Professional Documents
Culture Documents
by
MUHYIDDINE ABED EL HAKEEM JRADI
A thesis
submitted in partial fulfillment of the requirements
for the degree of Master of Mechanical Engineering
to the Department of Mechanical Engineering
of the Faculty of Engineering and Architecture
at the American University of Beirut
Beirut, Lebanon
February 2011
AMERICAN UNIVERSITY OF BEIRUT
by
MUHYIDDINE ABED EL HAKEEM JRADI
Approved by:
______________________________________________________________________
Dr. Nesreen Ghaddar, Professor Advisor
Department of Mechanical Engineering
______________________________________________________________________
Dr. Kamel Ghali, Associate Professor Member of Committee
Mechanical Engineering
______________________________________________________________________
Dr. Fouad Azizi, Assistant Professor Member of Committee
Mechanical Engineering
____________________
Signature
____________________
Date
ACKNOWLEDGMENTS
First and foremost, I would like to express my deep and sincere gratitude to my
advisors at the American University of Beirut for their continuous help and support that
enabled me to accomplish this work.
I would like to acknowledge with great appreciation Dr. Fouad Azizi for his
constant advice, constructive criticism, valuable notes and comments and for reviewing
my thesis as a member of my thesis committee.
I would like to acknowledge the support and help of the faculty at the
Mechanical Engineering Department for enhancing my scientific knowledge, analytical
and learning skills.
I would like to thank the staff at the American University of Beirut for their
continuous help and technical support.
During this work I have worked and collaborated with many friends and
colleagues in the Applied Energy program for whom I have great regard.
Most importantly, none of this would have been possible without the love and
patience of my family. My family, to whom this thesis is dedicated, has been a constant
source of love, concern, support and strength all these years. I would like to express my
heart-felt gratitude to my mother, father, and lovely brothers and sisters. I love you all.
v
AN ABSTRACT OF THE THESIS OF
vi
CONTENTS
ACKNOWLEDGMENTS………………………………………. v
ABSTRACT………………………………………..…………... vi
LIST OF ILLUSTRATIONS………………………..…………...x
LIST OF TABLES………………………………………....…...xiii
LIST OF NOMENCLATURE…………………………….........xiv
Chapter
1. INTRODUCTION……………………………………………..1
3. LITERATURE REVIEW…………………………………….12
5. MATHEMATICAL FORMULATION……………………... 21
vii
5.2. Cooling Channel……………………………………………………………... 26
7. EXPERIMENTAL METHODOLOGY……………………... 33
8. CASE STUDY………………………………………………. 59
Appendix
viii
3. HOURLY COOLING CAPACITY DATA…………………. 83
REFERENCES…………………………………………………. 97
ix
ILLUSTRATIONS
Figure Page
11. The 55*55 mm HXHF CPU coolers used with the heat sinks and the DC fans. 39
16. Amount of water condensate versus the air mass flow rate…………………… 51
x
20. Plots of (a) water condensate versus electric current as predicted by the model
and recorded experimentally, (b) water condensate versus mass flow rate as
predicted by the model and recorded experimentally and (c) water condensate
versus inlet air temperature as predicted by the model and recorded
experimentally…………………………………………………………………. 57
21. Air temperature variation through the cooling channel for different electric
current inputs, 0.01 kg/s air mass flow rate, 28 °C ambient temperature and 30
°C inlet air temperature (model predictions-experimental data comparison)…..58
22. Variation of water condensate with the variation of air mass flow rate under
different electric current supply to the system in August……………………… 61
23. The amount of fresh water produced and the PV power consumption as a
function of electric current input to the TEC modules for (a) August and (b)
September……………………………………………………………………… 63
24. Hourly fresh water production………………………………………………….66
26. Total fresh water production over 10 hours of the PV-powered TEC system
with and without the solar distiller…………………………………………….. 68
27. Plots of (a) the cooling capacity pumped by the thermoelectric cooling
modules/day and (b) the associated system energy consumption from the PV
in kWh/day over the summer months…………………………………………..69
28. The cost of fresh water production by the system for five months compared
to the cost for the conventional vapor compression systems…………………...71
29. Solar still sketch………………………………………………………………...77
xi
39. Hourly cooling capacity pumped by the TEC modules in October…………….85
xii
TABLES
Table Page
4. Water condensate and air temperature variation for different input electric
current…………………………………………………………………………..48
5. Water condensate and air temperature variation for differentt input air mass
flow rate ..............................................................................................................50
6. Water condensate and air temperature variation for different ambient and
input air temperature ……………………………………………………...........53
7. Hourly and total amount of condensed water over the five months ……….......65
xiii
NOMENCLATURE
A Area, m2
DC direct current
Gf geometry factor, cm
h enthalpy, J/kg
I electric current, A
m mass, kg
Nb number of thermocouples
P electric power, W
xiv
PV photovoltaic
t time, s
T temperature, °C
U voltage difference, V
V velocity, m/s
X salinity concentration
ΔT temperature difference, °C
Greek letters
transmissivity
emissivity
Subscripts
A air
amb ambient
C cold
xv
c-g air convection with glass
cond condensate
dist distiller
e thermoelectric element
g glass
h hot
i internal
in input
m module
max maximum
min minimum
n n type semiconductor
out output
p p type semiconductor
sky sky
w water
xvi
Dedication addressed
xvii
CHAPTER 1
INTRODUCTION
the fast rates of urbanization, the lack of fresh water resources emerges as one of the
critical problems threatening the humanity and the nature around us. The decline in the
fresh water availability and quality is affecting millions of people especially in the
developing and poor countries. Recent Statistics show that about 15 % of the people in
the Arab World don’t have access to clean and fresh water, and this percentage is
expected to increase in the upcoming years [1]. The warm and dry climates in the
Middle East and North Africa exhibit the severest fresh water scarcity problem due to
the increase in the salinity rate of the ground water and the sporadic rainfall [2].
According to Miller et al. [1] water scarcity and fresh water shortages affect 88
developing and poor countries contributing to about half the world’s population. In
2025, the number of people suffering from fresh water scarcity and the lack of access to
need for fresh water resources is faced with their limited financial conditions and their
For more than fifty years, many desalination techniques were developed to
solve part of this impending water shortage problem and meet the fresh water
requirements. The main focus was to enhance the extraction of fresh water from sea
water or other salty water sources. Common desalination techniques in this field include
1
Effect Evaporator, Multi Stage Flash Distillation and others. However, these
conventional energy consumption rates. Due to their high consumption of fossil fuels,
effects and nature unbalances. Moreover, they are in need for regular and complex
maintenance with high operation costs. On the other hand, the huge unprecedented
increase in oil prices and conventional energy resources makes the traditional
desalination processes economically very expensive with the need for huge energy
capital costs.
All of this raises the need for advanced, energy efficient and environmental
friendly solutions including fresh water extraction from the atmosphere while utilizing
surfaces to extract water from the atmosphere is one viable solution that takes advantage
of the humid climate prevailing in many areas of the Middle East. In the days with
relatively low air humidity, the power consumption of the thermoelectric cooling
modules would drastically increase which means that other methods are to be sought to
humidify ambient air. Integrating a solar distiller with a thermoelectric cooling system
would increase the water content of the air into the cooling system to produce the
integrated with a solar distiller humidifying unit for air dehumidification and fresh water
production. The work concentrates on studying the viability of applying the advanced
be driven using renewable energy source, the solar PV panels, to generate water in the
2
Lebanese humid climate. In this work, we will present an experimental and theoretical
air dehumidification and fresh water generation. Thermoelectric cooling modules are
resources and systems in cooling and refrigeration applications. This is due to their
through the photovoltaic solar panels. Therefore, with the free electrical energy supply
and environmental friendly system consuming less energy, conserving the environment
proposed system will be integrated with the solar distiller humidifying unit to enhance
the fresh water production by increasing the water content of the air exiting the solar
still. This humid air will be introduced to the cooling channel to be dehumidified using
the thermoelectric cooling modules which in turn are supplied with the needed electrical
current by the photovoltaic solar panels. All of this makes the overall system as a whole
a totally renewable energy-based system without any vapor compression cycle or any
follows:
3
Develop a robust simulation model of the thermoelectric cooling channel to
simulate the dehumidification of air through the thermoelectric channel and predict the
thermal and the electrical performance of the modules as well as the amount of
condensate generated.
