3. TECHNICAL PARAMETERS
3.1 NX2-G02 / 5
NX2-G02 /0042
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 43,6
Seasonal energy efficiency of the space cooling ηs,c [%] 183,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 43,6
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 32,1
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 28,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 31,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,20
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,18
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,43
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,74
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,113
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 85,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 17496,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0042
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 42,9
Seasonal energy efficiency of the space cooling ηs,c [%] 180,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 42,9
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 31,6
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 28,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 31,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,96
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,05
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,43
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,74
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,113
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 81,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 13500,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0042
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 42,3
Seasonal energy efficiency of the space cooling ηs,c [%] 180,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 42,3
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 31,2
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 28,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 31,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,94
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,07
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,43
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,74
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,113
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 77,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 12636,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0042
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 43,6
Seasonal energy efficiency of the space cooling ηs,c [%] 194,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 43,6
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 32,1
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 28,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 31,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,25
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,36
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,83
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 7,30
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,113
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,056
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 85,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 17496,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0042
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 42,9
Seasonal energy efficiency of the space cooling ηs,c [%] 191,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 42,9
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 31,6
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 28,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 31,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,07
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,28
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,83
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 7,30
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,113
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,056
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 81,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 13500,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0052
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 51,9
Seasonal energy efficiency of the space cooling ηs,c [%] 184,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 51,9
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 38,2
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 34,7
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 37,8
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,19
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,20
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,44
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,71
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,104
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 85,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 17496,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0052
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 50,8
Seasonal energy efficiency of the space cooling ηs,c [%] 180,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 50,8
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 37,4
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 34,7
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 37,8
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,91
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,07
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,44
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,71
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,104
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 82,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 13500,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0052
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 50,1
Seasonal energy efficiency of the space cooling ηs,c [%] 180,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 50,1
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 36,9
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 34,7
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 37,8
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,87
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,06
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,43
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,70
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,104
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 78,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 12636,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0052
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 51,9
Seasonal energy efficiency of the space cooling ηs,c [%] 193,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 51,9
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 38,2
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 34,7
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 37,8
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,22
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,35
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,76
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 7,17
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,104
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,056
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 85,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 17496,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0052
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 50,8
Seasonal energy efficiency of the space cooling ηs,c [%] 189,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 50,8
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 37,4
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 34,7
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 37,8
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,01
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,26
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,76
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 7,17
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,104
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,056
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 82,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 13500,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0062
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 58,0
Seasonal energy efficiency of the space cooling ηs,c [%] 176,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 58,0
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 42,7
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 38,2
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 41,3
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,23
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,16
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,17
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,95
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,129
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 85,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 17496,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0062
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 57,2
Seasonal energy efficiency of the space cooling ηs,c [%] 172,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 57,2
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 42,1
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 38,2
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 41,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,94
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,03
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,18
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,96
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,129
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 81,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 13500,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0062
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 56,6
Seasonal energy efficiency of the space cooling ηs,c [%] 171,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 56,6
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 41,7
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 38,2
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 41,3
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,89
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,01
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,17
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,96
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,129
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 77,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 12636,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0062
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 58,0
Seasonal energy efficiency of the space cooling ηs,c [%] 182,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 58,0
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 42,7
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 38,2
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 41,3
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,29
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,43
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,28
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,129
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,056
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 85,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 17496,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0062
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 57,2
Seasonal energy efficiency of the space cooling ηs,c [%] 179,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 57,2
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 42,1
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 38,2
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 41,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,02
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,19
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,44
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,29
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,129
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,056
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 81,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 13500,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0072
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 65,6
Seasonal energy efficiency of the space cooling ηs,c [%] 178,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 65,6
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 48,3
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 42,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 45,9
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,40
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,25
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,17
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,93
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,149
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 86,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 26352,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0072
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 65,0
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 65,0
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 47,9
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 42,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 45,9
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,17
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,13
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,17
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,93
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,149
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 83,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 20376,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0072
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 64,2
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 64,2
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 47,3
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 42,5
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 46,0
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,17
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,16
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,18
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,94
