estimation
(measurement data 2 exp1) (measurement data 2 exp2)
42
Table 15. The results of the target parameters after estimation (measurement data 2)
Final results
Observing the results from measurement data 1 and measurement data 2, the main
difference is the pipe diameter, the reason for that could be the pressure of measurement
data 1 is 5 bar higher than the measurement data 2. Therefore, it needs the larger pipe
diameter in measurement data 1 to compensate for the high pressure. Although the
sample data has only 2 measurement data, the final results of validating the condenser
still take the mean value of the results from measurement data 1 and measurement data
2. It is given in Table 16.
Measurement data 1
The results of validating the evaporator from measurement data 1 are given in Table 17.
The model responses after estimation are also different than the estimated model
responses that are shown in Figure 33 and Figure 34. The real model response for exp1
and exp 2 are given in Figure 44 and Figure 45. The iteration process of the parameter
estimation of measurement data 1 for the evaporator is shown in Figure 46. In total it has
10 iterations to reach the optimized values.
43
Figure 44. Real model response after estimation Figure 45. Real model response after estimation
(measurement data 1 exp1) (measurement data 1 exp2)
44
Table 17. The results of the target parameters after estimation (measurement data 1)
Measurement data 2
The results of validating the evaporator from measurement data 2 are given in Table 18.
The model responses after estimation are also different from the estimated model
responses that are shown in Figure 35 and Figure 36. The real model response for exp1
and exp 2 of measurement data 2 are given in Figure 47 and Figure 48. The iteration
process of the parameter estimation of measurement data 2 for the evaporator is shown
in Figure 49. In total it has 7 iterations to reach the optimized values.
Table 18. The results of the target parameters after estimation (measurement data 2)
45
Figure 49. Iteration process of the parameter estimation of measurement data 2
Final results
The final results for validating the target parameters of the evaporator are shown in
Table 19. They are the average value from the result of measurement data 1 and
measurement data 2.
46
Figure 50, four cycle sensors are added to measure the properties of the refrigerant at
different stages. The optimal parameters of each component that have been optimized in
the previous sector can be found in Table 20.
Figure 50. The design of the refrigerant cycle with cycle sensors in Simscape
47
Figure 51. Inside of the cycle sensors
Cycle sensors include a temperature sensor, a pressure sensor, and a vapor quality sensor.
The results from the cycle sensor will be shown in the following sections. Cycle sensors 2
and 3 can measure the properties of the refrigerant inlet and outlet of the condenser; cycle
sensors 4 and 1 can measure the properties of the refrigerant inlet and outlet of the
evaporator. In the water/brine cycle, there are also sensors to measure the properties of
the water/brine inlet and outlet. Following are the results of the model simulation of the
whole system run in full power mode in Simscape. The results will be compared with
measurement data 3 which are shown in Table 30 and Table 31.
Temperature
Sensor 1 measures the vapor temperature at the compressor inlet; sensor 2 measures the
vapor temperature of the condenser inlet; sensor 3 measures the vapor/liquid temperature
of the expansion valve inlet; sensor 4 measures the vapor/liquid temperature of the
evaporator inlet. Table 21 and Figure 52 are the temperature results from the cycle sensors.
The results of the temperature range are reasonable. Although the overheated
temperature is relatively high.
48
Figure 52. Temperature results from the cycle sensors
There is another sensor to measure the temperature of the water/brine cycle of the heat
pump. The results are shown in Table 22, Table 23, Figure 53, and Figure 54.
Table 22. Temperature results from the water cycle sensor from the condenser
The temperature of the water inlet The temperature of the water outlet
313.40 K 316.49 K
Figure 53. Temperature results from the water cycle sensor from the condenser
49
Table 23. Temperature results from the brine cycle sensor from the evaporator
The temperature of the brine inlet The temperature of the brine outlet
278.15 K 277.77 K
Figure 54. Temperature results from the brine cycle sensor from the evaporator
Pressure
50
Vapor quality
The third measurement data is used for validating the simulation model. To check if the
system performance in the simulation is equal to or better than the third measurement
data. The third measurement data are provided in Appendix K and Appendix L.
51
4.3.1 Results of validating the compressor
In this work, there is no measurement data for the mass flow rate of the refrigerant.
Therefore, to validate the compressor alone is not possible, but it’s possible to validate it
with the whole system. For example, the pressure of refrigerant of each component is
measured. Operate the heat pump in the specific mass flow and compare the pressure
between the simulation model and the measurement data from the prototype. The
pressure results from the simulation model are mentioned before in Table 24. The
comparison between measurement data 3 from the prototype and the simulation results
from the model can be found in the following Table 26. From observing the table, the
pressure of each point is similar. It can be assumed that the mass flow rate of the
simulation model (0.007385 kg/s) is reasonable and close to the prototype.
52
Table 29 can see the results of the comparison between measurement data and the
simulation results.
Table 28. The expansion valve results that have been operated in the Simscape model
53
Figure 58. The results that have been operated in the Simscape model
Table 29. The comparison between simulation results and the measurement data
From the results of validating the expansion valve, the error has been figured out. The
pressure of the refrigerant inlet of the model is 10 bar higher than the measurement data.
It is a huge error. So, another model of the expansion valve will be applied. The issue has
been found that the PWM signal cannot directly be assumed as the percentage of the
opening area. It can only present maybe the position height for opening the valve. That’s
another reason why the second solution which is the PID control model of the expansion
valve will be applied in the thesis, more details will be discussed in the following chapter.
54
4.3.3 Results of validating the condenser
The development of the condenser model is based on measurement data 1 and
measurement data 2. To validate the model, the third measurement data has been added.
Comparing the simulation results with the measurement data 3 is the way to validate the
condenser. The temperature of the refrigerant inlet/outlet and the temperature of the
water inlet/outlet are the data that are used for validation. Table 30 shows the comparison
between measurement data and the simulation results. If the two data are similar, means
the condenser model with a condenser length of 220.98m, a pipe diameter of 0.0056m,
and a pipe thickness of 3.73e-04m is correct and close to the prototype. However, from
observing the table, the temperature of the water outlet from the simulation results is
lower than the measurement data. The evaluation and discussion will be mentioned in the
discussion chapter.
Table 30. The comparison between measurement data 3 and simulation results of the condenser
55
Table 31. The comparison between measurement data 3 and simulation results of the evaporator
5 Discussion
The results of validating the compressor, condenser, expansion valve, and evaporator
have been done in the previous chapter. In this chapter, the focus will be on evaluating
the results, discussing the issues, and providing solutions.
