TEMPERATURE CONTROLLER: Technical Specifications: Front Facia:

151G11B 151F11B 151H11B


ON-OFF/PROPORTIONAL Supply Characteristics:
GIC PR - 43

SERIES: PR-43
Dear Customer,
Thank you for purchasing ‘Temperature Controller: ON-OFF
Supply Voltage (Un)
Supply Tolerance
Supply Frequency
Power Consumption
Reset Time
110 - 240 VAC/DC
-20% to +10% of Un
50/60 Hz
6 VA @ 265 VAC
50 to 500 ms
888 OP1
°F

/Proportional’ from GIC. To avoid problems & damages, please


read leaflet carefully before operating the unit. In case of Functional Characteristics:
complaint please contact our customer support number. Menu Password Password 60(Default Disabled)
Thermocouple (J & K) 1. Displays the ‘Process Value’ & ‘Menu’.
Sensor Inputs (IEC)
ORDERING INFORMATION: RTD (Pt-100, 3-wire) 2. :“ ESC” key (Press for >2 sec to view set point).
TC (J-type): 3. : Scroll “Down” key.
151G11B (Relay : 5A(NO), 3A(NC), 1C/O) -5 to 750°C OR 23 to 999°F 4. : Scroll “UP” key
TC (K-type): (Press for >2sec to view controller output).
151H11B (SSR Drive: 12VDC, 30mA max) Sensor Measurement
-20 to 850°C OR -4 to 999°F 5. : “ Enter” key.(Press 2sec for to view menu).
Range
RTD (Pt-100): 6. Op1 : LED indication for relay output.
151F11B (Relay: 10A 1C/O) -100 to 650°C OR -148 to 999°F 7. ‘°F’ : This LED indicates ‘°F’ unit setting.
8. + : Press “ESC” key for 2 sec to view SP then
RoHS Resolution 1°C Fixed
simultaneously press “DOWN” key to decrement SP value.
Measurement And release the “ESC” key to set the New SP value.
+/-0.5% of full scale
Accuracy 9. + : Press “ESC” key for 2 sec to view SP then
Temperature Unit °C/°F selectable simultaneously press “UP”key to increment SP value.
Signal Sampling Time 2 ms And release the “ESC” key to set the New SP value.
GIC
PR - 43 4 Keys as ESC ( ), DOWN ( ) Mode Functionality:
70 OP1 °F
Front Keypad