Design and build an experimental setup for the proposed system to validate the
numerical model results and predictions regarding the water condensate collected and
Apply the integrated proposed system to a case study in Lebanon to study the
feasibility of using such systems to generate fresh water in the Lebanese humid weather.
4
CHAPTER 2
electric current will pass through the module and heat will be absorbed from one side
and released at the opposite side. On the other hand, maintaining a temperature
difference between the two junctions of the module, a voltage difference will be
This includes commercial products such as beverage coolers, portable picnic cooling
modules are used in laser diodes, integrated circuits and microprocessor cooling, CCD
and LED cameras, infrared detectors cooling as well as night vision equipment for
military applications. Thermoelectric modules are also very effective in dew point
hygrometer, oil pour point apparatus, vidicon tubes, blood analyzers and recently well
known in DNA research. Moreover, thermoelectric modules are getting step by step on
the road of air conditioning, on-board refrigeration systems, compact heat exchangers,
immersion coolers as well as dehumidifiers and there are a lot of innovations in those
fields.
5
are a lot of materials used in producing the thermoelectric elements; however, the most
semiconductor pellet is positively doped so that the charge carriers in the material are
positive. Those positive charge carriers, called holes, enhance the flow of electrons
through the material under an applied voltage. They are attracted by the negative pole of
the DC power supply, so the holes flow in the opposite direction to the flow of the
6
Fig. 2: P-type semiconductor pellet operation
the charge carriers that are negative (called electrons), are attracted by the positive pole
7
As shown in the above two figures, the flow of heat follows the flow of the
holes in the P-type semiconductor, and it follows the flow of the electrons in the N-type
semiconductors. Therefore, the electrical current moves alternately back and forth
between the two substrates through each N-type and P-type thermoelectric
type and P-type semiconductor with a junction between them is the most appropriate
way in configuring a series circuit allowing to keep the heat flow in the same direction.
In order to provide a platform for the semiconductors and the small tabs
connecting them, metalized ceramic substrates are used in general to hold everything
together. Generally, those ceramic substrates are formed of aluminum oxide (Al2O3).
They provide the mechanical and structural integrity of the module, electrically insulate
the thermoelectric elements from any external conductor surface and provide a flat and
characteristics, the Seebeck coefficient, the thermal conductivity and the electric
dependent and vary according to the operating temperature. Moreover, the temperature
difference between the cold and the hot sides of the thermoelectric module is a crucial
factor in the operation of the module; the higher the temperature difference across the
hot and the cold junctions, the lower the coefficient of performance of the
thermoelectric module.
8
2.2. Thermoelectricity Basics
In the beginning of the nineteenth century, two scientists, Thomas Seebeck and
Jean Peltier, discovered the thermoelectric phenomenon which constitutes the basis of
all the thermoelectric applications and industry nowadays. The phenomenon is based on
three main effects: the Seebeck effect, the Thompson effect and the Peltier effect.
temperature difference across the thermoelectric module between the two junctions, the
hot and the cold one. The Seebeck coefficient is defined as the ratio of the temperature
The Thompson effect governs the cooling and the heating of a material
carrying a current and subjected to a temperature gradient. It states that any conductive
material across which a temperature gradient is applied will either emit or absorb heat
applications. It is the responsible for heat removal and heat absorbance. It states that
when an electric current flows across two dissimilar conductors, the junction of the
conductors will either absorb or emit heat depending on the flow of the electric current.
The heat absorbed or released at the junction is proportional to the input electric current.
9
2.3. Thermoelectric Cooling
A thermoelectric cooler simply can convert the input electrical energy into thermal
energy building up a temperature gradient between its hot and cold sides. Thus, by
applying a DC voltage across the thermoelectric cooling module, heat will be absorbed
from the cold side and released at the opposite hot side [3].
refrigerators were designed and have proven to be applicable in many fields. Moreover,
the photovoltaic solar arrays. Thus, using solar energy to power the cooling modules is
an energy efficient and environmental friendly solution to meet the cooling and the
refrigeration demands.
especially in many problems regarding low amount of heat removal. Some of the
Small size and very light weight compared to traditional mechanical systems
10
Ability to heat and cool with the same module by polarity inversion
11
CHAPTER 3
LITERATURE REVIEW
modules [4 -10]. Huang et al. [4] developed a new design method for the thermoelectric
cooling modules. This was based on experimentally testing the modules in order to
develop performance curves and empirical relations which were used later in the design
and calculations. They studied the effect of the heat sink on the overall performance of
the cooling module and reported that the two major factors for enhancing the efficiency
of the thermoelectric modules are the heat sink thermal resistance and the appropriate
cooling capacity to reach the optimal performance. Similar work reported by Chang et
al. [11] who studied the effect of the current input and the heat load on the performance
of the thermoelectric modules. They found that for a given heat load, there is a
corresponding optimal current for the module, and that the thermoelectric modules
thermoelectric system for air pre-cooling and pre-heating and found that the system is
feasible and efficient reaching a coefficient of performance (COP) of 1.5 in the cooling
mode and about 2 in the heating mode. This is achieved by supplying an optimal electric
using a proper heat sink. However, these results were not attained in the experimental
work due to the high resistance of the heat sink used. The work of Lertsatitthanakoran et
al. [13] has concentrated on studying the thermal comfort of a thermoelectric ceiling
12
cooling panel system. They used 36 cooling modules with aluminum at the cold side
and water heat exchanger at the hot side. A cooling capacity of 201.6 W was attained
along with a COP of 0.82 under 1 A electric current input to the thermoelectric
modules.
(PV) solar panels to supply electricity to the thermoelectric cooling modules [14-15].
Gillot et al. [14] used thermoelectric modules for small-scale space conditioning and
built a system prototype that consisted of eight cooling modules to generate a cooling
capacity up to 220 W with a COP of 0.46 under current input of 4.6A. They reported
that the hot side temperature is proportional to the input current and that the applications
with lower current input will have higher COP but lower cooling capacity. In addition,
they found that the use of solar PV to feed the thermoelectric modules would be
competitive and feasible if the PV's price is lower than £1.25/W. La Pierre et al. [15]
studied the use of thermoelectric modules supplied with electrical power generated by
photovoltaic panels for air pre-cooling and pre-heating. They investigated the optimal
number of thermoelectric modules that could be used as well as the optimal electric
current to the thermoelectric modules under different radiation intensities and found that
beyond those optimal conditions the system COP will begin to decline. Their study
shows that thermoelectric cooling could be efficient for summer cooling for small-scale
applications; however, the high investment cost of the PV panels should always be
13
cells to serve people in remote and rural areas. Their proposed system was tested under
different radiation intensities, and they found that the system performance is mainly
between 5 and 10C and the COP is about 0.3. Another portable solar thermoelectric
refrigerator was designed by Abdul-Wahab et al. [17]. The results presented in their
work shows that the refrigerator is able to attain a minimum temperature of 5C with a
COP of 0.16. They stated that the efficiency of the thermoelectric refrigerators is still
lower than its compressor counterparts, but some improvements were proposed to
increase the COP such as improving the thermal interfaces between the modules and the
As shown from the literature above, the majority of the studies and work done
thermoelectric dehumidification was examined by very few researchers. One study was
conducted by Vian et al. [18] who developed a small dehumidifier prototype made up of
three thermoelectric cooling modules and a computational model (AERO) was used for
the design and the optimization of the modules’ performance. Their system consumed
100 W at optimum conditions of 27C and 82% relative humidity with a COP much
integrated with solar distiller for air dehumidification and fresh water production. The
fresh water in the Lebanese coastal humid climate. A robust model will be developed to
simulate the dehumidification of the humid air through the thermoelectrically cooled
14
channel surface and to predict the thermal and the electrical performance of the modules
as well as the amount of condensate generated. A TEC channel prototype will be built
and experiments will be carried to validate the model predictions of the amount of water
condensate collected and the other system performance parameters. A case study will be
meeting the desired fresh water needs in the Lebanese humid climate.