𝑧 = 𝒑𝟏 + 𝒑𝟐 ∗ 𝑥 + 𝑝3 ∗ 𝑦 + 𝑝4 ∗ 𝑥 2 + 𝑝5 ∗ 𝑥 ∗ 𝑦 + 𝑃6 ∗ 𝑦 2 + 𝑝7 ∗ 𝑥 3 + 𝑝8 ∗ 𝑥 2 ∗ 𝑦 + 𝑷𝟗 ∗ 𝒙 ∗ 𝒚𝟐 + 𝑷𝟏𝟎 ∗ 𝒚𝟑
56
Mass Flow Rate(kg/h)
P1 3.77218957E+01
P2 1.08857765E+00
P3 1.92032390E-01
P4 3.59399767E-02
P5 2.01174342E-02
P6 -5.65675221E-03
P7 3.12094064E-04
P8 -1.81094325E-04
P9 -2.73841404E-04
P10 3.52556628E-05
454b is a non-ozone depleting, zeotropic blend designed to serve as a 78% lower global
warming potential (GWP) alternative to R-410A in heating applications (Solstice 454B
European Refrigerants, 2022). R454b has improved the efficiency but matching capacity
to R410a. The reason for that is to avoid the redesign cost for the applications. R454b has
a higher critical temperature than R410a which means it can have a broader operation
band. It is a better replacement for R410a in the high-pressure heat pump application.
The comparison between R410a and R454b is shown in Table 32. The shape of the pressure
enthalpy curve of R454b is wider than the shape of the pressure enthalpy curve of R410a
(see Figure 59) which indicates a higher evaporation enthalpy. It leads to having different
evaporating temperatures or condensing temperatures according to different P-T charts.
However, the shape of each curve is similar, and the liquid density ratio between R410a
and R454b is 1.056. So, there is another 5% of error margin that needs to be considered.
Although the modeled mass flow rate is different from the rated mass flow rate from the
datasheet, in the validation part, the difference between simulation results and the
measurement data is in the error margin. Therefore, modeling the compressor with the
empirical map is a promising method.
57
Table 32. The comparison between R410a and R454b
R410a R454b
Boiling temperature -52.7 °C -50.5 °C
Critical temperature 72.7 °C 78.1 °C
Critical pressure 49.6 bar 52.7 bar
Liquid Density at 25 °C 1 035.43 kg/m3 984.6 kg/m3
In the previous section, the measurement data of the PWM (Pulse-width modulation) signal
is directly assumed as the opening percentage of the expansion valve. It could be wrong
58
because the pulses are the signal for the stator which acts like a stepper motor, the pulses
energized different coils and create a magnetic field to control the opening of the electronic
expansion valve (see Figure 60). The PWM signal is related to the control of the expansion
valve, but it cannot be directly seen as the opening percentage of the valve. However, the
meaning of the PWM signal can be only known by the manufacturer. They have designed
and defined how the valve will be lifted or opened at the specific pulses. Thus, it could be
the reason why the current opening area is too small. As the result, another solution for
the model of the expansion valve will be implemented which is the PID-controlled model.
More detail on the PID-controlled model of the expansion valve will be explained in the
next chapter.
Figure 60. A stepper motor on the electronic expansion valve (Evans, 2018a)
59
If the current temperature – the saturation temperature > 4°C, then open the valve.
If the current temperature – the saturation temperature < 4°C, then close the valve.
The design of the model is to add a PID controller to set the output of the PID controller
between the minimal throat area and the maximal throat area. The desired set
temperature can be different and the corresponding opening area (output of the PID
controller) will be controlled by the PID controller. With the new model design, the opening
area of the expansion valve will be controlled according to the desired set temperature.
It’s more flexible than the previous model design to set a fixed throating temperature. For
tuning the parameter of the PID controller Kp, Ki, and Kd, they are set as 0.1.
After validating the model in the Simscape simulation and measuring the pressure inlet
and outlet of the expansion valve. The results are more reliable which are 23.09 bar of the
refrigerant inlet pressure and 6.3 bar of the refrigerant outlet pressure from the simulation
model (see Figure 62). For the measurement data, the inlet pressure is 24.22 bar and the
outlet pressure is 5.26 bar. The comparison table is shown in Table 33. From observing
the results, the PID control model is a more promising solution for the expansion valve
model of the heat pump
Table 33. Comparison between PID model simulation results and measurement data
60
Figure 61. PID Control model of the expansion valve
61
5.3 Discussion of the results for modeling and validating the
condenser and evaporator
In this chapter, the results of validating the condenser and evaporator will be evaluated
and analyzed. The MATLAB tool parameter estimator has been used for modeling the
condenser and the evaporator to find out the optimal value of condenser/evaporator length,
pipe diameter, and pipe thickness. However, there are much more parameters that can
be optimized. Such as the surface of the pipe, the material of the pipe, turbulence, and so
on. One of the potential errors is those parameters are not considered in the work.
Another potential error is the type of heat exchanger that has been developed in the
simulation model is a simple tube-in-tube heat exchanger. But the plate heat exchanger
has been used in the prototype and is very common in the market due to its high power
density. The different types of heat exchangers may lead to some errors. The reason for
using the tube-in-tube model in Simscape is, that it is a simple model that can be modified
and developed easier. Also, fewer factors will influence the heat exchanger.
If the condenser length has been enlarged to 220.98m, the heat exchange area will be
increased significantly. As the result, the heat exchange efficiency could be also increased.
That’s a logical and reasonable change. The change in the pipe diameter affects the
pressure drop or rise of the inlet and outlet significantly (Ham et al., 2020) In this case,
the pipe diameter has decreased to 0.0056m, which means the pressure is increased. It’s
hard to say if the pressure rise has a positive influence on the heat transfer without doing
a CFD analysis. Because there are lots more unknown factors that should be aware of.
Such as the turbulence, it is better to have turbulence in the heat exchangers. That’s also
the main reason that the parameter estimator tool is used in this paper. Because even
though there is no complex CFD analysis, according to the parameter estimation, we could
know that the higher pressure on the condenser is better for heat exchange in this specific
model (the tube in tube heat exchanger) under the specific output. Same for the pipe
thickness, in this case, it’s better to decrease the pipe thickness to 3.73e-04m.
62
Table 34. Results of validating the condenser
The reason for increasing the evaporator length could be the same as the condenser, to
increase the heat transfer area. But why the evaporator length is not as long as the
condenser length? The cause for that can be the difference in internal energy between the
condenser and evaporator. From Figure 63 can find out the internal energy at a different
point. To measure the heat transfer energy of the refrigerant in the condenser, cycle
sensors 2 and 3 need to be seen; To measure the heat transfer energy of the refrigerant
in the evaporator, cycle sensors 4 and 1 have to be checked. From analyzing Figure 63,
the internal energy of the evaporator is lower, that’s because of the measurement data.
That could be the reason why the evaporator length doesn’t need to be that long.
The pipe diameter, it’s about 5 times larger than the default value. The cause for that
could be the high-pressure issue on the expansion valve in the original design. As
mentioned in the previous chapter, when designing the first design (non-PID controlled)
of the expansion valve model in Simscape, it has a high-pressure issue. To compensate
for the issue, the pipe diameter of the evaporator, which is the outlet of the expansion
valve has to increase.