Key de-bounce time


Sbr
UP ( ), ENTER ( )
≥ 40 ms
Sensor open/Break error
ON/OFF Control: Parameters regarding ON/OFF control are
listed in group “rEg”. This type of control can be set by
programming parameter “Con”= OnS for ON-OFF action with
Error Indications ovr Over range error symmetric hysteresis OR OnA for ON-OFF action with
unr Under range error asymmetric hysteresis. It drives the output programmed as
Control output Relay Relay SSR Drive coP [in 0p1], depending on the measured temperature value,
Features: Relay Output Characteristics: (151G11B/151F11B ) on set point, function mode (Fun) and on the hysteresis (Hys).
Contact Arrangement 1 C/O (SPDT) In case of reverse action i.e. Het (HEAT)being set on par. “FUn”
Highly Accurate Performance.
in “rEg” menu, the controller activates the output when the
Luxurious Single 3-digit LED Display. Contact Rating 5A(NO), 10A RES. @ process value “PV” goes below [SP-HYS]. It deactivates the
Wide supply range:110-240VAC (Un),-20 to +10% of Un. 3A(NC), RES. 250VAC/
@ 250VAC/ 30VDC
output when the PV goes above “SP+HYS” in case of
Front keypad with 4 keys.
30VDC symmetric ON-OFF control and above “SP” in case of
Thermocouple (J & K)/RTD 3-wire (Pt-100) sensor inputs.
Asymmetric ON-OFF control. Similarly in case of direct action
Control Modes:Proportional, ON-OFF Contact Material AgNi i.e. CoL (COOL)being set on par. “Fun”, the controller activates
Asymmetric, ON-OFF Symmetric. Utilization Category Ue Rated Voltage (V) : 120 / 240 the output when the process value “PV” goes below ‘sP-Hys’ &
°C & °F temperature unit selectable (AC-15) Ie Rated Current (A) : 3.0 / 1.5 deactivates the output when “PV” goes above ‘sP+Hys’ in
Control Output: Relay & SSR Drive (Individual products) Switching Frequency 1800 Operations/Hour case of symmetric ON-OFF control & “SP” in case of
Electrical Life 1,00,000 Operations Asymmetric ON-OFF control.
Connection Diagram: Mechanical Life 5,000,000 Operations
SSR Output Characteristics: (151H11B)
Output Voltage 12 VDC (13.82 V Max.)
151G11B/151F11B 151H11B
Load Current 30 mA (Max) OFF OFF
OP1 Series Resistance 270 Ω (Internal) 0nA - HEAT 0nA - COOL
LED Indications:
L N NC NO P L N OP1
- OP1 (Red LED) ON Relay output ON
+ + -
‘°F’ (Red LED) ON Display ‘°F’ value
5 4 3 2 1 5 4 3 2 1 OFF OFF OFF OFF
‘°F’ (Red LED) OFF Display ‘°C’ value
0ns - HEAT 0ns - COOL
Environmental Characteristics:
6 14 6 14 Operating Temperature 0 to 50 °C Proportional Control: Parameters regarding proportional
7 13 7 Storage Temperature -20 to 60 °C control are listed in group “rEg”. This type of control can be set
13
Operating Humidity 5 to 80 % RH (Non-Condensing) by programming parameter “Con”= P for proportional action.
8 9 10 11 12 Operating Altitude 2000 m (max) A proportional controller decreases average power supplied to
8 9 10 11 12
Pollution Degree II the Heater/Cooler as temperature approaches setpoint. This
TC/mV TC/mV IP 20: Terminal & Enclosure
Degree of Protection has effect of slowing down heater/Cooler so that it will not
IP 40: Front Facial overshoot the setpoint, but will approach setpoint & maintain
Pt-100 Pt-100 Enclosure Flame Retardant (UL 94-V0) a stable temperature. This proportional action can be
Other Characteristics: accomplished by turning the output ON & OFF for short time
Mounting ‘48 x 48’ mm Panel Mounting intervals. This "time proportioning" varies the ratio of “ON”
Mechanical Dimensions (in mm): Weight (Un-Packed) 120 gm time to "OFF" time to control the temperature. Proportional
Operating Position Horizontal (Readable) action occurs within a “Proportional Band (Pb)” around the
GASKET GRID RING
CASING PANEL CUTOUT EMI/EMC Compliance: setpoint temperature. Outside this band, the controller
Harmonic Current IEC 61000-3-2 (Class A) functions as an ON-OFF unit, with the output either fully on
Emission
(below ‘Pb’) or fully OFF (above ‘Pb’).
Voltage Flicker IEC 61000-3-3 (Class A) Proportional band (Pb) is the area around set point
44.5
45