15
CHAPTER 4
solar distiller. The system is composed of three major elements, the thermoelectric
cooled channel/s, the photovoltaic solar panels, and the solar distiller humidification
unit.
16
4.1. Thermoelectric Cooling Channel
It is in fact the main component in our system and it is the responsible for air
simulated and designed where the air is introduced to be cooled and dehumidified in this
channel. The cooling channel is sized such that one side of the channel is cooled by
thermoelectric modules situated in an adjacent vertical manner, and the other three sides
power supply, and they will play the role of heat pumps. Thus applying a voltage
difference across the thermoelectric module will result into a temperature gradient
between the two sides of the module. As a result, the module will be extracting heat
from the air flowing along the channel at the cold side of the thermoelectric cooling
modules and rejecting this heat at the other side of the modules.
source. Photovoltaic generation using solar cells produce electricity directly from the
with photons from sunlight, a voltage difference will appear and as a result an electric
current will flow through the circuit and the connected load. Then the magnitude of
electric current produced is directly proportional to the amount of solar photons striking
the surface.
And since the equipped thermoelectric cooling modules need a DC electric power
17
supply source to operate, then the photovoltaic modules make the best appropriate
renewable solution for feeding the thermoelectric modules with the sufficient electric
power needed to pump the desired cooling capacity. It should be noted that the electrical
energy produced by the photovoltaic modules vary considerably between one month
and another depending on the solar irradiation presented and the ambient air conditions.
Since our system is proposed to produce fresh water in humid areas, then we
are in need for a humid air source to supply the thermoelectric cooling channel with the
needed air input. This role is achieved through using a solar distiller humidifying unit. A
solar distiller is a basin with a shallow depth of salty or impure water with a transparent
and vapor-tight cover sloped towards a collection channel. Therefore the solar distiller
will take advantage of the solar energy to heat and evaporate the water in the basin and
hence increase the water content of the air flowing through the distiller (as shown in
Fig. 4) and entering the cooling channel in order to enhance the fresh water production.
The three components presented above will be integrated to reach the project
objective. Solar energy from the sun will be captured by the photovoltaic modules
which will generate electricity and feed the thermoelectric modules, situated along the
entire cooling channel, with the needed DC voltage. In addition, solar energy will be
used also to heat the water basin inside the solar still. Then, air from the ambient
environment will flow through the distiller from one end above the water and leaves
from the other end with higher water content. Therefore ambient air is humidified by the
18
solar distiller and then dehumidified by the thermoelectric cooling modules to extract
water condensate and generate the needed fresh water. The main parameters governing
Mass flow rate of the supply air to the thermoelectric cooling channel ( ̇ ).
Temperature and humidity ratio of the air entering the thermoelectric cooling
Ambient air conditions controlling the operation of the system (Tamb and wamb).
Output air temperature and humidity ratio from the distiller (Ta-dist and wa-dist).
The thesis work will be divided into two main parts. In the first part, we will
simulate the dehumidification of the humid air through the thermoelectric channel and
predict the thermal and the electrical performance of the modules as well as the amount
of condensate generated in the Lebanese climatic conditions. The model will predict the
temperature and the humidity of the air leaving the cooling channel, the variation of the
air temperature through the whole channel, the thermoelectric modules hot and cold side
temperatures and their corresponding heating and cooling capacities as well as the
electric power consumption of the modules and the amount of water condensate
produced.
the solar still model developed by Alsaidi et al. [19] at AUB, which predicts well the
exit air temperature and relative humidity from the distiller, in order to get benefit and
to make use of the humid air exiting the distiller as a humid source input to the
thermoelectric cooling channel. In our application, the air input to the solar distiller
19
model is not the ambient air, but it is a mixed of fresh air from outside and return air
from the distiller (as shown in Fig. 4). This will enhance the operation of the solar
distiller and will allow us to get benefit of the re-circulated air to increase the water
content of the exiting air from the distiller, therefore increasing the amount of fresh
water produced.
And in the second part of our work, we will design and build an experimental
setup for the proposed system to validate the numerical model results and predictions
regarding the water condensate collected and the various system performance
parameters. The experiments will be conducted in the Energy Lab in the SRB building
at AUB, and the results will be recorded and compared with the numerical model
predictions under the same operational and ambient conditions in order to validate the
20
CHAPTER 5
MATHEMATICAL FORMULATION
In the first part of the methodology section, the thermoelectric cooling channel
air and moisture thermal transport model is presented. This will be followed by a
ΔTmax: is the maximum temperature difference between the hot side of the
Qmax: is the maximal pumping cooling capacity at the cold side corresponding to
ΔT = 0
ΔTmax
21
Fig. 5: Thermoelectric cooling module operation
include the cold side temperature (Tc), the hot side temperature (Th), the heat pumping
capacity at the cold side (Qc), the heat dissipated at the hot side (Qh), the electric current
22
Fig. 6: Thermoelectric cooling module energy modeling
represented by uniform value for each of its operational parameters, The modeling of
the thermoelectric cooling module will follow the derivations of Tsai et al. [20], where
the operation and the performance of the module is governed by three main energy
processes which are, the Joule’s effect, the Peltier cooling effect and the thermal
conduction.
The Joule’s effect is the heat dissipated due to the additional resistive heating
of the thermoelectric elements in the module caused by the flow of electric current and
is given by
23
where I is the electric current in A and Re is the electrical resistivity of the module in
ohm.
The Peltier effect describes the heat absorption or dissipation due to the
presence of two dissimilar semiconductors when an electric current flow through them.
It is given by
where α is the Seebeck coefficient of the module in V/K and Tc/h is the cold or hot side
temperature.
where k is the thermal conductance of the TEC module in W/K and ΔT is the
The heat cooling capacity at the cold side and the heat dissipated at the hot side
can be obtained by applying steady state energy balances for both sides of the
thermoelectric cooling module [21]. As a result, the heat pumping cooling capacity at
The heat dissipated at the hot side of the thermoelectric module is given by
This heat dissipated is the sum of both, the heat pumping capacity at the cold side of the
module and the electric power input to the module. In addition, the input voltage
24
The electric power consumption of the thermoelectric module is given by
The coefficient of performance (COP) is defined as the cooling heat capacity pumped
by the thermoelectric module divided by the electric power consumption of the module
and given by
Qc
COP = (8)
P
(α) in V/K, the thermal conductance (k) in W/K and the electrical resistivity (Re) in ohm
are given in terms of the characteristics of one thermoelectric element by the following
equations:
α = α_e Nb 2 (9.a)
k = k_e Nb 2 Gf (9.c)
the geometry factor of the thermoelectric element, α_e is the Seebeck coefficient for one
element in W/K and k_e is the thermal conductance for one element in W/K.
The Seebeck coefficient, the electrical resistivity and the thermal conductivity for a
single thermoelectric element can be given by the correlations presented by Gillot et al.
k_e = {5.06021 - 0.04244 Tm + 1.96459 10-4 Tm2 - 4.19064 10-7 Tm3 (10.c)
25
where Tm is the average temperature of the thermoelectric module in degrees Kelvin.
independent from the other modules. The air flow in the channel is modeled as 1-D
developing flow considering that the channel width is much smaller than its length.