63
Figure 63. The internal energy of the refrigerant cycle
5.4 Discussion of the results from validating the whole heat pump
system
After validating the parameters of each component of the heat pump, validating the whole
system of the heat pump model in Simscape will be the next goal. With the optimized
parameters, the compressor, condenser, expansion valve, and evaporator are combined
into a refrigerant cycle. Firstly, analyze the results of the simulation of the whole heat
pump system to check if the results are reasonable (see Table 36). Secondly, compare the
simulation results with the measurement data 3. That can validate the heat pump system
model in Simscape.
The cycle sensors are measuring the properties of the refrigerant, cycle sensor 1 is
measuring the inlet of the compressor which corresponds with the outlet of the evaporator;
cycle sensor 2 is measuring the outlet of the compressor which corresponds with the inlet
of the condenser; cycle sensor 3 is measuring the outlet of the condenser which
corresponds with the inlet of the expansion valve; cycle sensor 4 is measuring the outlet
of the expansion valve which corresponds with the inlet of the evaporator. Firstly, looking
64
at sensor 1, the refrigerant is at a state of low pressure, and low temperature (still slightly
higher than sensor 4 because, in the evaporator, the refrigerant will gain the positive heat
flux from the ambient and the overheating of the evaporator due to a small temperature
change over evaporation), and fully gaseous. Then the refrigerant will be compressed and
the temperature of the refrigerant will increase. This increase can be seen in the
measurement result of cycle sensor 2. Afterward, the refrigerant condenses and transfers
the heat to the water. The temperature of the refrigerant will decrease slightly. The main
reason is the cooling of the hot gas to condensing temperature and theoretically, some
undercooling, which is not happening here, since the gas content after the condenser is
still above 0. It can also be observed in sensor 3. Finally, the refrigerant passes through
the expansion valve and decreases the pressure, and the temperature, at the state, is at
the liquid gaseous mixture. This can also be observed in sensor 4 with a vapor quality of
0.41. As a result, the simulation result of the refrigerant is reasonable.
The simulation results are logical, but it is still uncertain if the heat pump model that is
built in Simscape is the optimized one that matches the prototype. Thus, a comparison
with the third measurement data set is required. Firstly, the parameters that have to be
compared need to be defined. We decided to focus on the parameters in the condenser
and the parameters in the evaporator. Because those are the most important components
in the heat pump system that will affect the efficiency. The comparison between
measurement data 3 and the results from the simulation are shown in Table 37 and Table
38 for the condenser and evaporator respectively.
From observing the comparison result of the condenser, it can be found that the results
from the simulation and the measurement data are similar (see Table 37). But the heat
exchange efficiency from the simulation seems to be worse than the measurement data 3.
Because the temperature of the water outlet from the simulation is lower than the
measurement data from the prototype. The reason for having worse heat transfer
efficiency in the simulation is still under investigation, it could be caused by the different
65
types of heat exchangers. In the prototype, the plate heat exchangers have been used,
but in the simulation, tube-in-tube heat exchangers are developed.
Table 37. Comparison of the temperatures of the condenser between measurement data 3 and
results from simulation
The comparison result of the evaporator has another issue (see Table 38). Normally the
outlet temperature of the evaporator should be slightly higher than the inlet temperature
of the evaporator because it got the heat transferred from the ambient. But for
measurement data 3, the outlet temperature of the evaporator is lower than the inlet
temperature of the evaporator which means the temperature of the refrigerant should
increase slightly in the evaporator. That means there is a negative heat flux in the
refrigerant. After double-checking the measurement data, it seems like the sensor on the
prototype is off or broken. It is always the false temperature reading. This is an
unavoidable error from the original measurement data. Another thing that can be observed
from the table is comparing the two energy fluxes, the measurement data is smaller than
in the simulation, and the temperature change in the brine is higher, meaning there is
more heat coming into the water. That could imply the false mass flow from the brine side,
or from the refrigerant side. Overall, for the comparison of the evaporator, the difference
between the measurement data and the simulation is relatively high. There are lots of
errors that mentioned above could be the reason for leading the results.
66
Table 38. Comparison of the temperatures of the evaporator between measurement data 3 and
results from simulation
6 Conclusions
The main goal of the thesis is to develop the heat pump system in Simscape and validated
it by the measurement data to match the prototype. The biggest advantage of this work
is to be another reference for the researchers to investigate the potential improvement or
the issues of the prototype. Experimenting with the simulation can also save cost and time.
The thesis provides the details of designing the heat pump model in Simscape. Starting
from the background knowledge of the heat pump and also the function of the Simscape
blocks. After developing the heat pump model in Simscape, each component of the heat
pump has been modeled separately with different methods, the compressor and expansion
valve are modeled by the technical datasheet from the manufacturer with the
measurement data; the condenser and the evaporator are modeled by the MATLAB tool
parameter estimator, which is also based on the measurement data. Finally, the optimized
parameters of each component have been found. And the whole system model has been
validated again with the third measurement data. The results of the final model are
functionally and logically, but it does not match the prototype 100%. There are still some
flaws and it is not the good results that we had expected especially on the evaporator side.
6.1 Outlook
To improve the work in the future, the design of the heat exchangers needs to be changed
to the plate heat exchangers. Moreover, other parameters which will affect the heat
transfer have to be considered. In the thesis, only the condenser/evaporator length, pipe
diameter, and pipe thickness are considered.
67
The most important thing to improve in the future is to add more measurement data. In
this work, only three measurement data are considered. And the third measurement data
seems to have some issues with the sensor. The modeling results are taken from the
average of the two measurement data sets. Maybe in the future, there are more
measurement data for reference to model development. It can make the parameters of
the model more precise. Same for the validation measurement data, otherwise, the errors
could be high according to the few samples. Another major thing that could be improved
in the future is to implement the PID control of the expansion valve earlier. The non-PID
control model that had been used at the beginning is one major error that leads the
validation result went wrong.
68
7 References
Bahrehmand, S., & Abbassi, A. (2016). Heat transfer and performance analysis of
nanofluid flow in helically coiled tube heat exchangers. Chemical Engineering
Research and Design, 109, 628–637.
https://doi.org/10.1016/j.cherd.2016.03.022
Cheung, H., & Bach, C. K. (2015). Prediction of uncertainty of 10-coefficient compressor
maps for extreme operating conditions. IOP Conference Series: Materials Science
and Engineering, 90(1), 12078. https://doi.org/10.1088/1757-899X/90/1/012078
Chua, K. J., Chou, S. K., & Yang, W. M. (2010). Advances in heat pump systems: A
review. Applied Energy, 87(12), 3611–3624.
https://doi.org/10.1016/j.apenergy.2010.06.014
Devecioğlu, A. G. (2017). Seasonal performance assessment of refrigerants with low
GWP as substitutes for R410A in heat pump air conditioning devices. Applied
Thermal Engineering, 125, 401–411.
https://doi.org/10.1016/j.applthermaleng.2017.07.034
Energy.gov. (2022, May 17). Air-Source Heat Pumps.