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,150
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 79,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 19224,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0072
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 65,6
Seasonal energy efficiency of the space cooling ηs,c [%] 187,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 65,6
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 48,3
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 42,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 45,9
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,45
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,43
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,53
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,37
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,149
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,066
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 86,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 26352,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0072
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 65,0
Seasonal energy efficiency of the space cooling ηs,c [%] 185,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 65,0
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 47,9
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 42,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 45,9
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,36
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,53
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,37
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,149
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,066
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 83,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 20376,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0082
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 72,7
Seasonal energy efficiency of the space cooling ηs,c [%] 178,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 72,7
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 53,6
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 47,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 51,8
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,23
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,20
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,170
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 87,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 26352,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0082
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 72,1
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 72,1
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 53,1
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 47,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 51,8
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,08
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,11
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,20
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,98
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,170
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 20376,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0082
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 71,3
Seasonal energy efficiency of the space cooling ηs,c [%] 174,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 71,3
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 52,5
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 47,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 51,7
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,07
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,12
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,20
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,97
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,170
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 80,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 19224,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0082
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 72,7
Seasonal energy efficiency of the space cooling ηs,c [%] 186,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 72,7
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 53,6
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 47,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 51,8
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,37
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,39
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,53
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,37
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,170
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,066
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 87,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 26352,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0082
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 72,1
Seasonal energy efficiency of the space cooling ηs,c [%] 184,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 72,1
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 53,1
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 47,8
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 51,8
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,20
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,31
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,53
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,37
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,170
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,066
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 20376,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0092
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 86,1
Seasonal energy efficiency of the space cooling ηs,c [%] 178,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 86,1
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 63,4
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 56,5
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 61,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,27
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,21
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,09
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,199
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 87,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 26352,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0092
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 85,3
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 85,3
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 62,9
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 56,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 61,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,99
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,05
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,09
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,199
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 20376,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0092
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 84,3
Seasonal energy efficiency of the space cooling ηs,c [%] 174,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 84,3
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 62,1
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 56,5
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 61,5
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,95
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,06
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,26
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,10
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,200
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,036
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 80,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 19224,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0092
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 86,1
Seasonal energy efficiency of the space cooling ηs,c [%] 186,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 86,1
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 63,4
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 56,5
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 61,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,31
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,34
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,53
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,44
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,199
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,066
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 87,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 26352,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0092
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 85,3
Seasonal energy efficiency of the space cooling ηs,c [%] 183,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 85,3
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 62,9
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 56,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 61,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,08
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,21
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,52
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,43
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,199
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,066
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 20376,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0102
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 100,1
Seasonal energy efficiency of the space cooling ηs,c [%] 176,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 100
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 73,8
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 57,1
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 62,1
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,26
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,06
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,12
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,88
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,130
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,107
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 89,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 39708,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0102
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 99,1
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 99,1
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 73,0
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 56,9
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 61,9
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,23
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,05
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,10
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,86
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,129
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,107
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 30780,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0102
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 98,2
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 98,2
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 72,4
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 57,1
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 62,1
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,15
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,02
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,16
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,94
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,130
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,107
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 80,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 28404,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0102
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 100,1
Seasonal energy efficiency of the space cooling ηs,c [%] 187,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 100
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 73,8
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 57,1
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 62,1
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,33
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,21
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,46
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,29
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,130
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,042
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 89,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 39708,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0102
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 99,1
Seasonal energy efficiency of the space cooling ηs,c [%] 186,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 99,1
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 73,0
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 56,9
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 61,9
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,30
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,21
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,45
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,27
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,129
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,042
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 30780,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0112
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 110,8
Seasonal energy efficiency of the space cooling ηs,c [%] 167,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 111
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 81,6
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 72,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 78,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,14
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,01
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,93
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,61
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,240
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,107