ESD IEC 61000-4-2 (Level II) where controller is actually controlling the process; output
is at some level other than 100 or 0%. ‘Pb’ is expressed in
91.5
Radiated Susceptibility IEC 61000-4-3 (Level III) terms of 'ºC/ºF'. If controlling is not Satisfactory by using
107.4 45 Electrical Fast Transients IEC 61000-4-4 (Level IV) default ‘Pb’ value, following adjustment can be done in 'Pb'.
BACK PLATE_WITH TERMINAL RECOMMENDED PANEL CUTOUT
(Power Ports) Parameter Problem Occured
45 mmX 45 mm +/- 1.0 mm
Adjustment
Surge IEC 61000-4-5 (Level IV) Proportional PV not reach SP/Slow response Decrease ‘Pb’
Band (Pb) High overshoot or Oscillations Increase ‘Pb’
Terminal Details: Conducted Susceptibility IEC 61000-4-6 (Level III)
0.5 N.m (4.4 Lb.in) to
Cycle time (Ct): Also known as duty cycle; Total length of
Power Frequency IEC 61000-4-8 (Class 4)
4.....5.0mm 0.7 N.m (6.2Lb.in) time for controller to complete one ON/OFF cycle.
Combi head Bit./Flat
Magnetic Field
2 x 2.5mm E.g.: If Ct=20 sec, TON=10 sec & TOFF=10 sec, then it
Solid /Standard wire
Voltage Dips/Interruption IEC 61000-4-11 represents a 50 % power output. In this case, controller will
20 to 12
BACK VIEW Conducted & Radiated CISPR 14-1 (Class A) cycle ON & OFF while within the set proportional band 'Pb'.
Emission Rate (rte) & Offset (Oft): Product can be re-calibrated
Caution:
Product Standard IEC 61326-1 according to application needs, by using par. “OFt” and “rte”.
Installation should be done by skilled person only. If “rte” = 1.00, then using par “OFt”, it is possible to set
Safety Compliance:
When extending the thermocouple lead wires, always use positive or negative offset that is simply added to the value
thermocouple compensation wires for wiring. Dielectric Strength IEC 60974-5-1 (2 kV)
(Input & Output)
read by the probe.
For RTD sensor, use a wiring material with a small lead If the offset set is not to be constant for all measurements, it
resistance (5Ω max per line) & no resistance differentials Impulse IEC 60974-5-1 (Level IV) is possible to operate the calibration on any of two points. In
among 3 wires. (Input & Output)
this case, in order to decide which values to program on par.
Product should be cleaned regularly to avoid blockage of Single Fault IEC 61010-1 “OFt” and “rte”, the following formulae must be applied:
ventilating parts. Insulation Resistance UL 508 (>50 kΩ) “rte” = (y2-y1)/(x2-x1)
Clean the product with a clean soft cloth. Do not use Leakage Current UL 508 (< 3.5 mA) “OFt” = y2 - rte*x2
isopropyl alcohol or any other cleaning agent. Where,
Environmental Compliance:
Use of contactors is recommended if load exceeds the y1 = Measured temperature 1
contact rating. Please see Inductive load category. Cold Heat IEC 60068-2-1
x1 = temperature displayed by instrument
For Thermocouple (J & K): To make output ON ensure that, Dry Heat IEC 60068-2-2 y2 = Measured temperature 2
CJC setting is ON. Vibration IEC 60068-2-6 (5g) x2 = temperature displayed by instrument.
When replacing the sensor, please turn OFF the power. The instrument thus visualizes the temperature as:
Repetitive Shock IEC 60068-2-27 (40g, 6ms)
y = x * “rte” + “OFt”
Note: Non-Repetitive Shock IEC 60068-2-27 (30g, 15ms) where y = displayed value and x = measured value.
Product innovation being a continuous process, we reserve
Cold Junction Compensation (CJC): The cold junction, or
the right to alter specifications without any prior notice.
reference junction, is the one that connects the
User is recommended to ensure the suitability of the
thermocouple to the product. The product itself measures the
product for the intended application
cold junction temperature and adds it to the temperature
differences measured from the thermocouple. CJC allows
product to convert temperature differences to actual
temperature. For compensation, CJC should kept ‘ON’ when
thermocouple (J & K) is connected as a sensor.
NOTE: For Pt100 sensor CJC option is not visible in REG
In case of complaint, contact us on 020 - 30680011 or E-mail us o‘service@gicindia.com’ menu.