https://www.energy.gov/energysaver/air-source-heat-pumps
Evans, P. (2018a, June 5). How Electronic Expansion Valves work. The Engineering
Mindset. https://theengineeringmindset.com/how-electronic-expansion-valves-
work/
Evans, P. (2018b, September 15). HVAC Heat Exchangers Explained. The Engineering
Mindset. https://theengineeringmindset.com/hvac-heat-exchangers-explained/
Fallahsohi, H., Changenet, C., Placé, S., Ligeret, C., & Lin-Shi, X. (2010). Predictive
functional control of an expansion valve for minimizing the superheat of an
evaporator. International Journal of Refrigeration, 33(2), 409–418.
https://doi.org/10.1016/j.ijrefrig.2009.10.008
Geothermal Heat Pumps | Building America Solution Center. (2022, May 17).
https://basc.pnnl.gov/resource-guides/geothermal-heat-pumps
GFC Rogers, & YR Mayhew (1992). Engineering Thermodynamics, Work and Heat
Transfer (4th Edition). https://research-
information.bris.ac.uk/en/publications/engineering-thermodynamics-work-and-
heat-transfer-4th-edition
Gopalnarayanan, S. (1998). Choosing the Right Refrigerant. Mechanical Engineering,
120(10), 92–95. https://doi.org/10.1115/1.1998-OCT-6
Ham, J., Shin, Y., & Cho, H. (2020). Theoretical investigation of the influence of pipe
diameter and exit channel width in welded plate heat exchanger on heat
exchanger performance. Heat and Mass Transfer, 56(3), 759–771.
https://doi.org/10.1007/s00231-019-02733-8
69
Huchtemann, K. (2015). Supply Temperature Control Concepts in Heat Pump Heating
Systems [Doctor's dissertation]. Technischen Hochschule Aachen, Aachen.
Hughes, D. W., McMullan, J. T., Mawhinney, K. A., & Morgan, R. (1982). Pressure-
enthalpy charts for mixtures of oil and refrigerant R 12. International Journal of
Refrigeration, 5(4), 199–202. https://doi.org/10.1016/0140-7007(82)90019-6
IEA. (2022, May 2). Heat – Renewables 2019 – Analysis - IEA.
https://www.iea.org/reports/renewables-2019/heat
MathWorks. (2022). Matlab and Simulink: Simscape user's guide.
https://de.mathworks.com/help/pdf_doc/physmod/simscape/simscape_ug.pdf
Miao, Q., You, S., Zheng, W., Zheng, X., Zhang, H., & Wang, Y. (2017). A Grey-Box
Dynamic Model of Plate Heat Exchangers Used in an Urban Heating System.
Energies, 10(9), 1398. https://doi.org/10.3390/en10091398
Moisi, H. (2017). Refrigerant Selection and Cycle Development for a High Temperature
Vapor Compression Heat Pump, O.3.4.3.
Parameter Estimation - MATLAB & Simulink - MathWorks Deutschland. (2022, May 20).
https://de.mathworks.com/help/sldo/parameter-estimation.html
Pelda, J., Holler, S., & Persson, U. (2021). District heating atlas - Analysis of the German
district heating sector. Energy, 233, 121018.
https://doi.org/10.1016/j.energy.2021.121018
Qu, M., Xia, L., Deng, S., & Jiang, Y. (2012). An experimental investigation on reverse-
cycle defrosting performance for an air source heat pump using an electronic
expansion valve. Applied Energy, 97, 327–333.
https://doi.org/10.1016/j.apenergy.2011.11.057
Self, S. J., Reddy, B. V., & Rosen, M. A. (2013). Geothermal heat pump systems: Status
review and comparison with other heating options. Applied Energy, 101, 341–
348. https://doi.org/10.1016/j.apenergy.2012.01.048
Singh, S., & Sørensen, K. (2018). Dynamic model of a heat pump based house heating
system. In Linköping Electronic Conference Proceedings, Proceedings of The 59th
Conference on simulation and Modelling (SIMS 59), 26-28 September 2018, Oslo
Metropolitan University, Norway (pp. 87–94). Linköping University Electronic
Press. https://doi.org/10.3384/ecp1815387
Solstice 454B European Refrigerants. (2022, May 28). https://www.honeywell-
refrigerants.com/europe/product/solstice-454b-r-454b/
Webseite der Bundesregierung | Startseite. (2022, May 2). Wohlstand sichern – Klima
schützen | Bundesregierung. https://www.bundesregierung.de/breg-
de/themen/klimaschutz/wohlstand-und-klimaschutz-2018366
70
Yang, Z., Xiao, H., Shi, W., Zhang, M., & Wang, B. (2021). Analysis and determination of
a seasonal performance evaluation for air source heat pumps. Journal of Building
Engineering, 43, 102574. https://doi.org/10.1016/j.jobe.2021.102574
71
Appendix A - Pressure Temperature Tables for Opteon™ XL41
(R‐454B)
Opteon™ XL41 (R-454B) is a mildly flammable low global warming potential (GWP)
hydrofluoro- olefin (HFO) based refrigerant to replace R-410A in new equipment designs.
Opteon™ XL41 offers the optimal balance of properties to replace R-410A in positive
displacement, direct expansion air conditioning, heat pump and chiller applications.
Opteon™ XL41 is the lowest GWP Opteon™ replacement for R-410A (78% reduction) and
provides improved performance. Opteon™ XL41 offers similar properties to R-410A which
makes it easy and cost-effective to apply in new equipment without major modifications.
Opteon™ XL41 is classified as a mildly flammable (ISO/ ASHRAE class 2L) refrigerant. Please
check your local regulations and Standards such as PED, EN 378 or ISO 5149 to verify the
allowable filling charge, new equipment design and safe handling requirements for the
intended application.