There will be an initial length of the channel where sensible cooling will take place until
the TE module cold surface temperature is equal to the dew point of the passing air
flow. Once dew point is reached at the surface, it is treated as wet over the rest of the
modules in the channel [22]. The pumping cooling capacity at the cold module side is
where ̇ is the air mass flow rate ha-in and ha-out are the enthalpies of the air at inlet and
exit of each module part of the channel. The heat dissipated at the hot side is given by
(Th Tamb )
Qh (12)
R0
where Tamb is the ambient air temperature, R0 is overall thermal resistance on the hot
side. The variation in air temperature over the dry part of the channel for each module
Ta in Tc
exp(
Ahi
Ta out Tc
) (13.a)
m c p
The variation in the air enthalpy along each of all the wet modules is given by
26
ha in hsurface
exp(
Ahi
ha out hsurface
) (13.b)
m c p
where cp is the specific heat capacity in J/kgK, A is the cooled surface area, hi is the
overall internal convective heat coefficient inside the duct which is calculated and
updated in both dry and wet conditions, Ta-in and Ta-out are the temperatures of inlet and
exit air flow of the ducted module while ha-in and ha-out are the enthalpies of inlet and
exit air flow of the wet ducted module, and hsurface is the saturation enthalpy of the
The workable range of air flow in the TEC channel for dehumidification to take place
corresponds to transitional and turbulent flow ranging from 5,000 to 20,000 based on
the hydraulic diameter. By design, almost half of the channel length will be dry and the
rest is wet. The temperature of the modules of the dry section is almost isothermal with
difference between first module surface temperature and last dry module temperature is
less than 1 °C. The wet section temperature difference between first and last wet
modules is less than 1.6°C. The developing turbulent flow correlation of average
Nusselt in terms of Reynolds and Greatz number over each section was used to estimate
The internal heat convective transfer coefficient for the wet part of the cooling channel
where hi_dry is the internal heat convective transfer coefficient for the dry part and Cd-w
is given by
Cd w
dh 1
(15)
dT cp m
27
Hence, is the change in the enthalpy with respect to the change in temperature and it
is obtained by the following correlation based on the cold surface temperature (Tc) [23]
dT
Finally, the specific heat of moist air is determined by the following equation
cp m cp w cp w (17)
where w is air humidity ratio in kg(water)/kg (air), cpw is the water vapor specific heat
capacity in J/kgK.
The channel flow model will be integrated with the solar still humidification
model developed by Alsaidi et al. [19]. The solar distiller air flow and brackish water
basin are modeled as lumped quasi-static systems. The solar distiller model predicts
well the exit air temperature and humidity from the distiller. It assumes a well-insulated
solar distiller with a lumped glass temperature. In addition, the solar distiller model
assumes that air is a low capacity fluid and neglects the spatial and transient variation in
the temperature of air. The model is based on a set of energy balances developed for the
distiller glass, the air flow, the water in the basin, and the water vapor flow.
The experimentally validated solar still model of Alsaidi et al. [19] predicts the
humidified air exit temperature and humidity for an open cycle. In our work, the air
input to the solar distiller model is not the ambient air, but is a mixture of fresh air from
outside and return air from the distiller. This will increase the water content of the air
28
CHAPTER 6
The set of energy balance equations of the three system units of thermoelectric
cooling modules, cooling channel, and solar distiller described in the previous section
will be solved numerically to predict the exit air conditions from the cooling channel.
Input parameters to the distiller unit are time dependent ambient air temperature and
humidity and intensity of solar radiation. Given ambient and solar conditions and
mixing ratio of re-circulated air flow to ambient flow, the solar distiller model predicts
the temperature and the water content of the air exiting the solar distiller and entering
operational parameters which dictate the accurate selection of the optimal cooling
module for the cooling application. Given the characteristic thermoelectric cooling
module values as provided by manufacturer on Imax, Umax, Qmax, and ΔTmax at the hot side
temperature (Th), we can obtain other design parameters. These include the number of
thermocouples (Nb) in the thermoelectric cooling module, the geometry factor of the
thermoelectric element (Gf), the module width, length, thickness, and the module
and a statistical correlation for this resistance is developed for use in our model in terms
of the two main governing parameters, the input electric current and the ambient
thermoelectric cooling module is treated as a lumped system, and its parameters are
coupled with the next one, through the channel airflow where the air exiting after one
29
module is considered as inlet air input to the next channel section containing the
following module. Therefore, the thermal and electrical parameters will not be the same
for all the thermoelectric modules in the cooling channel because each one is working
module ten equations in ten unknowns which are Tc, Th, Qc, Qh, P, U, ha_out, α, k, and
Re. The Gauss-Seidal iterative method will be used to solve for the ten unknowns.
Given the mass flow rate of the air entering the thermoelectric cooling channel and the
TEC module input electric current, we assume a cold side temperature Tc. Using
Equation (13), the temperature and the enthalpy of the air exiting the thermoelectric
cooling module Ta-out and ha_out are obtained. The cooling capacity can then be found
from Equation (11). By equating Equations (5) and (12) of heat dissipation on the hot
side, and substituting α, k, and Re with their correlations in terms of the average
temperature of the module Tm, we can then calculate the value of the average
temperature of the module Tm. As a result, the hot side temperature Th and the new
updated values for the thermoelectric cooling module characteristics α, k, and Re can be
Hence, we can calculate the total amount of heat dissipated at the hot side Qh
by Equation (12). The final step in the iterative method is calculating a new updated
value for the thermoelectric module cold side temperature Tc from Equation (4) and
than 0.001 C after which we calculate the electric power consumption and the
modules until exit air conditions from the channel are obtained. Finally, from the
30
properties of the humid air entering the cooling channel and that leaving the channel, we
can evaluate the total amount of condensate produced. A flow chart showing the Gauss-
31
Since the solar distiller model is a quasi-static and lumped model, it predicts
the exit air temperature and humidity from the distiller. In addition, while varying inlet
conditions coming from the distiller from hour to hour, the variables are considered
constant during every hour of analysis and study. The presented numerical model
predicts every hour the temperature and the humidity of the air leaving the cooling
channel, the variation of the air temperature through the channel, the thermoelectric
modules hot and cold side temperatures and their corresponding heating and cooling
capacities as well as the electric power consumption and the amount of collected water
condensate.
32
CHAPTER 7
EXPERIMENTAL METHODOLOGY
This section presents the experimental setup used for validating the developed
of the cooling system and condensed water output under different operational and
ambient conditions. A system prototype was built, tested and operated under different
conditions in the climatic chamber and under different electrical current supply to study
the effect of varying the experiment conditions on the system performance and the fresh
An experimental station was set up in the Energy lab in the Scientific Research
Building (SRB) at AUB. A system prototype was built and tested under different
advanced temperature and relative humidity level control system. Many experiments
cooling channel simulation model, taking into consideration that the solar still model
developed by Alsaidi et al. [19] was validated with an experimental setup and was
shown to predict well the exit air temperature and humidity. The experimental setup is
an important step in our work to ensure that our developed model predicts well the
amount of water condensate, the variation in air temperature along the cooling channel
and the thermal and electrical performance of the thermoelectric cooling modules on an
hourly basis.
33
Fig. 8: Experimental system unit
modules for air cooling and heat rejection, heat exchanger at the hot side to enhance
heat dissipation, a humid air source, a heater, electric power supplies, an axial fan to
supply the channel with air and a water collection graduated beaker. The humid air
source replaces the solar still in providing supply air at high humidity content to the
34
thermoelectrically cooled channel, and the electric heater is used to control the channel
inlet air temperature. In addition, the electric power supply (a DC voltage source)
replaces the photovoltaic system and provides the electricity needed to power the
thermoelectric cooling modules to pump the needed cooling capacity. The variation of
the air mass flow rate to the channel is regulated using a damper. This climatic air is
mixed with the water vapor sprayed by the humidifier and heated using the electric
heater to reach the desirable input air conditions to the cooling channel. Then it will
flow along the entire cooling channel and will be cooled and dehumidified by the
thermoelectric cooling modules in order to generate water condensate. The heat emitted
at the hot side of the modules is removed using aluminum heat sinks with integrated DC
graduated beaker.
was built and twenty thermoelectric cooling modules were integrated along one side of
the channel with one cm gap between each two consecutive thermoelectric modules.
The other three sides of the cooling channel were insulated tightly with a fiber glass
help in providing the suitable ambient air temperature and relative humidity level for
our thermoelectric cooling system operation. As shown in the figure below, the chamber
the chamber, any component or appliance up to 1.5 kW added heat load, may be tested
35
in a controlled environment between 10°C and 43°C and within a humidity range of 45
to 75% RH.