15LL001_07
Function Menu: Functional Parameters: Frequently Asked Questions (FAQ’s):
Parameter Description Default Q.1: Which parameters can affect the product accuracy?
This Screen is applicable only for password
60 pwd Product Version:
enable selection(pwd - en) A.1: a. Check whether the correct sensor input is selected on
Onf ON-OFF Controller -
xx.x Version ‘XX.X’ eg. 27.0 - product (Check 'SEn' parameter in 'InP' menu)
Error Indications: - b. Check whether power lines & Sensor lines are routed
ovr Over range (If PV > Specified Range) - through the same conduit, Due-to this, the sensor
SP SPL SPH Sp1 Unr Under range (If PV< Specified Range) wires can get affected by noise from the power line
-
sbr Sensor Break/Open - (Route the sensor lines & power lines separate)
-100 650 50 Sp Menu: c. If thermocouple wires are extended with copper wires,
Set Point LOW range setable as, product accuracy can affect (Either connect
TC (J-type):’-5°C (23°F) to SP1’ thermocouple leads directly or use suitable
sPL TC (K-type):’-20°C (-4°F) to SP1’ -100
compensating conductors).
RTD (Pt-100):’-100°C (-148°F) to SP1’
1np Sen Unt 0Ft rte Set Point HIGH range settable as, Q.2: What is 'rtE' and 'OFt' parameter in the 'Inp' menu?'
sPH TC (J-type):SP1 to 750°C (999°F) A.2: If it is required to apply slope/offset or both to the
TC (K-type):SP1 to 850°C (999°F) 650 temperature measured by the instrument, it can be done
o
pt1 c 0 1.00 RTD (Pt-100):SP1 to 650°C (999°F) by using the above parameters. Any value set on above
sP1 ‘Set point 1’ settable as ‘SPL to SPH’ 50 parameter allows device to see temperature as below:
Display temp. = rtE* Measured Temp + OFt
y
o
f PWD Menu:
EN Password Enable This helps to reset the parameters.
DIS
DIS Password Disable
J Q.3: Output not operates when Thermocouple input is
Inp Menu:
sen Sensor input setting configured?
0p 0p1 Pt1 Pt-100 A.3: CJC is Cold Junction Compensation given for
Pt1
j J-type
y thermocouple. It can be enabled or disabled during the
K-type thermocouple configuration. To make output ON with
Cop unt oc Temperature Unit oC thermocouple configuration, CJC parameter in 'rEg' menu
o °C Unit should be enabled (ON).
f °F Unit
0ff 0ft Offset (Range: -100 to 100) 0
rte Rate (Range: 0.01 to 2.00) 1.00 Q.4: How to change SP value directly, without entering in the
0p Menu: Edit menu?
reg Con CjC Hys Ct Pb fun 0p1 Relay output setting A.4: If it is required to edit the SP value in RUN mode.
Cop Controller output Cop a. Press ESC( ) key for 2 sec., then SP value is shown.
0ff Output OFF b. Press ESC( )+UP( ) key to increment SP value.
p 0n 1 20 10 Het
reg Menu: c. And ESC( )+Down( ) key to decrement SP value.
Con Controlling action d. And release the ESC( ) key to set the new SP value.
0na 0ff CoL p Proportional p
0na On-off Asymmetrical Q.5: How to reset device to get factory defaults ?
0ns On-off Symmetrical
A.5: To reset device ,
0ns CjC CJC Settings (Only for ‘J’ & ‘K’ type)*
a. Press Enter button for 2sec.
0n CJC ON 0n b. It will display the main menu, press UP key for reset
pwd dis en 0ff CJC OFF menu.
fvn Controlling mode c. Press enter key on “rSt” menu.
Het Heat mode Het d. If press “no” then it will get back to main screen.
rst no yes
CoL Cool mode Press “YES” to continue , It will display the “Cnf”
Proportional band(Only for ‘P’ action)* menu. Press “YES” to confirm and it will reset your
pb 10
Range:1 to 850 device.
cnF no yes
Cycle Time (Only for ‘P’ action)*
* * Ct 20
Range:1 to 130 sec
sbr sbr Hysteresis (Only for ‘0nA’ & ‘0nS’)* 1
Hys
Range: OFF (0) to 100

* After Factory reset the device return to main screen in both cases when confirmation
rst Menu:
is given as "Yes" or "No". “sbr” displayed on device only when Device is disconnected
from sensor.
rst To reset device for default value no

cnf To confirm reset device no

NOTE: Non-higlighted parameters are visible only for settings given in ‘Functional
Parameters’ table.
* Parameters are visible only for mentioned settings.