72
Units: Temperature = °C, Pressure = bar absolute Units: Pressure = bar absolute, Temperature = °C
Saturated Pressure (bar) Saturated Pressure (bar) Saturated Pressure (bar) Saturated Temperature (°C) Saturated Temperature (°C) Saturated Temperature (°C)
Temperature Temperature Temperature
Liquid Vapor Liquid Vapor Liquid Vapor Pressure (bar) Liquid Vapor Pressure (bar) Liquid Vapor Pressure (bar) Liquid Vapor
(ºC) (ºC) (ºC)
(Bubble) (Dew) (Bubble) (Dew) (Bubble) (Dew) (Bubble) (Dew) (Bubble) (Dew) (Bubble) (Dew)
-60 0.613 0.582 -13 4.913 4.705 34 19.810 19.165 0.6 -60.4 -59.5 2.472 -30.9 -29.8 10.176 9.5 10.8
-59 0.648 0.615 -12 5.089 4.874 35 20.311 19.656 0.617 -59.9 -58.9 2.542 -30.3 -29.1 10.462 10.4 11.8
-58 0.685 0.650 -11 5.270 5.048 36 20.821 20.155 0.634 -59.4 -58.5 2.614 -29.6 -28.5 10.756 11.4 12.7
-57 0.723 0.686 -10 5.456 5.227 37 21.340 20.665 0.652 -58.9 -57.9 2.688 -28.9 -27.8 11.059 12.4 13.7
-56 0.762 0.724 -9 5.647 5.411 38 21.870 21.184 0.67 -58.4 -57.4 2.764 -28.2 -27.1 11.37 13.3 14.6
-55 0.804 0.764 -8 5.842 5.600 39 22.409 21.713 0.689 -57.9 -56.9 2.842 -27.5 -26.4 11.69 14.3 15.6
-54 0.847 0.805 -7 6.043 5.793 40 22.958 22.252 0.708 -57.4 -56.4 2.922 -26.8 -25.7 12.019 15.3 16.6
-53 0.892 0.848 -6 6.249 5.992 41 23.517 22.802 0.728 -56.9 -55.9 3.004 -26.1 -25.0 12.357 16.2 17.6
-52 0.939 0.893 -5 6.461 6.195 42 24.086 23.361 0.748 -56.4 -55.4 3.088 -25.4 -24.3 12.705 17.2 18.6
-51 0.988 0.939 -4 6.677 6.404 43 24.665 23.932 0.769 -55.8 -54.9 3.175 -24.7 -23.6 13.062 18.2 19.5
-50 1.039 0.988 -3 6.899 6.619 44 25.255 24.513 0.791 -55.3 -54.3 3.264 -24.0 -22.9 13.429 19.2 20.5
-49 1.092 1.038 -2 7.127 6.838 45 25.855 25.104 0.813 -54.8 -53.8 3.356 -23.3 -22.1 13.807 20.2 21.6
-48 1.147 1.091 -1 7.360 7.063 46 26.466 25.707 0.836 -54.3 -53.3 3.45 -22.6 -21.4 14.195 21.2 22.6
-47 1.204 1.146 0 7.599 7.294 47 27.088 26.321 0.86 -53.7 -52.7 3.547 -21.9 -20.7 14.594 22.3 23.6
-46 1.263 1.202 1 7.844 7.531 48 27.721 26.947 0.884 -53.2 -52.2 3.647 -21.1 -20.0 15.005 23.3 24.6
-45 1.325 1.261 2 8.095 7.773 49 28.365 27.583 0.909 -52.6 -51.6 3.75 -20.4 -19.2 15.427 24.3 25.7
-44 1.389 1.323 3 8.352 8.021 50 29.020 28.232 0.935 -52.1 -51.1 3.855 -19.7 -18.5 15.861 25.4 26.7
-43 1.456 1.386 4 8.614 8.275 51 29.687 28.893 0.961 -51.5 -50.5 3.963 -18.9 -17.7 16.307 26.4 27.7
-42 1.525 1.452 5 8.883 8.535 52 30.365 29.565 0.988 -51.0 -50.0 4.074 -18.2 -17.0 16.766 27.5 28.8
-41 1.596 1.521 6 9.159 8.801 53 31.055 30.250 1.016 -50.4 -49.4 4.189 -17.4 -16.2 17.238 28.5 29.9
-40 1.670 1.592 7 9.440 9.074 54 31.757 30.947 1.045 -49.9 -48.9 4.307 -16.7 -15.5 17.723 29.6 30.9
-39 1.747 1.665 8 9.728 9.352 55 32.471 31.657 1.074 -49.3 -48.3 4.428 -15.9 -14.7 18.222 30.7 32.0
-38 1.827 1.742 9 10.023 9.638 56 33.197 32.381 1.104 -48.8 -47.8 4.553 -15.1 -13.9 18.735 31.8 33.1
-37 1.909 1.820 10 10.324 9.929 57 33.935 33.117 1.135 -48.2 -47.2 4.681 -14.4 -13.1 19.262 32.9 34.2
-36 1.994 1.902 11 10.632 10.228 58 34.686 33.867 1.167 -47.6 -46.6 4.813 -13.6 -12.4 19.804 34.0 35.3
-35 2.082 1.987 12 10.947 10.533 59 35.450 34.630 1.2 -47.1 -46.0 4.948 -12.8 -11.6 20.361 35.1 36.4
-34 2.174 2.074 13 11.269 10.845 60 36.226 35.407 1.234 -46.5 -45.5 5.087 -12.0 -10.8 20.934 36.2 37.5
-33 2.268 2.164 14 11.598 11.164 61 37.016 36.199 1.269 -45.9 -44.9 5.23 -11.2 -10.0 21.523 37.3 38.6
-32 2.365 2.258 15 11.934 11.490 62 37.819 37.005 1.305 -45.3 -44.3 5.377 -10.4 -9.2 22.128 38.5 39.8
-31 2.466 2.354 16 12.277 11.823 63 38.635 37.827 1.342 -44.7 -43.7 5.528 -9.6 -8.4 22.75 39.6 40.9
-30 2.570 2.454 17 12.627 12.163 64 39.465 38.663 1.38 -44.1 -43.1 5.683 -8.8 -7.6 23.39 40.8 42.1
-29 2.677 2.557 18 12.985 12.511 65 40.309 39.515 1.419 -43.5 -42.5 5.843 -8.0 -6.7 24.048 41.9 43.2
-28 2.788 2.663 19 13.351 12.866 66 41.167 40.383 1.459 -43.0 -41.9 6.007 -7.2 -5.9 24.724 43.1 44.4
-27 2.902 2.772 20 13.724 13.228 67 42.040 41.268 1.5 -42.4 -41.3 6.176 -6.4 -5.1 25.419 44.3 45.5
-26 3.020 2.886 21 14.105 13.599 68 42.927 42.170 1.542 -41.8 -40.7 6.35 -5.5 -4.3 26.134 45.5 46.7
-25 3.142 3.002 22 14.494 13.977 69 - - 1.585 -41.2 -40.1 6.529 -4.7 -3.4 26.869 46.6 47.9
-24 3.267 3.122 23 14.890 14.363 70 - - 1.63 -40.5 -39.5 6.713 -3.8 -2.6 27.625 47.8 49.1
-23 3.396 3.246 24 15.295 14.757 71 - - 1.676 -39.9 -38.9 6.902 -3.0 -1.7 28.402 49.1 50.3
-22 3.529 3.374 25 15.708 15.159 72 - - 1.723 -39.3 -38.2 7.096 -2.1 -0.9 29.201 50.3 51.5
-21 3.666 3.505 26 16.129 15.570 73 - - 1.771 -38.7 -37.6 7.296 -1.3 0.0 30.022 51.5 52.7
-20 3.807 3.641 27 16.559 15.989 74 - - 1.821 -38.1 -37.0 7.501 -0.4 0.9 30.866 52.7 53.9
-19 3.952 3.780 28 16.997 16.416 75 - - 1.872 -37.4 -36.4 7.712 0.5 1.8 31.734 54.0 55.1
-18 4.101 3.924 29 17.444 16.852 76 - - 1.925 -36.8 -35.7 7.929 1.3 2.6 32.627 55.2 56.3
-17 4.255 4.071 30 17.899 17.297 77 - - 1.979 -36.2 -35.1 8.152 2.2 3.5 33.545 56.5 57.6
-16 4.412 4.223 31 18.363 17.750 78 - - 2.035 -35.5 -34.4 8.381 3.1 4.4 34.489 57.7 58.8
-15 4.575 4.379 32 18.836 18.213 79 - - 2.092 -34.9 -33.8 8.617 4.0 5.3 35.459 59.0 60.1
-14 4.742 4.540 33 19.319 18.684 80 - - 2.151 -34.2 -33.1 8.859 4.9 6.2 36.456 60.3 61.3
2.212 -33.6 -32.5 9.108 5.8 7.1 37.481 61.6 62.6
2.274 -32.9 -31.8 9.364 6.7 8.0 38.535 62.9 63.8
2.338 -32.3 -31.2 9.627 7.7 9.0 39.619 64.2 65.1
2.404 -31.6 -30.5 9.898 8.6 9.9 40.733 65.5 66.4
41.879 66.8 67.7
Appendix B – Datasheet of KTN110D42UFZ_Brinecompressor
7000.