Fig. 9: HTS700B climatic chamber with the HTS700 temperature and relative humidity
control system
twenty thermoelectric cooling modules will be installed along one side of the built well
36
127 couples of (n-p) semiconductors. As shown in the figure below, it is 50 mm 50
TEC1-12714 are single stage Bi2Te3-based cooling modules designed for both
cooling and heating applications depending on the polarity of the DC voltage supply
source. The two ceramic substrates joining the thermoelectric elements in the module is
formed of Alumina (Al2O3, white 96%). These cooling modules can be used for cooling
down to -20°C and heating up to 100°C. In addition, those cooling modules are
designed for many applications including food and beverages refrigeration services,
liquid cooling, portable cooler boxes for cars, CPU coolers and for cooling scientific
37
Table. 1: Performance specifications for the (n) and (p) semiconductor elements
maximal operating current Imax , maximal applied voltage difference Umax and maximum
cooling capacity Qcmax based on the module hot side temperature Th are given in Table
2:
38
Qcmax (Cooling Capacity in Watts) 135 148
Twenty 55*55 mm HXHF CPU coolers formed of an aluminum heat sink and
an integrated DC fan will be equipped and placed at the hot side of the thermoelectric
modules to repel heat out. Each CPU cooler will be mounted at the hot side of a
thermoelectric module and conductive silicone-based thermal grease (silica gel) will be
filled at the module-cooler interface to ensure that no thermal gaps will occur.
Fig. 11: The 55*55 mm HXHF CPU coolers used with the heat sinks and the DC fans
39
7.1.4. Electric Power Supplies
Four electric power supplies will be used to feed the thermoelectric modules in
a manner that each power supply will be responsible to supply electrical power to five
control more precisely the voltage difference applied and the electric current input to the
feed the DC cooling fans integrated on each heat sink of the CPU coolers.
the air flowing inside the thermoelectric cooling channel. The humidifier disperses
water vapor in the form of small droplets through the channel to mix with the ambient
input air. This amount of water vapor sprayed could be controlled manually through the
mounted at the inlet of the thermoelectric cooling channel as shown in Fig. 8. The role
of the heater is to control the input air temperature entering the thermoelectric cooling
channel reaching the desired temperature. Therefore, by utilizing both the electric heater
and the electric humidifier, we can adopt to the needed input air conditions to
thermoelectric cooling channel by controlling the temperature and the relative humidity
An axial 12 W AC supply fan rated at maximum flow rate of 54 cfm was used
and mounted at the top of the vertical mounted cooling channel in order to supply
40
ambient air to the channel.
the air through the cooling channel at six positions with an accuracy of 3°C: the
temperature of the air entering the channel, the temperature of the air exiting the
channel, and the temperature of the air at four different positions along the
side and hot side temperatures. Thus, we will be recording the variation of the air
In addition, a humidity sensor will be used to record the humidity of the air
entering the cooling channel with an accuracy of 1%and a flow meter to measure the
air flow rate in the channel by recording the velocity of the air with an accuracy of
0.01 m/s. Moreover, a heat flux meter of 0.6 s response was equipped to measure the
heat flux emitted at the hot side of the thermoelectric cooling modules. The water
weight of collected water. The digital precision balance is of maximum scale reading of
3500 g and accuracy of 0.01 g. Preliminary experiments were carried out to determine
41
the overall thermal resistance at the hot side of the thermoelectric modules by recording
the heat flux released at the hot side of the thermoelectric modules as well as the
temperature. The heat flux is recorded in Volts where each 1.77 µV is equivalent to 1.0
The experiments were conducted in the first two weeks of August 2010. A
system prototype was built inside the climatic chamber situated in the Energy lab in the
scientific research building (SRB) at AUB. Four sessions of experiments were carried
out as follows:
Session 2 aims to study experimentally the effect of varying the mass flow rate
Session 3 aims to study experimentally the effect of changing the electric current
temperature in the climatic chamber as well as the input air temperature to the cooling
channel
Several experiments were performed for different mass flow rates of inlet air,
electric current input to the thermoelectric cooling modules, and different channel inlet
air temperature and humidity. The electric current varied between 1 A to 3.5 A, channel
air mass flow rate was varied between 0.005 to 0.012 kg/s, inlet air temperature to the
cooling channel varied between 25 °C to 34 °C, inlet air relative humidity varied
42
between 70 % to 90 %, and ambient air temperature varied between 25 °C to 34 °C. The
variation in the air temperature along the thermoelectric cooling channel was recorded,
and the amount of water condensate generated was collected and measured in intervals
43
2. Control the temperature and the relative humidity level inside the climatic
3. Then, prepare all the devices and the instruments needed to be used in the
experiment including the power supplies, the electric humidifier, the electric heater and
5. Using electrical wires connect the thermoelectric cooling modules and the DC
6. Turn on the power supplies and regulate the needed voltage difference applied to
the thermoelectric cooling modules and the DC fans mounted on the heat sinks.
44
8. Turn on the air supply axial fan mounted at the top of the thermoelectric cooling
channel.
10. Through the damper, control the relative humidity of the input air to the channel.
11. Record the mass flow rate of the input air using an air flow meter, the
temperature of the input air to the channel as well as the variation in the air temperature
at six positions along the thermoelectric cooling channel using thermocouples, the cold
and the hot side temperature of the thermoelectric cooling modules, the relative
humidity of the input air using a humidity sensor, and the heat released at the hot side of
12. Collect and measure the amount of water condensate in intervals of one hour of
system operation.
These steps were repeated during the four sessions of experimentations with some
thermal resistance at the hot side of the thermoelectric modules. Many experiments
were conducted and we were using a heat flux meter to measure the heat released at the
hot side of the modules. In addition, we were measuring the temperature of the hot side
of the modules as well as the ambient air temperature using K-type thermocouples. As a
result we were able to obtain the overall thermal resistance at the hot side of the
thermoelectric modules.
45
The heat flux meter used is a self-generating device giving readings on a
microvolt basis. So, by using a multimeter to read the voltage output from the heat flux
meter, we were able to deduce the heat flux emitted in Watts based on the sensor
calibration report. Many experiments were done and it is found that the two dominating
parameters affecting the thermal resistance are the electric current input to the
thermoelectric cooling modules and the ambient air temperature The experiments were
done for the ranges of ambient and operational parameters of electric current [2-3.5 A]
and climatic chamber ambient air temperature [25-32 °C]. Table 3 presents the
46
Current Tamb Reading Qhot Thot Resistance
(A) (°C) (mV) (W) (°C) (K/W)
2 32 18.3 15.508 46.1 0.909
2.5 32 24.5 20.762 51.1 0.919
3 32 29.8 25.254 55.5 0.930
3.5 32 34.4 29.152 59.6 0.946
Based on the experimental results presented in the table above, we were able to
develop a statistical correlation for the overall thermal resistance at the hot side in terms
of the ambient air temperature (Tamb) and the input electric current (I). This correlation
will be integrated in our developed simulation model and will be used in the model
predictions:
R2-value = 0.98
water condensate collected and the variation in the air temperature along the
Between the 4th and the 5th thermoelectric modules designated by (T2)
Between the 8th and the 9th thermoelectric modules designated by (T3)
Between the 12th and the 13th thermoelectric modules designated by (T4)
Between the 16th and the 17th thermoelectric modules designated by (T5)
47
In Session 2, we were aiming to study experimentally the effect of varying the
electric current input to the thermoelectric cooling modules on the air temperature
variation inside the cooling channel and the water condensate output from the system.