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 89,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 39708,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0112
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 109,7
Seasonal energy efficiency of the space cooling ηs,c [%] 166,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 110
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 80,8
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 72,5
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 78,5
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,07
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,99
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,93
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,62
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,241
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,107
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 30780,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0112
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 108,4
Seasonal energy efficiency of the space cooling ηs,c [%] 166,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 108
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 79,9
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 72,6
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 78,7
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,98
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,96
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,95
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,65
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,242
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,107
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 80,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 28404,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0112
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 110,8
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 111
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 81,6
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 72,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 78,4
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,20
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,14
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,17
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,90
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,240
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,042
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 89,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 39708,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0112
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 109,7
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 110
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 80,8
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 72,5
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 78,5
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,13
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,13
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,18
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,91
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,241
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,042
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 30780,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0122
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 125,4
Seasonal energy efficiency of the space cooling ηs,c [%] 169,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 125
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 92,4
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 73,0
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 79,0
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,04
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,91
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,98
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,67
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,200
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,107
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 89,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 39708,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0122
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 123,5
Seasonal energy efficiency of the space cooling ηs,c [%] 167,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 123
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 91,0
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 72,9
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 79,0
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,90
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,83
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,97
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,66
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,199
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,107
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 30780,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0122
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 121,8
Seasonal energy efficiency of the space cooling ηs,c [%] 166,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 122
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 89,7
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 73,0
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 79,1
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,78
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,76
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 4,99
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,70
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,200
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,107
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 80,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 28404,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0122
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 125,4
Seasonal energy efficiency of the space cooling ηs,c [%] 178,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 125
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 92,4
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 73,0
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 79,0
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,09
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,03
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,23
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,97
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,200
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,042
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 89,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 39708,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0122
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 123,5
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 123
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 91,0
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 72,9
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 79,0
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,94
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,95
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,22
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 5,96
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,199
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,042
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 30780,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0142
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 140,1
Seasonal energy efficiency of the space cooling ηs,c [%] 172,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 140
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 103
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,7
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 103
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,93
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,01
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,09
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,321
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 90,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 39708,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0142
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 137,3
Seasonal energy efficiency of the space cooling ηs,c [%] 170,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 137
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 101
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,5
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 103
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,73
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,93
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,18
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,07
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,320
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 85,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 30780,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0142
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 135,3
Seasonal energy efficiency of the space cooling ηs,c [%] 167,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 135
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 99,7
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,6
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 103
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,61
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,88
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,15
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,05
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,321
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 82,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 28404,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0142
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 140,1
Seasonal energy efficiency of the space cooling ηs,c [%] 179,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 140
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 103
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,7
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 103
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,97
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,12
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,40
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,35
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,321
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,048
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 90,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 39708,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0142
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 137,3
Seasonal energy efficiency of the space cooling ηs,c [%] 176,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 137
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 101
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,5
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 103
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,77
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,04
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,39
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,34
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,320
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,048
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 85,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 30780,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0162
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 163,5
Seasonal energy efficiency of the space cooling ηs,c [%] 178,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 163
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 120
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,6
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 103
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,12
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,02
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,22
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,04
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,264
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 91,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 59796,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0162
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 161,1
Seasonal energy efficiency of the space cooling ηs,c [%] 176,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 161
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 119
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 102
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,01
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,97
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,21
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,03
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,262
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 86,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 46188,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0162
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 159,0
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 159
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 117
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 103
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,91
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,91
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,25
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,09
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,263
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 82,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 42912,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0162
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 163,5
Seasonal energy efficiency of the space cooling ηs,c [%] 187,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 163
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 120
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,6
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 103
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,17
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,16
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,54
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,44
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,264