0
CONDENSING
CAPACITY
60.
TEMP(oC3
0
5000. 55.
(W)
0 0
6000.
4000. 50.
0 0
45.
3000. 0
0 40.
2000. 0
0
35.
0
0.0
- -5.0 0.0 5.0 10. 1
1000. 30.
10.0 0 5
0 EVAPORATING 0
TEMP.(?)
1400.
0
60.
1000. 0
CONDENSING
0 55.
INPUT
1200. 0
800.
(W)
50.
TEMP(oC3
00 0
600. 45.
0 0
400. 40.
0 0
35.
0.0 0
- -5.0 0.0 5.0 10. 1
200. 10.0 0 5
0 30.
EVAPORATING
TEMP.(?) 0
80.
0
RATE
CONDENSING
70. 60.
0
TEMP(oC3
0
(kg/h)
FLOW
50.
60. 0
55.
0
40.0 0
45.
50. 0
0
30.0
40.
0
20.0
35.
0
10.0
9.0
0
0.0
8.0 30.60.
0
0
0
CURRENT
7.0
(A)
TEMP(oC3
0 55.
0
EVAPORATING TEMP.(?)
6.0
0
Evaporating Temp(°C)
Input Power(W)
-10.0 -5.0 0.0 5.0 10.0 15
60.0 1103.4 1171.3 1225.2 1260. 1278.9 1279.6
6
55.0 1024.6 1076.0 1112.9 1134. 1142.0 1133.7
9
Condensing 50.0 953.3 991.5 1015.9 1027. 1025.1 1008.3
Temp(°C) 2
45.0 887.1 913.1 927.4 929. 919.2 894.0
6
40.0 821.0 837.2 842.6 836. 817.7 783.4
7
35.0 753.0 760.6 758.1 744. 716.1 670.9
1
30.0 680.1 680.3 670.6 648. 610.2 550.9
4
Evaporating Temp(°C)
Flow Rate(kg/h)
-10.0 -5.0 0.0 5.0 10.0 15
60.0 25.5 30.5 36.5 43.8 52.4 62.9
55.0 25.7 30.8 37.0 44.5 53.5 64.4
50.0 25.9 31.2 37.6 45.3 54.6 65.8
Condensing 45.0 26.3 31.6 38.1 46.0 55.6 67.1
Temp(°C) 40.0 26.6 32.0 38.6 46.7 56.3 68.0
35.0 26.8 32.4 39.1 47.2 56.9 68.6
30.0 27.9 32.7 39.4 47.4 57.2 68.8
Evaporating Temp(°C)
Current(A)
-10.0 -5.0 0.0 5.0 10.0 15
60.0 7.21 7.65 8.01 8.24 8.37 8.38
55.0 6.70 7.04 7.28 7.42 7.47 7.42
50.0 6.24 6.49 6.64 6.72 6.71 6.60
Condensing 45.0 5.81 5.97 6.06 6.08 6.01 5.85
Temp(°C) 40.0 5.37 5.48 5.51 5.47 5.35 5.13
35.0 4.92 4.97 4.95 4.86 4.68 4.39
30.0 4.45 4.45 4.38 4.24 3.99 3.61
Application
DPF Series electronic expansion valve is mainly composed of step
motor and valve needle with magnetic rotor, driven by coil which
receives pulse signals from controller.The transmission screw
converts the rotary motion of the rotor component into the axial
linear motion of the valve needle to regulate the flow areathe
of
valve port, adjustingthe refrigerantflow rate.
Features
1. Low noise and high control precision
2. Bi-directional flow;
3. Low power consumption and wide flow regulation range;
4. Superior self-lubricating thread transmission;
5. Application spectrum has extended into systems under potentially explosive conditions
6. Plastic packaging anti-corrosion coil
7.Advanced and highly reliable welding
8. Good actuating performance
9. Lightweight and compact construction
Approvals
Declarationaccordingto PED, LVD,IECEx and UL.