So, we have maintained constant air mass flow rate of 0.01 kg/s, input air temperature
and relative humidity of 30°C and 85% and constant ambient air temperature of 28 °C,
while varying the input electric current to the thermoelectric modules in the range of [1-
3.5 A]. The amount of condensate was measured and the variation in the air temperature
along the channel was recorded at six different heights for six different cases. The
Table. 4: Water condensate and air temperature variation for different input electric
current
Electric Condensate
T1 T2 T3 T4 T5 T6
Current (A) (kg)
Figure 14 shows the increase in the amount of water condensate with the increase in the
48
0.35
0.3
Water Condensate (kg)
0.25
0.2
0.15
0.1
0.05
0
0 0.5 1 1.5 2 2.5 3 3.5 4
Fig. 14: Amount of water condensate versus the input electric current
Figure 15 shows the variation in the air temperature along the cooling channel for
31
1A 1.5 A 2A 2.5 A 3A 3.5 A
29
27
Air Temperature (°C)
25
23
21
19
17
15
T1 T2 T3 T4 T5 T6
Temperature Recording Position
Fig. 15: Air temperature variation with electric current input
49
7.4.3. Experiment Session 3
effect of varying the mass flow rate of the air input to the thermoelectric cooling
channel on the variation of air temperature inside the cooling channel and the water
condensate output from the system. So, we have maintained constant electric current
input to the thermoelectric modules of 2 A/module, input air temperature and relative
humidity of 30°C and 85% and constant ambient air temperature of 28 °C, while
varying the input air mass flow rate in the range of [0.005-0.011 kg/s]. The amount of
water condensate was measured and the variation in the air temperature along the
channel was recorded at six different heights for seven different cases. The experimental
Table. 5: Water condensate and air temperature variation for different input air mass
flow rate
50
Figure 16 shows the increase in the amount of water condensate with the increase in the
0.3
0.25
0.2
Water Condensate (kg)
0.15
0.1
0.05
0
0.004 0.005 0.006 0.007 0.008 0.009 0.01 0.011
Fig. 16: Amount of water condensate versus the air mass flow rate
Figure 17 shows the variation in the air temperature along the cooling channel for
51
0.005 kg/s 0.0059 kg/s 0.0067 kg/s 0.0076 kg/s
29
27
Air Temperature (°C)
25
23
21
19
17
T1 T2 T3 T4 T5 T6
Temperature Recording Position
Fig. 17: Air temperature variation with air mass flow rate
effect of changing the climatic chamber ambient air temperature and the air input
temperature to the thermoelectric cooling channel on the air temperature inside the
cooling channel and the water condensate output from the system. So, we have
A/module, input air relative humidity of 80% and constant input air mass flow rate of
52
0.01 kg/s, while changing the input air temperature in the range of [28-34 °C] and the
climatic chamber ambient air temperature in the range of [26-32 °C]. The amount of
condensate was measured and the variation in the air temperature along the channel was
recorded at six different heights for seven different cases. The experimental results are
presented in Table 6:
Table. 6: Water condensate and air temperature variation for different ambient and input
air temperature
Ambient Air
Condensate
Temperature T1 T2 T3 T4 T5 T6
(kg)
(°C)
Figure 18 shows the increase in the amount of water condensate with the increase in the
input air temperature to the cooling channel and the ambient air temperature:
53
0.35
0.3
Water Condensate (kg)
0.25
0.2
0.15
0.1
0.05
0
26 27 28 29 30 31 32 33 34 35 36
Fig. 18: Amount of water condensate versus the input air temperature
The chart below shows the variation in the air temperature along the cooling channel for
54
Ta_in = 28 Ta_in = 29 Ta_in = 30 Ta_in = 31
34
32
AIr Temperature (°C)
30
28
26
24
22
20
T1 T2 T3 T4 T5 T6
Temperature Recording Position
Fig. 19: Air temperature variation with air mass flow rate
function of (a) electric current, (b) air mass flow rate, and (c) inlet air temperature for
predicts well the amount of water condensate produced by the new integrated system
over hourly intervals with a maximum relative error less that 8 %. Figure 21 presents
the variation in the air temperature through the thermoelectric cooling channel recorded
at six different heights: at the channel inlet (T1), between the 4th and the 5th
thermoelectric cooling modules (T2), between the 8th and the 9th modules (T3), between
55
the 12th and the 13th modules (T4), between the 16th and the 17th modules (T5) and at the
channel outlet (T6),at different electric current input to the thermoelectric modules for
the case of 28°C ambient temperature, 0.01 kg/s air mass flow rate at 30°C inlet air
temperature. Our thermoelectric cooling channel simulation model predicted well the
variation in the air temperature through the thermoelectric cooling module with a
56
Fig. 20: Plots of (a) water condensate versus electric current as predicted by the model
and recorded experimentally, (b) water condensate versus mass flow rate as
predicted by the model and recorded experimentally and (c) water condensate
versus inlet air temperature as predicted by the model and recorded
experimentally
57
Fig. 21:Air temperature variation through the cooling channel for different electric
current inputs, 0.01 kg/s air mass flow rate, 28 °C ambient temperature and 30
°C inlet air temperature (model predictions-experimental data comparison)
58
CHAPTER 8
CASE STUDY
system will be sized to provide at least 10 liters of fresh water over a period of operation
from 10:00 am to 7:00 pm during the summer months from June till October. An
optimization problem is formulated such that the energy consumption of the unit is
dictated by fresh water demand and the availability of electrical energy supplied by the
photovoltaic system. The integrated system design, operation and optimization are
performed for the Beirut local humid weather conditions. The system is sized such that
multiple thermoelectric cooling channels of 120 cm length and 75 cm2 cross sectional
area with 20 thermoelectric cooling modules per each cooling channel as described in
the previous section. Moreover, the thermoelectric cooling modules use solar
photovoltaic modules to provide them with the needed electrical input. Five UE 200 M5
solar photovoltaic modules are considered for the case study to provide a 1 kW capacity
photovoltaic system. The number of channels needed and their associated number of
The amount of fresh water produced over the 10 hours of daily operation.
A solar distiller of 1.2 m2 area with a constant air mass flow rate of 0.15 kg/s is
flow to the cooling channels and enhance fresh water production. The solar distiller air
59
flow is partially re-circulated while only a fraction of this flow is drawn from ambient
air equal to the dehumidified air stream supplied to the thermoelectric cooling channels
(see Fig. 4). This modification helps in increasing the system fresh water output by
increasing further the water content in the supply air to the dehumidifying
thermoelectric channel.
The optimization problem is controlled by the air mass flow rate of the
thermoelectric channels and the electric current input to the thermoelectric cooling
modules. A minimum of five thermoelectric cooling channels are needed to produce the
different air mass flow rates from 0.005 kg/s to 0.02 kg/s, to find the optimal humid air
mass flow rate to be introduced to the thermoelectric cooling channels from the solar
distiller based on the electrical energy consumption of the system and the amount of
water condensate produced. It was found that the amount of water produced increases
with the increase in the air mass flow rate until the air mass flow rate reaches 0.0155
kg/s per channel. Figure 22 shows the variation of water condensate produced with the
variation in the air mass flow rate in the thermoelectric cooling channels for different
electric current input in the month of August. For air mass flow rates higher than 0.0155
kg/s, a decrease is exhibited in the amount of fresh water produced by the system. Based
on these results, an air mass flow rate of 0.0155 kg/s will be adopted per cooling
channel.
60
20
18
16
Water Condensate (liters)
14
12
10
0
0.010 0.011 0.012 0.013 0.014 0.015 0.016 0.017 0.018 0.019 0.020
Air mass flow rate (kg/s)
Fig. 22: Variation of water condensate with the variation of air mass flow rate under
different electric current supply to the system in August
selected such that a minimum of 10 liters of fresh water is obtained at the maximum
electrical energy available from the photovoltaic system. The first step in solving for the
photovoltaic system in the Lebanese summer humid climate. This is governed mainly
by the solar irradiation intensity and the ambient air properties that vary significantly
from one month to another. As a result, this maximal energy is calculated for each of the
five sunny months from June till October. Simulations were performed while varying
the electrical current input to the thermoelectric cooling modules with a step of 0.1 A in
the range of 1 to 3 A. Based on the electrical energy consumption results and the
61
amount of fresh water collected, we can determine the optimal electrical current input to
Figure 23 (a-b) shows the amount of fresh water produced and the PV power
consumption as a function of electric current input to the thermoelectric modules for (a)
August and (b) September. On the same plots, the constraint values for minimum water
production and maximum power consumption are indicated. It is clear that the month of
August provides wider operating range (shown by the dark rectangle borders in the
figure) for the system to produce more than 10 liters per day, while in September, the
operating margin for current input is very small (1.95 to 2.05 A).
(a)
62
(b)
Fig. 23 (a-b): The amount of fresh water produced and the PV power consumption as a
function of electric current input to the TEC modules for (a) August and (b) September.
Performing the simulations over all the summer months leads to the optimal
electric current input values of 2.2 A/module for the month of June, 2.1 A/module in
July, and 2.0 A/module for August, September and October. The selected current input
values provide the needed cooling capacity, produce the desired fresh water, and meet
over the 10 hours of system operation per day for the five studied months.