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,051
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 91,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 59796,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0162
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 161,1
Seasonal energy efficiency of the space cooling ηs,c [%] 186,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 161
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 119
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 94,4
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 102
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,07
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,11
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,53
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,43
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,262
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,051
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 86,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 46188,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0182
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 187,0
Seasonal energy efficiency of the space cooling ηs,c [%] 175,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 187
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 138
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 124
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 135
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,08
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,08
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,04
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,404
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 91,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 59796,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0182
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 184,0
Seasonal energy efficiency of the space cooling ηs,c [%] 173,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 184
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 136
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 124
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 135
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,93
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,04
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,20
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,05
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,406
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 87,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 46188,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0182
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 181,6
Seasonal energy efficiency of the space cooling ηs,c [%] 172,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 182
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 134
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 124
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 135
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,82
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,99
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,06
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,408
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 83,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 42912,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0182
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 187,0
Seasonal energy efficiency of the space cooling ηs,c [%] 182,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 187
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 138
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 124
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 135
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,13
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,21
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,43
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,34
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,404
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,051
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 91,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 59796,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0182
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 184,0
Seasonal energy efficiency of the space cooling ηs,c [%] 180,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 184
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 136
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 124
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 135
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,98
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,16
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,44
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,35
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,406
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,051
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 87,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 46188,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0202
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 200,7
Seasonal energy efficiency of the space cooling ηs,c [%] 177,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 201
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 148
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 135
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,04
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,12
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,28
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,17
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,402
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 91,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 59796,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0202
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 196,6
Seasonal energy efficiency of the space cooling ηs,c [%] 174,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 197
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 145
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 135
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 147
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,84
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,05
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,28
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,16
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,401
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 87,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 46188,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0202
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 193,9
Seasonal energy efficiency of the space cooling ηs,c [%] 173,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 194
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 143
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 136
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,73
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,02
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,28
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,18
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,406
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 83,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 42912,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0202
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 200,7
Seasonal energy efficiency of the space cooling ηs,c [%] 184,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 201
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 148
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 135
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 148
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 3,08
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,24
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,51
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,45
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,402
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,051
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 91,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 59796,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0202
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 196,6
Seasonal energy efficiency of the space cooling ηs,c [%] 181,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 197
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 145
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 135
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 147
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,89
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,18
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,50
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,45
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,401
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,051
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 87,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 46188,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0222
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 225,7
Seasonal energy efficiency of the space cooling ηs,c [%] 172,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 226
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 166
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 152
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 166
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,94
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,01
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,19
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,07
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,566
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 92,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 59796,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0222
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 220,9
Seasonal energy efficiency of the space cooling ηs,c [%] 169,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 221
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 163
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 152
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 166
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,71
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,92
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,18
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,06
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,564
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 88,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 46188,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0222
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 217,4
Seasonal energy efficiency of the space cooling ηs,c [%] 167,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 217
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 160
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 152
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 166
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,59
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 3,86
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,14
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,03
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,566
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,113
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 84,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 42912,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0222
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 225,7
Seasonal energy efficiency of the space cooling ηs,c [%] 179,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 226
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 166
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 152
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 166
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,97
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,12
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,38
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,31
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,566
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,051
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 92,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 59796,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy
NX2-G02 /0222
-
Outdoor side heat exchanger of chiller air or water/brine Air
Indoor side heat exchanger chiller water Water
Type compressor driven vapour compression or sorption Compressor driven
process vapour compression
Driver of compressor electric motor or fuel driven, gaseous or liquid fuel, Electric motor
internal or external combustion engine
Rated cooling capacity Prated,c [kW] 220,9
Seasonal energy efficiency of the space cooling ηs,c [%] 176,0
Declared cooling capacity for part load at given outdoor temperatures Tj
Declared cooling capacity at given outdoor temperatures Tj = 35°C Pdc [kW] 221
Declared cooling capacity at given outdoor temperatures Tj = 30°C Pdc [kW] 163
Declared cooling capacity at given outdoor temperatures Tj = 25°C Pdc [kW] 152
Declared cooling capacity at given outdoor temperatures Tj = 20°C Pdc [kW] 166
Degradation coefficient for chillers Cdc 0,9
Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Declared energy efficiency ratio at given outdoor temperatures Tj = 35°C EERd [%] 2,74
Declared energy efficiency ratio at given outdoor temperatures Tj = 30°C EERd [%] 4,03
Declared energy efficiency ratio at given outdoor temperatures Tj = 25°C EERd [%] 5,37
Declared energy efficiency ratio at given outdoor temperatures Tj = 20°C EERd [%] 6,30
Power consumption in modes other than "active mode"
Off mode POFF [kW] 0,000
Thermostat-off mode PTO [kW] 0,564
Crankcase heater mode PCK [kW] 0,000
Standby mode PSB [kW] 0,051
Other items
Capacity control fixed/staged/variable Variable
Sound power level, outdoor LWA [dB(A)] 88,0
GWP of the refrigerant [Kg CO2eq] 2088
For air-to-water comfort chillers: air flow rate, outdoor measured [m³/h] 46188,00
For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side [m³/h] -
heat exchanger
Standard rating conditions used: low temperature application/medium temperature Low temperature
application application
Contact details: Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A., via Caduti di Cefalonia 1 - 36061 Bassano del Grappa (VI) - Italy