Technical Data
Applicable Refrigerant: R134a, R407C, R404A, R410A, R290 and
R32Relative Humidity:≤95%
Medium Temperature:-30°C~+70°C(energizedrate below 50%)
AmbientTemperature:-30°C~+60°C(energizedrate below 50%)
Max. Operating Pressure: 4.5 MPa
DPF series selection table
DPF(B)2.2-101 310002001000 A 45 1
DPF(B)2.2-103 310002005100 A 19 2
2.2 ≥ 60
DPF(B)2.2-105 310002003600 B 45 1 4.5
DPF(B)2.2-106 310002001700 B 19 2
DPF(B)2.4-101 310003207500 A 55 1
DPF(B)2.4-103 310003207600 A 23 2
2.4 ≥ 74
DPF(B)2.4-105 310003201900 B 55 1
DPF(B)2.4-106 310003203500 B 23 2
DPF(B)2.8-101 310008002900 A 67 1
DPF(B)2.8-103 310008003000 A 29 2
2.8 ≥ 95
DPF(B)2.8-105 310008000800 B 67 1
DPF(B)2.8-106 310008003100 B 29 2
DPF(B)3.0-101 310004003600 A 79 1
DPF(B)3.0-103 310004003700 A 31 2
3.0 ≥ 105 ≤ 1000 ≥ 1.5 2.8
DPF(B)3.0-105 310004003800 B 79 1
DPF(B)3.0-106 310004003900 B 31 2
DPF(B)3.2-101 310009004300 A 91 1
DPF(B)3.2-103 310009004600 A 33 2
3.2 ≥ 115
DPF(B)3.2-105 310009000800 B 91 1
DPF(B)3.2-106 310009001800 B 33 2
DPF(B)3.5C-P001 310026000300 B 3.5 95 ≥ 113 1
DPF(B)4.0C-P001 310017004000 B 4.0 135 ≥ 213 1
DPF(B)4.5C-P001 310018001900 B 4.5 180 ≥ 268 1 ≤ 1500 ≥2.2 3.5
DPF(B)5.5C-P001 310020001500 B 5.5 245 ≥ 397 1
DPF(B)6.5C-P001 310022001200 B 6.5 260 ≥ 483 1
Appendix F – Measurement data for modeling the expansion valve (2022-01-
20)
Temp
Temp_in _out pressure before pressure after
Time PWM (%) (K) (°C) expansion (bar) expansion (bar)
15:02:48 39.8 313.95 -3.8 24.16 5.31
15:02:58 40 313.85 -3.8 24.17 5.4
15:03:08 39.8 313.85 -3.7 24.19 5.47
15:03:18 36.2 313.95 -3.5 24.24 5.48
15:03:28 32.4 314.05 -3.4 24.34 5.35
15:03:38 32.2 314.25 -3.4 24.4 5.22
15:03:48 33 314.35 -3.4 24.45 5.11
15:03:58 35.2 314.25 -3.5 24.44 5.09
15:04:08 36.8 314.25 -3.7 24.36 5.13
15:04:18 37.6 314.15 -3.7 24.26 5.19
15:04:28 39.2 314.05 -3.8 24.23 5.23
15:04:38 39.8 313.95 -3.8 24.2 5.31
15:04:48 39.8 313.95 -3.7 24.17 5.38
15:04:58 39.6 313.85 -3.6 24.16 5.45
15:05:08 37.6 313.85 -3.5 24.15 5.46
15:05:18 32.8 313.95 -3.4 24.19 5.35
15:05:28 31.8 314.05 -3.4 24.24 5.22
15:05:38 32.6 314.05 -3.4 24.32 5.1
15:05:48 34.8 314.05 -3.6 24.38 5.06
15:05:58 36.4 314.05 -3.7 24.35 5.1
15:06:08 37.8 314.05 -3.8 24.26 5.15
15:06:18 38.8 313.95 -3.8 24.18 5.2
15:06:28 39.6 313.95 -3.9 24.12 5.27
15:06:38 40 313.85 -3.8 24.09 5.35
15:06:48 39.8 313.75 -3.7 24.08 5.43
15:06:58 39.4 313.75 -3.6 24.11 5.49
15:07:08 33.8 313.85 -3.4 24.17 5.44
15:07:18 32 313.95 -3.4 24.26 5.28
15:07:28 32.2 314.05 -3.4 24.35 5.14
15:07:38 33.6 314.15 -3.5 24.39 5.07
15:07:48 35.8 314.15 -3.6 24.34 5.09
15:07:58 37.2 314.05 -3.7 24.25 5.13
15:08:08 38.2 313.95 -3.8 24.2 5.19
15:08:18 39 313.95 -3.8 24.18 5.25
15:08:28 39.8 313.85 -3.8 24.15 5.32
15:08:38 40 313.75 -3.7 24.12 5.39
15:08:48 39.6 313.75 -3.6 24.13 5.47
15:08:58 37.2 313.85 -3.5 24.14 5.49
15:09:08 32.4 313.95 -3.4 24.21 5.36
15:09:18 31.8 314.05 -3.3 24.31 5.21
15:09:28 32.8 314.15 -3.4 24.4 5.1
15:09:38 35.2 314.15 -3.5 24.42 5.08
15:09:48 37 314.15 -3.7 24.32 5.12
15:09:58 38 314.05 -3.8 24.21 5.17
15:10:08 39 313.95 -3.8 24.12 5.2
15:10:18 39.6 313.85 -3.8 24.08 5.28
15:10:28 39.8 313.75 -3.8 24.07 5.35
15:10:38 39.8 313.65 -3.7 24.08 5.43
15:10:48 39 313.75 -3.6 24.15 5.49
15:10:58 33.2 313.85 -3.5 24.23 5.41
15:11:08 31.6 314.05 -3.4 24.3 5.27
15:11:18 32.2 314.15 -3.4 24.36 5.14
15:11:28 34.2 314.15 -3.5 24.42 5.07
15:11:38 35.6 314.15 -3.7 24.38 5.09
15:11:48 37.2 314.05 -3.8 24.28 5.14
15:11:58 38.2 314.05 -3.8 24.21 5.19
15:12:08 39.4 313.95 -3.9 24.12 5.24
15:12:18 39.8 313.85 -3.9 24.07 5.32
15:12:28 40 313.75 -3.8 24.05 5.38
15:12:38 39.6 313.65 -3.7 24.07 5.45
15:12:48 37.8 313.75 -3.6 24.15 5.48
15:12:58 32.4 313.85 -3.5 24.24 5.39
15:13:08 31.8 314.05 -3.4 24.3 5.24
15:13:18 32.6 314.15 -3.4 24.35 5.12
15:13:28 34.8 314.15 -3.6 24.39 5.07
15:13:38 36.4 314.15 -3.7 24.36 5.1
15:13:48 37.6 314.05 -3.8 24.26 5.15
15:13:58 38.8 313.95 -3.9 24.18 5.19
15:14:08 39.6 313.85 -3.9 24.08 5.24
15:14:18 39.8 313.75 -3.9 24.04 5.33
15:14:28 39.8 313.65 -3.8 24.02 5.4
15:14:38 39.4 313.55 -3.7 24.06 5.48
15:14:48 35.2 313.75 -3.6 24.1 5.46
15:14:58 32 313.85 -3.4 24.22 5.33
15:15:08 31.6 314.05 -3.4 24.28 5.19
15:15:18 32.8 314.05 -3.5 24.34 5.08
15:15:28 35 314.05 -3.7 24.33 5.07
15:15:38 36.8 314.05 -3.8 24.25 5.11
15:15:48 38 313.95 -3.9 24.2 5.15
15:15:58 39 313.85 -3.9 24.18 5.19
15:16:08 39.6 313.85 -4 24.11 5.25
15:16:18 39.8 313.75 -3.9 24.07 5.33
15:16:28 39.8 313.65 -3.9 24.07 5.4
15:16:38 39.4 313.75 -3.7 24.12 5.48
15:16:48 35.2 313.85 -3.6 24.19 5.46
15:16:58 31.8 313.95 -3.5 24.26 5.32
15:17:08 31.6 314.05 -3.5 24.3 5.16
15:17:18 33.2 314.15 -3.6 24.35 5.08
15:17:28 35.4 314.05 -3.7 24.32 5.09
15:17:38 36.8 314.05 -3.9 24.22 5.12
15:17:48 38 313.95 -3.9 24.11 5.17
15:17:58 39.2 313.85 -4 24.05 5.2
15:18:08 39.6 313.75 -4 24.07 5.28
15:18:18 39.8 313.65 -3.9 24.11 5.36
15:18:28 39.8 313.65 -3.8 24.17 5.43
15:18:38 39.2 313.85 -3.7 24.24 5.49