63
CHAPTER 9
thermoelectric cooling system integrated with solar distiller to produce at least 10 liters
of fresh water per day are presented in this section. Our main concern in the case study
was to optimize the performance of the system in order to attain our objective to collect
at least 10 liters of fresh water during the period of 10 hours of the system operation per
day, taking into account the electrical energy available from the solar photovoltaic
system in the five studied months. Table 7 presents the hourly and the total amount of
fresh water produced for the summer months showing how the system, with the
optimized air mass flow rate and input electric current to the thermoelectric cooling
modules, met its goal of producing at least 10 liters of fresh water during the 10 hours of
operation per day. Also, Fig. 24 shows the hourly amounts of fresh water condensate
collected during the five months. It is obviously shown that the maximum amount of
fresh water produced is attained during the period of the system operation between 3:00
64
Table.7: Hourly and total amount of condensed water over the five months
Month
Electric
Current Input 2.2 2.1 2 2 2
(A)
65
2
1.8
1.6
Water Condensate (liters)
1.4
june
1.2
july
1
august
0.8
september
0.6
october
0.4
0.2
0
10 11 12 13 14 15 16 17 18 19
Hour
In addition, and based on the results obtained and shown in Fig. 25, the total
amount of fresh water produced ranged from about 14.09 liter/day in August to about
10.06 liter/day in October during 10 hours of the system operation. This is mainly due
to the humid ambient air conditions and the higher solar radiation intensity which vary
66
16
14
12
Water Production (Liters)
10
0
June July August September October
Fig. 25: Daily fresh water production for the five months
Figure 26 compares the total amount of fresh water collected for the PV-
powered thermoelectric cooling system operation with and without integration with the
solar distiller. The requirement for producing the 10 liters of water cannot be met for all
the months without the humidification process through the solar distiller. The solar
distiller enhances the water condensate yield by increasing the water content of the air
a portion of this humid air back to the solar distiller has proven to be a very wise
decision enhancing further the water condensate produced. The amount of water
condensate produced due to the integration of the solar distiller in the process has
increased from 4.72 liters to 14.09 liters in August and from 2.31 liters to 10.06 liters in
October.
67
16
14
12
Water Production (Liters)
10
0
June July August September October
Fig. 26: Total fresh water production over 10 hours of the PV-powered TEC system
with and without the solar distiller
68
10
7
Cooling Capacity (kWh)
0
June July August September October
(a)
6
Energy Consumption (kWh)
0
June July August September October
(b)
Fig. 27(a-b): Plots of (a) the cooling capacity pumped by the thermoelectric cooling
modules/ day and (b) the associated system energy consumption from the
PV in kWh/day over the summer months.
69
Fig. 27 presents the amount of cooling capacity pumped by the thermoelectric
cooling modules situated along the thermoelectric cooling channels. This cooling
capacity reaches its maximum in June with about 9.07 kWh/day while decreases to
performance is attained in October with a COP of 1.52. Thus, although the amount of
fresh water produced in October is the lowest among all the five months studied, we can
notice that the month of October exhibits the highest COP values, meaning the highest
cooling channels. This is based on the relatively lower ambient temperature values in
October compared to the other months, and thus these lower ambient temperature values
allow attaining lower temperature gradient between the two sides of the thermoelectric
cooling modules (the hot and the cold side). And based on the thermoelectric modules
allowing more heat to be extracted, and as a result more cooling capacity is pumped.
the PV in kWh/day over the summer months during 10 hours of the system operation.
maximum value of 6.73 kWh/day in June. Regarding the optimal operational energy
consumption of the system, we will compare this energy consumption with that of the
70
systems consume about 0.7 kWh to produce 1 liter of fresh water. However, the energy
intensity of our proposed integrated solar distiller with PV-powered TEC channel
system is found minimum at 0.387 kWh/liter in August and maximum in June at 0.586
kWh/liter.
9
Cost of Water Production (cents/liter)
0
June July August September October
Fig. 28: The cost of fresh water production by the system for five months compared to
the cost for the conventional vapor compression systems
As shown in Fig. 28, the cost of production of one liter of fresh water was
about 7.03 cents/liter in June and boils down to 4.65 cents/liter in August at 0.12
$/kWh. On the other hand, the cost of production of one liter of fresh water by the
cents/liter. Therefore, comparing the costs, we can notice that the proposed system
allows significant savings on the energy consumption ranging between 17.26 % in June
71
and 45.25 % in August, compared to the vapor compression atmospheric water
72
CHAPTER 10
validated in this work. The system is totally powered by renewable energy sources. A
model of the integrated system is developed and is validated experimentally. The air
flow rate, air inlet conditions and electric current input to the thermoelectric cooling
modules are the controlling parameters for optimal system operation to meet desired
need of water condensate. The developed numerical simulation model predicted well
the temperature and the humidity of the air leaving the channel, the variation of the air
temperature through the whole channel, the thermoelectric modules’ hot and cold-side
temperatures and their corresponding heating and cooling capacities as well as the
experimentally and found to predict well the variation in the air temperature through the
thermoelectric cooling channel with a maximum relative error less than 2.4 %
(±0.55°C). In addition, the simulation model predicts well the amount of water
condensate produced by the new integrated system with a maximum relative error less
that 8 %.
integrated solar distiller PV powered TEC channel system in Beirut climate for
producing at least 10 liters of water per day over the summer months. The aim of the
case study was to predict the overall system performance in terms of the amount of
water condensate and energy consumption. It was found that the optimal operation total
73
energy consumption varied between 5.32 kWh/day in October and 6.73 kWh/day in
June. Moreover, the cost of production of one liter of fresh water was about 6.34
cents/liter in October with about 17.26 % saving compared to the vapor compression
atmospheric water extraction residential systems, and the cost boils down to 4.65
has many advantages. First of all, the proposed system is powered totally by renewable
energy sources depending solely on solar energy which is used by the solar distiller and
by the photovoltaic solar panels. Moreover, the thermoelectric cooling modules used are
addition, the proposed system will help in solving a part of the fresh water scarcity
problem in our region in an efficient and environmental friendly manner especially for
stand-alone remote areas applications in the humid climates and in the areas where the
electrical supply is intermittent. Although the initial investment cost of the system is
relatively high, the proposed system would be a long term cost saving system because
the solar energy source is free and the system components generally need no
maintenance.
vertical upward flow of the humidified air through the thermoelectric cooling channel
rather than the vertical downward flow presented in the study. Another alternative may
be considered through studying the effect of using a more complex PV system, with
storage batteries and advanced charge controller, on the overall performance of the
74
getting benefit of the heat dissipated at the hot side of the thermoelectric cooling
modules in heating the ambient air before introducing it through the solar distiller. This
may help in decreasing the temperature at the hot side of the thermoelectric module and
in increasing the temperature of the ambient air introduced to the solar distiller. In
addition, and as shown in the study, decreasing the thermoelectric module’s hot side
temperature will result into more favorable conditions for the module performance;
therefore, one possible improvement to the system is making use of the cooled air
exiting the channels and re-circulating this air along the hot side of the thermoelectric
cooling channel.
75
APPENDIX I
In this appendix, we will present a brief description for the solar still model
which was integrated with the thermoelectric cooling model developed. The solar still
model is a quasi-static and lumped model which predicts well the exit air temperature
and humidity from the distiller. As shown in Fig. 29, ambient air enters the distiller at a
lower point passing over the water basin and leaving the distiller at the other higher end.
Energy balances are developed for the glass, air flow, seawater in the basin and the
76
Fig. 29: Solar still sketch
lumped energy balance. In the energy balance are the effects of air convection, radiation
with water and sky and solar radiation. The transient temperature of the glass cover can
be represented by
where mg is the glass cover mass, Cpg is the glass specific heat capacity, Tg is the glass
temperature, t is the time, I(t) is the incident solar irradiation on the glass surface, Tw is
the water temperature, Tair is the air temperature inside the still, and Tis the ambient air
temperature, Ag is the glass cover area, Tsky is the sky temperature, and hc-g is the
convective coefficient between glass and air flow in the still, while hc-a is the convective
77
coefficient between glass and ambient air. The term on the right hand side represents the
The inner and outer radiative heat transfer coefficients hr1 and hr2 are given by
where is the Stephan Boltzman constant, is the glass emissivity, Fwg is the view
factor between water and glass surface, and Fgs is the view factor between the glass and
sky.