15:18:48 34.2 313.95 -3.6 24.32 5.45
15:18:58 31.6 314.15 -3.5 24.36 5.29
15:19:08 31.6 314.25 -3.5 24.37 5.17
15:19:18 33.2 314.25 -3.5 24.38 5.07
269.4
Mean 36.57 313.95 9 (K) 24.22 5.26
Appendix G – Measurement data 1 for modeling condenser (2022-01-20)
Time Pressure (bar) T_ref_in (K) T_ref_out (K) T_water_in (K) T_water_out (K)
13:05:38 24.27 357.65 314.75 313.052 318.032
13:05:48 24.29 357.65 314.75 313.47 318.016
13:05:58 24.3 357.65 314.65 313.281 318.006
13:06:08 24.37 357.65 314.75 313.192 318.048
13:06:18 24.34 357.65 314.75 313.116 318.08
13:06:28 24.3 357.65 314.75 313.092 318.094
13:06:38 24.24 357.75 314.75 312.998 318.092
13:06:48 24.22 357.75 314.65 312.937 318.098
13:06:58 24.23 357.75 314.65 312.966 318.135
13:07:08 24.27 357.75 314.65 312.927 318.178
13:07:18 24.3 357.75 314.65 312.905 318.194
13:07:28 24.3 357.75 314.75 313.026 318.171
13:07:38 24.28 357.75 314.75 313.047 318.16
13:07:48 24.27 357.75 314.75 313.152 318.133
13:07:58 24.29 357.85 314.65 313.153 318.103
13:08:08 24.31 357.85 314.75 313.129 318.078
13:08:18 24.27 357.85 314.75 313.151 318.056
13:08:28 24.23 357.85 314.65 313.098 318.028
13:08:38 24.23 357.85 314.65 313.12 318.027
13:08:48 24.21 357.85 314.65 313.123 318.032
13:08:58 24.24 357.85 314.65 313.097 318.045
13:09:08 24.24 357.85 314.65 313.117 318.068
13:09:18 24.21 357.85 314.65 313.087 318.088
13:09:28 24.19 357.85 314.65 313.097 318.103
13:09:38 24.23 357.85 314.55 313.14 318.11
13:09:48 24.27 357.95 314.65 313.194 318.108
13:09:58 24.24 357.95 314.65 313.106 318.101
13:10:08 24.22 357.95 314.65 313.012 318.099
13:10:18 24.23 357.95 314.65 312.992 318.087
13:10:28 24.23 357.95 314.65 313.075 318.094
13:10:38 24.24 357.95 314.65 312.984 318.099
13:10:48 24.3 357.95 314.65 312.937 318.099
13:10:58 24.31 357.95 314.75 312.972 318.105
13:11:08 24.29 357.95 314.75 312.998 318.117
13:11:18 24.27 357.95 314.75 313.022 318.11
13:11:28 24.19 357.95 314.65 313.086 318.084
13:11:38 24.15 357.95 314.65 313.147 318.057
13:11:48 24.23 357.95 314.55 313.042 318.039
13:11:58 24.27 357.95 314.55 313.006 318.017
13:12:08 24.31 357.95 314.65 313.017 318
13:12:18 24.33 357.95 314.75 312.895 317.997
13:12:28 24.27 357.95 314.75 312.922 317.987
13:12:38 24.26 358.05 314.75 312.995 317.987
13:12:48 24.27 357.95 314.65 313.112 318.011
13:12:58 24.25 358.05 314.65 313.11 318.031
13:13:08 24.26 358.05 314.65 313.092 318.027
13:13:18 24.35 358.05 314.65 313.13 318.01
13:13:28 24.29 358.05 314.75 313.099 317.98
13:13:38 24.27 358.05 314.75 313.012 317.955
13:13:48 24.27 358.05 314.75 312.988 317.947
13:13:58 24.23 358.05 314.65 312.977 317.951
13:14:08 24.23 358.05 314.65 313.027 317.984
13:14:18 24.27 358.05 314.65 313.078 318.005
13:14:28 24.34 358.05 314.65 313.073 318.023
13:14:38 24.31 358.05 314.75 313.064 318.03
13:14:48 24.27 358.05 314.75 313.085 318.016
13:14:58 24.28 358.15 314.75 313.186 318.004
13:15:08 24.28 358.05 314.75 313.202 317.989
13:15:18 24.31 358.05 314.75 313.291 317.987
13:15:28 24.34 358.15 314.75 313.271 317.987
13:15:38 24.35 358.05 314.75 313.209 317.977
13:15:48 24.3 358.15 314.75 313.104 317.968
13:15:58 24.27 358.15 314.75 313.135 317.974
13:16:08 24.3 358.15 314.75 313.094 318.002
13:16:18 24.25 358.15 314.65 313.098 318.044
13:16:28 24.21 358.15 314.65 312.927 318.064
13:16:38 24.3 358.15 314.75 312.895 318.074
13:16:48 24.35 358.15 314.75 312.909 318.08
13:16:58 24.32 358.15 314.75 312.925 318.083
13:17:08 24.31 358.15 314.75 313.083 318.093
13:17:18 24.27 358.15 314.75 313.178 318.09
13:17:28 24.2 358.15 314.75 313.125 318.061
13:17:38 24.23 358.25 314.65 313.227 318.009
13:17:48 24.29 358.25 314.65 313.275 317.957
13:17:58 24.31 358.25 314.65 313.268 317.92
13:18:08 24.34 358.25 314.75 313.215 317.912
13:18:18 24.39 358.25 314.75 313.179 317.939
13:18:28 24.33 358.25 314.85 313.044 317.968
13:18:38 24.29 358.25 314.85 313.079 317.99
13:18:48 24.31 358.25 314.75 313.055 318.009
13:18:58 24.31 358.25 314.75 313.073 318.041
13:19:08 24.35 358.35 314.75 313.068 318.089
13:19:18 24.35 358.35 314.75 313.164 318.126
13:19:28 24.32 358.35 314.75 313.117 318.13
13:19:38 24.28 358.35 314.75 313.105 318.105
13:19:48 24.31 358.35 314.75 313.053 318.066
13:19:58 24.28 358.35 314.75 313.223 318.047
13:20:08 24.27 358.35 314.75 313.339 318.039
13:20:18 24.27 358.35 314.75 313.375 318.056
13:20:28 24.26 358.35 314.75 313.259 318.071
13:20:38 24.25 358.45 314.75 313.074 318.055
13:20:48 24.27 358.45 314.75 313.043 318.026
13:20:58 24.28 358.45 314.75 313.094 318.013
13:21:08 24.25 358.45 314.75 313.164 318.036
13:21:18 24.27 358.45 314.75 313.199 318.088
13:21:28 24.27 358.45 314.75 313.159 318.141
13:21:38 24.27 358.55 314.65 313.107 318.148
13:21:48 24.26 358.55 314.65 313.035 318.11
13:21:58 24.3 358.55 314.65 313.073 318.064
13:22:08 24.28 358.55 314.65 313.133 318.052
Average 24.2768 358.064 314.706 313.09553 318.05016
Appendix L – Measurement data 3 for validating evaporator (20220201)