Based on an energy balance between the solar energy absorbed by the water
and the energy losses by convection to the flowing air, radiation to the glass and
where mw is the water mass, Cpw is the water specific heat, g is the glass transmission
coefficient, w is the water absorption coefficient, and hc-w is the convective heat
Neglecting the spatial and transient variation in the temperature of the air (low
capacity fluid), the net energy flow (convection energy exchange with both the water
78
basin and glass cover and energy of the evaporated water) to the air stream passing
where Aw is the water basin surface area, Cpv is water vapor specific heat, Tair1 and Tair2
are the inlet and exit air flow temperatures, hfg is the water heat of evaporation, m air is
The rate of water evaporation can be obtained from the correlation developed
Al-Shammiri et al. [24] that takes into account the water salinity
where V is the velocity of flowing air, X is the salinity concentration and P is the water
vapor difference between the flowing air and the water basin vapor.
79
APPENDIX II
In this appendix, the hourly fresh water production for the integrated
1.6
1.4
Water Production (liters/h)
1.2
0.8
0.6
0.4
0.2
0
10 11 12 13 14 15 16 17 18 19
Time of the Day
80
1.8
1.6
Water Production (liters/h)
1.4
1.2
0.8
0.6
0.4
0.2
0
10 11 12 13 14 15 16 17 18 19
Time of the Day
1.8
Water Production (liters/h)
1.6
1.4
1.2
0.8
0.6
0.4
0.2
0
10 11 12 13 14 15 16 17 18 19
Time of the Day
81
1.6
1.4
Water Production (liters/h)
1.2
0.8
0.6
0.4
0.2
0
10 11 12 13 14 15 16 17 18 19
Time of the Day
1.6
1.4
Water Production (liters/h)
1.2
0.8
0.6
0.4
0.2
0
10 11 12 13 14 15 16 17 18 19
Time of the Day
82
APPENDIX III
In this appendix, the hourly cooling capacity pumped at the cold side of the
1000
950
Pumped Cooling Capacity (Wh)
900
850
800
750
700
10 11 12 13 14 15 16 17 18 19
Time of the Day
Fig. 35: Hourly cooling capacity pumped by the TEC modules in June
83
830
Pumped Cooling Capacity (Wh)
780
730
680
630
580
10 11 12 13 14 15 16 17 18 19
Time of the Day
Fig. 36: Hourly cooling capacity pumped by the TEC modules in July
750
Pumped Cooling Capacity (Wh)
700
650
600
550
500
10 11 12 13 14 15 16 17 18 19
Time of the Day
Fig. 37: Hourly cooling capacity pumped by the TEC modules in August
84
820
780
Pumped Cooling Capacity (Wh)
740
700
660
620
580
540
500
460
10 11 12 13 14 15 16 17 18 19
Time of the Day
Fig. 38: Hourly cooling capacity pumped by the TEC modules in September
900
860
Pumped Cooling Capacity (Wh)
820
780
740
700
10 11 12 13 14 15 16 17 18 19
Time of the Day
Fig. 39: Hourly cooling capacity pumped by the TEC modules in October
85
APPENDIX IV
In this appendix, the hourly heat dissipated at the hot side of the thermoelectric
1650
1600
Heat Disssipated (Wh)
1550
1500
1450
1400
10 11 12 13 14 15 16 17 18 19
Time of the Day
86
1450
1400
Heat Disssipated (Wh)
1350
1300
1250
1200
10 11 12 13 14 15 16 17 18 19
Time of the Day
1300
1250
Heat Disssipated (Wh)
1200
1150
1100
1050
10 11 12 13 14 15 16 17 18 19
Time of the Day
87
1350
1300
1250
Heat Disssipated (Wh)
1200
1150
1100
1050
1000
10 11 12 13 14 15 16 17 18 19
Time of the Day
1410
1360
Heat Disssipated (Wh)
1310
1260
1210
1160
10 11 12 13 14 15 16 17 18 19
Time of the Day
88
APPENDIX V
energy consumption from the solar photovoltaic panels is presented over the five
months studied.
680
675
670
Power Consumption (Wh)
665
660
655
650
645
640
10 11 12 13 14 15 16 17 18 19
Time of the Day
89
620
610
600
Power Consumption (Wh)
590
580
570
560
550
10 11 12 13 14 15 16 17 18 19
Time of the Day
560
550
540
Power Consumption (Wh)
530
520
510
500
490
10 11 12 13 14 15 16 17 18 19
Time of the Day
90
560
550
540
Power Consumption (Wh)
530
520
510
500
490
480
10 11 12 13 14 15 16 17 18 19
Time of the Day
540
530
Power Consumption (Wh)
520
510
500
490
480
10 11 12 13 14 15 16 17 18 19
Time of the Day
91
APPENDIX VI
manufacturer’s datasheets.
92
Fig. 51: Qc vs ΔT under various currents (Th = 27°C)
93
2- 50°C Hot Side Temperature
94
Fig. 55: Voltage vs ΔT under various currents (Th = 50°C)
95
Fig. 56: UE 200 M5 electrical specifications
96
REFERENCES
[1] Miller JE, Review of Water Resources and Desalination Technologies, Sandia
National Laboratories, Albuquerque Sand 2003-0800, 2003.
[3] Rowe DM. CRC Handbook of Thermoelectric, CRC Press Inc. Boca Raton
U.S.A. Chapter 55: Modeling of thermoelectric cooling systems, 677-683;
1995.
[4] Huang BJ, Chin CJ, Duang CL. A design method for thermoelectric cooler.
International Journal of Refrigeration 2000; 23: 208-218.
[5] Khattab NM, El Shenawy ET. Optimal operation of thermoelectric cooler driven
by solar thermoelectric generator. Energy Conversion and Management 2006;
47: 407-426.
[6] Astrain D., Vian JG, Dominguez M. Increase of COP in the thermoelectric
refrigeration by optimization of heat dissipation. Applied Thermal Engineering
2003; 23: 2183-2200.
[7] Nolwenn LP, Matthieu C., Luo L, Fraisse G. Coupling of thermoelectric modules
with a photovoltaic panel for air pre-heating and pre-cooling application; an
annual simulation. International Journal of Energy Research 2008; 32: 1316-
1328.
[9] Tan F.L. and S.C Fok (2008). "Methodology on sizing and selecting
thermoelectric cooler from different TEC manufacturers in cooling system
design." Energy Conversion and Management". 49, 2008: 1715-1723.
[10] Xi Hongxia, Lingai Luo and Gilles Fraisse (2007). "Development and
applications of solar-based thermoelectric technologies." Renewable and
Sustainable Energy Reviews. 11, 2007: 923-936.
[11] Chang Yu-Wei, Cheng CH, Wu WF, Chen SL. An experimental investigation of
thermoelectric air-cooling module. World Academy of Science, Engineering
and Technology 2007; 33: 128-133.
97
[12] Cosnier M, Fraisse G, Luo L. An experimental and numerical study of a
thermoelectric air-cooling and air-heating system. International Journal of
Refrigeration 2008; 31: 1051-1062.
[15] Le Pierre Nolwenn, Matthieu Cosnier, Lingai Luo and Gilles Fraisse (2008). "
Coupling of thermoelectric modules with a photovoltaic panel for air pre-
heating and pre-cooling application; an annual simulation." International
Journal of Energy Research. 32, 2008: 1316-1328.
[16] Dai YJ, Wang RZ, Ni L. Experimental investigation and analysis on a
thermoelectric refrigerator driven by solar cells. Solar Energy Materials and
Solar Cells 2003; 77(4): 377-391.
[20] Tsai HL, Lin JM. Model building and simulation of thermoelectric module using
Matlab/Simulink. Journal of Electronic Materials 2010; 39 (9): 2105-2111.
[22] Lienhard V John H., A Heat Transfer Textbook, Third Edition, Phlogiston Press,
New York, 2003.
[23] Kuehn HT, Ramsey JW, Threlkeld JL. Thermal Environmental Engineering. 3rd
Edition, Prentice-hall Inc. New York, 1998, Ch. 7.
98